Honeywell C7600A User Manual

C7600A
63-2150-5
Solid State Humidity Sensor
PRODUCT DATA
FEATURES
• Long-lasting solid state sensing element is accurate and stable over time.
• Sensor enclosed in rugged glass-fiber reinforced plastic case.
• Compact size and lightweight construction for easy mounting in duct or on wall.
•Vents in top of cover allow air flow to internal humidity sensing element.
•4 to 20 mA output inversely proportional to relative air humidity.
• Can be used indoors or outdoors.
GENERAL
The C7600A Solid State Humidity Sensor senses the relative humidity of the return air and is used with the W7600 Multifunction Controller or any controller capable of processing a 4 to 20 mA signal.
Contents
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 3
Operation ............................................................................ 5
Copyright © 1996 Honeywell Inc. • All Rights Reserved
C7600A SOLID STATE HUMIDITY SENSOR
SPECIFICATIONS
IMPORTANT
Model:
C7600A Solid State Humidity Sensor. Use with W7600 Multifunction Controller or any controller capable of processing 4 to 20 mA signal.
Electrical Ratings:
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed.
Input:
18 to 24 Vdc.
Output:
4 to 20 mA current signal; increases from 4 to 20 mA as humidity decreases. The relationship of the C7600A output current vs. relative humidity is shown in Fig. 2. It is not possible to develop a straight-line formula for calculating the C7600A current output from a given relative humidity; however, the exponential formula below gives accurate results for this relationship.
I = 19.12925 - 0.1507896RH + 1.720302(10
- 1.598528(10-7)RH
3
-4
)RH
Where:
I is the current output of the C7600A in mA. RH is the percent relative humidity.
Maximum Power Consumption: 0.48 VA.
Humidity Sensitivity:
+/- 3 percent.
Humidity Sensing Element:
Polyamide film (capacitance changes with change in humidity).
Case:
Compact, rugged, lightweight plastic case.
Mounting:
Duct-mounted indoors, or wall-mounted outdoors in a location protected from rain, snow, or direct sunlight.
Terminals:
Tw o 1/4 in. (6 mm) quick-connect terminals.
Dimensions:
See Fig. 1.
Time Constants:
Airflow: 500 fpm. Time: 15 minutes.
Approvals:
Underwriters Laboratories Inc.: Flammability rating UL94-5V.
3-5/32
(80)
2-3/4
(70)
7/32 (6)
5/16 (8)
2
Ambient Temperature Ranges:
Operating:
32°F to 125°F (0°C to 52°C).
Shipping:
-40°F to +150°F (-40°C to +66°C).
Humidity Range:
10 to 90 percent relative humidity.
9/16 (14)
1(25)
Fig. 1. C7600A Solid State Humidity Sensor
dimensions in in. (mm).
3-7/8 (96)
M3129A
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2150—5
2
C7600A SOLID STATE HUNIDITY SENSOR
20
18
16
14
12
10
CURRENT IN mA
8
6
4
0
10
20 10090807060504030
HUMIDITY IN % RH
RH (%) I (mA)
18.4
10
16.8
20
15.2
30
13.6
40
12.0
50
10.4
60
8.8
70
7.2
80
5.6
90
M3130
Fig. 2. C7600A output current vs. relative humidity.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. Checkout according to instructions provided with the controller before leaving installation.
CAUTION
Disconnect power before installation to prevent electrical shock or equipment damage.
Location
When selecting the location, make certain that the humidity sensor is not exposed to rain, snow, or direct sunlight. The C7600A Solid State Humidity Sensor is designed to operate in 500 ft/min minimum airflow.
Mounting
The C7600A Solid State Humidity Sensor can be mounted in any position; however, the sensor must be installed where it is exposed to freely circulating air, with at least 500 ft/min airflow.
Mounting the C7600 Solid State Humidity Sensor Outdoors
Select a location protected from rain, snow or direct
sunlight.
Attach the sensor to the wall with two 1/8 in. (3 mm)
diameter screws.
Wire as shown in the Wiring section.
