13.7.1. Navigation and function overview ........................ 15
Contents
3
About these instructions
1. About these instructions
Fold out the left-hand cover. This shows all the operating
elements and connections. Leave the cover folded out while
reading further.
Technical terms are explained in the glossary (Page 12).
Legend for fold-out page
Fig. 1 Scope of delivery
Fig. 2 Opening housing
Fig. 3 Display and operating elements
Number Labelling Function
(1)
(2)
(3)
(4)
(5)
(6)
Power
Mode
Power supply on/off
Information display
Installation display
Operating mode button
Installation button
Pump on/off display
(7) 1...8 Zone LEDs
(8) Labelling of Zones 1...8
Fig. 4 Connections
Number Function
(9) I/O connector
(10) Switch for setting normally open/normally closed
(11) Slot for expansion module HCS 80
(12) Connector for supply voltage, pump
(13) Fuse
(14) Slot for internal antenna
(Z1 - Z8) Connector for Zones 1...8
Fig. 5 I/O connector
Fig. 6 Connector for Zones 1...8
Fig. 7 Connector for supply voltage, pump
2. General safety instructions
DANGER
WARNING
Danger to life through electric
shock!
Contacts that are open are live.
► Unplug the power plug before open-
ing the housing.
,
► Have all the work carried out by
authorised specialist personnel.
► Observe the valid VDE regulations
during the installation.
Damage to the underfloor heating
controller!
Short-circuiting through humidity and
moisture.
► Mount the device at a site that is
protected against humidity and moisture.
3. Overview
The floor hearing system is an intelligent system for individual room temperature control. The following overview shows
devices that can operate together with the underfloor heating controller.
(B)
(E)
(I)
(J)
(I)
A Setpoint adjuster HCW 82
Controls the setpoint temperature for each temperature
zone via adjustment dial
B Central operating device CM67z
Controls the room temperature via programmable time
programs
C Room temperature sensor HCF 82
Transmits room temperature information to underfloor
heating controller
D Hometronic Manager HCM 200D
Central operating unit of the house-automation system
E Underfloor heating controller
HCE 80/HCC 80/HCE 80R/HCC 80R
Controls actuators; communicates with setpoint adjusters
and room temperature sensors
F Boiler feedback,
Analog output (only HCE 80/HCC 80) or
Relay output (only HCE 80R/HCC 80R)
G Integrated pump relay
H Thermal actuators
I External antenna HCE 80/HCE 80R
• 5 controllable temperature zones, extendable to 8
• Up to 3 thermal actuators can be connected per zone
• Normally open and normally closed thermal actuators
can be used
• Integrated pump relay
• Boiler feedback
– Analog (only HCE 80/HCC 80)
– Integrated relay with floating contact 42 V AC/DC
(only at HCE 80R/HCC 80R)
– Wireless via relay HC60NG/R6660D
• Underfloor heating controller can be switched between
heating and cooling
• 1 antenna can be used for 3 controllers
• Internal or external antenna can be used
• Rapid mounting by screwless terminals of the thermal
actuators
• Intelligent controlling via fuzzy logic
• Simple diagnosis of the wireless transmission
• Operating state display via LEDs
4. Creating a zoning plan
Within a building rooms (zones) can be controlled with different room setpoint temperatures. The thermal actuators of
the allocated zone (room) are controlled depending on the
room setpoint temperature.
A maximum of 5 temperature zones can be set
for each underfloor heating controller. This number can be increased to 8 by using the expansion
module HCS 80.
A maximum of 3 actuators can be connected in
Temperature zones
(maximum)
8 24 1
16 48 2
24 72 3
Tab. 1: Overview of temperature zones/ underfloor heating controllers
each zone.
Actuators
(maximum)
No. of underfloor
heating controllers
4.1. Specifying temperature zones
► Specify the number of zones and corresponding rooms.
► Allocate the corresponding room device, for example
HCW 82, CM67z, and the required thermal actuators to
each zone.
► Label the room devices and thermal drives for the respec-
tive zone (refer to the fold-out page Fig. 4, Z1...Z8).
4.1.1. Example of zone divisions
kitchen
hall
dining room
living room
bathroom
Explanation of this example:
• The living area is covered by six temperature zones. The
additional module HCS 80 is required for this partitioning.
• The underfloor heating controller controls 8 actuators.
bedroom
toilet
5. Installation
WARNING Insufficient data transfer!
Interference of the radio receiver in the
device through metallic objects and
further radio devices.
