Honeywell CD3200 User Manual

EN1I-6312
USER’S MANUAL
CD3200
THYRISTOR UNIT
Up To 110A
Rev. 12/2004
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
1 www.honeywell.com/imc
CD3200 Thyristor Unit up to 110A
Index:
1. Glossary 5
1.1 Terminology 5
1.2 Input signal 5
1.3 Power feed back 5
1.4 What is a thyristor unit 5
2. Technical specifications 6
2.1 General Features: 6
2.2 Input features 7
2.3 Output features 7
2.4 Derating curve 7
3. Ordering information 8
4. Installation and wiring information 9
4.1 Identification of the unit 9
4.2 Installation 9
4.3 Dimensions 10
4.4 Dimension CT (Heater Break HB) 10
4.5 Fixing holes 11
5. Wiring Instructions 12
5.2 Cabling detail 13
5.3 Wiring connection 15
5.4 LED Status Table 17
6. Start up 18
6.1 To remove the board 19
6.2 Auxiliary supply 20
6.3 Analog input 21
6.4 Heater Break Alarm 23
6.5 Current Limit Tuning 28
7. Thyristor firing mode 29
7.1 Phase Angle + Current Limit (PA) 29
7.2 Configurator 30
8. Fuse and fuseholder for UL certification units 32
8.1 Fuse and Fuse Code 32
8.2 FuseHolder size 33
9. Fuse and fuseholder for CE mark unit 34
9.1 Fuse and Fuse Code 34
9.2 FuseHolder size 35
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 2
10. Modbus communication 36
10.1 Physical requirements 36
10.2 ModBus RTU protocol 36
10.3 Word parameters 41
10.4 Address Configuration 48
11. Maintenance 51
11.1 Trouble Shooting 51
11.2 Repairing procedure 52
11.3 Fans 52
11.4 Servicing 52
11.5 Warranty conditions 52
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
3 www.honeywell.com/imc
CAUTION
Thyristor units are used in power industrial equipment. When the thyristor unit is working, there are on the unit the following voltages
- Maximum main supply voltage on power terminals up to 600V.
- Auxiliary supply 230-460Vac.
- Fan voltage 230Vac 50/60Hz Power consumption 14W. Don't remove the plastic cover which provides adequate protection against electric shock. Don’t use this thyristor in aerospace and nuclear application.
Electric Shock Hazard
When thyristor unit has been connected to main supply voltage and is switched off, before to touch it be secure that the unit is isolated and wait at least one minu te to permit to discharge internal capacitors. Thus be secure that:
access to thyristor unit is only permitted to specialized personnel;
the authorised personnel must read this manual before to have access to the unit;
the access to the units must be denied to unauthorized personnel.
Important warnings
Local regulations regarding electrical installation should be rigidly observed.
Safety regulations must be rigidly observed.
Don't bend components to maintain insulation distances.
Protect the units from high temperature, humidity and vibrations.
Don't touch components to prevent elettrostatichal discharges on them.
Verify that all ratings are in line with real needs.
If authorized personnel must measure voltage, current etc. on units, take away rings and other
jewels from fingers and hands.
Authorized personnel working on thyristor unit under power supply voltage must work on insulated board. Be secure that board is not connected to earth.
This listing does not represent a complete enumeration of all necessary safety cautions.
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 4
Protection
CD3000 thyristor family has a polymeric plastic cover in compliance to International specification IP20. To understand if IP20 protection is sufficient should be evaluated the installation place where the units are installed. Open Type Equipment. Maximum surrounding air temperature 40°C.
Earth
CD3000 family has isolated heatsink. For safety connect the heatsink to earth to avoid shocks in case that circuit board or thyristors lost insulation. Earth impedance should be correspondent to local earth regulation. Periodically the earth efficiency should be inspected.
Electronic Supply
CD3000 family electronic circuit should be supplied by dedicated voltage supply for all electronic circuit but not in parallel with contactor's coil, solenoids and other inductive or capacitive loads. It's recommended to use a shielded transformer.
