Honeywell C6097A User Manual

65- 0237- 1
The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
C6097A,B
Pressure Switches
PRODUCT DATA

FEATURES

• For use with natural gas, liquid propane (LP) gas, or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint on pressure fall.
• C6097B models break control circuit at setpoint on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset button.
• Removable transparent cover protects scaleplate and adjusting knob.
• Pipe tappings allow selection of positive pressure, differential pressure (air only) or venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi.
• Surge orifice.
CP-UM-5109E
® U.S. Registered Trademark Copyright © 2000 Honeywell Inc. • All Rights Reserved
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 5
Settings and Adjustments ................................................. 5
Operation and Checkout .................................................. 6
C6097A,B PRESSURE SWITCHES

SPECIFICATIONS

Models:
C6097A Pressure Switch: Breaks a circuit when pressure falls
to scale setting. See Table 1.
C6097B Pressure Switch: Breaks a circuit when pressure
rises to scale setting. See Table 1. Table 2 shows switch ratings and Table 3 shows alternate electrical ratings when used with Honeywell Flame Safeguard Programmers.
Minimum Ambient Temperature:
Maximum Ambient Temperature:
-40°F (-40°C).
140°F (60°C).
Connections (Depending on Model):
1/4-18 NPT tapping for main or high-pressure connection. 1/8-27 NPT tapping for vent or low-pressure connection (air
only). Flange mount for connection to Honeywell Integrated Valve Train (internal vent only, no external connections).
Scale Range:
0.4 to 5 in. wc (0.10 kPa to 1.25 kPa). 3 to 21 in. wc (0.75 to 5.23 kPa). 12 to 60 in. wc (3.0 kPa to 15 kPa).
1.5 to 7 psi (10.3 kPa to 48 kPa).
Approvals:
Underwriters Laboratories Inc. listed. Canadian Standards Association listed. Factory Mutual: Approved. Industrial Risk Insurers: Acceptable. CSD-1 AFB: Acceptable.
Accessories:
32003041-001 C6097 Cover for manual reset models. 32003040-001 C6097 Cover for recycle models. 32003039-001 Position Indication Lamp Kit.
Dimensions:
1-3/32 (28)
13/32
(11)
DIFFERENTIAL CONNECTION 1/8 NPT
See Fig. 1 and 2.
2-23/32 (69)
1-3/4 (45)
GAS CONNECTION 1/4 NPT WITH DUST SEAL
31/32
(25)
25/32
(21)
27/32 (22) HOLE
2-1/4
(57)
2-13/32
3-3/16
(61)
(81)
1-17/32
(90)
HOUSING
TERMINAL DIAGRAM
12 3
2-21/32 (68)2-21/32 (68)
15/32 (12)
2-23/32 (69)
NO
NC
P
INDICATOR
COM
Fig. 1. C6097 1/4 in. NPT Mount dimensions in in. (mm).
M17125
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Logistics Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000 In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0237—1 2
C6097A,B PRESSURE SWITCHES
Table 1. Pressure Switch Model Selection.
Manual Reset
Differential
Operating
Model
C6097A1004 0.4 to 5 in.
C6097A1012 3 to 21 in.
C6097A1020 3 to 21 in. wc2.4 in. wc 4.2 in. wc 4.3 Yes Air/Gas Flange Mount
Pressure
Range
wc
wc
Maximum
Minimum
Setpoint
0.16 in. wc0.24 in. wc Additive 2.9 No Air/Gas Breaks N.O.
2.4 in. wc 4.2 in. wc 4.3 Yes Air/Gas 1/4 in. NPT
Maximum
at
at
Maximum
Setpoint Nominal Maximum
Non-Manual Reset
Differential
Differential
Typ e
Maximum
Rated
Pressure
(continuous)
(psi)
Manual
Reset Media
Switch
Action at
a
Setpoint Comments
1/4 in. NPT to C. connection on pressure fall.
Mount
Mount
C6097A1038 12 to 60
C6097A1046 12 to 60
C6097A1053 3 to 21 in. wc— 0.24 in. wc0.48 in. wc 4.3 No Air/Gas 1/4 in. NPT
C6097A1061 3 to 21 in. wc— 0.24 in. wc0.48 in. wc 4.3 No Air/Gas Flange Mount
C6097A1079 12 to 60
C6097A1087 12 to 60
C6097A1095 0.4 to 5 in. wc0.6 in. wc 1.0 in. wc 2.9 Yes Air/Gas 1/4 in. NPT
C6097A1103 1.5 to 7
C6 0 9 7A 1111 1.5 t o 7
C6097A1129 1.5 to 7
C6097A1137 1.5 to 7
C6097A1210 0.4 to 5 in. wc— 0.16 in. wc0.24 in. wc 2.9 No Air/Gas Flange Mount
C6097A1228 0.4 to 5 in. wc— 2.9 Yes Air/Gas Flange Mount
C6097B1002 12 to 60
C6097B1010 12 to 60
C6097B1028 3 to 21 in. wc2.4 in. wc 4.2 in. wc 4.3 Yes Air/Gas 1/4 in. NPT
C6097B1036 3 to 21 in. wc2.4 in. wc 4.2 in. wc 4.3 Yes Air/Gas Flange Mount
in. wc
in. wc
in. wc
in. wc
psi
psi
psi
psi
in. wc
in. wc
10 in. wc 12 in. wc 4.8 Yes Air/Gas 1/4 in. NPT
10 in. wc 12 in. wc 4.8 Yes Air/Gas Flange Mount
1.1 in. wc 2.4 in. wc 4.8 No Air/Gas 1/4 in. NPT
1.1 in. wc 2.4 in. wc 4.8 No Air/Gas Flange Mount
1.1 psi 1.4 psi 9.3 Yes Air/Gas Flange Mount
1.1 psi 1.4 psi 9.3 Yes Air/Gas 14 in. NPT Mount
0.1 psi 0.3 9.3 No Air/Gas Flange Mount
0.1 psi 0.3 9.3 No Air/Gas 1/4 in. NPT
10 in. wc 12 in. wc Subtractive 4.8 Yes Air/Gas Breaks N.C.
10 in. wc 12 in. wc 4.8 Yes Air/Gas Flange Mount
to C. connection on pressure rise.
Mount
Mount
Mount
Mount
Mount
1/4 in. NPT
Mount
Mount
C6097B1044 1.5 to 7
C6097B1051 1.5 to 7
C6097B1069 3 to 21 in. wc— 0.24 in. wc0.48 in. wc 4.3 No Air/Gas Flange Mount
C6097B1077 12 to 60
C6097B1085 12 to 60
C6097B1093 1.5 to 7
C6097B1101 1.5 to 7
C6097B1119 3 to 21 in. wc— 0.24 in. wc0.48 in. wc 4.3 No Air/Gas 1/4 in. NPT
a
Acceptable media: Natural gas, liquid propane (LP) gas, and air
psi
psi
in. wc
in. wc
psi
psi
1.1 psi 1.4 psi 21.0 Yes Air/Gas Flange Mount
1.1 psi 1.4 psi 21.0 Yes Air/Gas 1/4 in. NPT
1.1 in. wc 2.4 in. wc 4.8 No Air/Gas Flange Mount
1.1 in. wc 2.4 in. wc 4.8 No Air/Gas 1/4 in. NPT
0.1 psi 0.3 psi 21.0 No Air/Gas Flange Mount
0.1 psi 0.3 psi 21.0 No Air/Gas 1/4 in. NPT
Mount
Mount
Mount
Mount
.
3 65-0237—1