Honeywell CD3200 User Manual

Page 1
EN1I-6312
USER’S MANUAL
CD3200
THYRISTOR UNIT
Up To 110A
Rev. 12/2004
Page 2
Page 3
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
1 www.honeywell.com/imc
CD3200 Thyristor Unit up to 110A
Index:
1. Glossary 5
1.1 Terminology 5
1.2 Input signal 5
1.3 Power feed back 5
1.4 What is a thyristor unit 5
2. Technical specifications 6
2.1 General Features: 6
2.2 Input features 7
2.3 Output features 7
2.4 Derating curve 7
3. Ordering information 8
4. Installation and wiring information 9
4.1 Identification of the unit 9
4.2 Installation 9
4.3 Dimensions 10
4.4 Dimension CT (Heater Break HB) 10
4.5 Fixing holes 11
5. Wiring Instructions 12
5.2 Cabling detail 13
5.3 Wiring connection 15
5.4 LED Status Table 17
6. Start up 18
6.1 To remove the board 19
6.2 Auxiliary supply 20
6.3 Analog input 21
6.4 Heater Break Alarm 23
6.5 Current Limit Tuning 28
7. Thyristor firing mode 29
7.1 Phase Angle + Current Limit (PA) 29
7.2 Configurator 30
8. Fuse and fuseholder for UL certification units 32
8.1 Fuse and Fuse Code 32
8.2 FuseHolder size 33
9. Fuse and fuseholder for CE mark unit 34
9.1 Fuse and Fuse Code 34
9.2 FuseHolder size 35
Page 4
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 2
10. Modbus communication 36
10.1 Physical requirements 36
10.2 ModBus RTU protocol 36
10.3 Word parameters 41
10.4 Address Configuration 48
11. Maintenance 51
11.1 Trouble Shooting 51
11.2 Repairing procedure 52
11.3 Fans 52
11.4 Servicing 52
11.5 Warranty conditions 52
Page 5
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
3 www.honeywell.com/imc
CAUTION
Thyristor units are used in power industrial equipment. When the thyristor unit is working, there are on the unit the following voltages
- Maximum main supply voltage on power terminals up to 600V.
- Auxiliary supply 230-460Vac.
- Fan voltage 230Vac 50/60Hz Power consumption 14W. Don't remove the plastic cover which provides adequate protection against electric shock. Don’t use this thyristor in aerospace and nuclear application.
Electric Shock Hazard
When thyristor unit has been connected to main supply voltage and is switched off, before to touch it be secure that the unit is isolated and wait at least one minu te to permit to discharge internal capacitors. Thus be secure that:
access to thyristor unit is only permitted to specialized personnel;
the authorised personnel must read this manual before to have access to the unit;
the access to the units must be denied to unauthorized personnel.
Important warnings
Local regulations regarding electrical installation should be rigidly observed.
Safety regulations must be rigidly observed.
Don't bend components to maintain insulation distances.
Protect the units from high temperature, humidity and vibrations.
Don't touch components to prevent elettrostatichal discharges on them.
Verify that all ratings are in line with real needs.
If authorized personnel must measure voltage, current etc. on units, take away rings and other
jewels from fingers and hands.
Authorized personnel working on thyristor unit under power supply voltage must work on insulated board. Be secure that board is not connected to earth.
This listing does not represent a complete enumeration of all necessary safety cautions.
Page 6
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 4
Protection
CD3000 thyristor family has a polymeric plastic cover in compliance to International specification IP20. To understand if IP20 protection is sufficient should be evaluated the installation place where the units are installed. Open Type Equipment. Maximum surrounding air temperature 40°C.
Earth
CD3000 family has isolated heatsink. For safety connect the heatsink to earth to avoid shocks in case that circuit board or thyristors lost insulation. Earth impedance should be correspondent to local earth regulation. Periodically the earth efficiency should be inspected.
Electronic Supply
CD3000 family electronic circuit should be supplied by dedicated voltage supply for all electronic circuit but not in parallel with contactor's coil, solenoids and other inductive or capacitive loads. It's recommended to use a shielded transformer.
Electromagnetic compatibility
Our thyristor unit has an excellent immunity to electromagnetic interferences if all suggestions contained in this manual are respected. In respect to a good Engineering practise, all inductive loads like solenoids contactor coils should have a filter in parallel.
Emissions
All thyristor switching at high speed generate some radiofrequency disturbance. CD3000 serie complies with EMC rules for CE mark. In many installations near electronic devices has not been noted problems. If radiofrequency device at low frequency are used near the thyristor unit, some precautions should be taken like line filters and shielded cables for input signal an d for load cables.
CU
LISTED
S
U
L
®
NOTE
We reserves the right to apply modifications to the our products without any advice.
Page 7
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
5 www.honeywell.com/imc
1.Glossary
1.1 Terminology
V: voltage power supply. I: the full circulating current in thyristor unit. P: total load power.
1.2 Input signal
SSR: This input type is a square waveform generated by a temperature controller. AN: Analog input. IRS: Communication command.
1.3 Power feed back
Feedback: supply voltage fluctuation changes the power to the load. To overcome this effect the voltage supplied to the load is measured and compared with power demand from controller, the error signal is used to automatically hold the power at demanded level.
1.4 What is a thyristor unit
A thyristor unit is semiconductor device which acts as a switch formed by two thyristors in antiparallel. To switch on the alternating current the input signal will be on and the thyristor will switch off at first zero crossing voltage with no input signal. The benefits of thyristor units compared with elettromechanical contactors are numerouses: no mooving parts, no maintenance and capacity to switch very fast. Thyristors are the only solution to control transformers and special loads that change resistance with temperature and with age.
LOAD
Page 8
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 6
2. Technical specifications
2.1 General Features:
Operating temperature
0÷40°C for higher temperature see derating curve
Voltage power supply 24V minimum, 480V max and 600V on request Input signal SSR
4÷20mA 0÷10V potentiometer (10k ohm) customer configurable with automatic zero/span calibration
Firing mode One of these firing modes can be configured on line via serial port
Phase Angle + Current Limit (PA) Soft Start + Phase Angle + Current Limit (S + PA)
Auxiliary voltage supply 230V ±15%; 10VA power consumption
440V ±15%; 10VA power consumption
Fan voltage supply 230V ±15%;
110V ±15%; on request
Heater break alarm
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors. Latching alarm plus reset. Relay output 0,5A at 125V
Feedback
Voltage feedbak (V) Square Voltage feedbak (V²) Power feedback (VxI) (option)
Serial communication RS485 Modbus protocol (option) Mounting
Din rail mounting up to 45A
Bulk head over 45A
Protection IP20
Page 9
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
7 www.honeywell.com/imc
2.2 Input features
Input signal
Input
Impedance
Analog 0÷10V 8200 ohm
Analog 4÷20mA 100 ohm
Potentiometer 10Kohm
8200 ohm
2.3 Output features
NA=not Available
Current Voltage range Ripetitive peak
reverse voltage
Latching
current
Max peak one cycle
Leakage
current
I2T value for
fusing
Frequency
range
Power
loss
Isolation
Voltage
(A) (V) (440V)
(500V) (mAeff)
(10msec.)
