Honeywell HCC80, HCC80R, HCE80R, HCE80 PRODUCT DATA

HCE80/HCC80/HCE80R/HCC80R
UNDERFLOOR HEATING-ZONEING CONTROLLERS
PRODUCT DATA
FEATURES
Pluggable terminals for fast wiring connection because clamp contacts
Integrated pump relay for pump control Relay (230V AC non potential free contact)
Integrated antenna for the controllers HCC80 and HCC80R only
External antenna for HCE80 and HCE80R only
Up to 3 controllers can be connected to one antenna
external HRA80 or integrated antenna
Basic 5 configuration 5 zones
Easy extendable with HCS80 for up to 8 zones
Central operating via HCM200D / CM67z possible
LED indication for voltage, operation mode, status
and errors, RF check
Outputs for a maximum of 24 thermal actuators
Analogue output for boiler feedback to MCR200 /
MCR40/ Panther / Smile (only HCE80/HCC80)
Boiler control with integrated boiler relay potential free contact 42V (only HCE80R and HCC80R)
Boiler feedback in dependence of valve setting with HC60NG possible
Switchable between normally closed/open thermal actuators
Potential free switch over contact heating / cooling
GENERAL
The underfloor heating-zoning controllers are used for individual room temperature control. The applications are underfloor heating and radiator control as well. Each zone can be controlled with easily operating devices used as analogue or digital interface. The controllers are designed with an intelligent control algorithm (Fuzzy control) to keep the room setpoint temperature constant. Because of the used system components HCW82/HCF82/CM67z the measured room temperature will be sent to the controllers. The basic configuration of each controller HCE80/HCC80/HCE80R and HCC80R is 5 zones however it can be upgraded up to 8 zones by using the extension module HCS80.
Each zone can be controlled individually with time program by using the CM67z and HCM200D. With HCM200D up to 16 zones can be controlled with their own time program which save energy costs.
Two types of controllers are provided with internal and external antenna HRA80. Up to 3 controllers can be connected to one antenna. The controllers HCE80/HCE80R are connected with the external antenna HRA80. The controllers HCC80/HCC80R include the antenna on the circuit board. The antenna includes also the transceiver 868,3MHZ.
Because of the new wiring concept the thermal actuators can be installed very fast and pre wired without screws. All connectors are pluggable.
Cooling applications are also possible by switching from heating into the cooling mode with potential free change over contact.
Note: The controllers HCE80/HCC80/HCE80R and HCC80R have the same functionality exception the output for the boiler feedback. HCE80/HCC80: Analogue output for OTC controllers MCR, Panther, Smile (additional boiler relay not available) HCE80R/HCC80R: Additional boiler relay 42V (analogue output for OTC controllers is not available
EN0H0501GE51 R0805
HCE80/HCC 80../R
SPECIFICATIONS
Electrical Voltage supply : 230 V AC, 50 Hz + 10 % / -15
Power consumption :max. 1750 VA with connected
Integrated pump relay : 42 Volt potential contact, 6A Safety fuse : Ceramics safety fuse 230 VAC,
2,5 A swift, 5 x 20 mm
Optional : Expansion module HCS80 enhance the controller to 8 zones
Wiring Admissible cable types and lengths :
Thermal actuators
Cable diameter Cable length Cable cross-section Strip length
Network and pump connection 230 VAC
Outside cable diameter Cable length Cable cross-section Strip length
Antenna
Cable length Cable cross-section / type
Heating / Cooling, Boiler feedback
Cable length Cable cross-section / type
Pump6A) max180 VA without pump
Min. 3.5 mm/Max. 5.3mm Max. 400 m Max. 1.0 mm² 4 mm
Min. 8.0 mm/Max. 11 mm Max. 100 m Max. 1.5 mm² 7 mm
Max. 30 m JE-LiYCY 2x2x0.8 mm²;
JE-Y(St)2Y 2x2x0.8 mm²; 2 x 0.5 mm²
Max. 100 m JE-LiYCY 2x2x0.8 mm²;
JE-Y(St)2Y 2x2x0.8 mm²; 2 x 0.5 mm²
RF COMMUNICATION
RF band : 868,3 MHz Transceiver
(integrated in the antenna) The external HRA80 includes the transceiver used for
HCE80 and HCE80R HCC80 and HCC80R includes the antenna and transceiver
on the circuit board
Receiver class : 2 RF communication range : 30m in a residential building
environment
RF communication : short, high rate transmission to Technology minimize air time and avoid
collisions
ENVIRONMENTAL and STANDARDS
Mounting : Wall mounting or DIN track Measurements (WxHxD) : 350 x 52 x 82 mm Protection class : IP 30 Operating temperature : 0…+50 °C
Storage temperature : -20......+70 °C
Relative humidity : max. 5…93 % Fire protection class : 0 Authorization : C
EN0H0501GE51 R0805