Settings and Adjustments .................................................5
Operation and Checkout ..................................................6
C6097A,B PRESSURE SWITCHES
SPECIFICATIONS
Models:
C6097A Pressure Switch: Breaks a circuit when pressure falls
to scale setting. See Table 1.
C6097B Pressure Switch: Breaks a circuit when pressure
rises to scale setting. See Table 1.
Table 2 shows switch ratings and Table 3 shows alternate
electrical ratings when used with Honeywell Flame Safeguard
Programmers.
Minimum Ambient Temperature:
Maximum Ambient Temperature:
-40°F (-40°C).
140°F (60°C).
Connections (Depending on Model):
1/4-18 NPT tapping for main or high-pressure connection.
1/8-27 NPT tapping for vent or low-pressure connection (air
only).
Flange mount for connection to Honeywell Integrated Valve
Train (internal vent only, no external connections).
Scale Range:
0.4 to 5 in. wc (0.10 kPa to 1.25 kPa).
3 to 21 in. wc (0.75 to 5.23 kPa).
12 to 60 in. wc (3.0 kPa to 15 kPa).
1.5 to 7 psi (10.3 kPa to 48 kPa).
Approvals:
Underwriters Laboratories Inc. listed.
Canadian Standards Association listed.
Factory Mutual: Approved.
Industrial Risk Insurers: Acceptable.
CSD-1 AFB: Acceptable.
Accessories:
32003041-001 C6097 Cover for manual reset models.
32003040-001 C6097 Cover for recycle models.
32003039-001 Position Indication Lamp Kit.
Dimensions:
1-3/32 (28)
13/32
(11)
DIFFERENTIAL
CONNECTION
1/8 NPT
See Fig. 1 and 2.
2-23/32 (69)
1-3/4 (45)
GAS CONNECTION
1/4 NPT WITH DUST SEAL
31/32
(25)
25/32
(21)
27/32
(22)
HOLE
2-1/4
(57)
2-13/32
3-3/16
(61)
(81)
1-17/32
(90)
HOUSING
TERMINAL DIAGRAM
123
2-21/32 (68)2-21/32 (68)
15/32 (12)
2-23/32 (69)
NO
NC
P
INDICATOR
COM
Fig. 1. C6097 1/4 in. NPT Mount dimensions in in. (mm).
M17125
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0237—12
C6097A,B PRESSURE SWITCHES
Table 1. Pressure Switch Model Selection.
Manual Reset
Differential
Operating
Model
C6097A10040.4 to 5 in.
C6097A10123 to 21 in.
C6097A10203 to 21 in. wc2.4 in. wc4.2 in. wc——4.3YesAir/GasFlange Mount
Pressure
Range
wc
wc
Maximum
Minimum
Setpoint
——0.16 in. wc0.24 in. wc Additive2.9 NoAir/GasBreaks N.O.
2.4 in. wc4.2 in. wc——4.3YesAir/Gas1/4 in. NPT
Maximum
at
at
Maximum
Setpoint Nominal Maximum
Non-Manual Reset
Differential
Differential
Typ e
Maximum
Rated
Pressure
(continuous)
(psi)
Manual
ResetMedia
Switch
Action at
a
SetpointComments
1/4 in. NPT
to C.
connection
on pressure
fall.
Mount
Mount
C6097A103812 to 60
C6097A104612 to 60
C6097A10533 to 21 in. wc—0.24 in. wc0.48 in. wc4.3NoAir/Gas1/4 in. NPT
C6097A10613 to 21 in. wc——0.24 in. wc0.48 in. wc4.3NoAir/GasFlange Mount
C6097A107912 to 60
C6097A108712 to 60
C6097A10950.4 to 5 in. wc0.6 in. wc1.0 in. wc——2.9YesAir/Gas1/4 in. NPT
C6097A11031.5 to 7
C6 0 9 7A 11111.5 t o 7
C6097A11291.5 to 7
C6097A11371.5 to 7
C6097A12100.4 to 5 in. wc——0.16 in. wc0.24 in. wc2.9NoAir/GasFlange Mount
C6097A12280.4 to 5 in. wc————2.9YesAir/GasFlange Mount
C6097B100212 to 60
C6097B101012 to 60
C6097B10283 to 21 in. wc2.4 in. wc4.2 in. wc——4.3YesAir/Gas1/4 in. NPT
C6097B10363 to 21 in. wc2.4 in. wc4.2 in. wc——4.3YesAir/GasFlange Mount
in. wc
in. wc
in. wc
in. wc
psi
psi
psi
psi
in. wc
in. wc
10 in. wc12 in. wc——4.8YesAir/Gas1/4 in. NPT
10 in. wc12 in. wc——4.8YesAir/GasFlange Mount
——1.1 in. wc 2.4 in. wc4.8NoAir/Gas1/4 in. NPT
——1.1 in. wc 2.4 in. wc4.8NoAir/GasFlange Mount
1.1 psi1.4 psi——9.3YesAir/GasFlange Mount
1.1 psi1.4 psi——9.3YesAir/Gas14 in. NPT Mount
——0.1 psi0.39.3NoAir/GasFlange Mount
——0.1 psi0.39.3NoAir/Gas1/4 in. NPT
10 in. wc12 in. wc——Subtractive 4.8YesAir/GasBreaks N.C.