(A)
(mAeff) tp=10msec (Hz)
I=Inom
(W)
Vac
15A 24÷440 1200 NA 150 230 15 610 47÷70 18 2500
25A 24÷440 1200 NA 150 230 15 610 47÷70 30 2500
35A 24÷500 1200 1600 250 400 15 780 47÷70 42 2500
45A 24÷500 1200 1600 250 600 15 1800 47÷70 54 2500
60A 24÷500 1200 1600 450 1000 15 4750 47÷70 72 2500
90A 24÷500 1200 1600 450 2000 15 19200 47÷70 108 2500
110A 24÷500 1200 1600 450 1350 15 8830 47÷70 137 2500
2.4 Derating curve
1
0.8
0.6
0.4
0.2
0
45 55 65 75 85
K
°C
I = I x K
NOMMAX
Page 10
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 8
3. Ordering information
Model CD3200
1 2 3 4 5 6 7 8
CD3200
Ex:CD3200 90A/ 400/ 480/ 460/ SSR/ ZC/ V2/ UL
1 Nominal current of CD3200M
15A 45A 110A 25A 60A 35A 90A
2 Operating Load Voltage (incoming voltage supply)
Specify the value of the line supply.
3 Max VOLTAGE of CD3200
480V 600V The voltage on the identification label must be equal or more than operating voltage. The minimum voltage supply to the load is 24V.
4 Auxiliary Voltage
230V 200÷230V ±15%; 10VA 460V 300÷460V ±15%; 10VA 600V 600V ±15%; 10VA (on request)
5 Input
SSR 4÷30VDC 0-10V 0÷10V analog input 4-20mA 4÷20mA analog input 10K pot Potentiometer
6 Firing
PA Phase Angle + Current Limit S + PA Soft Start + Phase Angle + Current Limit
7 Feedback
V Voltage feedback (V) V2 Square Voltage feedback (V²) VxI Power feedback (VxI) (option)
8 Options
COMM MODBUS protocol in RS485 is standard CD-KP External Keypad HB Heater Break Alarm FAN110
Fan voltage supply 110VAC ± 15% (std 230VAC ± 15%) 14W
50/60Hz UL UL Certification EF External fuse and fuseholder NF No Fuse
Page 11
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
9 www.honeywell.com/imc
4.Installation and wiring information
4.1 Identification of the unit
Before to install the CD3200 unit examine for damages or deficiencies. If any is found, notify the carrier immediately. Check that the product features shown on CD3200 cover and identification label corresponds to that ordered.
INPUTAMPS AUX. FIRING OPT.
0-10V15 60
240V
____
4-20mA25 90
440V
SC DT SSR35 110 POT45
___
____
PA
S.S
ZC
An identification label provides all the informations regarding the factory settings of the unit. This label is on the board inside the unit, as represented
4.2 Installation
CD3200 unit should be always mounted in vertical position to improve air cooling on heatsink.
Maintain minimum distances in vertical and in horizontal as below represented. Don’t install in proximity of hot elements and near units generating electromagnetic interferences.
A
IR OUTPUT
A
IR INP UT
15cm
2 cm
When more units are mounted inside a cubicle provide air circulation as below represented. Sometimes it is necessary to provide a fan to have a better air circulation.
Page 12
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 10
4.3 Dimensions
Size W(mm) H(mm) D(mm)
15A (S0C) 63 120 120
25A (S0C) 63 120 120 35A (S3C) 85 120 120 45A (S3C) 85 120 120 60A (S7C) 148 120 159 90A (S7C) 148 120 159
110A (S8C) 148 138 159
4.4 Dimension CT (Heater Break HB)
8
1
2
39
39 20
Page 13
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
11 www.honeywell.com/imc
4.5 Fixing holes
A
B
C
D
Size A(mm) B(mm) C(mm) D(mm)
15A (S0C) 110 - - -
25A (S0C) 110 - - -
35A (S3C) - 110 - -
45A (S3C) - 110 - -
60A (S7C) - - 110 65
90A (S7C) - - 110 65
110A (S8C) - - 110 65
Page 14
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 12
5. Wiring Instructions
Warning: this procedure can be done just by specialized personnel.
CD3000M unit has isolated heatsink. For safety connect the heatsink to hearth using its terminal with hearth symbol. CD3000M can be susceptible to airborne interferences from near equipment or from interferences on main supply, so a number of precautions must be taken.
Contactors coils and chokes must have in parallel a RC filter and must be supplied with a
different voltage line.
All input/output signal must use screened bifilar wires.
Signal input and output must not routing in same cable try and must not be parallel.
Local regulations regarding electrical installation should be rigidly observed.
3.3.2 Auxiliary terminals
Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage.
Terminal Description
1 - External Calibration command 24Vdc max 2 + External Calibration command 24Vdc max 3 Reset 4 Reset 5 + Output Command signal to CD3200 (Internal Connections) 6 - Output Command signal to CD3200 (Internal Connections)
A2+ + Input command signal 4÷20mA, 0÷10V
A1- - Input command signal 4÷20mA, 0÷10V
7 RS485 A 8 RS485 B
9 Output +8Vdc stabilized 1mA MAX potentiometer power supply 10 Common relay H.B. alarm 11 NC/NO H.B. relay alarm 12 External Current Profile 13 CT input with H.B. option 14 CT input with H.B. option 15 Nc not connected 16 Auxiliary supply voltage 240-440Vac 17 Ground 18 Auxiliary supply voltage 240-440Vac
5.1.1 Power Terminals
Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage
Terminal Description
L1 Line Input T1 Load Output
Page 15
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
13 www.honeywell.com/imc
5.2Cabling detail
Use 75°C copper (CU) conductor only, provided with the terminal type indicated below. (Utiliser conducteur de cuivre (CU) pour 75°C seulement , avec les terminal suivants )
Current/courant
Torque/couple
Lb-in (N-m)
Wire/cable
Wire
terminal/terminal
15A, 25A, 35A, 45A 26.6 (3.0) 18-8
UL Listed (ZMVV) Wire Pin Terminal
(terminal avec cosse)
60A, 90A, 110A 70.8 (8.0) 18-1
UL Listed (ZMVV)
- Fork/Spade Terminal (terminal avec cosse a fourche)
- Copper Tube Cr. Lug (cosse tubulaire a plage étroite)
Page 16
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 14
Power terminals wire details:
Current Supply Load
Cable Clable
mm
2
AWG
Screw
M
mm
2
AWG
Screw
M
15A 4 12 M5 4 12 M5 25A 6 10 M5 6 10 M5 35A 10 8 M5 10 8 M5 45A 10 8 M5 10 8 M5 60A 16 6 M6 16 6 M6 90A 35 3 M6 35 3 M6
110A 35 2 M6 35 2 M6
Auxiliary connectors and earth:
Current Auxiliary Supply Earth
Cable Clable
mm
2
AWG
mm
2
AWG
Screw
M
15A 0,50 18 4 12 M4 25A 0,50 18 4 12 M4 35A 0,50 18 6 10 M5 45A 0,50 18 6 10 M5 60A 0,50 18 6 10 M5 90A 0,50 18 10 8 M5
110A 0,50 18 16 6 M5
Page 17
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
15 www.honeywell.com/imc
5.3 Wiring connection
5.3.1 CD3200 15-25A
POWER UNIT
Input
CT
Reset
-
+
RS485-B
1
65
7 8 9
10 11
12 13 14 15
16 17 18
2
A2+3A1-
4
RS485-A
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
L1 L2
CT
**
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE:
IMPORTANT
To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
5.3.2 CD3200 35-45A
POWER UNIT
Input
CT
Reset
-
+
RS485-A
162738495
10
RS485-B
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
1
65
7 8
9 10 11 12 13
14 15
16 17 18
2
A
2+
3
A
1-
4
CT
L1 L2
**
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE: IMPORTANT To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
Page 18
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 16
5.3.3 CD3200 60-90A
Input
CT
Reset
-
+
RS485-A RS485-B
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
1
65
7 8
9 10 11 12 13 14 15 16 17 18
2
A
2+
3
A
1-
4
CT
L1 L2
**
L1
T1
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE:
IMPORTANT
To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
5.3.4 CD3200 110A
Input
CT
Reset
-
+
RS485-A RS485-B
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
1
65
7
8
9 10 11 12 13 14 15 16 17 18
2
A
2+
3
A
1-
4
CT
L1 L2
**
L1
T1
FAN
220 Vac
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE:
IMPORTANT
To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
Fan voltage supply standard 230VAC ±15% 14W 50/60Hz or optional110VAC ±15% 14W 50/60Hz
Page 19
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
17 www.honeywell.com/imc
5.4 LED Status Table
LED STATUS DESCRIPTION
PW
Auxiliary supply is not connect
Auxiliary supply is connect
SC
SCR OK
SCR short circuit
HB
Laod OK
Load Fault
ON
OFF Condition(Load IS NOT Powered)
ON Condition(Load IS Powered)
= OFF
= ON
Page 20
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 18
6. Start up
Before to supply the thyristor unit:
verify that load current equal or less than nominal; For resistive load For indu ctive load
I
=
V
P
Tot
I
=
V
cos
φ
P
Tot
verify that there is no short circuit on load;
verify that main voltage equal or less than nominal;
verify that all auxiliary connections are right and syncronized to main voltage!!!;
Fan voltage equal than nominal (230V std, 120V optional)
After which supply thyristor unit giving the maximum input signal and verify that load current is equal or less than thyristor unit nominal current.
