Honeywell DMG 971 Installation Instructions And Maintenance

1
A Honeywell Company
certified Qualitysystem
ISO 9001 / EN 29001
Reg. Nr. 10529
INTRODUCTION
The burner control box DMG 971 controls and supervises power burner for gas and dual fuel. The control box is approved and certified according the relevant European standards. The use on direct air heaters according DIN 4794 is also possible. The microprocessor- based programming sequence ensu­res extremely stable timings independent of voltage varia­tions, ambient temperature and/or switch-on cycles. The built-in information system not only provides a continuous monitoring of the actual state of the box (very helpful es­pecially for monitoring the start-up phase) but also informs about the cause of a possible lock out. The lock out cause is stored in such a way that it can be retrieved even after a power failure. The control box is designed for maximum safety in case of fluctuations in the voltage supply. If the mains voltage drops below the permitted level, operation is interrupted and the control box automatically prevents the start sequence from being repeated. In this way, the safety of the system is not put at risk by a drop in the mains voltage. This low-voltage protection works not only during start-up but also perma­nently during operation.
CONSTRUCTIONAL FEATURES
Microprocessor, electronic components, output relais and flame amplifier are placed on two printed circuit boards. These plus the lockout- and reset circuit are well protected inside a flame resistant, plug-in type plastic housing. The reset switch for reset / remote lockout with its built-in LED for displaying the information system plus the central fixing screw are placed on top of the housing. The wiring base S98 is equipped with spare- and extraterminals and allows together with a variety of cable entry points utmost flexibility of electrical wiring.
The DMG 971 is funstionally compatible to MMI 811 and MMI 811.1
Please note: Is the DMG 971 to be used to replace the MMI 811 or 811.1, care has to be taken to make sure the air proving switch (LW) is wired between terminals 4 and 7 and not like on the MMI between 5 and 7.
DMG 971
Gas Burner Safety Control
For 2-stage forced draught and combi oil/gas burners
Possible flame detectors:
- Ionisation probe
- Infrared flicker detector 1020
- UV flame sensor UVD 971
TECHNICAL DATA
Operating voltage 220 / 240 V (-15... +10%)
50 Hz ( ±5%)
Fuse rating 10 A fast, 6 A slow Power consumption ca. 15 VA Max. load per output
- term. 3 ignition trafo 1.5 A, cos ϕ 0.2
- term. 4 motor 2.0 A, cos ϕ 0.4
- term. 5 + 6 solenoid valves 1.0 A, cos ϕ 0.4
- term. B alarm indicator 1.0 A, cos ϕ 0.4 total load 5.0 A, cos ϕ 0.4
max. 10 A during 0.5 sec Air proving switch 1 working contact 4 A, 230V Stray light monitoring 5 sec Sensitivity (operation) 1 µA Min. required ion. current 1.5 µA Sensitivity for stray light 0.4µA Ionisation probe insulation Probe - earth
greater than 50 M stray capacity Probe - earth
less than 1000 pF cable lenght < 3 m Flame detectors
IRD 1020 side-on or end-on viewing
UVD 971 end-on viewing Weight incl. Wiring base 190 g Mounting position any Protection class IP 40 Approved ambient parameter for control and flame detector max. 95% at 30° C
- for operation -20° C... +60° C
- for storage -20° C... +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 298 and EN 230, as
well as all other relevant Directives and standards
Classified acc. to EN 298 FTLLXN
Timings (sec.)
0737.11-00-e/01/99
Model waiting time max. reaction time for supervised pre-ignition ignition time Stray light safety time delay
start air proving switch pre-purge time time total monitoring 2nd-stage
tlw tv1 tvz tz tf ts tv2
01 0 60 24 3 5 5 3 12.5
2
APPLICATION FEATURES
1. Information system
The information system is microprocessor based and re­ports on all aspects of burner control box operation and flame supervision. It informs continuously about the actual programming sequence the unit is just performing. Besides monitoring of the programming sequence it also allows to identify errors during start-up of operation without any additional testing devices. The automatically performed diagnosis is a valuable tool which facilitates service/ maintenance work and therefore saves costs. The analyses of the error cause can be done directly on stage or if not possible afterwards as the lock out reason is stored in a non­volatile lock out mode memory. The information system communicates with the outside world using a LED (the used Flash-Code is similar to the Morse-Code). The messages are optically transmitted by a appropriately flashing LED. Using an additional terminal (optional), the messages can be recorded and displayed in easy readable form.
1.1 Programming sequence display
The built-in microprocessor controls not only the pro­gramming sequence but the information system too. The individual phases of the programming sequence are displayed as Flash-Code. The following messages can be distinguished:
Message Flash-Code waiting for ❘ ❘ .
air proving switch pre-purge ❘ ❘ ❘ .
tv1 pre-ignition ❘ ❘ ❘ ❘ .
tvz safety time ❚ ❘ .
ts delay 2nd stage ❚ ❘ ❘ .
tv2 running ❘ _ low mains voltage ❘ ❚ ❚ _
Description
= short pulse= long pulse
. = short pause _ = long pause
1.2 Lock-out diagnoses
In case of a failure the LED is permanently illuminated. Every 10 seconds the illumination is interrupted by a flash code, which indicates the cause of the error. Therefore the following sequence is performed which is repeated as long as the unit is not reset.
Sequence:
illuminated phase dark phase Flash-Code dark phase
❘ ❚ ❚ ❚ ❚
for 10 sec for 0.6 sec for 1.2 sec
Error diagnosis Error message Flash-Code Possible fault lock out ❘ ❚ ❚ ❚ ❚ within lock out safety time
safety time no flame establishment stray light ❘ ❘ ❚ ❚ ❚ stray light
during monitored phase, detector may be faulty
air proving switch ❚ ❚ ❘ ❘ ❘ air proving switch in closed position contact welded
air proving switch ❘ ❘ ❘ ❚ ❚ air proving switch does not time-out close within specified time
air proving switch ❘ ❘ ❘ ❘ ❚ air proving switch opens opened during start or operation
loss of flame ❚ ❚ ❚ ❚ ❘ loss of flame during
operation
Flash-Code for manual lock out anual/external ❘ ❘ ❚ ❚ ❚ _ ❚ ❚ ❚ ❚ ❚
lock out (see also 3. lock out and reset)
2. Flame detection
The following types of flame detectors are suitable: – Ionisation probe, temperature resistant material, well
insulated (material and insulation same as for ignition electrode).
– Infrared-flicker detector type IRD 1020 with mounting
flange M 93 or the UV solid state flame sensor UVD 971. Flame detection using an ionisation probe is only possible in conjunction with mains supplies which provides a neu­tral earth connection. Connecting the IRD 1020 or UVD 971 the correct wiring has to be observed.
2.1 Stray light monitoring
The stray light check is performed at the end of the pre­purge time for thr duration as mentioned in the technical datas.
DMG 971
Loading...
+ 4 hidden pages