Honeywell C7061A, C7061F Product Data

65-0223-07
SIL
3
Capable
C7061A,F Dynamic Self-Check
C7061F
C7061A
PRODUCT DATA

FEATURES

• Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor 12 times per minute to provide the UV sensor tube checking function. Amplifier circuitry components are checked from the microprocessor in the 7800 Series Control.
• Detectors can be mounted horizontally, vertically or at any other angle. The self-checking C7061 models require faceplate alignment and have integral locating reference points to assure proper shutter mechanism operation.
• Ultraviolet radiation sensing tube and quartz viewing window are field replaceable.
• Threaded conduit fitting and color-coded leadwires allow rapid electrical installation.
• Models available using Brad Harrison® 41310 connector.
• Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
• -40°F (-40°C) rated ultraviolet sensing tube.

APPLICATION

The C7061A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels.
• Incorporates UV sensor tube checking feature; used with R7861 Dynamic Self-check Amplifiers.
• Housing meets NEMA 4 enclosure standards (C7061A).
• Protective heat block built into mounting flange.
C7061F
• Housing designed to be explosion-proof and Underwriters Laboratories Inc. listed for use in hazardous locations; Class I, groups C and D; and Class II, groups E, F and G.
• Viewing window rated for 100psi (690 kPa).
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Wiring (Fig. 10) ................................................................. 7
Adjustments and Checkout .............................................. 8
Troubleshooting ................................................................ 10
C7061A,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the specifications listed. This product is tested and calibrated under closely controlled conditions, and minor differences in performance can be expected if those conditions are changed.
Models:
C7061A Dynamic Self-Check Ultraviolet Flame Detector. C7061F Dynamic Self-Check Ultraviolet Flame Detector.
(Same as C7061A except with explosion-proof housing for use in hazardous locations).
Electrical Ratings:
Voltage and Frequency: The C7061 is powered from the Flame Safeguard unit that
delivers the necessary voltages to operate the tube and shutter.
Ambient Operating Temperature Ratings
(Outside the Case): -40°F to 175°F (-40°C to 80°C) using
part no. 129464N UV Sensing Tube.
Storage Temperature Ratings: -60°F to 175°F (-50°C to 80°C).
Housing:
C7061A:
Violet, cast-aluminum cover. Separate mounting flange
(with heat block) and faceplate provide heat insulation and sealoff.
Meets NEMA 4 enclosure requirements (indoor, outdoor
protection; rain-tight, dust-tight, hose-directed water protection).
Optional water jacket available; see Accessories.
C7061F: Explosion-proof, two-piece, violet, cast aluminum.
Pressure Rating of Quartz Viewing Window:
C7061A: 20 psi (138 kPa), see Replacement Parts. C7061F: 100 psi (690 kPa).
Mounting: C7061A: Mounting flange with 3/4 NPT internal
threads for attaching to sight pipe.
C7061A1046: Mounting flange with 1 inch NPT internal
threads for attaching to sight pipe.
C7061F: Pipe union with 1 inch NPT internal threads for
attaching to sight pipe.
Wiring Connections:
Leadwire: NEC Class 1 color coded. Length: 8 ft (2.4m).
Threaded Leadwire Faceplate Opening: 1/2-14 NPSM internal threads for attaching conduit.
Connector: C7061A1038 and C7061A1046: Brad Harrison®
41310.
Dimensions: See Fig. 1.
Weight:
C7061A: 2.6 lbs (1.2 kg). C7061F: 14.5 lbs (6.6 kg).
Serviceability:
C7061A: Field replaceable ultraviolet sensing tube viewing
