FEATURES

• Low profile when mounted on industry standard utility conduit box.
• Rugged, brushed stainless steel wallplate.
• Integral foam pad isolates wallplate sensor from conduit box.
• Insulated screw terminals ensure reliable field wiring connection.
• Models available with a variety of resistive temperature sensor elements.
PRODUCT DATA

APPLICATION

The C7772A series of Wallplate Temperature Sensors are designed to be used with the Excel 5000 family and other Honeywell controllers. The C7772F Series is designed to be used with the TB7600, TB7300, and TB7200 Series communicating thermostats and other controllers that require a 10K ohm NTC Type II sensor. The C7772G is designed to be used with WEBs-AX I/O modules and other controllers that require a 10K ohm NTC Type III sensor. The C7772 sensors provide a resistive output signal proportional to sensed room or space temperature. The C7772 is well suited for low-profile wall-mounted applications where durability and tamper-proof construction is desired, such as schools, prisons and institutions.
C7772A, F, G WALLPLATE TEMPERATURE SENSOR
CAUTION
4-1/2 (114)
3-5/16
(84)
2-3/4 (70)
5/16 (8)
M16295A

SPECIFICATIONS

Models: See Table 1.
Dimensions: See Fig. 1.
Temperature Ratings: Operating: 45°F to 99°F (7°C to 37°C). Shipping: -40°F to 150°F (-40°C to 65°C).
Long-term temperature sensor drift: (for 20K ohm sensors only) Maximum sensor drift is nominally +/-0.13°F after 5 years of operation, no appreciable drift thereafter. No calibration of the device is possible. Long term drift calibration/maintenance through controller software is typically not necessary.
Humidity Ratings: 5 to 95% rh, non-condensing.
Approvals: National Electrical Code (NEC) Class II.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
5. Follow local codes for installation and application.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect all power supplies before installation.

Location

The C7772 Wallplate Temperature Sensor should be located where it can sample an average air temperature. Avoid locations where air stratification can cause sensing errors. The sensor mounts directly on a 2 in. x 4 in. conduit box with the screws provided.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
68-0213-04 2
Fig. 1. C7772 Dimensions in in. (mm).
1885 Douglas Drive North Minneapolis, Minnesota 55422-4386