Electromagnetic compatibility
Our thyristor unit has an excellent immunity to electromagnetic interferences if all suggestions contained in this manual are respected. In respect to a good Engineering practise, all inductive loads like solenoids contactor coils should have a filter in parallel.
Emissions
All thyristor switching at high speed generate some radiofrequency disturbance. CD3000 serie complies with EMC rules for CE mark. In many installations near electronic devices has not been noted problems. If radiofrequency device at low frequency are used near the thyristor unit, some precautions should be taken like line filters and shielded cables for input signal an d for load cables.
CU
LISTED
S
U
L
®
NOTE
We reserves the right to apply modifications to the our products without any advice.
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
5 www.honeywell.com/imc
1.Glossary
1.1 Terminology
V: voltage power supply. I: the full circulating current in thyristor unit. P: total load power.
1.2 Input signal
SSR: This input type is a square waveform generated by a temperature controller. AN: Analog input. IRS: Communication command.
1.3 Power feed back
Feedback: supply voltage fluctuation changes the power to the load. To overcome this effect the voltage supplied to the load is measured and compared with power demand from controller, the error signal is used to automatically hold the power at demanded level.
1.4 What is a thyristor unit
A thyristor unit is semiconductor device which acts as a switch formed by two thyristors in antiparallel. To switch on the alternating current the input signal will be on and the thyristor will switch off at first zero crossing voltage with no input signal. The benefits of thyristor units compared with elettromechanical contactors are numerouses: no mooving parts, no maintenance and capacity to switch very fast. Thyristors are the only solution to control transformers and special loads that change resistance with temperature and with age.
LOAD
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 6
2. Technical specifications
2.1 General Features:
Operating temperature
0÷40°C for higher temperature see derating curve
Voltage power supply 24V minimum, 480V max and 600V on request Input signal SSR
4÷20mA 0÷10V potentiometer (10k ohm) customer configurable with automatic zero/span calibration
Firing mode One of these firing modes can be configured on line via serial port
Phase Angle + Current Limit (PA) Soft Start + Phase Angle + Current Limit (S + PA)
Auxiliary voltage supply 230V ±15%; 10VA power consumption
440V ±15%; 10VA power consumption
Fan voltage supply 230V ±15%;
110V ±15%; on request
Heater break alarm
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors. Latching alarm plus reset. Relay output 0,5A at 125V
Feedback
Voltage feedbak (V) Square Voltage feedbak (V²) Power feedback (VxI) (option)
Serial communication RS485 Modbus protocol (option) Mounting
Din rail mounting up to 45A
Bulk head over 45A
Protection IP20
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
7 www.honeywell.com/imc
2.2 Input features
Input signal
Input
Impedance
Analog 0÷10V 8200 ohm
Analog 4÷20mA 100 ohm
Potentiometer 10Kohm
8200 ohm
2.3 Output features
NA=not Available
Current Voltage range Ripetitive peak
reverse voltage
Latching
current
Max peak one cycle
Leakage
current
I2T value for
fusing
Frequency
range
Power
loss
Isolation
Voltage
(A) (V) (440V)
(500V) (mAeff)
(10msec.)
(A)
(mAeff) tp=10msec (Hz)
I=Inom
(W)
Vac
15A 24÷440 1200 NA 150 230 15 610 47÷70 18 2500
25A 24÷440 1200 NA 150 230 15 610 47÷70 30 2500
35A 24÷500 1200 1600 250 400 15 780 47÷70 42 2500
45A 24÷500 1200 1600 250 600 15 1800 47÷70 54 2500
60A 24÷500 1200 1600 450 1000 15 4750 47÷70 72 2500
90A 24÷500 1200 1600 450 2000 15 19200 47÷70 108 2500
110A 24÷500 1200 1600 450 1350 15 8830 47÷70 137 2500
2.4 Derating curve
1
0.8
0.6
0.4
0.2
0
45 55 65 75 85
K
°C
I = I x K
NOMMAX
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 8
3. Ordering information
Model CD3200
1 2 3 4 5 6 7 8
CD3200
Ex:CD3200 90A/ 400/ 480/ 460/ SSR/ ZC/ V2/ UL
1 Nominal current of CD3200M
15A 45A 110A 25A 60A 35A 90A
2 Operating Load Voltage (incoming voltage supply)
Specify the value of the line supply.
