Honeywell C7057 Installation Instructions Manual

C7057
1
8
Cadmium Sulfide Photocell
INSTALLATION INSTRUCTIONS
APPLICATION
The C7057 Cadmium Sulfide Photocell is used to sense ambient light levels. It is used as the sensing element for the CR7075A Lighting Controller which can provide on/off control of two separate lighting banks based on user determined ambient light intensity levels. Typical applications include outdoor cosmetic and parking lot lighting in fast food restaurants retail establishments, supermarkets, banks and lighted billboards.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Dimensions (Fig. 1)
3/4 (19)
3/16
(21)
1-9/16
(40)
Location
Locate the photocell sensor so that the lens is exposed to full daylight. (See Fig. 2.)
NOTES:
Select an area which will not become shaded. — Mount only with light entrance facing
horizontally.
Avoid overexposure to direct east/west
sunlight.
Mounting
IMPORTANT
Mount the photocell sensor to the top of a watertight, outdoor FS junction box.
1. Use the gasket provided to prevent moisture entry.
2. Screw stem into 1/2-14 threaded knockout.
NOTE: The photocell sensor can be mounted in a
7/8 in. hole (or knockout).
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
2-1/8 (54)
3 (76)
Fig. 1. C7057 approximate dimensions in in. (mm).
Before Installation
IMPORTANT
The photocells develop a hysteresis (or “light memory”) when packed for shipping. Until the photocell has been exposed to bright light for at least 16 hours, light level setpoints will shift.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Expose the photocell to light for 16 hours.
1-9/16 (40)
M2007
IMPORTANT
• All wiring must agree with applicable codes, ordinances and regulations.
• When wiring the input power, apply only one source of power to the CR7505A.
• With line-voltage loads, the power and load voltage must be the same.
Refer to chart on the inside of the controller cover or Fig. 3 for locating the power inputs, photocell sensor inputs, TOD and load relay terminals.
62- 0074- 1
C7057 CADMIUM SULFIDE PHOTOCELL
M
LENS
PHOTOCELL
GASKET
1/2-14 THREADED KNOCKOUT OR 7/8 INCH HOLE
HEX NUT
JUNCTION BOX
1
FOR BEST RESULTS, EXPOSE LENS TO LIGHT FROM THE NORTHERN SKY (IN THE NORTHERN HEMISPHERE) OR THE SOUTHERN SKY (IN THE SOUTHERN HEMISPHERE).
2
USE WATERTIGHT JUNCTION BOX WITH PROPER GASKETS AND SEALS.
20060
1
2
Fig. 2. Vertical mounting configuration.
NOTES:
The photocell sensor has no polarity. — Wire to terminal strip T2, terminals 4 and 5. — Access to terminals can be gained through
standard conduit knockouts (A-E) located around the perimeter of the enclosure.
Use knockout A only for the photocell sensor
and TOD wiring.
Photocell wires should be at least 18 AWG
two conductor. If not run in watertight conduit, use suitable outdoor wiring insulation.
Shielded wiring is not required.
OPERATION AND CHECKOUT
CAUTION
ONE POWER SOURCE ONLY
M2032A
LINE POWER
240
120
COM
VAC
VAC
1 2 3 4 5
OUTPUT 1
N0 COMNCN0 COM NC
SET
T.O .D. 1 T.O .D. 2
T2
POWER
SENSOR
RUN
7 8 9
10
STAGE 1
OUTPUT 2
LIGHT LEVEL
56
4
7
3
8
2
9
1
10
STAGE 2
56
4
3 2
1
Fig. 3. Wiring for 120 Vac input; 24 Vac load.
Calibration
After the controller and photocell sensor are installed (with wiring and settings verified), and the photocell has been exposed to light for 16 hours, apply power. The light intensity threshold levels can be calibrated when the desired outdoor light level has occurred.
NOTES:
Calibration achieves best results when
making adjustments at or near the light conditions required for equipment switching.
Calibrating at extreme light conditions can
cause switching to be unachievable.
1. At the desired outdoor light level place SET-RUN switch to the SET position.
2. Slowly rotate stage 1 light level potentiometer counterclockwise until the stage 1 LED lights.
3. Stage 1 is now calibrated to the light level existing at the sensor and the stage 1 load is energized.
4. Return the SET-RUN switch to the RUN position.
NOTE: To calibrate stage 2, repeat this process
except adjust the stage 2 light level potentiometer.
In the following procedures, refer to the diagram inside the CR7075A cover or Fig. 3. These show locations of all operating controls, LED lights, and wiring connection points.
Initial Adjustments
1. Adjust both light level potentiometers to the fully clockwise position (#1 index level).
2. Place the SET-RUN switch to the RUN position.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
62-0074—1 B.B. Rev. 9-01 www.honeywell.com
M1V 4Z9
IMPORTANT
After initial setup is complete, make certain the switch is in the RUN position to avoid short cycling the loads.
NOTE: The SET-RUN switch removes the integrating
time delay (short-cycle protection) circuitry in the SET position. In the RUN position (normal operation) the calibrated light level must be present for 30 seconds before the load switches.
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...