C7650A
Solid State Temperature Sensor
PRODUCT DATA
FEATURES
• Senses temperature of outdoor air.
• Long lasting thermistor sensing element is accurate
and stable over time.
• When temperature of outdoor air increases, the
outdoor air damper is closed to a preset minimum
position.
• When temperature of outdoor air is low, the outdoor
air damper is opened to reduce the cooling load in the
building.
•Provides 10 to 20 mA output signal to W7459 Solid
State Economizer Control; setpoint is located on solid
state economizer control.
GENERAL
C7650A Solid State Thermistor Sensor is used with the
W7459 Solid State Economizer Control Package. The W7459
Solid State Economizer Control Package is usually mounted
on an M7405/M7415 Actuator. It permits the use of outdoor
air as the first stage of cooling in heating, ventilating and air
conditioning (HVAC) systems. The application is for
differential or single temperature economizer control on
HVAC equipment up to approximately 20 tons.
• Sensor is enclosed in a rugged, corrosion-resistant
glass-fiber reinforced plastic case.
• Compact size and lightweight construction provide
easy mounting in HVAC rooftop unit.
Contents
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 2
Operation ............................................................................ 3
Copyright © 1996 Honeywell Inc. • All Rights Reserved
63-2499-1
C7650A SOLID STATE TEMPERATURE SENSOR
SPECIFICATIONS
5
(8)
16
Model:
C7650A Solid State Temperature Sensor.
Case:
Duct mount.
Temperature Sensing Element:
Thermistor.
Output Signal:
10 to 20 mA current signal; increases from 10 mA to 20 mA
as temperature decreases.
Operating Ambient Temperature Range:
+40°F to +100°F (+4°C to +38°C).
Shipping Temperature Range:
-40°F to +150°F (-40°C to +66°C).
Maximum Power Consumption:
0.45 VA.
Supply Voltage:
15 to 23 Vdc.
Electrical Connections:
Tw o 1/4 in. (6.5 mm) quick connect terminals.
Approval:
Underwriters Laboratories Inc. Flammability Rating: UL94-5V.
Dimensions:
See Fig. 1.
5
3
16
(14)
9
1 (25)
32
(80)
2
(70)
7
32
(6)
3
4
7
3 (96)
8
+
S
M9096
Fig. 1. C7650A Thermistor Temperature Sensor
Dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2499—1 2