3 Max VOLTAGE of CD3200
480V 600V The voltage on the identification label must be equal or more than operating voltage. The minimum voltage supply to the load is 24V.
4 Auxiliary Voltage
230V 200÷230V ±15%; 10VA 460V 300÷460V ±15%; 10VA 600V 600V ±15%; 10VA (on request)
5 Input
SSR 4÷30VDC 0-10V 0÷10V analog input 4-20mA 4÷20mA analog input 10K pot Potentiometer
6 Firing
PA Phase Angle + Current Limit S + PA Soft Start + Phase Angle + Current Limit
7 Feedback
V Voltage feedback (V) V2 Square Voltage feedback (V²) VxI Power feedback (VxI) (option)
8 Options
COMM MODBUS protocol in RS485 is standard CD-KP External Keypad HB Heater Break Alarm FAN110
Fan voltage supply 110VAC ± 15% (std 230VAC ± 15%) 14W
50/60Hz UL UL Certification EF External fuse and fuseholder NF No Fuse
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
9 www.honeywell.com/imc
4.Installation and wiring information
4.1 Identification of the unit
Before to install the CD3200 unit examine for damages or deficiencies. If any is found, notify the carrier immediately. Check that the product features shown on CD3200 cover and identification label corresponds to that ordered.
INPUTAMPS AUX. FIRING OPT.
0-10V15 60
240V
____
4-20mA25 90
440V
SC DT SSR35 110 POT45
___
____
PA
S.S
ZC
An identification label provides all the informations regarding the factory settings of the unit. This label is on the board inside the unit, as represented
4.2 Installation
CD3200 unit should be always mounted in vertical position to improve air cooling on heatsink.
Maintain minimum distances in vertical and in horizontal as below represented. Don’t install in proximity of hot elements and near units generating electromagnetic interferences.
A
IR OUTPUT
A
IR INP UT
15cm
2 cm
When more units are mounted inside a cubicle provide air circulation as below represented. Sometimes it is necessary to provide a fan to have a better air circulation.
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 10
4.3 Dimensions
Size W(mm) H(mm) D(mm)
15A (S0C) 63 120 120
25A (S0C) 63 120 120 35A (S3C) 85 120 120 45A (S3C) 85 120 120 60A (S7C) 148 120 159 90A (S7C) 148 120 159
110A (S8C) 148 138 159
4.4 Dimension CT (Heater Break HB)
8
1
2
39
39 20
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
11 www.honeywell.com/imc
4.5 Fixing holes
A
B
C
D
Size A(mm) B(mm) C(mm) D(mm)
15A (S0C) 110 - - -
25A (S0C) 110 - - -
35A (S3C) - 110 - -
45A (S3C) - 110 - -
60A (S7C) - - 110 65
90A (S7C) - - 110 65
110A (S8C) - - 110 65
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 12
5. Wiring Instructions
Warning: this procedure can be done just by specialized personnel.
CD3000M unit has isolated heatsink. For safety connect the heatsink to hearth using its terminal with hearth symbol. CD3000M can be susceptible to airborne interferences from near equipment or from interferences on main supply, so a number of precautions must be taken.
Contactors coils and chokes must have in parallel a RC filter and must be supplied with a
different voltage line.
All input/output signal must use screened bifilar wires.
Signal input and output must not routing in same cable try and must not be parallel.
Local regulations regarding electrical installation should be rigidly observed.