► When selecting the operating site
ensure that the distance to radio devices such as radio headphones,
cordless phones, etc. according to
the DECT standard amounts to at
least 1 m.
► Ensure that there is sufficient dis-
tance to metallic objects.
► Select another installation site if the
WARNING
The underfloor heating controller was designed for installation in a distributor box. If insufficient space is available,
select an area where the underfloor heating controller can
communicate with the setpoint adjusters by radio without
interference and that is protected from moisture and water.
The underfloor heating controller can be installed in one of 2
ways:
• Wall installation
• DIN rail installation
radio interference cannot be rectified.
Damage to the underfloor heating
controller!
Short-circuiting through humidity and
moisture.
► Mount the device at a site that is
protected against humidity and moisture.
5
Installation and configuration
5.1. Wall installation
Four 4.2 mm holes for installation are located on the underfloor heating controller.
Take the 52 mm installation height of the underfloor heating controller into account. If the underfloor heating controller is installed at a severe
angle, the transformer must be on top to allow for
ventilation.
57
52.0
337
∅
4.2
349.5
Dimensions of underfloor heating controller in mm
► Mark, drill and insert plugs into fastening holes.
► Screw on the underfloor heating controller.
5.2. DIN rail installation
► Place the housing on the DIN
rail from below (1).
► Press the housing upwards
until it snaps into place (2).
5.3. Installing components
Install the components as described in the accompanying
installation instructions.
6. Installation and configuration
DANGER
WARNING Damage to exposed components!
Danger to life through electric
shock!
Contacts that are open are live.
► Unplug the power plug before open-
ing the housing.
► Have all the work carried out by
authorised specialist personnel.
► All wiring must be in accordance with
IEE & Building Regulations.
Destruction of the electronic components through electrostatic discharges.
► Do not touch the components.
► Touch an earthed piece of metal to
discharge static electricity from your
body.
85
6.1. Opening the housing
► Open the housing as shown in Fig. 2 on the fold-out page.
6.1.1. Plugging in the expansion module
(optional)
The expansion module HCS 80 expands the number of
possible temperature zones of the underfloor heating controller from 5 through 8.
► Insert the expansion
module with the adapter
connector into the provided slot.
6.1.2. Setting the thermal actuator type
Only one thermal actuator type can be connected
per underfloor heating controller. If normally open
and normally closed actuators are to be operated, you require two underfloor heating control-
► Check the type of thermal actuator being used.
► Set the switches in accordance with the following table
Switch
position
lers.
The thermal actuators are protected by a ceramic
fuse.
(see the fold-out page, Fig. 4 (10)):
Thermal actuator type
Normally closed
Normally open
Property
Opens the heating circuit if
power is present at its control
input
Opens the heating circuit if
power is not present at its
control input
6.2. Cabling connections
6.2.1. Permissible cable types and lengths
Thermal actuators
Outer cable diameter
Cable length Max. 400 m
Cable cross-section Max. 1.0 mm²
Stripping length 4 mm
Terminal range of
the connectors
Power and pump connection 230 V AC
Outer cable diameter
Cable length Max. 100 m
Cable cross-section Max. 1.5 mm²
Stripping length 7 mm
Terminal range of
the connectors
Min. 3.5 mm/Max. 5.3 mm
0.07–1.33 mm²; flexible wire
Min. 8.0 mm/Max. 11 mm
0.50–2.50 mm²; flexible/fixed connection
0.50–1.50 mm²; flexible, with wire end
ferrule
6
Installation and configuration
Antenna connection
Cable length Max. 30 m
Cable cross-section
JE-LiYCY 2x2x0.5 mm²;
JE-Y(St)Y ∅2x2x0.8 mm;
2x0.5 mm²
Stripping length 5.5 mm
Terminal range of
0.07–1.54 mm²
the connectors
Heating/cooling, boiler feedback
Cable length Max. 100 m
Cable cross-section
JE-LiYCY 2x2x0.5 mm²;
JE-Y(St)Y ∅2x2x0.8 mm;
2x0.5 mm²
Stripping length 5.5 mm
Terminal range of
0.07–1.54 mm²
the connectors
Tab. 2: Permissible cable types and lengths
6.2.2. Connecting power cable
DANGER
► Select a suitable cable in accordance with Table 2 for the
power supply.
► Strip the connections 7 mm (see fold-out page, Fig. 7).
Danger to life through electric
shock!
Contacts that are open are live.
► Ensure that the cable is deenergized.