Warning: this procedure can be done just by specialized personnel.
The thyristor unit is delivered configured and tuned in line with customer requirements. If it’s necessary to change on site the configuration, procede as below specified.
Page 21
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
19 www.honeywell.com/imc
6.1To remove the board
1 Remove plastic Cover 2 Pull the PCB
Page 22
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 20
6.2 Auxiliary supply
Warning: this procedure can be done just by specialized personnel.
To change auxiliary supply voltage sold the correct link-jumper on main PCB
230V Auxiliary supply
Main PCB
460V Auxiliary supply
J9
J10
J11
J9
J11
J10
J9
J10
J11
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer.
If load voltage is not included in range of 230V ±15% or 460V +15% provide an external transformer with primary equal to load voltage and secondary 230V if your unit is setted to 230V.
Page 23
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
21 www.honeywell.com/imc
6.3 Analog input
Warning: this procedure can be done just by specialized personnel.
6.3.1 Setting Analog input
To change input type remove plastic cover and configure jumpers as represented below:
Jumpers Configuration FRONT PCB Input
J7 J16 J17
SSR
ABC
ABC
ABC
0÷10V
ABC
ABC
ABC
4÷20MA
ABC
ABC
ABC
Front PCB
Page 24
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 22
6.3.2 Tuning Analog input
Warning: this procedure can be done just by specialized personnel.
UNIT OFF
ST AR T TUNE
END
TUNE
Mantain Kay CAL pushed
and Switch ON
SSR input (3-30V)
is tuned
Analog input
is tuned
Wait for more than 10 sec.
from start flashing
yellow and red leds
Within 10 sec. from start
flashing yellow and red leds
push again moment ary
CAL Key
Yellow led only is
flashing, apply
0 input Signal
I.E.: 0V for 0-10V
4mA for 4-20mA
Red led only is
flashing, apply
10V for 0-10V input
or
20mA for 4-20mA input
Now press CAL Key again
Now press CAL Key again
The leds will stop flashing
Release key
when red and yellow
led are ON
Y ello and red leds
are flashing
SSR
ANALOG
INPUT TYPE
ON
ON
ON
2sec.
S/C
S/C
S/C
H.B.
H.B.
H.B.
ON S/C H.B
ON S/C H.B
0 Signal
Max Signal
Page 25
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
23 www.honeywell.com/imc
6.4 Heater Break Alarm
Heater Break Alarm is a microprocessor based circuit to diagnose partial or total load failure and short circuit on SCR and fuses failure.
discrimination better than 20%;
latching alarm plus reset;
relay output 0.5A at 125VAC.
Minimum current 3A. If load current is below this value make two turns or more around current transformer. H.B. circuit also diagnose fuse failure.
H.B. circuit reads load current via a current transformer 25-50/0.05 or 100/0.05 depending on thyristor size.
6.4.1 Heater Break Alarm indication
LED STATUS DESCRIPTION
SC
SCR OK
SCR short circuit
HB
Laod OK
Load Fault
: LED off : LED on
The thyristor unit is supplied with a normally closed (N/C) contact.
In alarm condition and without auxiliary voltage the contact is closed (relay coil not energized). In normal condition (no alarm) the contact is open (relay coil energized).
6.4.2 Reset
To reset Heater Break Alarm open RESET contact on terminal 3-4.
Page 26
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 24
6.4.3HB alarm contact
Warning: this procedure can be done just by specialized personnel.
The contact of the H.B. Relay is available on auxiliary termin als.
Terminal Descriprion
10 Common relay HB alarm 11 NO/NC HB relay alarm
To change relay status remove plastic cover and configure jumpers as represented below:
STATUS RELE STATUS
MAIN PCB
J19
IN Alarm Close
Circuit not
powered
Close
CB
A
(std)
OK Open
IN Alarm Open
Circuit not
powered
Open
CB
A
OK Close
Page 27
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
25 www.honeywell.com/imc
Main PCB
Page 28
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 26
6.4.4 Calibration
This procedure it’s necessary to give set point to Heater Break. CD3000M reads the load current many times and when the value is the same for three times takes it as set point.
Calibration procedure:
verify that connections are correct;
supply the thyristor unit;
push “CAL” button on front of CD3200 unit,
or supply with 24Vdc terminals 1-2 or send command via RS485;
the thyristor unit goes in conduction state to measure load current;
all LEDS are ON, this means that calibration procedure is active;
after one minute LEDS for H.B. and S/C switch off (calibration procedure is done);
the thyristor unit is ready to work.
Page 29
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
27 www.honeywell.com/imc
6.4.5 Digital input Command
POWER UNIT
Reset
1
65
7 8 9
10 11
12 13 14 15
16
17 18
2
A2+3A1-
4
COM NO/NC
H.B. Contact
POWER UNIT
Reset
1
65
7
8 9
10 11
12 13 14 15
16 17 18
2
A2+3A1-
4
COM NO/NC
H.B. Contact
6.4.6 RS485 Command
POWER UNIT
Reset
1
65
7 8
9 10 11 12 13 14
15
16
17 18
2
A2+3A1-
4
COM NO/NC
H.B. Contact
POWER UNIT
Reset
1
65
7
8
9 10 11 12 13 14 15
16 17 18
2
A2+3A1-
4
COM NO/NC
H.B. Contact
If load current decreases for partial or total load failure (sensitivity 20% standard adjustable v ia RS485) the yellow LED becomes ON and alarm relay changes status. If CD3200 is still in conduction with no input signal (LED green OFF) it means that there is a short circuit on thyristors and red LED (SC) becomes ON.
