Honeywell DT906AM, DT900AM Installation Instructions And Instructions For Use

DT900AM Series DUAL TEC® Motion Sensor for Commercial
and Light Industrial Applications—Installation Instructions
Step 1
Select mounting height.
Step 2
Carefully push screwdriver into slots to disengage latches and open top cover.
Step 3
DT906AM ONLY: Firmly insert screwdriver into slot in arrow and rotate PIR Mirror Selector to the correct range.
Step 5
Locate correct sensor range scale and rotate Vertical Adjustment Screw until the diamond corresponds to the sensor mounting height (coarse adjust).
Step 6
Set switch S3 to establish the sensitivity best suited to your appli­cation.
Step 7
Select INFORMER
®
mode with switch S2, if desired. (See INFORMER Mode section).
SENSITIVITY
HIGH (Pulse Count 1)
NORMAL (Pulse Count 2)
LOW (Pulse Count 3)
H* N
L**
S3
*Factory default setting; recommended setting for DT906AM. **Not connected.
Step 8
Carefully push screwdriver into slot to disengage latch and remove bottom cover.
Step 9
Unfasten screws and remove mount­ing plate from sensor. If required, remove the knockout to allow wire entry via electric metallic tubing or surface wiring conduit.
Step 10
Attach mounting plate to wall at desired height, using four screws (not supplied).
Step 11
Install M5 (#10) screw (not supplied) in wall 1.9 cm (3/4”) below mounting screw, as shown, for tamper activa­tion.
Step 12
Pull about 30 cm (12”) of wire from wall through the opening in the mounting plate and route wire to the terminal strip.
Step 13
Hang the sensor on the mounting plate hooks and fasten with the two mounting plate screws.
Step 14
Wire the unit as shown.
Use
0.8 - 1.5 mm (22-16 AWG).
NOTE: Secure wires to mounting plate with tie wraps.
Step 15
Loosen horizontal locking screw in sensor support base.
Step 16
Grasp housing and rotate it to the desired position (coarse adjust). If fine adjust is needed see Steps 21-
23.
NOTE: Reference marks = 5° change.
Step 18
Apply power to the sensor, and all the LED’s will start flashing rapidly.
Wait 90 seconds for the power-up self-test to finish, at which point, if there is no motion in the detection area, all the LED’s will be off, and the sensor will be ready for walk testing.
If the three LED’s do not go off after 90 seconds, refer to the Trouble­shooting section.
1.9 cm (3/4”)
Step 21
For fine horizontal adjustment, loosen the PIR horizontal fine locking screw on the PCB.
Step 23
Tighten the horizontal fine locking screw on the PCB.
NOTE: Fine adjustment allows for small changes (3 degrees right or left) between coarse settings.
Step 22
Rotate the horizontal fine adjust knob to the desired position.
30 cm (12”) minimum
*Factory default setting.
Step 4
Set switch S4 to establish microwave range.
Step 17
Tighten horizontal locking screw in sensor support base.
Step 24
Remove the jumper at J4 on the PCB to disable the LEDs after walk­testing, and complete installation by closing the top cover and replacing the bottom cover.
NOTE: Fine adjust may be needed during walk-test. (See Troubleshooting section.)
2 m (6’)
4 m (12’)
Step 20
Walk-test the sensor to check for adequate detection coverage and to verify the sensor is fully functional. Depending on the selected sensitiv­ity level, the sensor will alarm after taking between 2 and 4 steps in the detection pattern.
NOTE: If an on-going trouble, mask or INFORMER condition occurs, the LEDs will display a pattern that identifies the trouble. (See the Troubleshooting section).
Step 19
Turn the microwave potentiometer counterclockwise to decrease the microwave range to minimum.
During walk-test, gradually turn the potentiometer clockwise increasing microwave sensitivity until the desired range is obtained.