► Lay the actuator cables to the distribution box.
► Connect the actuator wires.
► Break out the openings for
the cables on the housing
using a diagonal cutter.
► Strip the connections 5.5 mm (see
fold-out page, Fig. 6).
► Insert the connecting cables of the
actuators into the cable openings of
the connectors.
► Close the terminators.
► Plug the connectors into the sockets of the corresponding
zones (see the fold-out page, Fig. 4 (Z1 -Z8)).
► Clamp the cables into the stress relief clamp.
► Secure the cable with the cable clamp.
Installation Disassembling
► Connect the cable to the connector in
accordance with the graphics (see
L
fold-out page, Fig. 4 (12)).
► Plug the connector into Socket 12
(see the fold-out page, Fig. 4).
► Secure the cable with the cable clamp.
Installation Disassembling
6.2.3. Connecting the thermal actuators
WARNING
Damage to the underfloor heating
controller!
► Take the technical data into account
at thermal actuators: Total of 3 A
maximum current, 250 mA continuous current per zone.
Each zone can control up to 3 actuators. 3 actuators can be
connected directly for zone 1, 2 for zone 2 and 1 each for
zones 3 through 5. One connection for the expansion module is available for each of the zones 6 through 8.
If more than 11 thermal actuators are to be connected to the
underfloor heating controller, the cables of the actuator must
be wired in a distribution box.
6.3. Boiler feedback
6.3.1. Connecting the boiler feedback via
an analog output (only HCE 80/
HCC 80) to external controllers
The analog output voltage changes depending on the valve
position.
► Strip the connections 5.5 mm (see fold-out page, Fig. 5).
► Connect the boiler feedback
in accordance with the following graphics (see the
fold-out page, Fig. 4 (9)).
Boiler feedback is possible with the controllers MCR 200,
MCR 40, ZG 252 N, Panther and Smile.
► Connect the controller inputs in accordance with the en-
closed instructions (earth input to Terminal 6, temperature
input to Terminal 5 of the underfloor heating controller).
TW
H/C
B+
7
Commissioning
A
With controller MCR 40, the temperature and earth inputs
are located at the following terminals:
Earth input
MCR 40
Low-voltage side
Temperature input
TW
78910456123
With controller ZG 252 N, the temperature and earth inputs
are located at the following terminals:
ZG 252 N
45610
789 1112
Earth input
TW
Temperature input
Depending on the design, the temperature selector and earth inputs are found on different terminals of the controller MCR 200.
6.3.2. Implementing a boiler feedback via
a wireless connection (with
HC60NG/R6660D)
The relay is switched on and off depending on the valve
setting.
6.3.3. Implementing a boiler feedback with
an integrated relay 42 V AC, floating
contact (only HCE 80R/HCC 80R)
The relay is switched on and off depending on the valve
setting.
► Strip the connections 5.5 mm (see fold-out page, Fig. 5).
► Connect the boiler feedback
in accordance with the following graphics (see the fold-out
page, Fig. 4 (9)).
B+
H/C
TW
6.4. Pump
6.4.1. Pump control
As soon as a zone is active, the pump is activated with a
time delay. The pump switches off as soon as all the valves
are closed.
LED (see fold-out page, Fig. 3 (6)) lights up green
The
when the pump is running.
6.4.2. Connecting a pump (230 V AC)
► Strip the connections 7 mm
(see fold-out page, Fig. 7).
► Connect the pump in accor-
dance with the following
graphics (see the fold-out
page, Fig. 4 (12)).
WARNING
Damage to the underfloor heating
controller!
Short-circuit due to incorrect installation.
► Connect all the controllers to the
same phase.
L
Pump
PE
Controller 1
L
N
PE
6.4.3. Installing an external antenna
Controller 2Controller 3
Pump
N
PE
Up to three underfloor heating controllers can be
connected to an antenna. When selecting the
operating site ensure that the function of the
antenna is not impaired.
► Only install the external antenna outside metal housings
(e.g. control cabinets).
► Install the antenna at a suitable location near the under-
floor heating controller. Ensure that a radio connection to
the setpoint adjuster exists.
► Strip the connections 5.5 mm (see fold-out page, Fig. 5).
► Connect the antenna in accor-
dance with the following graphics
(see the fold-out page, Fig. 4 (9)).
B+H/C
TW
Shield to 2
Second conductor to 1
► Close the terminals.