window, coil and shutter assembly gaskets.
C7061F: Field replaceable self-checking coil and shutter
assembly.
SIL 3 Capable:
The C7061A or F when used with a R7861 self-check ampli-
fier in Relay Module EC7810A, 20A, 30A, 40L, 50A; RM7800[E,G,L,M], 30A, 38[A,B,C], 40[E,G,L,M] 50A, 90[A,B,C,D], 97[A,C], 98A is SIL 3 Capable in a properly designed Safety Instrumented System. See form number 65-0312 for Certificate Agreement.
Approvals:
Underwriters Laboratories Inc. Listed: File Number MP268,
Guide Number MCCZZ.
Canadian Standards Association Certified: Master File
LR95329-1. Factory Mutual Approved: 14740.01. SwissRe (formerly Industrial Risk Insurers) Acceptable. C7061F: For use in hazardous locations; Class I, Groups C
and D; Class II, Groups E, F, and G; File no. E34649.
Pressure Rating of Quartz Focusing Lens: 20 psi (138 kPa), see Accessories.
Replacement Parts:
All Models:
129464N Ultraviolet Sensing Tube; -40°F (-40°C).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0223—07 2
C7061A,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR
CAUTION
WARNING
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167A
3-3/4
(95)
7-7/32
(183)
5-1/8 (130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046: 1 INCH NPT
C7061A1038 AND C7061A1046: BRAD HARRISON® CONNECTOR.
M1963
FACEPLATE
PIPE UNION
8 (203) DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2 (51)
5 (127)
1-11 1/2 NPT
2-1/16 (52)
1­1/2 (38)
5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2)
2 (51)
1 (25)
3 (76)
114465 Gasket, silicone rubber; for installing viewing
window (three required).
190971B Coil and Shutter Assembly.
C7061A:
114372 Quartz Viewing Window; rated for 20 psi (138 kPa). 120739 Gasket, fiber-neoprene; heat insulation and
seal-off for mounting flange.
C7061F:
122037 Quartz Viewing Window; rated for 100 psi
(690 kPa).
Fig. 1. Dimensions of C7061A in in. (mm).
Fig. 2. Dimensions of C7061F in in. (mm).
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced flame safeguard
service technician.
4. After installation is complete, check out product
operation as provided in these instructions.
Equipment damage hazard. Sensing tube can fail to discriminate between flame conditions.
Change sensing tube after 40,000 hours of continuous use.
Electrical shock hazard. Can cause serious injury or death.
Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be involved.
IMPORTANT
1. Do not connect these detectors to non-Honeywell manufactured controls (primaries, programmers, multiburner systems, and burner management systems). Unsafe conditions could result.
2. All wiring must be NEC Class 1 (line voltage).
3. Voltage and frequency of the power supply connected to this detector must agree with the values marked on the detector.
4. Sight the detector so it does not respond to ignition spark.
5. On multiburner installations, each detector must respond only to the flame of the burner it is supervising.
6. Do not connect more than two C7061 Flame Detectors in parallel.
Proper flame detector installation is the basis of a safe and reliable flame safeguard installation. Refer also to the burner manufacturer instructions. Carefully follow all instructions for the best possible flame detection application.
Accessories:
C7061A:
122748 Quartz Viewing Window, rated for 50 psi
(345 kPa).
124204 Quartz Focusing Lens, rated for 20 psi (138 kPa);
increases the detector-sensed ultraviolet radiation. 123539 Antivibration Mount. 204341 Mirror Assembly. 124198 Mounting Flange, aluminum, with 1 inch NPT
internal threads for attaching to sight pipe. 190105 Water Jacket.

When Installing this Product...

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.

