3 EN1C-0015SZ20 R0602
TECHNICAL DATA
SPECIFICATION
Specification
Models
C7061A: Self checking UV flame detector in standard
housing.
C7061F: Self checking UV flame detector in explosion proof
housing. Designed for use with either,
R7061 Dynamic Self-Check Ultraviolet amplifier and
• R4348 Flame Switch
or with,
R7861A Dynamic Self-Check Ultraviolet amplifier and,
• 7800 SERIES Burner Programmers
Ambient Operating temperature ratings
C7061A: -40°C to +70°C (-40°F to +160°F)“(derate ambient
1°F for every 13°F of aspirator temperature over
160°F).
C7061F: -20°C to +70°C (-22°F to +160°F)
Storage temperature ratings
• -51°C to +85°C (-60°F to +185°F)
Voltage and Frequency
C7061A1004 120 VAC, 50/60 Hz
C7061A1020 115/230 VAC, 50/60 Hz
C7061F1003 115/230 VAC, 50/60 Hz
The System operates correctly at a nominal voltage (-15%,
+10%), 50/60 Hz.
Flame Signal
Measured at the flame current meter jack.
C7061 Detector: 1.4 to 5.5 micro amps (nominal).
R7061A Amplifier: 2.5 to 5.5 micro amps (nominal).
R7861A Amplifier: 1.25 to 5.0 Volts (On keyboard
display module).
Flame Signal amplifier
R7061A Dynamic Self-Check Ultraviolet amplifier
R7861A Dynamic Self-Check Ultraviolet amplifier
(Order separately)
lnterchangeability
Models C7061A and C7061F are not interchangeable with
other flame detector models.
Shutter frequency
0.2 Hz, nominal (when used in combination with 7800 SERIE). Interrupts the line-of-sight of the detector about 12 times
per minute to provide self-checking. Any malfunction in the
flame detection system results in a safety shutdown. 1Hz
nominal when used with R4348 in combination with R7061
amplifier.
Pressure rating of quarz viewing window
C7061A: 138 kPa (20 psi) maximum.
C7061F: 690 kPa (100 psi) maximum
Dimensions
C7061A: see figure 1.
C7061F: see figure 2.
Housing
C7061A:
Construction:
cast-aluminum cover.
Color:
Violet.
Mounting flange (with heat block) and faceplate are separate
to provide heat insulation and seal-Off.
C7061F:
Meets requirements (explosion-proof): EEx d IIC T6
Construction:
cast-aluminum Cover.
Color:
Violet. Mounting flange (with heat block) and faceplate
are separate to provide heat insulation and seal-Off.
Enclosure
C7061A: Meets IP66 enclosure requirements (indoor,
outdoor protection; rain-tight, dust-tight, hosedirected water). “Optional water jacket available.
C7061F: IP65 according to DIN 40050
Weight
C7061A: 3.3 kg (7.3 Ib)
C7061F: 6.3 kg (13.9 Ib)
Mounting and orientation
C7061A : Mounting flange with 3/4 inch NPT internal threads
for attaching to sight pipe.
C7061F: Mounting flange with 1 inch NPT internal threads
for attaching to sight pipe.
For allowable mounting positions of model C7061A and F,
see Page 9.
Wiring Connections
C7061A1004:
NEC Class 1 color coded leadwire.
Length: 8 ft (2.4m).
C7061A1020:
Terminal block
Threaded leadwire opening in faceplate:
1/2-14 NPSM internal threads for attaching conduit.
One brass cable gland standard with housing.
For C7061F only:
Terminal block:
Terminal block inside the housing, wire clamp type,
removable screws (terminal lugs can be used).
Cable entry holes:
One brass cable gland Ex classification: EExdII C, is
standard provided in the housing.
Inner sheath diameter 6 to 12 mm
Outer sheat diameter 8.5 to 16 mm
Tightening torque:
• cable gland into rear cover plate: 20 Nm
• cap into cable gland: 3 Nm
Serviceability
Field replaceable viewing window and ultraviolet sensing
tube, coil and shutter assembly.
Maximum cable length
300 meter between sensor and amplifier
Design life
Ultraviolet sensing tube: limited life, see sections
Troubleshooting and Service.