If several underfloor heating controllers are operated simultaneously, an antenna (internal or
external) may only be connected to one controller.
ntenna
Controller 1
Regler 1Regler 2Regler 3
Controller 2
Controller 3
B+B+B+
6.4.4. Closing the housing of the underfloor heating controller
► Place the housing cover back on (see fold-out page).
► Snap the left and right snap lock back into place.
► Tighten the screws on the top.
7. Commissioning
During commissioning, setpoint adjusters – and the time
programs of the radio setpoint adjuster CM67z if applicable
– are assigned to the temperature zones of the underfloor
heating controller. A room name is defined for each temperature zone at the Hometronic Manager.
7.1.1. Commissioning the underfloor heating controller
► Switch on the operating voltage.
The mains voltage LED (POWER) lights up.
8
Assigning zones and allocating room names (teach-in)
7.2. LED indicators on underfloor heating controller
The LEDs on the underfloor heating controller indicate the
operating mode of the Underfloor Heating controller and the
installed temperature zones.
Meaning of the 3 LEDs (see fold-out page, Fig. 3 (1,2,3)):
LED Display Meaning
POWER (green) Lights up Normal mode
(red)
Flashing Antenna fault display
(yellow)
Lights up Group alarm
Rapid
flashing
No device installed
7.3. Checking the signal strength of the
radio transmission
The signal strength of the radio transmission can be
checked for the transmitter and the receiver. Refer to Section "Checking radio transmission
" on Page 11.
7.4. Operating modes of the Underfloor
Heating controller
7.4.1. Normal mode
In normal mode the LEDs 1...8 show the position of the
actuators, see Fig. 3 (7) on the fold-out page:
Green Thermal drive opened
Off Thermal drive closed
7.4.2. Fault mode
The various faults are indicated by the zone LEDs in fault
mode. Refer to Section "Displaying faults" on Page 12.
7.4.3. Installation mode
In installation mode temperature zones are assigned to
the setpoint adjusters and the Hometronic Manager. Refer to Section "Assigning zones and allocating room
names (teach-in)" on Page 9.
7.4.4. Device display
The device display shows which devices are assigned to
the underfloor heating controller. Refer to Section
"Checking the configuration" on Page 11.
7.5. Cooling function
If the underfloor heating controller is used as a cooling regulator, this function has to be activated once during installation.
7.5.1. Activating the cooling function
► Keep the Mode button pressed for at least 4 seconds.
LED shows whether heating or cooling mode is
The
activated:
LED lights up green
LED lights up red
► Change the setting by pressing the installation button .
Cooling mode active
Heating mode active
The underfloor heating controller switches back
to normal mode automatically after 60 seconds.
You can also exit the installation mode by pressing the Mode button.
7.5.2. Switching between heating and
cooling
Switching between heating and cooling is carried
out via the changeover contacts 3 and 4.
► In order to activate the cool-
ing function connect the
changeover contacts 3
and 4, (see fold-out page,
Fig. 4 (9)), e.g. through an
external switch.
B+H/C
External switch
TW
7.5.3. Assigning room names
► Enter the room names in the zoning plan.
► Press the installation button
flashes.
The LED of zone 1 flashes red.
► Allocate the setpoint adjuster.
► Press the installation button
The LED of zone 1 flashes green.
► Allocate a time program for Heating.
► Press the installation button .
The LED of zone 1 flashes yellow.
► Allocate a time program for Cooling.
Repeat the steps until two room names are assigned to all
the temperature zones.
until the LED of Zone 1
.
8. Assigning zones and allocat-
ing room names (teach-in)
The following section explains how you can assign the various components to a temperature zone and allocate room
names if a Hometronic Manager is used.
Only one setpoint adjuster can be assigned to a
temperature zone. If a room temperature sensor
HCF 82 is combined with a remote setpoint adjuster HCW 82, i.e. assigned to the same zone,
first assign the remote setpoint adjuster and then
the room temperature sensor.
If the installation button at the underfloor heating controller is not pressed for 4 minutes, the
underfloor heating controller reverts automatically
8.1. Allocating the setpoint adjuster
In the following example the setpoint adjuster HCW 82 is
assigned to Zone 1. Subsequently the room name "Living" is
assigned to Zone 1 in the time program of the Hometronic
Manager.
► Keep the zoning plan at hand.
► Keep the installation button
to normal mode.
HCW 82, room temperature sensor
HCF 82
at the underfloor heating
controller pressed for 2 seconds.
LED lights up. The LED of Zone 1 flashes red.
The
9
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.