Installing C7600 Solid State Humidity Sensor in Return Air Duct (See Fig. 3)
NOTE: Installers need to supply the following: sheet metal
cutter or snips; drill with 1/16 in. (2 mm), 1/8 in. (3 mm) and 1/2 in. (13 mm) bits; screwdrivers; 1/2 in. (13 mm) rubber grommet; eight self-tapping sheet metal screws; and two 1/8 in. (3 mm) by 3/4 in. (19 mm) machine screws with lockwashers and nuts.
Cut a 5 in. (127 mm) by 6 in. (152 mm) rectangular
hole in one side of the return air duct.
Center the sensor on a 6 in. (152 mm) by 7 in. (178 mm)
piece of sheet metal. Mark locations for mounting screws and for a hole for the control wire.
Drill two 1/8 in. (3 mm) mounting holes for the sensor
and one 1/2 in. (13 mm) hole for the control wire.
Drill eight starting holes in the sheet metal rectangle for
self-tapping sheet metal screws.
Center sheet metal rectangle over opening in duct so
there is a 1 in. (25 mm) overlap on all four sides. Then mark the eight sheetmetal screw locations on the duct.
Drill eight starting holes in the duct for self-tapping
sheet metal screws.
Attach sensor to sheet metal rectangle with 1/8 in.
(3 mm) by 3/4 in. (19 mm) machine screws, washers and nuts. Attach the machine screws from the outside of the sheet metal to eliminate protrusions and possible sharp edges.
Place a rubber grommet in the 1/2 in. (13 mm) hole in
the sheet metal to protect the control wires from abrasions.
Put the control wires through the 1/2 in. (13 mm) hole
and wire as shown in the Wiring section.
Attach the sheet metal rectangle to the duct with self-
tapping sheet metal screws. Make sure that airflow over the sensor is as shown in Fig. 3.
3
63-2150—5
C7600A SOLID STATE HUMIDITY SENSOR
(127)
5
6
(152)
AIR FLOW
1
6
(152)
AIR FLOW
7
AIR FLOW
8
AIR FLOW
3
7
(178)
9
4
2
10
5,6
M5242A
63-2150—5
Fig. 3. Installing C7600A Solid State Humidity Sensor in return air duct.
4
C7600A SOLID STATE HUNIDITY SENSOR
Wiring
Disconnect the power supply before beginning wiring to prevent electrical shock or equipment damage. All wiring must comply with applicable codes and ordinances. Follow the wiring information furnished by the controller manufacturer or refer to Fig. 4 for a typical wiring hookup. Note and follow polarity markings for hookup.
=8 =7 =6 =5 =4 =3 =2 =1 =D COM
=24 VDC(+) =8 =7 =6 =5 =A COM
OPERATION
The C7600A Solid State Humidity Sensor provides a 4 to 20 mA output signal that is inversely proportional to the relative humidity of the return air.
The sensing element in the C7600A Solid State Humidity Sensor is a humidity-sensitive polyamide film that changes capacitance with a change in humidity. This change in capacitance is converted by a printed circuit board assembly to an output current between 4 and 20 mA. The output current is used by an analog or a microprocessor-based controller to measure and control humidity.
W7600
8=
DIGITAL INPUTS
ANALOG INPUTS
DIGITAL
OUTPUTS
DIGITAL
OUTPUTS
D COM=
D COM=
7= 6= 5=
4= 3= 2= 1=
+
C7600C RETURN AIR HUMIDITY SENSOR
1
237 OHM, 1 PERCENT, 1/8 WATT METAL FILM RESISTOR.
M3128
Fig. 4. Wiring C7600A Solid State Humidity Sensor to W7600.
4=
A COM=
GND=
V2= V1=
V2= V1=
3= 2= 1=
4= 3= 2= 1=
ANALOG
OUTPUTS
=20 VDC(+) =4 =3 =2 =1 =A COM
1
=V1 =V2 =GND
ANALOG INPUTS
24 VAC INPUT
S7600A
24 VAC
OUT
24 VAC
OUT
5
63-2150—5
C7600A SOLID STATE HUMIDITY SENSOR
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524
Honeywell Latin American Division
Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016
63-2150—5 G.H. Rev. 12-96
63-2150—5
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9
Honeywell Europe S.A.
3 Avenue du Bourget B-1140 Brussels Belgium
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers
6