HCE80/HCC80/HCE80R/HCC80R
UNDERFLOOR HEATING-ZONEING CONTROLLERS
PRODUCT DATA
FEATURES
• Easy and fast installation because the new wiring
design
• Pluggable terminals for fast wiring connection
because clamp contacts
• Integrated pump relay for pump control
Relay (230V AC non potential free contact)
• Integrated antenna for the controllers HCC80 and
HCC80R only
• External antenna for HCE80 and HCE80R only
• Up to 3 controllers can be connected to one antenna
external HRA80 or integrated antenna
• Basic 5 configuration 5 zones
• Easy extendable with HCS80 for up to 8 zones
• Central operating via HCM200D / CM67z possible
• LED indication for voltage, operation mode, status
and errors, RF check
• Outputs for a maximum of 24 thermal actuators
• Analogue output for boiler feedback to MCR200 /
MCR40/ Panther / Smile (only HCE80/HCC80)
• Boiler control with integrated boiler relay potential
free contact 42V (only HCE80R and HCC80R)
• Boiler feedback in dependence of valve setting with
HC60NG possible
• Switchable between normally closed/open thermal
actuators
• Potential free switch over contact heating / cooling
GENERAL
The underfloor heating-zoning controllers are used for
individual room temperature control. The applications are
underfloor heating and radiator control as well. Each zone
can be controlled with easily operating devices used as
analogue or digital interface. The controllers are designed
with an intelligent control algorithm (Fuzzy control) to keep
the room setpoint temperature constant. Because of the used
system components HCW82/HCF82/CM67z the measured
room temperature will be sent to the controllers. The basic
configuration of each controller HCE80/HCC80/HCE80R and
HCC80R is 5 zones however it can be upgraded up to 8
zones by using the extension module HCS80.
Each zone can be controlled individually with time program
by using the CM67z and HCM200D. With HCM200D up to 16
zones can be controlled with their own time program which
save energy costs.
Two types of controllers are provided with internal and
external antenna HRA80. Up to 3 controllers can be
connected to one antenna. The controllers HCE80/HCE80R
are connected with the external antenna HRA80. The
controllers HCC80/HCC80R include the antenna on the
circuit board. The antenna includes also the transceiver
868,3MHZ.
Because of the new wiring concept the thermal actuators can
be installed very fast and pre wired without screws. All
connectors are pluggable.
Cooling applications are also possible by switching from
heating into the cooling mode with potential free change over
contact.
Note: The controllers HCE80/HCC80/HCE80R and HCC80R
have the same functionality exception the output for the boiler
feedback.
HCE80/HCC80: Analogue output for OTC controllers MCR,
Panther, Smile (additional boiler relay not available)
HCE80R/HCC80R: Additional boiler relay 42V (analogue
output for OTC controllers is not available
EN0H0501GE51 R0805

HCE80/HCC 80../R
SPECIFICATIONS
Electrical
Voltage supply : 230 V AC, 50 Hz + 10 % / -15
Power consumption :max. 1750 VA with connected
Integrated pump relay : 42 Volt potential contact, 6A
Safety fuse : Ceramics safety fuse 230 VAC,
2,5 A swift,
5 x 20 mm
Optional : Expansion module HCS80
enhance the controller to 8
zones
Wiring
Admissible cable types and lengths :
Thermal actuators
Cable diameter
Cable length
Cable cross-section
Strip length
Network and pump connection 230 VAC
Outside cable diameter
Cable length
Cable cross-section
Strip length
Antenna
Cable length
Cable cross-section / type
Heating / Cooling, Boiler feedback
Cable length
Cable cross-section / type
Pump6A)
max180 VA without pump
Min. 3.5 mm/Max. 5.3mm
Max. 400 m
Max. 1.0 mm²
4 mm
Min. 8.0 mm/Max. 11 mm
Max. 100 m
Max. 1.5 mm²
7 mm
Max. 30 m
JE-LiYCY 2x2x0.8 mm²;
JE-Y(St)2Y 2x2x0.8 mm²;
2 x 0.5 mm²
Max. 100 m
JE-LiYCY 2x2x0.8 mm²;
JE-Y(St)2Y 2x2x0.8 mm²;
2 x 0.5 mm²
RF COMMUNICATION
RF band : 868,3 MHz Transceiver
(integrated in the antenna)
The external HRA80 includes the transceiver used for
HCE80 and HCE80R
HCC80 and HCC80R includes the antenna and transceiver
on the circuit board
Receiver class : 2
RF communication range : 30m in a residential building
environment
RF communication : short, high rate transmission to
Technology minimize air time and avoid
collisions
ENVIRONMENTAL and STANDARDS
Mounting : Wall mounting or DIN track
Measurements (WxHxD) : 350 x 52 x 82 mm
Protection class : IP 30
Operating temperature : 0…+50 °C
Storage temperature : -20......+70 °C
Relative humidity : max. 5…93 %
Fire protection class : 0
Authorization : C
EN0H0501GE51 R0805