The diagnostic is active only when the switching period is longer than 60ms (3 main voltage cycles).
If the load has been changed calibration procedure must be done again.
Page 30
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 28
6.5 Current Limit Tuning
Warning: this procedure can be done just by specialized personnel.
To adjust the current limit, remove the cover of the CD3200 module and tune the trimmer R13 as below represented. Completely anti-clockwise: current limit = 0%. Completely clockwise: current limit = 100% of the maximum value of the used current transformer.
Front PCB
Current Limit Pot.
Page 31
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
29 www.honeywell.com/imc
7. Thyristor firing mode
7.1 Phase Angle + Current Limit (PA)
With Phase Angle is possible to control the power to the load allowing to Thyristor to be in conduction for a variable part of the voltage supply halt cycle. The load power can be adjusted from 0 to 100% as a function of analog input signal, normally delivered by temperature controller or by potentiometer. Normal it's used with inductive loads. The only disadvantage with phase angle is the generation of interferences that can be reduced with filters.
LINE VOLT AGE
T
V
LOA D SUPPLY
T
Page 32
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 30
7.2 Configurator
To configure CD3200 unit, you can download the free software and the Configurator Manual from our web site www.honeywell.com/imc.
To configure the unit you can use the standard communication on terminals 7-8 or use a programming cable.
Page 33
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
31 www.honeywell.com/imc
To connect the programming cable to the thyristor unit, remove cover as in picture
PROG. CONN.
Once removed the cover, put a side of cable in prog connector(K10) and the other side in the PC RS232(9PIN) serial port.
Page 34
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 32
8.Fuse and fuseholder for UL certification units
8.1 Fuse and Fuse Code
CD3200 unit must be protected by fuses against short circuit selecting the proper I²t that must be lower than thyristor one. The same caution must be taken if Circuit Breaker is used. Remember that is very difficult to protect the thyristor if this choise is done.
WARNING!! USE SEMICONDUCTOR FUSES ONLY WITH proper I
2
t
Bussmann Div - Cooper (UK) Ltd (200 kA
RMS
Symmetrical A.I.C.)
Ferraz Shawmut SA (200 kA
RMS
Symmetrical A.I.C.)
Sizes
Fuse Mod. No. /modéle fusible
Current
(A
RMS
)
I²t
(A2sec)
V ac Fuse Mod. No.
/modéle fusible
Current
(A
RMS
)
I²t
(A2sec)
Vac
15A FWC 16A10F 16 150 600 660 Grb 10-16 16 145 660 25A FWC 32A10F 32 600 600 660 Grb 10-32 32 740 660 35A FWP 40A14F 40 980 700 CP URC 14x51/40 40 700 660 45A FWP 50A14F 50 1800 700 CP URC 14x51/50 50 1500 660 60A FWP 80A22F 80 5100 700 CP URD 22x58/80 80 3800 660
90A N.A. - - - - - -
CP URQ
27x60/125
125 6970 660
110A N.A. - - - - - -
CP URQ
27x60/160
160 15000 660
High speed fuses are only used for the thyristor protection and can not be used to protect the installation.
The user installation must be protect by electromagnetic circuit breaker or by fuse isolator.
The warranty of thyristor is null if no proper fuses are used. See tab above.
Page 35
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
33 www.honeywell.com/imc
8.2 FuseHolder size
15-25A 35-45A
60 mm
80 mm
17mm
110 mm
77 mm
26mm
60A 90-110A
150 mm
107 mm
37mm
70 mm
9 mm
9 mm
6mm
19 mm
35mm
77 mm
125 mm
Page 36
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 34
9. Fuse and fuseholder for CE mark unit
9.1 Fuse and Fuse Code
The thyristor unit must be protected by fuses against short circuit selecting the proper I²t that must be lower than thyristor one. The same caution must be taken if Circuit Breaker is used. Remember that is very difficult to protect the thyristor if this choise is done.
WARNING!! USE SEMICONDUCTOR FUSES ONLY WITH proper I
2
t
Sizes I²T (max)
(A² sec.)
Size and current Fuse and
Fuseholder
Code
Fuse
Code
15 600 10,3X38 / 16A FFH1038/16A FU1038/16A 25 600 10,3X38 / 32A FFH1038/32A FU1038/32A 35 780 14X15 / 40A FFH1451/40A FU1451/40A 45 1500 14X15 / 50A FFH1451/50A FU1451/50A 60 3800 22X58 / 80A FFH2258/80A FU2258/80A 90 6970 22X58 / 125A FFH2258/125A FU2258/125A
110 11000 27x60 / 160A FFHPSI27/160A FFHPSI27/160A
High speed fuses are only used for the thyristor protection and can not be used to protect the installation.
The user installation must be protect by electromagnetic circuit breaker or by fuse isolator.
The warranty of thyristor is null if no proper fuses are used. See tab above.
Page 37
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
35 www.honeywell.com/imc
9.2 FuseHolder size
15-25A 35-45A
60 mm
80 mm
17mm
110 mm
77 mm
26mm
60-90A 110A
150 mm
107 mm
37mm
70 mm
9 mm
9 mm
6mm
19 mm
35mm
77 mm
125 mm
Page 38
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 36
10.Modbus communication
The CD3200 is equipped with two-wire RS485-compatible serial communications, by which means communication may occur between the Controller and a master device (e.g. a computer or terminal).
10.1 Physical requirements
10.1.1 Character Transmission
Data format is fixed to be one start bit, eight data bits, one stop bit, baud rate 9600 and the parity none.
10.2 ModBus RTU protocol
The standard RS485 Communications uses the industry standard MODBUS RTU protocol. The following restrictions are imposed:
Baud rates is fixed to 9600 Baud only.
Support for multi-parameter Write operations is limited to support of the Multi-
Word Write Function (Number 16) but it permits the writing of only one parameter per message.
The following MODBUS functions are supported:
Function Function Number Read Holding Registers (Read n Word) 03 Preset Multiple Registers (Write n Word) 16
The Controller will identify itself in response to a Read Holding Registers message which enquires the values of word parameters 121 and 122 (see Table 4-2). MODBUS Function 17 (Report Slave ID) is not supported.
10.2.1 Message Formats
The first character of every message is the Controller address, in the range 1 - 255 and 0 for broadcast messages. The second character is always the Function Number. The contents of the remainder of the message depends upon this Function Number. In most cases the Controller is required to reply to the message by echoing the address and Function Number.
Broadcast messages are supported at address 0 (to which the CD3000M responds by taking some action without sending back any reply).
Data is transmitted as eight-bit binary bytes with one start bit, one stop bit and parity checking set to none. A message is terminated simply by a delay of more than three character lengths at the Baud rate used(in this case 9600 baud); any character received after such a delay is considered to be the potential address at the start of a new message.
Page 39
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
37 www.honeywell.com/imc
Since only the RTU form of the protocol is supported, each message is followed by a two-byte CRC 16 (a 16-bit cyclic redundancy checksum). This checksum is calculated in accordance with a formula which involves recursive division of the data by a polynomial, with the input to each division being the remainder of the results of the previous division.
The dividing polynomial is 2
16
+ 215 + 22 + 1(Hex 18005)
but this is modified in two ways:
because the bit order is reversed, the binary pattern is also reversed, making the most significant bit (MSB) the right-most bit;
because only the remainder is of interest, the right-most (most significant) bit can be discarded.
