Honeywell DU146M User Manual

AUTOMATIC BYPASS AND DIFFERENTIAL PRESSURE VALVE
FOR INSTALLATION IN DISTRICT HEATING SYSTEMS
Design
The automatic bypass and differential pressure valve com­prises:
Spring bonnet
Adjustment facility
Valve disc
Spring
Materials
Unpolished brass housing
Untreated brass spring bonnet
High-quality synthetic material adjus ter knob
Brass valve disc
Stainless-steel spring
EPDM seals
DU146 M
PRODUCT DATA
Application
The DU146 M automatic bypass and differential pressure valve is used to maintain constant differential pressure in a heating system. It reduces flow noise in a system, particularly as thermostatic radiator valves are closing. The boiler return temperature is raised and this reduces the corrosion caused by flue gas condensation. In addition, when radiator valves are closed it also maintains flow over the temperature sensor on the boiler to ensure proper operation of external tempera­ture compensating controls. On gas fired water heaters it guarantees a minimum flow circulation when thermostats or radiator valves are closed.
Features
• Simple installation between the flow and return pipe-
work
• Minimises flow noise
• No external controls required
• Differential pressure finely adjustable
• Problemlose Einregulierung durch eingebaute
Differenzdruck-Istwertanzeige
• Hinders boiler corrosion
• Setting value is in meters water column
• Tried and tested
Range of Applicati on
For pumped hot water heating systems
Specifications
Medium Operating temperature Operating pressure Differential pressure
Connection size
Hot water max. 130°C (230°F) max. 16 bar (232 P.S.I.) Adjustable between
0,05...0,5 bar (0,7...7,3 P.S.I.) Set during manufacture at
0,2 bar (2,9 P.S.I.) 3/4" and 1 1/4"
Copyright © 2001 Honeywell AG • All rights reserved EN0H-182GE25 R0301
DU146 M
Function
At equal pressure between the inlet and outlet side the valve is closed. The valve disc is pushed by a spring against the valve seat. If there is a pressure difference between the inlet and outlet sides, then a force is exerted on the valve disc and against the spring. If this force exceeds the force of the spring, then the valve begins to open in proportion to the rise in differential pressure and maintains a constant bypas s flow as indicated on the flow diagram.
Versions
A = Standard version Special version on request
Dimensions Flow rate V m3/hType R
L I H h
3/4" 36 50 160 100 3 DU146M-3/4A
1 1/4" 51 58 213 155 10 DU146M-1 1/4A
.
Ordering-No.
EN0H-182GE25 R0301 2 Honeywell AG • All rights reserved
Loading...
+ 2 hidden pages