C7735A1000 Duct Air
M33115
2-7/16 (62)
1-1/32
(26)
3-15/16 (100)
2-7/16
(62)
Temperature Sensor
INSTALLATION INSTRUCTIONS
APPLICATION
The C7735A1000 Duct Air Temperature Sensor (DATS)
is a duct-mounted temperature probe used to sense
discharge air temperature in zoning applications for high
and low temperature limit protection. Alternatively, it is
used with certain Honeywell thermostats for delta-T
diagnostics and IAQ control. For more on these
applications, please see the installation instructions for
those products.
Fig. 1. C7735A dimensions in in. (mm).
INSTALLATION
1. Assemble the DATS by attaching the metal sensor
probe to the plastic cap. Insert the plate of the
probe into the two tabs on the inside bottom of the
cap. Then rotate the plate clockwise until it clicks
into the single top tab.
2. Locate the DATS on the supply trunk between the
bypass damper and the evaporator coil and/or heat
exchanger. If a bypass damper is not used, locate
the DATS between the zone dampers and the
evaporator coil and/or heat exchanger. See Fig. 2.
BY PASS DAMPER
PLACE SENSOR
INTHIS AREA.
ZONE DAMPERS
EVAPORATOR COIL
HEAT EXCHANGER
DO NOT
PLACE
SENSOR IN
THIS AREA.
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
IMPORTANT
Do not locate the DATS probe in a duct near the
heat exchanger or strip heat, which can cause
false temperature readings.
BLOWER
M14877A
Fig. 2. DATS mounting location.
3. Drill a 1/4 in. hole in the duct at the location
selected for the sensor.
4. Attach wire using wire nuts and push them into the
cover, then insert the probe into the hole drilled in
step 2.
5. Secure the DATS to the side of the duct, through
the two mounting holes, with the screws supplied.
IMPORTANT
Use 18-22 gauge thermostat wire for shorter
runs. For longer runs or when wiring near voltage, use shielded cable.
6. Run wire to zone panel or thermostat. See zone
panel or thermostat installation instructions.
C7735A1000 DUCT AIR TEMPERATURE SENSOR
Table 1. DATS Resistance Cross Reference.
Temperature (°F) Resistance
32 33630
33 32668
34 31737
35 30835
36 29962
37 29117
38 28298
39 27505
40 26737
41 25993
42 25272
43 24573
44 23896
45 23240
46 22604
47 21988
48 21390
49 20810
50 20248
51 19703
52 19175
53 18662
54 18165
55 17683
56 17215
57 16761
58 16320
59 15892
60 15477
61 15074
62 14683
63 14303
64 13934
65 13576
66 13229
67 12891
68 12563
69 12244
70 11935
71 11634
72 11342
73 11058
74 10782
For more information: http://customer.honeywell.com
For technical support, call 1-800-TAT-Temp (1-800-828-8367).
Temperature (°F) Resistance
75 10514
76 10253
77 10000
78 9754
79 9514
80 9281
81 9055
82 8835
83 8621
84 8412
85 8210
86 8013
87 7821
88 7634
89 7453
90 7276
91 7104
92 6937
93 6774
94 6615
95 6461
96 6311
97 6164
98 6022
99 5883
100 5748
101 5617
102 5488
103 5363
104 5242
105 5123
106 5008
107 4895
108 4786
109 4679
110 4575
111 4473
112 4374
113 4278
114 4183
115 4092
116 4002
117 3915
Temperature (°F) Resistance
118 3830
119 3747
120 3666
121 3587
122 3510
123 3435
124 3362
125 3290
126 3221
127 3153
128 3086
129 3021
130 2958
131 2896
132 2836
133 2777
134 2720
135 2664
136 2609
137 2555
138 2503
139 2452
140 2402
141 2353
142 2306
143 2259
144 2214
145 2170
146 2126
147 2084
148 2043
149 2002
150 1963
151 1924
152 1886
153 1849
154 1813
155 1778
156 1744
157 1710
158 1677
159 1645
160 1613
Temperature (°F) Resistance
160 1582
162 1552
163 1523
164 1494
165 1466
166 1438
167 1411
168 1385
169 1359
170 1334
171 1309
172 1285
173 1261
174 1238
175 1215
176 1193
177 1171
178 1150
179 1129
180 1108
181 1088
182 1069
183 1050
184 1031
185 1012
186 994
187 977
188 959
189 943
190 926
191 910
192 894
193 878
194 863
195 848
196 833
197 819
198 805
199 791
200 777
——
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
69-1521EFS—01 M.S. 10-11
Printed in United States
Capteur de température d’air de
M33115
2-7/16 (62)
1-1/32
(26)
3-15/16 (100)
2-7/16
(62)
REGISTRES DE ZONE
REGISTRE DE
DÉRIVATION
PLACER LE
CAPTEUR DANS
CETTE ZONE.