Thus, the polynomial has the value Hex A001.
10.2.2 Bit’s order
Normal bit order
Most significant bit Least significant bit
Most significant byte Least significant Byte
Reversed bit order
Least significant bit Most significant bit
Least significant Byte Most significant byte
N.B.: Reversed order apples, so CRC16 return Reversed bit order
Page 40
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 38
START
Setting FFFF (Hex) To CR
CR= CRC error check data (1 wo rd) I = Digits of calculation characters in command message J = Check on the number of times of CR calculation
Settin g 1 to I
Settin g 1 to J
CR is shifted by
1 bit to right
Added 1t o J
Added 1 to I
END
After shifting CR by 1 bit to righ t, A001(Hex) and exclusive logical sum
(XOR) are executed for setting the result in CR
Bit at right and of CR is 1?
NO
NO
NO
YES
YES
YES
Eight times of calculation
is completed?
J>8
Calculation of all charactersis completed?
I>All charac ters numbers
Exclusive lo gic a l Sum (XO R ) is e x ecu ted on one charac ter (1 byte) at I
charactor of CR and de signat ed messa ge , an d results are set t o CR.
Page 41
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
39 www.honeywell.com/imc
10.2.3 C Language CRC 16 Example
static short CRC16 (unsigned char *p_first,unsigned char *p_last) { unsigned int crc=0xffff; short j;
for (;p_first<=p_last;p_first++) { crc ^= *p_first; for(j=8;j>0;j--) { if(crc & 0x0001) { crc = crc >> 1; crc ^= 0xA001; } else { crc = crc >> 1; } }
} return (crc); }
10.2.4 Read Holding Registers (Read n Words) – Function 03
The message sent to the Controller to obtain the value of one or more registers comprises the following eight bytes:
Addr. unit Func. Address
1° word
N° of Word CRC 16
3
3Hex
HI LO HI LO HI LO
The normal reply will echo the first two characters of the message received follow ed by a single­byte data byte count (which will not includ e itself or the CRC). For this message, the count value equals the number of parameter v a lues read multiplied by two. Following the byte count, the specified number of parameter values are transmitted, followed by the CRC16 bytes:
Addr. unit Func. Cont. 1° Value Last Value CRC 16
3
3Hex
HI LO HI LO HI LO
Page 42
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 40
10.2.5 Preset Multiple Registers (Write n Words) - Function 16
This is an eleven-byte message. only one parameter may be written for each received message. The usual pre-amble is followed by the address of the parameter to be written, a two-byte word count (always set to 1), a single-byte byte count (always set to 2), the value to be written and the CRC16 bytes:
Addr. unit Func. Addr of
1° Word
N° of Word Cont. Valore CRC 16
16
10Hex
HI LO 0 1 2 HI LO HI LO
The Controller normally responds with the following eight-bit reply:
Addr. unit Func. N° of Word N° Word CRC 16
16
10Hex
HI LO 0 1 HI LO
10.2.6 Error and Exception Responses
If a received message contains a corrupted character (parity check failure, framing error etc.) or if the CRC16 check fails, or if the received message is otherwise syntact ically flawed (e.g. byte count or word count is incorrect), the thyristor will ignore that message.
If the received message is syntactically correct but nonetheless contains an illegal value, the thyristor will send a five-byte exception response as follows :
Addr. unit Func. N.Exception CRC 16
HI LO
The Function Number byte contains the function number contained in the message which caused the error, with its top bit set (i.e. Function 3 becomes 0x83) and the Exception Number is on of the following codes:
Code Name Cause 1 ILLEGAL FUNCTION Function number out of range 2 ILLEGAL DATA ADDRES Parameter ID out of range or not supported 3 ILLEGAL DATA VALUE Attempt to write invalid data/required action not
executed
NOTE: Writing a parameter value equal to its current value is a valid transaction; this will not cause an error response.
Page 43
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
41 www.honeywell.com/imc
10.3 Word parameters
Parametr N. Note
Actual Current 1H Read only Actual Voltage 1L Read only Set Current 2H Read /write Set Voltage 2L Read /write Status Table (shown in Tab 2.1.2) 3 Read only Comand Table (shown in Tab 2.1.3) 4 Read /write
Output Power (0 – FFH) 5L
Read - (Write if BIT1i n Command table i = 1) (0->0% - FF->100%)
Output Power Ramping (0 – FFH) 5L Read only Power Scaling (0 – FFH) 6
Read - (Write if BIT1 in Command table i = 1) (0->0% - FF->100%)*
Current Limit (0 – FFH) 7
Read - (Write if BIT4 in Command table i = 1) (0->0% - FF->100%)
Manufact ID 121 Read only Equipment ID 122 Read only
10.3.1 Actual Current Parameter 1H Operations: Read
10.3.2 Actual Voltage Parameter 1L Operations: Read
10.3.3 Set Current Parameter 2H Operations: Read
10.3.4 Set Voltage Parameter 2L Operations: Read
10.3.5 Status Table Parameter 3 Operations: Read
Meaning:
It’s a tab in bit that represents the “Status” of thyristor unit.
10.3.6 Comand Table Parameter 4 Operations: Read/Write
Meaning:
It’s a tab in bit for remote commands via RS485 (see tab).
Page 44
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 42
10.3.7 Output Power Parameter 5L
Command from controller
Operations: Read
Meaning:
It rapresents a value in points (0-255, 0-FF Hex) and it’s the power demand in % of controller. Example:
0% = 0 0 (Hex) 50% = 128 80 (Hex) 100% = 255 FF (Hex)
Command via RS485
Operations: Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex). It’s power set point setted in thirst buffer.
Example: 0% = 0 0 (Hex) 50% = 128 80 (Hex) 100% = 255 FF (Hex)
10.3.8 Output Power Ramping (0 – FFH) Operations: Read
10.3.9 Power adjust Parameter 6 Operations: Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex). It’s a scaling factor of power demand.
Example 1: 0% = 0 50% = 128 100% = 255
Example 2:
Output Power: 100 Power Limit: 100%
-> Real power: 100
Output Power: 100 Power Limit: 50%
-> Real power: 50
Output Power: 80 Power Limit: 50%
-> Real power : 40
100
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
80
60
40
20
0
4020 60 10080
Input %
OUT
%
Page 45
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
43 www.honeywell.com/imc
10.3.10 Current Limit Parameter 7
Command from current limit pot.