Optimal
Mounting
Height
2.3m (7’6”)
Mounting Location Guidelines
• Avoid direct or reflected sunlight
• Aim sensor away from windows, heating/ cooling devices or large moving objects.
• Sensor must have a clear line-of-sight to protected area
INFORMER MODE
OFF MODE 1 MODE 2
S2
OFF*
1 2
*Factory default setting (not connected).
Knockout
MODEL RANGE
Switch S4
MIRROR Selector
DT906AM 61 m (200’) OPEN* 200’ *
DT906AM
37 m (120’) CLOSED 120’
DT900AM 24.4 m (80’) OPEN* N/A
DT900AM 15 m (50’) CLOSED N/A
DT900AM Series DUAL TEC® Motion Sensor Product Information
6 8 10 12 80 120 200
1.8 2.4 3 3.7 24.4 37 61
Feet
Meters
Red
Yellow
Green
Normal
ON
Alarm
ON
Microwave
ON PIR
Power Up/Trouble
1
Rapid Flash
Rapid Flash
Rapid Flash
Mask
Rapid Flash
OFF
Rapid Flash
Microwave INFORMER
1,2
Rapid Flash
Rapid Flash
OFF
OPERATION MODE
Figure 1 DT900AM Printed Circuit Board (PCB)
LED INDICATORS
LED
PIR INFORMER
1,2
Rapid Flash
OFF
Rapid Flash
1
If a Trouble or INFORMER condition LED pattern disappears before being noted, initiate a self test (see Self Test section),
and the sensor will show the last LED pattern stored in the sensor’s memory. To clear this display, initiate another self test.
2
The noted LED patterns will only occur when no motion is present in the detection pattern. For additional microwave
and PIR INFORMER mode LED information, see the Troubleshooting section.
NOTE: LED’s operate as listed only when the LED’s are enabled (see LED Enable section).
Alarm Relay
Trouble Relay
Mask Relay
Normal
Closed
Closed
Closed
Intrusion
Open
Closed
Closed
Trouble
1
Closed
Open
Closed
Mask
1
Closed
Closed
Open
OPERATION MODE
RELAY OPERATION
Relay
PIR/MW INFORMER
2
Closed
Open
Closed
1
In a Trouble or Mask condition, the Trouble relay or Mask relay (respectively) will latch open until the condition has been
cleared. For more information, see the Troubleshooting section.
2
For information on INFORMER conditions, see the INFORMER Troubleshooting Matrix in the Troubleshooting section.
MASK FUNCTION
Normal Anti-Mask Operation
The DT900AM series features an anti-mask function that detects attempts to mask the sensor. The sensor sends active Infra-Red beams out into the sensor’s field-of-view, and monitors for reflections from materials that will block or cover the sensor. If the sensor registers a mask condition, it will open the mask relay and rapidly flash the red and green LEDs. To avoid false mask alarms, follow the mounting guidelines shown in Step 1.
Clearing an Anti-Mask Condition
Visually inspect the sensor, and remove any materials blocking the sensor’s view, and the sensor will normally reset automatically. If the sensor remains in a Mask condition, walk test the sensor to ensure a maximum detection range, and then cycle the sensor’s power to reset it.
LED ENABLE (Note: TS50131-2-4 Compliant)
The LED’s will only be enabled either by installing Jumper J4 or by connecting the Remote LED Enable terminal as per the table below (see also INPUT 1 & 2 in the Product Specifications section).
High/Not Connected Low
LED’s Disabled LED’s Enabled
Remote LED Enable
NOTE: Do not fit jumper J4 at the same time as the Remote LED Enable terminal is low, or the LED’s will not illuminate.
SELF TEST
The sensor will perform a series of self-tests in the following instances:
• On power up
• Automatically every hour during normal operation
• On installer initiation. Self tests can be installer initiated either by momentarily short circuiting the two self test pads on the PCB (see Figure 1), or by connecting the Remote Self Test terminal, as per the table below. (See INPUT 1 & 2 in the Product Specifications section.)