NE PAS
PLACER LE
CAPTEUR
DANS CETTE
ZONE.
MF14877
SERPENTIN D’ÉVAPORATION
ÉCHANGEUR DE CHALEUR
SOUFFLANTE
gaine C7735A1000
NOTICE D'INSTALLATION
APPLICATION
Le capteur de température d’air de gaine C7735A1000
est une sonde de température montée en gaine utilisée
pour détecter la température de l'air de soufflage dans
les applications de zonage pour la protection avec
limiteur de température haute et basse. Il peut aussi être
utilisé avec certains thermostats Honeywell pour le
diagnostic Delta-T et la régulation IAQ. Pour en savoir
plus sur ces applications, veuillez consulter la notice
d'installation de ces produits.
Fig. 1. Dimensions du C7735A en po (mm).
INSTALLATION
Lors de l’installation du produit...
1. Lire attentivement ces instructions. Le non-respect
des instructions peut endommager le produit ou
provoquer une situation dangereuse.
2. Vérifier les caractéristiques nominales indiquées
dans les instructions et sur le produit pour vous
assurer que le produit correspond bien à
l’application prévue.
3. L’installateur doit être un technicien expérimenté
ayant reçu la formation adéquate.
4. Une fois l’installation terminée, utiliser ces
IMPORTANT
1. Assembler le capteur de température d’air de
instructions pour vérifier le bon fonctionnement du
produit.
Ne pas installer la sonde du capteur de
température d’air de gaine dans une gaine près
d’un échangeur de chaleur ou d’une bande
chauffante pour ne pas causer des relevés de
température inexacts.
gaine en attachant la sonde en métal au capuchon
en plastique. Insérer la plaque de la sonde dans
les deux languettes à l’intérieur du bas du
capuchon. Faire ensuite tourner la plaque dans le
sens horaire jusqu’à ce qu’elle s’enclenche dans la
languette supérieure unique.
2. Placer le capteur de température d’air de gaine sur
le bloc d’alimentation entre le registre de dérivation
et le serpentin d’évaporation et/ou l’échangeur de
chaleur. Si aucun registre de dérivation n’est
utilisé, placer le capteur de température d’air de
gaine entre les registres de zone et le serpentin
évaporateur et/ou l’échangeur de chaleur. Voir la
Fig. 2.
Fig. 2. Emplacement de montage du capteur de
3. Percer un trou de ¼ po dans la gaine à
4. Attacher le fil en utilisant les deux serre-fils et le
5. Attacher le capteur de température d’air de gaine
IMPORTANT
6. Acheminer le fil jusqu’au tableau de zone ou
température d’air de gaine.
l’emplacement sélectionné pour le capteur.
pousser dans le couvercle, puis insérer la sonde
dans le trou percé à l’étape 2.
sur le côté de la gaine, par les deux trous de
montage, avec les vis fournies.
Utiliser un câble de thermostat de calibre 18-22
pour les longueurs réduites. Pour les longueurs
plus longues ou pour un câblage près
d’équipement sous tension, utiliser un câble
blindé.
jusqu’au thermostat. Consulter la notice
d’installation du tableau de zone ou du thermostat.