Operations: Read
Meaning:
It represents a value in points (0-255, 0-FF Hex) and it’s the power demand in % of controller. Example:
0% = 0 0 (Hex) 50% = 128 80 (Hex) 100% = 255 FF (Hex)
Command via RS485
Operations: Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex) It’s the power set point setted in thirst buffer
Example: 0% = 0 0 (Hex) 50% = 128 80 (Hex) 100% = 255 FF (Hex)
10.3.11 Status Table Bit Meaning Notes
0 Short circuit on SCR Read only 1 Load Failure Read only 2 On-Off Read only 3 HB Calibration in progress Read only 0=Normal - 1=Calibration 4 Current Limit Flag Read only 0=Normal - 1= Working in C.L. 5 Termal Read only
10.3.12Short circuit on SCR Bit 0 Operations: Read
Meaning:
It’s a bit indicating when the thyristor is in short circuit. 0 = OK
1 = Short circuit
10.3.13 Load Failure Bit 1 Operations: Read
Meaning:
It’s a bit indicating the partial or total load failure. 0 = OK
1 = Load failure
Page 46
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 44
10.3.14 On-Off Bit 2 Operations: Read
Meaning:
It’s a bit indicating when input signal is ON. 0 = Input signal OFF
1 = Input signal ON
10.3.15 Calibration in progress Bit 3 Operations: Read
Meaning:
It’s a bit representing the “calibration in progress” status. 0 = No calibration
1 = Calibration in progress
10.3.16 Current Limit Bit 4 Operations: Read
Meaning:
This bit indicates when the unit is working in current limit. 0 = Normal
1 = Working in current limit
10.3.17 Command Table Bit Meaning Notes
0 Calibration
Read /write 0=Off - 1=ACTVATE Calibration ( normal mode set to 0)
1 Firing command Read /write 0=from terminal - 1=from RS485 2 On-Off Read /write 0=Off - 1=On
3 RESET HB
Read /write 0=Off - 1=RESET
( normal mode set to 0) 4 Current Limit control Read /write 0=from C.L. pot. - 1=from RS485 N.B.: When the unit is switched off all command parameters are setted to 0.
10.3.18 Calibration Bit 0 Operations: Read / Write
Meaning:
It’s a bit that starts the calibration procedure When this bit is zero the calibration procedure starts and automatically resets itself at the end.
Page 47
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
45 www.honeywell.com/imc
10.3.19 Firing command Bit 1 Operations: Read / Write
Meaning:
It’s a command bit used to switch from analog external command to command via RS485 0 = Command from analog input
1 = Command from RS485 input
10.3.20 On-Off Bit 2 Operations: Read / Write
Meaning:
It’s used to switch ON-OFF the power. 0 = Power disabled
1 = Power enabled
10.3.21 HB RESET Bit 3 Operations: Read / Write
Meaning:
It’s a command bit to reset HB alarm. This parameter has to be at 0 to have the alarm working properly.
0 = Reset disabled 1 = Reset enabled
10.3.22 Current Limit control Bit 4 Operations: Read / Write
Meaning:
It’s a command bit used to switch from analog C.L. potentiometer to command via RS485. 0 = Command from Current Limit pot.
1 = Command from RS485 input
10.3.23 Configuration Parameter N. Note
Password 123 Write Actual Power 124 Read /write Feed-Back Selection 125L Read /write Soft Start 125H Read /write HB Delay 126L Read /write HB sensibility % 126H Read /write Power Set 127 Read /write Integral 128L Read /write Prop. 128H Read /write
Page 48
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 46
10.3.24 Password Parameter 123 Operations: Write
Meaning:
If properly setted, gives the access to configuration.
10.3.25 Actual power Parameter 124 Operations: Read
10.3.26 Feed-Back Parameter 125L Operations: Read
10.3.27 Soft start time Parameter 125H Operations: Read/Write
Meaning:
Time
Soft Start Time Par 125H x 5msec
OUT
It’s corresponds to the value in points (0 – 255, 0 – FF Hex). Each step is 5msec .
The unit starts in phase angle mode with a ramp starting from zero up to full voltage in a presetted and Adjustable time. The time is setted by this parameter.
10.3.28 Delay time HB Parameter 126L Operations: Read/Write
Meaning:
It’s a value in point (0 – 255, 0 – FF Hex). Each step is 50msec. It represents a delay time before to have HB alarm active.
When is used with soft start, this time must be longer than soft start time. Par126H x 50msec > Par125H x 5msec
10.3.29 % HB Parameter 126H Operations: Read/Write
Meaning:
It corresponds to a value in point (0-255, 0-FF Hex) The maximum load current (100%) minus this parameter (x%) is the value establishing the HB current set point.
Example: Load current = 10A
Parameter 124H = 20% 51 Dec 33 Hex Parameter 2 will be setted at 8A.
Page 49
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
47 www.honeywell.com/imc
10.3.29.1 Set power Parameter 127
Operations: Read/Write
10.3.29.2 Integral Parameter 128L
Operations: Read/Write
10.3.29.3 Prop Parameter 128H
Operations: Read/Write
Page 50
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 48
10.4 Address Configuration
Up to 255 CD3200 units, each with a unique address, may be connected to a master device. To configure communication address open cover and set the dip-switch as specified
10.4.1ADDRESS TABLE
ID 8 7 6
1
ON OFF
2
3
4
5
6
7
8
5 4 3 2 1 ID 8 7 6 5 4 3 2 1
1 - - - - - - - X 26 - - - X X - X ­2 - - - - - - X - 27 - - - X X - X X 3 - - - - - - X X 28 - - - X X X - ­4 - - - - - X - - 29 - - - X X X - X 5 - - - - - X - X 30 - - - X X X X ­6 - - - - - X X - 31 - - - X X X X X 7 - - - - - X X X 32 - - X - - - - ­8 - - - - X - - - 33 - - X - - - - X 9 - - - - X - - X 34 - - X - - - X ­10 - - - - X - X - 35 - - X - - - X X 11 - - - - X - X X 36 - - X - - X - ­12 - - - - X X - - 37 - - X - - X - X 13 - - - - X X - X 38 - - X - - X X ­14 - - - - X X X - 39 - - X - - X X X 15 - - - - X X X X 40 - - X - X - - ­16 - - - X - - - - 41 - - X - X - - X 17 - - - X - - - X 42 - - X - X - X ­18 - - - X - - X - 43 - - X - X - X X 19 - - - X - - X X 44 - - X - X X - ­20 - - - X - X - - 45 - - X - X X - X 21 - - - X - X - X 46 - - X - X X X ­22 - - - X - X X - 47 - - X - X X X X 23 - - - X - X X X 48 - - X X - - - ­24 - - - X X - - - 49 - - X X - - - X 25 - - - X X - - X 50 - - X X - - X -
Page 51
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
49 www.honeywell.com/imc
ID 8 7 6 5 4 3 2 1 ID 8 7 6 5 4 3 2 1