Remote Self Test
NOTE: When a self test error occurs, the Trouble relay will latch open and all three LED’s will flash rapidly. If the problem persists, refer to the Trouble­shooting section.
High/Not Connected Low
Normal Operation Self Test
INFORMER MODE
The INFORMER mode is a useful diagnostic tool for identifying environmental conditions that are liable to cause installation problems.
The INFORMER circuit counts the number of events registered by both the microwave and PIR technologies, and uses the resulting ratio to determine if either technology is working properly or is misapplied. Establish the INFORMER mode using switch S2 (see Step 7).
Mode 1: Set S2 to position 1. In Mode 1, 32 PIR events without a microwave event will cause the unit to go into PIR INFORMER. 128 microwave events without a PIR event will cause the unit to go into microwave INFORMER.
Mode 2: Set S2 to position 2. In Mode 2, 16 PIR events without a microwave event will cause the unit to go into PIR INFORMER. 16 microwave events without a PIR event will cause the unit to go into microwave INFORMER.
NOTE: The Mode 2 setting is not recommended. Use only if INFORMER indication is required quickly.
Disabled: To disable INFORMER function, set S2 to the open (OFF) position (factory default setting).
When an INFORMER condition occurs, the trouble relay opens, and the LEDs display an INFORMER trouble code (see the INFORMER Troubleshooting Matrix in the Troubleshooting section).
NOTE: One LED indication does not relate to one PIR or Microwave event.
TROUBLESHOOTING (Continued)
Problem: The sensor’s PIR range is too long or short. Explanation: Various mounting locations may require fine vertical adjustment (e.g., due to uneven walls
or floors, etc.). Solution: During the walk-test, if the PIR is short-ranged, turn the Vertical Adjust Screw counterclockwise. If the PIR is over-ranged, turn the Vertical Adjust Screw clockwise. (See Step 5.)
Problem: A combination of the sensor’s LED’s are flashing slowly when there is no motion in the detection area. Explanation: INFORMER mode is selected on the sensor, and there is a potential false alarm source in the
local environment. Solution: The table below describes two trouble alerts which are reported by the INFORMER circuit. To use this troubleshooting matrix:
1) Find the trouble alert that describes the condition of the walk-test LEDs (with no motion in the area).
2) Walk-test the sensor, carefully watching the reaction of the diagnostic LEDs.
3) Refer to the Possible Causes column of the matrix for an explanation of the way in which the diagnostic LEDs reacted to the walk-test.
4) If no environmental sources can be found, initiate a self test. If the sensor fails the self test, replace the sensor. If not, relocate the sensor and re-test.
NOTE: If on entering the detection pattern the LEDs go off, the INFORMER LED pattern can be retrieved by initiating a self test. (See Note 1 in the LED Indica­tors section.)