10 in. wc12 in. wc——4.8YesAir/GasFlange Mount
to C.
connection
on pressure
rise.
Mount
Mount
Mount
Mount
Mount
1/4 in. NPT
Mount
Mount
C6097B10441.5 to 7
C6097B10511.5 to 7
C6097B10693 to 21 in. wc——0.24 in. wc0.48 in. wc4.3NoAir/GasFlange Mount
C6097B107712 to 60
C6097B108512 to 60
C6097B10931.5 to 7
C6097B11011.5 to 7
C6097B11193 to 21 in. wc——0.24 in. wc0.48 in. wc4.3NoAir/Gas1/4 in. NPT
a
Acceptable media: Natural gas, liquid propane (LP) gas, and air
psi
psi
in. wc
in. wc
psi
psi
1.1 psi1.4 psi——21.0YesAir/GasFlange Mount
1.1 psi1.4 psi——21.0YesAir/Gas1/4 in. NPT
——1.1 in. wc 2.4 in. wc4.8NoAir/GasFlange Mount
——1.1 in. wc 2.4 in. wc4.8NoAir/Gas1/4 in. NPT
——0.1 psi0.3 psi21.0NoAir/GasFlange Mount
——0.1 psi0.3 psi21.0NoAir/Gas1/4 in. NPT
Mount
Mount
Mount
Mount
.
365-0237—1
C6097A,B PRESSURE SWITCHES
Table 2. Switch Ratings (Amperes)
120/240 Vac, 50/60 Hz
InductiveFull Load3.0
Locked Rotor18.0
Resistive5.0
Table 3. Alternate Electrical Ratings when used with
Honeywell Flame Safeguard Programmers.
DeviceRating
Ignition Transformer 540 VA
Pilot Valve50 VA
Main Valve400 VA with 2-1/2 times inrush.
27/32 (22) HOLE
5/8 (16)
2-23/32 (69)
PRESSURE INLET
1-1/4
(32)
1/32
(1)
2-1/4
(57)
(52)
2
2-21/32 (68)
2-23/32 (69)
INDICATOR
When Installing this Product...
1.
Read these instructions carefully. Failure to follow them
can damage the product or cause a hazardous
condition.
2.
Check the ratings given in the instructions and on the
product to make sure that the product is suitable for
your application.
3.
Installer must be a trained, experienced service
technician.
4.
After installation is completed, check out product
operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause serious personal injury or death.
Disconnect power supply before beginning installation.
More than one disconnection can be involved.
Mounting
NOTE: On flange models, remove the label holding the
O-ring in place and make sure O-ring seal is in place
before mounting the pressure switch on the valve.
The C6097 models allow NPT or flange (directly to valve)
mounting. The NPT models have a hexagonal fitting with a
1/4 in. NPT tapping, which is the high pressure connection, in
differential applications. The bleed fitting is 1/8 in. NPT
tapped. In differential pressure control applications using air
only, connect the lower pressure to the bleed fitting. See Fig. 1
and Table 1. In applications using combustible gases, vent the
bleed tapping according to applicable standard code or
jurisdictional authority.
TERMINAL DIAGRAM
123
NO
COM
NC
P
2 (52)
Fig. 2. C6097 Flange Mount dimensions in in. (mm).
INSTALLATION
WARNING
Explosion or Fire Hazard.
Can cause severe personal injury, death or
property damage.
Observe all safety requirements each time a control is
installed on a burner.
M17124
C6097 models with flange mount can be fitted directly to
Honeywell Integrated Valve Train (model specific). See Fig. 2
and Table 1. The flange mount models vent internally, with no
external tap.
