Temperature Sensors
C7021 10K ohm NTC Type II Temperature Sensors
The Series 2000 10K ohm NTC Electronic Temperature Sensors are designed for use with electronic controllers in domestic or commercial heating and cooling systems.
•B and C Model sense duct air temperature
•D models for immersion mounting sense water temperature
•F models sense outdoor air temperature and are weatherproof for outdoor use (knockouts allow for 1/2 in. conduit connection).
•J and R models sense average duct air temperature
•K models with strap-on mounting senses water temperature
•P models sense air temperature
•Solid state components not affected by dust or dirt
Sensor Type: 10 K ohm NTC @ 77 F Type II
Maximum Ambient Temperature: 302 F (150 C)
Shipping Temperature Range: -30 F to +160 F (-34 C to +71 C)
Used With: TB7600, TB7300, TB7200 Series communicating thermostats
|
|
|
|
|
|
|
|
Insertion Length |
Operating Temperature Range |
||
|
|
|
|
|
|
Product Number |
Application |
(inch) |
(mm) |
(F) |
(C) |
|
|
|
|
|
|
C7021B2005/U |
Duct Discharge |
6 in. |
152 mm |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021B2013/U |
Duct Discharge |
12 in. |
305 mm |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021C2003/U |
Duct Discharge |
18 in. |
457 mm |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021D2001/U |
Immersion sensor for hot or chilled water, |
5 in. |
127 mm |
-40 F to +250 F |
-40 C to +121 C |
|
purchase well 50001774-001 separately |
|
|
|
|
|
|
|
|
|
|
C7021F2009/U |
Outside air temperature |
— |
— |
-40 F to +158 F |
-40 C to +70 C |
|
|
|
|
|
|
C7021J2007/U |
Duct discharge air (averaging) |
12 ft. |
3.66 m |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021K2005/U |
Hot or chilled water (strap on) |
— |
— |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021N2001/U |
Water or air temperature sensor (probe sensor) |
— |
— |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021P2004/U |
Temperature sensor |
— |
— |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021R2000/U |
Duct discharge air (averaging) |
12 ft. |
3.66 m |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
C7021R2018/U |
Duct discharge air (averaging) |
24 ft. |
7.3 m |
-40 F to +250 F |
-40 C to +121 C |
|
|
|
|
|
|
<![endif]>Commercial
<![if ! IE]><![endif]>Components
70-6910 |
|
|
|
457 |
|
|