INFORMER Troubleshooting Matrix
MW environmental problem MW unstable MW range too long PIR was blocked
(Pattern disappears)
Reaction of LEDs
to Walk-Test
Condition of LEDs
with No Motion
MW
(Yellow)
ALARM
(Red)
PIR
(Green)
PIR
(Green)MW(Yellow)
ALARM
(Red)
RATIO
IMBALANCE
RATIO
IMBALANCE
Type of
Problem
RATIO
IMBALANCE
RATIO
IMBALANCE
PIR environmental problem PIR unstable MW range too short
Possible Causes
PIR range too short PIR aimed wrong PIR not reporting
MW range too short MW not reporting
LED Legend:
(Pattern disappears)
(Microwave INFORMER)
(PIR INFORMER)
PRODUCT SPECIFICATIONS
Range:
DT906AM
200’ Mirror - 61 m x 3 m (200' x 10') 120’ Mirror - 37 m x 3 m (120' x 10')
DT900AM
24.4 m x 21 m (80' x 69')
Power requirements:
10 - 15 VDC 50 mA (max) at 12 VDC AC Ripple: 3V peak-to-peak at nominal 12 VDC
Alarm relay:
Energized Form C 25 VDC, 125 mA 22 ohm series protection resistor
Trouble relay:
De-energized Form B (Normally closed) 30 VDC, 25mA
Mask relay:
De-energized Form B (Normally closed) 30 VDC, 25mA
Tamper Switches:
Wall, top & bottom covers 30 VDC, 25 mA (NC)
INPUT 1 (Remote LED Enable) & INPUT 2 (Remote Self Test):
Active low (0 to 1.5V) Inactive high (5 to V+ / Unconnected)
Microwave frequency:
X-Band; 10.687 GHz
PIR white light immunity:
6500 Lux typical
RFI immunity:
30 V/m, 10 MHz - 1000 MHz
Operating temperature:
-10
o
to 55o C / 14o to 131o F
(Indoor use environment)
Relative humidity:
5% to 95% relative humidity (non-condensing)
PIR fields of view:
61 m (200’) Range 37 m (120’) Range 24.4 m (80’) Range
2 long 6 long 22 long 6 intermediate long 4 intermediate long 18 intermediate long 4 intermediate 4 intermediate 16 intermediate 4 intermediate lower 8 lower 12 intermediate lower 8 lower 2 down 8 lower 2 down 2 down
Sensitivity:
2 - 4 steps within field-of-view
Dimensions:
20 cm x 16.5 cm x 15.2 cm 8” x 6 1/2” x 6”
Weight:
1.36 kg Packaged Product Approx.: 1.60 kg
Approvals/listings:
CE PD6662:2004, prEN 50131-1:2004 and TS50131-2-4:2004 Security Grade 3, Environmental Class II.
Suitable for connection to an EN 60950 Class II Limited Power Source in European installations.
Note: In TS50131-2-4 compliant installations, mount the sensor at 2.3 m, select the high sensitivity setting and set switch S4 to OPEN.
To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our Website, http://www.security.honeywell.com/hsce/international/index.html. For any additional information regarding the compliance of this product to any EU specific requirements, please contact:
Quality Assurance Department, Honeywell Security & Custom Electronics, Newhouse Industrial Estate Motherwell, Lanarkshire ML1 5SB, Scotland, United Kingdom.
Tel: +44(0)1698 738200 Email: UK64Sales@Honeywell.com
TROUBLESHOOTING
Problem: All three LED’s are flashing rapidly (LED’s are enabled), and the Trouble relay is activated. Explanation: The sensor is in one of the following three conditions:
Power Up: The sensor is still warming up. Low Voltage: The sensor’s supply voltage is too low. Self Test Failure: The sensor has failed one of its internal tests.
Solution: Wait for at least 90 seconds for the sensor to power up, and then ensure that the power supply is greater than 8 VDC. If the three LED’s are still flashing rapidly, the sensor is faulty and should be replaced.
Problem: The sensor’s LED’s are not illuminating. Explanation: The sensor is not set up correctly. Solution: Check that either the Jumper J4 is fitted or that the Remote LED Enable terminal is connected to
0V, but NOT both at the same time. If only one of these options is selected, and the LED’s still do not illuminate, the sensor is faulty and should be replaced.
DETECTION PATTERNS
Honeywell, IntelliSense, DUAL TEC and INFORMER are registered trademarks of Honeywell International Inc. All right reserved. Made in China
Copyright 2006 Honeywell International Inc. 5-051-367-00 Rev A
Please contact your local authorised Honeywell representative for product warranty information.
37 m (120’) Range
Patterns for: DT906AM 61 m (200’) Range
TOP VIEW
SIDE VIEW
TOP VIEW
Patterns for: DT900AM
24.4 m (80’) Range
SIDE VIEW
TOP VIEW
SIDE VIEW
INPUT 1
INPUT 2
=LED is OFF
= LED is Flashing Rapidly
= LED is Flashing Slowly
Loading...