Honeywell HCD 6003, HCD 6010, HCD 6050, HCD 6150 DATASHEET

Honeywell HCD 6003, HCD 6010, HCD 6050, HCD 6150 DATASHEET

(according to Gas Appliance Directive 90/396/EEC)

P r e s s u r e s w i t c h e s

39

Mechanical pressure switches

 

H C D s e r i e s

P r e s s u r e a n d d i f f e r e n t i a l p r e s s u r e s w i t c h e s f o r n e u t r a l g a s e s ( D V G W - t e s t e d )

Pressure switches of the HCD series are suitable

connection piece G 1/8” (remove sealing cham-

for neutral and non-aggressive gases. They can

ber). For differential pressure detection the high

be used for monitoring overpressure and differ-

pressure is applied to the lower connection

ential pressure. For overpressure detection the

piece (G 1/4”) and the low pressure side to the

pressure side is connected to the lower connec-

upper connection piece (G 1/8”). A pressure

tion piece G 1/4”; for vacuum detection the

measurement connector (9 mm ø) is available for

pressure side is connected to the upper

accurate setpoint adjustment.

Technical data

Pressure connection

Pressure connection for overpressure: G 1/4” internal thread.

For vacuum and differential pressure: G 1/8” internal thread.

Switch housing

Diecast aluminium.

Medium temperature

–15 to +60 °C.

Maximum working pressure

See Product Summary

Mounting position

Horizontal with connection pieces pointing downwards.

Type of protection IP 40 according to DIN 40050.

Mounting

Either directly on pipe or with mounting bracket (supplied) on a vertical surface.

Setting the switching point

Remove the cover and turn the setting spindle marked +/– in the corresponding direction. The scale shows only guideline values. For accurate setpoint adjustment it is necessary to use a pressure gauge which can be attached to the measuring point (9 mm ø pressure measurement connector).

Switching function Single pole switching.

Electrical connection

Switching capacity

2 A/220–240 VAC (inductive load)

10 A/220–240 V AC (resistive load)

Cable entry Pg 13.5

Tested according to Gas Appliance Directive 90/396/EEC, DVGW reg. no. E 3085/2.

Type

Setting range

 

Switching differential

Max.

 

 

 

 

in lower range

in upper range

working

 

 

 

 

 

 

 

pressure

HCD 6003

0.2…3 mbar

0.3…

mbar

0.5 mbar

100

mbar

HCD 6010

1…10

mbar

0.3…

mbar

1

mbar

100

mbar

HCD 6050

5…50

mbar

1.5…

mbar

3

mbar

200

mbar

HCD 6150

15…150

mbar

4…

mbar

10

mbar

300

mbar

The switching differential is not adjustable. The low switching differentials are for the lower setting range; the higher values relate to the upper ranges.

Dimensioned drawing

s

GASTEC

IP 40

 

 

Degree of protection:

 

tested

 

 

 

 

Loading...