51 - - X X - - X X 101 - X X - - X - X 52 - - X X - X - - 102 - X X - - X X ­53 - - X X - X - X 103 - X X - - X X X 54 - - X X - X X - 104 - X X - X - - ­55 - - X X - X X X 105 - X X - X - - X 56 - - X X X - - - 106 - X X - X - X ­57 - - X X X - - X 107 - X X - X - X X 58 - - X X X - X - 108 - X X - X X - ­59 - - X X X - X X 109 - X X - X X - X 60 - - X X X X - - 110 - X X - X X X ­61 - - X X X X - X 111 - X X - X X X X 62 - - X X X X X - 112 - X X X - - - ­63 - - X X X X X X 113 - X X X - - - X 64 - X - - - - - - 114 - X X X - - X ­65 - X - - - - - X 115 - X X X - - X X 66 - X - - - - X - 116 - X X X - X - ­67 - X - - - - X X 117 - X X X - X - X 68 - X - - - X - - 118 - X X X - X X ­69 - X - - - X - X 119 - X X X - X X X 70 - X - - - X X - 120 - X X X X - - ­71 - X - - - X X X 121 - X X X X - - X 72 - X - - X - - - 122 - X X X X - X ­73 - X - - X - - X 123 - X X X X - X X 74 - X - - X - X - 124 - X X X X X - ­75 - X - - X - X X 125 - X X X X X - X 76 - X - - X X - - 126 - X X X X X X ­77 - X - - X X - X 127 - X X X X X X X 78 - X - - X X X - 128 X - - - - - - ­79 - X - - X X X X 129 X - - - - - - X 80 - X - X - - - - 130 X - - - - - X ­81 - X - X - - - X 131 X - - - - - X X 82 - X - X - - X - 132 X - - - - X - ­83 - X - X - - X X 133 X - - - - X - X 84 - X - X - X - - 134 X - - - - X X ­85 - X - X - X - X 135 X - - - - X X X 86 - X - X - X X - 136 X - - - X - - ­87 - X - X - X X X 137 X - - - X - - X 88 - X - X X - - - 138 X - - - X - X ­89 - X - X X - - X 139 X - - - X - X X 90 - X - X X - X - 140 X - - - X X - ­91 - X - X X - X X 141 X - - - X X - X 92 - X - X X X - - 142 X - - - X X X ­93 - X - X X X - X 143 X - - - X X X X 94 - X - X X X X - 144 X - - X - - - ­95 - X - X X X X X 145 X - - X - - - X 96 - X X - - - - - 146 X - - X - - X ­97 - X X - - - - X 147 X - - X - - X X 98 - X X - - - X - 148 X - - X - X - ­99 - X X - - - X X 149 X - - X - X - X 100 - X X - - X - - 150 X - - X - X X -
Page 52
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 50
ID 8 7 6 5 4 3 2 1 ID 8 7 6 5 4 3 2 1
151 X - - X - X X X 201 X X - - X - - X 152 X - - X X - - - 202 X X - - X - X ­153 X - - X X - - X 203 X X - - X - X X 154 X - - X X - X - 204 X X - - X X - ­155 X - - X X - X X 205 X X - - X X - X 156 X - - X X X - - 206 X X - - X X X ­157 X - - X X X - X 207 X X - - X X X X 158 X - - X X X X - 208 X X - X - - - ­159 X - - X X X X X 209 X X - X - - - X 160 X - X - - - - - 210 X X - X - - X ­161 X - X - - - - X 211 X X - X - - X X 162 X - X - - - X - 212 X X - X - X - ­163 X - X - - - X X 213 X X - X - X - X 164 X - X - - X - - 214 X X - X - X X ­165 X - X - - X - X 215 X X - X - X X X 166 X - X - - X X - 216 X X - X X - - ­167 X - X - - X X X 217 X X - X X - - X 168 X - X - X - - - 218 X X - X X - X ­169 X - X - X - - X 219 X X - X X - X X 170 X - X - X - X - 220 X X - X X X - ­171 X - X - X - X X 221 X X - X X X - X 172 X - X - X X - - 222 X X - X X X X ­173 X - X - X X - X 223 X X - X X X X X 174 X - X - X X X - 224 X X X - - - - ­175 X - X - X X X X 225 X X X - - - - X 176 X - X X - - - - 226 X X X - - - X ­177 X - X X - - - X 227 X X X - - - X X 178 X - X X - - X - 228 X X X - - X - ­179 X - X X - - X X 229 X X X - - X - X 180 X - X X - X - - 230 X X X - - X X ­181 X - X X - X - X 231 X X X - - X X X 182 X - X X - X X - 232 X X X - X - - ­183 X - X X - X X X 233 X X X - X - - X 184 X - X X X - - - 234 X X X - X - X ­185 X - X X X - - X 235 X X X - X - X X 186 X - X X X - X - 236 X X X - X X - ­187 X - X X X - X X 237 X X X - X X - X 188 X - X X X X - - 238 X X X - X X X ­189 X - X X X X - X 239 X X X - X X X X 190 X - X X X X X - 240 X X X X - - - ­191 X - X X X X X X 241 X X X X - - - X 192 X X - - - - - - 242 X X X X - - X ­193 X X - - - - - X 243 X X X X - - X X 194 X X - - - - X - 244 X X X X - X - ­195 X X - - - - X X 245 X X X X - X - X 196 X X - - - X - - 246 X X X X - X X ­197 X X - - - X - X 247 X X X X - X X X 198 X X - - - X X - 248 X X X X X - - ­199 X X - - - X X X 249 X X X X X - - X 200 X X - - X - - - 250 X X X X X - X ­ 251 X X X X X - X X X = ON 252 X X X X X X
- = OFF 253 X X X X X X X 254 X X X X X X X 255 X X X X X X X X
Page 53
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
51 www.honeywell.com/imc
11. Maintenance
11.1 Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of t rouble shootin g. If you don’t succeed, contact us or your nearest distributor.
Symptom Indication on
front unit
Possible reasons of the symptom
Actions
Green LED is
always light off.
- No voltage auxiliary power supply to terminals 1-3 (see wiring diagram).
- Give auxiliary voltage supply to terminals 1-3.
Green LED (PW) light on and green LED (ON) in light off condition.
- No input signal.
- Reversed polarities of
input signal.
- Reset contact in open condition (see wiring diagram).
- Provide to give input signal.
- Reverse the input signal
polarity.
- Make link on reset terminals. Thyristor unit doesn’t go in conduction with input signal.
Green LED (PW) in light on condition and green LED (ON) in light on condition.
- Fuse failure.
- Load failure.
- Load connection
interruption.
- Thyristor faulty and always in open circuit.
- With HB option the yellow led (HB) in light on condition.
- Substitute the fuse.
- Repair the load.
- Provide to repair the wiring.
- Substitute the faulty thyristor.
- Check the load.
Load current flows also with no input signal.
Green LED (ON) always in light off condition.
- Short circuit on thyristor. If there is HB circuit the red LED (SC) is light on.
- Substitute the thyristor. Check that load is not in short circuit.
Current flows at nominal value but yellow LED (HB) in light on condition.
Yellow HB in light on condition.
- HB circuit not tuned.
- Current transformers
not properly wired (if are external to CD3200).
- Push CAL button in front unit to start HB calibration procedure.
- Control current transformers wiring and Push CAL button in front unit to start HB calibration procedure.
RED LED (SC)
IS LIGHTED ALSO IF CURRENT IS AT NOMINAL VALUE
.
Red LED in light on condition.
- HB circuit not properly tuned.
- Push CAL button in front unit to start HB calibration procedure.
Thyristor unit doesn’t work properly.
- Wrong input signal selection.
- Wrong input signal calibration (out of range).
- Auxiliary voltage supply out of limits.
- Control input signal setting.
- Repeat input calibration
procedure.
- Verify the auxiliary voltage supply.
Page 54
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 52
11.2 Repairing procedure
Phone to us.
Explain to Service Engineer the problem because sometimes it can be solved with a phone call.
If this is not possible ship the unit to us or to your distributor.
Write a fault description and give the name of your personnel to which refer.
Use a rugged packaging to ship the unit.
11.3 Fans
The thyristor unit with forced ventilation uses fans that rotate permanently when the unit is supplied. In case of accidental fan failure, there is an over heating temperature on heatsink. In this case to give protection to thyristor there is a thermal switch properly setted. The function of this switch is to open the input signal until the h eatsink temperature falls below the setted value. This means that also with input signal in ON condition the unit is switched OFF and the system can not work at full power. For these reason is important to control periodically the fan status checking that is rotating.
11.4 Servicing
In order to have correct cooling, the user must clean the heatsink and the protective grill of fan. The frequence of this servicing depends on environmenta l pollution. Check periodically also if the screw for the power cables and safety earth are tightened correctly
11.5 Warranty conditions
We gives a 12 months warranty to its products. The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses. Warranty does not includes products with serial numbers deleted. The faulty product should be shipped to us at your cost and our Service will evaluate if product is un d er warranty terms. Substituted parts remains our property.
