Honeywell C7776A, C7778A, T7022A Catalog Page

Temperature Sensors
C7776A Duct Probe
Application: Primary and/or secondary sensors in electronic control
systems
Dimensions, Approximate: 1 in. high x 2 in. wide x 7 in. deep (25 mm
high x 51 mm wide x 177 mm deep)
Operating Temperature Range: 45 F to 99 F (7 C to 37 C) Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C)
Insertion Length
Product Number Sensor Type
C7776A1006/U 10 K ohm NTC Type II
C7776A1040/U 10 K ohm NTC Type II
non-linear
non-linear
6 in. 152 mm 6 in. Duct Probe for Return Air 10 K ohm NTC Type II non-
6 in. 152 mm 6 in. Duct Probe for Return Air 10 K ohm NTC Type II non-
Description Comments(inch) (mm)
linear Temperature Sensor
linear Temperature Sensor
C7778A Duct Probe
Application: Primary and/or secondary sensors in electronic control
systems
Dimensions, Approximate: 1 in. high x 2 in. wide x 7 in. deep
(25 mm high x 51 mm wide x 177 mm deep)
Operating Temperature Range: 45 F to 99 F (7 C to 37 C)
The C7776 Air Temperature Sensors are direct wired temperature sensors that are used to sense discharge or return air in a duct. The sensors are 10 ohm NTC Type II sensors that are compatible with TB7600, TB7300, and TB7200 communicating thermostats.
• Primary and/or secondary sensor for use with
• electronic control systems
• Integral 10K ohm NTC Type II nonlinear sensors
• Operating range of 45 to 99 F (7 to 37 C)
• Mounts on a flat duct or plenum surface or, for a plenum-rated application, in a standard utility conduit box
• Probe length of 6 in. (152 mm)
• Rugged 1/4 in. diameter aluminum insertion probe
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Mounting: Mounts on flat duct or plenum surface with integral mounting
flange or in a 2 in. x 4 in. (51 mm x 102 mm) junction box.
Used With: TB7600, TB7300, TB7200 Series communicating
thermostats
6 foot plenum rated cable
The C7778 Air Temperature Sensors are direct wired temperature sensors that are used to sense discharge or return air in a duct. The sensors are 10 ohm NTC Type III sensors that are compatible with WEBs-AX I/O modules.
• Primary and/or secondary sensor for use with
• electronic control systems
• Integral 10K ohm NTC Type III nonlinear sensors
• Operating range of 45 to 99 F (7 to 37 C)
• Mounts on a flat duct or plenum surface or, for a plenum-rated application, in a standard utility conduit box
• Probe length of 6 in. (152 mm)
• Rugged 1/4 in. diameter aluminum insertion probe
Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C) Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Mounting: Mounts on flat duct or plenum surface with integral mounting
flange or in a 2 in. x 4 in. (51 mm x 102 mm) junction box.
Used With: WEBs-AX I/O Modules
Commercial
Components
Insertion Length
Product Number Sensor Type
C7778A1006/U 10 K ohm NTC Type III
C7778A1040/U 10 K ohm NTC Type III
non-linear
non-linear
6 in. 152 mm 6 in. Duct Probe for Return Air 10 K ohm NTC Type III non-linear
6 in. 152 mm 6 in. Duct Probe for Return Air 10 K ohm NTC Type III non-linear
Description Comments(inch) (mm)
Temperature Sensor
Temperature Sensor
T7022A Return Air Temperature Sensor
The T7022 Remote Temperature Sensor is a non-adjustable thermistor sensor. Its primary use is with the T7300 Programmable Commercial Thermostat (only in return air) to control heating or cooling equipment.
Application: Remote Temperature Sensors for use with T7300
thermostats
Dimensions, Approximate: 3/8 in. dia. x 2 3/4 in. long
(10 mm dia. x 70 mm long)
Operating Temperature Range: 60 F to 90 F (16 C to 32 C) Used With: T7300, T7067B, W927
Insertion Length
Product Number Sensor Type
T7022A1010/U 1420 ohms @ 75 F 2 3/4 in. 70 mm 1420 ohm Remote Temperature Sensor
Description(inch) (mm)
70-6910 467
6 foot plenum rated cable
Loading...