3.3.2 Auxiliary terminals
Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage.
Terminal Description
1 - External Calibration command 24Vdc max 2 + External Calibration command 24Vdc max 3 Reset 4 Reset 5 + Output Command signal to CD3200 (Internal Connections) 6 - Output Command signal to CD3200 (Internal Connections)
A2+ + Input command signal 4÷20mA, 0÷10V
A1- - Input command signal 4÷20mA, 0÷10V
7 RS485 A 8 RS485 B
9 Output +8Vdc stabilized 1mA MAX potentiometer power supply 10 Common relay H.B. alarm 11 NC/NO H.B. relay alarm 12 External Current Profile 13 CT input with H.B. option 14 CT input with H.B. option 15 Nc not connected 16 Auxiliary supply voltage 240-440Vac 17 Ground 18 Auxiliary supply voltage 240-440Vac
5.1.1 Power Terminals
Before connect or disconnect, make sure that the power, control cables and wires are insulated from the voltage
Terminal Description
L1 Line Input T1 Load Output
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
13 www.honeywell.com/imc
5.2Cabling detail
Use 75°C copper (CU) conductor only, provided with the terminal type indicated below. (Utiliser conducteur de cuivre (CU) pour 75°C seulement , avec les terminal suivants )
Current/courant
Torque/couple
Lb-in (N-m)
Wire/cable
Wire
terminal/terminal
15A, 25A, 35A, 45A 26.6 (3.0) 18-8
UL Listed (ZMVV) Wire Pin Terminal
(terminal avec cosse)
60A, 90A, 110A 70.8 (8.0) 18-1
UL Listed (ZMVV)
- Fork/Spade Terminal (terminal avec cosse a fourche)
- Copper Tube Cr. Lug (cosse tubulaire a plage étroite)
Honeywell CD3200 up to110A User’s Manual ver. 2.0
www.honeywell.com/imc 14
Power terminals wire details:
Current Supply Load
Cable Clable
mm
2
AWG
Screw
M
mm
2
AWG
Screw
M
15A 4 12 M5 4 12 M5 25A 6 10 M5 6 10 M5 35A 10 8 M5 10 8 M5 45A 10 8 M5 10 8 M5 60A 16 6 M6 16 6 M6 90A 35 3 M6 35 3 M6
110A 35 2 M6 35 2 M6
Auxiliary connectors and earth:
Current Auxiliary Supply Earth
Cable Clable
mm
2
AWG
mm
2
AWG
Screw
M
15A 0,50 18 4 12 M4 25A 0,50 18 4 12 M4 35A 0,50 18 6 10 M5 45A 0,50 18 6 10 M5 60A 0,50 18 6 10 M5 90A 0,50 18 10 8 M5
110A 0,50 18 16 6 M5
User’s Manual ver. 2.0 CD3200 up to110A Honeywell
15 www.honeywell.com/imc
5.3 Wiring connection
5.3.1 CD3200 15-25A
POWER UNIT
Input
CT
Reset
-
+
RS485-B
1
65
7 8 9
10 11
12 13 14 15
16 17 18
2
A2+3A1-
4
RS485-A
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
L1 L2
CT
**
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE:
IMPORTANT
To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
5.3.2 CD3200 35-45A
POWER UNIT
Input
CT
Reset
-
+
RS485-A
162738495
10
RS485-B
COM NO/NC
H.B. Contact
8V
External
Calibration
+-
1
65
7 8
9 10 11 12 13
14 15
16 17 18
2
A
2+
3
A
1-
4
CT
L1 L2
**
* The user installation must be protect by electromagnetic circuit breaker or by fuse isolator
** If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load ), use an external transformer as designated above.
NOTE: IMPORTANT To work, terminals 3-4 must be linked. The auxiliary voltage supply of CD3200 unit must be connected as above, and must be syncronized with load voltage power supply (L1, L2).
Loading...
+ 38 hidden pages