Mount the C6097A,B in any position.
Leak Check
After installation, perform a leak check on the pressure switch:
1.
Turn on main gas. Make sure gas has reached the
pressure switch (e.g., high gas pressure switch)
2.
Check installation for gas leaks using a gas leak
detector or a soap solution.
65-0237—14
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious personal injury or death.
Disconnect power supply before beginning installation.
More than one disconnection can be involved.
Make sure that all wiring agrees with all applicable local
codes, ordinances and regulations. An opening is provided to
accommodate rigid conduit or armored cable for line voltage
operation (see Fig. 3 and 4). Do not overload the switch
contacts (see Switch Ratings in the Specifications section).
The switching schematic is shown in Fig. 5.
C6097A,B PRESSURE SWITCHES
Fig. 4. C6097 (recycle model) with cover removed.
Fig. 3. C6097 (manual reset switch model)
with cover removed.
SETTINGS AND ADJUSTMENTS
Pressure Setpoint Adjustment
To adjust the pressure setting, turn the setpoint adjustment
dial (Fig. 3, 4 and 5) clockwise to increase the
pressure setting and counterclockwise to decrease the
pressure setting.
NO
2
NC
1
C
C6097A BREAKS C-NO, MAKES C-NC ON PRESSURE
1
FALL. MANUAL RESET MODELS LOCK OUT.
C6097B BREAKS C-NC, MAKES C-NO ON
2
PRESSURE RISE AND LOCKS OUT.
Fig. 5. C6097 schematic.
M17123
565-0237—1
C6097A,B PRESSURE SWITCHES
OPERATION AND CHECKOUT
Operation
The manual reset C6097A diaphragm actuates the snapacting switch to break a control circuit and lock out when
pressure falls to the scale setting. The recycle C6097A
models recycle automatically when the control circuit returns
to scale setting plus differential.
The manual reset C6097B diaphragm actuates the snapacting switch that breaks a control circuit and locks out when
the pressure rises to the scale setting. The recycle C6097B
models recycle automatically when the control pressure falls
to the scale setting minus differential.
Manual Resetting
The C6097A manual reset models lock out when pressure
falls to the scale setting and require manual resetting after the
pressure rises to scale setting plus differential to resume
normal operation.
The C6097B manual reset models lock out when pressure
rises to the scale setting and require manual resetting after
the pressure falls to scale setting minus the differential to
resume normal operation.
To reset, once normal operating pressure is restored, push the
reset button in as far as it goes, then release.
IMPORTANT
Lockout models cannot be made to recycle
automatically by permanently holding in the reset
lever.
Checkout
C6097 Gas Fuel Application
1.
Set cutoff pressure.
2.
Open main supply line. Depress reset lever on lockout
models until switch makes control circuit.
3.
Set controller and limit switch to call for heat.
4.
For C6097A: Close the manual gas shutoff valve.
C6097 should open control circuit when pressure
reaches cutoff point.
For C6097B: Open the manual gas shutoff valve, wait a
few minutes for the pressure to rise; then lower the
scale setting until the switch breaks control circuit and
locks out.
5.
For C6097A: Open the shutoff valve, return the
pressure switch to its original setting and press the reset
button (if necessary).
For C6097B: raise setting to normal and press reset
button (if necessary).
6.
Allow system to operate through at least one complete
cycle to make sure all components are functioning
properly.
C6097A Air Application
1.
Set cutoff pressure.
2.
Turn on fan.
3.
Block fan inlet or filter area. Switch should break control
circuit when pressure drops to cutoff point. Manual reset
models lock out.
4.
Remove obstruction. Press reset lever (manual reset
models) and allow system to operate through at least
one complete cycle to be sure all components are
functioning properly.
65-0237—16
765-0237—1
Home and Building ControlHome and Building ControlHoneywell Asia Pacific Inc.
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Honeywell Inc.Honeywell Limited-Honeywell LimitéeRoom 3213-3225
Honeywell Plaza155 Gordon Baker RoadSun Hung Kai Centre
P.O. Box 524North York, OntarioNo. 30 Harbour Road
Minneapolis, MN 55408-0524M2H 3N7Wanchai
Hong Kong
Honeywell Latin American RegionHoneywell Europe S.A.
480 Sawgrass Corporate Parkway3 Avenue du Bourget
Suite 2001140 Brussels
Sunrise FL 33325Belgium
65-0237—1 G.R. Rev. 4-00 www.honeywell.com