Page 55
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
53 www.honeywell.com/imc
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty work-manship. Contact your local sales office of warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair of replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy
and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate
and reliable as of printing. However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell website, it is up to the customer to determine the suitability of the product in the application.
ASIA PACIFIC
Control Products Asia Pacific Headquarters
Phone: +(65) 6355-2828 Fax: +(65) 6445-3033
Australia
Honeywell Limited Phone: +(61) 2-9370-4500 FAX: +(61) 2-9370-4525 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
China – PRC - Beijing
Honeywell China Inc. Phone: +(86-10) 8458-3280 Fax: +(86-10) 8458-3102
China – PRC - Shanghai
Honeywell China Inc. Phone: (86-21) 6237-0237 Fax: (86-21) 6237-1237
China - Hong Kong S.A.R.
Honeywell Ltd. Phone: +(852) 2953-6412 Fax: +(852) 2953-6767
China – PRC - Chengdu
Honeywell China Inc. Phone: +(86-28) 6786-348 Fax: +(86-28) 6787-061
China – PRC - Guangzhou
Honeywell China Inc. Phone: +(86-20) 3879-1169 Fax: +(86-20) 3879-1269
China – PRC - Shenzhen
Honeywell China Inc. Phone: +(86) 755-518-1226 Fax: +(86) 755-518-1221
Indonesia
Honeywell Indonesia Pte Ltd. Phone: +(62) 21-535-8833 FAX: +(62) 21-5367 1008
India
TATA Honeywell Ltd. Phone: +(91) 20 687 0445/0446 Fax: +(91) 20 681 2243/ 687 5992
Japan
Honeywell Inc Phone: +(81) 3 5440 1425 Fax: +(81) 3 5440 1368
South Korea
Honeywell Korea Co Ltd Phone: +(822) 799-6167 Fax: +(822) 792-9013
Malaysia
Honeywell Engineering Sdn Bhd Phone: +(60-3) 7958­4988 Fax: +(60-3) 7958-8922
New Zealand
Honeywell Limited Phone: +(64-9) 623-5050 Fax: +(64-9) 623-5060 Toll Free (0800) 202-088
Philippines
Honeywell Systems (Philippines) Inc. Phone: +(63-2) 636-1661 /1662
Fax: +(63-2) 638-4013
Singapore
Honeywell South East Asia Phone: +(65) 6355-2828 Fax: +(65) 6445-3033
Thailand
Honeywell Systems (Thailand) Ltd. Phone: +(662) 693-3099 FAX: +(662) 693-3085
Taiwan R.O.C.
Honeywell Taiwan Ltd. Phone: +(886-2) 2245­1000 FAX: +(886-2) 2245­3242
EUROPE
Austria
Honeywell Austria GmbH Phone: +43 (316)400123 FAX: +43 (316)40017
Belgium
Honeywell SA/NV Phone: +31(0)205656999 FAX: +31(0)165330746
Bulgaria
Honeywell EOOD Phone: +(359) 2 79 40 27 FAX: +(359) 2 79 40 90
Czech Republic
Honeywell spol. s.r.o. Phone: +420-54324­5014 FAX: +420-54324-5011
Denmark
Honeywell A/S Phone: +(45) 39 55 55 55 FAX: +(45) 39 55 55 58
Finland
Honeywell OY Phone: +358 (3) 2727625 FAX: +358 (3) 2728600
France
Honeywell SA Phone: +33 (0)1 60198075 FAX: +33 (0)1 60198201
Germany
Honeywell AG Phone: +49 (69)8064336 FAX: +49 (69)806497336
Hungary
Honeywell Kft. Phone: +36-1-451 4335 FAX: +36-1-451 4343
Italy
Honeywell S.p.A. Phone: +39 02 9214 6503 FAX: +39 0292146377
The Netherlands
Honeywell B.V. Phone: +31(0)205656999 FAX: +31(0)165330746
Norway
Honeywell A/S Phone: (45) 39 55 55 55
Poland
Honeywell Sp. zo.o Phone: +48-22-6060900 FAX: +48-22-6060901
Portugal
Honeywell Portugal Lda Phone: +351 21 424 5000 FAX: +351 21 424 50 99
Romania
Honeywell Bucharest Phone: 40212110076 FAX: +40 (40212103375)
Commonwealth of Independent States (CIS)
Z.A.O. Honeywell Phone: +(7 095) 796 98 36 FAX: +(7 095) 796 98 93
Slovak Republic
Honeywell s.r.o. Phone: +421-2-58247 410 FAX: +421-2-58247 415
Spain
Honeywell S.A. Phone: +34 (0)91313 61 00 FAX: +34 (0)91313 61 30
Sweden
Honeywell AB Phone: +(46) 8 775 55 00 FAX: +(46) 8 775 56 00
Switzerland
Honeywell AG Phone: +41 18552448 FAX: +(41) 1 855 24 45
Turkey
Honeywell Turkey A.S. Phone: +90 216 575 6600 FAX: +90 216 575 6637
United Kingdom
Honeywell Control Systems Ltd Phone: +(44) 1698 481730 FAX: +(44) 1698 481276
MIDDLE EAST
Abu Dhabi U A E
Middle East Headquarters Honeywell Middle East Ltd Phone: +971 2 4041220 FAX: +971 2 4432536
Sultanate of Oman
Honeywell & Co Oman LLC Phone: +968 701397 FAX +968 787351
Egypt Honeywell Egypt Ltd Phone: +202 4514460 /1/ 2/ 3/ 4/ 5/ 6 FAX : +2024514467
Saudia Arabia Honeywell Turki Arabia Limited Phone: +966-3-341-0140 Fax: +966-3-341-0216
Kuwait Honeywell Kuwait KSC Phone: +965 2421327
AFRICA
Mediterranean & African Distributors
Honeywell SpA Phone: +39 (02) 250 10 604 FAX: +39 (02) 250 10 659
South Africa (Republic of)
Honeywell Southern Africa Honeywell S.A. Pty. Ltd Phone: +27 11 6958000 FAX +27 118051504
NORTH AMERICA
Canada
Honeywell LTD Phone: 1-800-737-3360 FAX: 1-800-565-4130
USA
Honeywell Control Products, International Headquarters Phone: 1-800-537-6945 1-815-235-6847 FAX: 1-815-235-6545 E-mail: info.sc@honeywell.com
LATIN AMERICA
Argentina
Honeywell S.A.I.C. Phone: +(54-11) 4383-3637 FAX: +(54-11) 4325-6470
Brazil
Honeywell do Brasil & Cia Phone: +(55-11) 7266-1900 FAX: +(55-11) 7266-1905
Chile
Honeywell Chile, S.A. Phone: +(56-2) 233-0688 FAX: +(56-2) 231-6679
Mexico
Honeywell S.A. de C.V. Phone: +(52) 55 5259-1966 FAX: +(52) 55 5570-2985
Puerto Rico
Honeywell Inc. Phone: +(809) 792-7075 FAX: +(809) 792-0053
Trinidad
Honeywell Inc Phone: +(868) 624-3964 FAX: +(868) 624-3969
Venezuela
Honeywell CA Phone: +(58-2) 238-0211
FAX: +(58-2) 238-3391
Loading...