INSTALLATION

Basic Requirements

The combustion flames of most carbon-based fuels emit sufficient ultraviolet radiation to enable the C7061 Solid State (Purple Peeper) Ultraviolet Flame Detector to prove the presence of a flame in a combustion chamber. The detector is mounted outside the combustion chamber with its mounting flange or union threaded to one end of a sight pipe inserted through the wall of the combustion chamber. The ultraviolet sensing tube in the flame detector sights the flame through the pipe.
When a flame is present, the UV tube in the C7061 senses the ultraviolet radiation emitted. The C7061 then produces a signal that is sent to the amplifier in the flame safeguard control. The amplified signal pulls the flame relay into the control to allow proper system operation.
Because it is necessary for the UV sensing tube to actually see the flame, it is best to locate the detector as close to the flame as physical arrangement, temperature, and other restrictions permit. These restrictions are described in detail in the following paragraphs.
3 65-0223—07
C7061A,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR
M1956
DETECTOR IN GOOD SIGHTING POSITION (LOW ANGLE SIGHTING)
FLAME DEPTH­ANGLE VIEW
BURNER NOZZLE
DETECTOR IN POOR SIGHTING POSITION
FLAME DEPTH­PERPENDICULAR VIEW
UNBURNED FUEL

Determine Location

Before beginning the actual installation, determine the best location for mounting the detector. Carefully consider the factors discussed in this section before deciding on the location.
Temperature
Install the C7061 where the ambient temperature (outside the case) stays within the ambient operating temperature ratings.
To keep the C7061 below its maximum rating, it may be necessary to add additional insulation between the wall of the combustion chamber and the detector. A shield or screen can be added to reflect radiated heat away from the detector. If the detector continues to get too hot, cooling is necessary. Refer to the Sight Pipe Ventilation section. (A 190105 Water Jacket is also available for cooling the C7061.)
Vibration
If the C7061 is subject to excessive vibration, use a special 123539 Antivibration Mount. If you use this mount, install it before you position and sight the detector.
Clearance
Make sure there is enough room to easily mount the sight pipe, detector, and all required fittings, and to remove the detector for troubleshooting and servicing.

Radiation Sources (Other than Flame)

Examples of radiation sources (other than flame) that could actuate the detection system:
Ultraviolet sources:
Hot refractory above 2300°F (1260°C).
Spark:
— Ignition transformers. — Welding arcs. — Lightning. Welding flames.
High voltage condensers.
High voltage coronas.
Radioisotopes.
Except under unusual circumstances, none of these sources except hot refractory and ignition spark would be present in or near the combustion chamber.
The detector can respond to hot refractory above 2300°F (1260°C) if the refractory surface represents a significant percentage of the detector field of view. If the temperature of the hot refractory causes the flame relay (in the flame safeguard control) to pull in, re-aim the sight pipe so the detector views a cooler area of the refractory.
Ignition spark is an intense source of ultraviolet radiation.
When installing the detector, make sure it does not respond to ignition spark.

Single Burner Requirements

The detector must have an unobstructed view of a steady part of the flame it is supervising. This requires a proper sighting angle and minimized ultraviolet radiation attenuation effects. However, when supervising only one burner, sighting requirements are simplified.

Sighting Angle (Fig. 3)

The first 30 percent of a flame closest to the burner nozzle (the flame root) emits the most ultraviolet energy. Also, if the detector sights the flame at an angle instead of perpendicularly, it views more flame depth. Therefore, the best sighting angle is nearly parallel to the axis of the flame, permitting the detector to view a large portion of the first 30 percent of the flame closest to the burner nozzle, as illustrated in Fig. 3.
Low angle sighting permits the detector to view a greater depth of flame, thus reducing the effects of instabilities in the flame pattern. Also, the environment near the burner nozzle is usually cleaner than at any other part of the combustion chamber. This provides a clearer line of sight and can keep the viewing window cleaner, thus reducing the maintenance required.
Bright incandescent or fluorescent artificial light.
Solar radiation.
Gas lasers.
Sun lamps.
Germicidal lamps.
Bright flashlight held close to the sensing tube.
Gamma ray and X-ray sources:
Diffraction analyzers.
Electron microscopes.
Radiographic X-ray machines.
High voltage vacuum switches.
65-0223—07 4
Fig. 3. Detector sighting angle.
NOTE: When possible, it is desirable to tilt the detector and
sight pipe downward to prevent the buildup of soot in the pipe or on the viewing window.
Loading...
+ 8 hidden pages