Honeywell AT150F, AT175F Installation Instructions Manual

AT150F, AT175F
Universal Circuit Breaker T ransformers
INSTALLATION INSTRUCTIONS
APPLICA TION
These transformers provide power to 24 Vac circuits in heating/cooling control systems. Although the transformers are typically used in heating/cooling control systems, they can be used in any application that does not exceed the load ratings. They include a button for manually resetting the circuit breaker. They meet National Electrical Code Class 2 “not wet” and Class 3 “wet” requirements and are Underwriters Laboratories (UL) Inc. listed under UL 1585. Transformers can be foot-mounted or conduit/panel mounted. See Table 1 for additional specifications.
Table 1. Model Specifications.
Primary Secondary
Voltage
Model
Number
AT150F 120/208/240 9 in. leadwires 27.0 24.0 9 in. leadwires 50 VA
AT175F 120/208/240 9 in. leadwires 27.0 24.0 9 in. leadwires 75 VA
Input Voltage
(60 Hz)
208/277/480
208/277/480
Wiring
Connections
Open
Circuit
At Rated Power
Output
Wiring
Connections
INST ALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
The transformer can be foot-mounted or conduit/panel mounted.
USE SCREWS OR BOLTS THROUGH SLOTS (4) IN MOUNTING FEET
LEADWIRES FOR PRIMARY AND SECONDARY CONNECTIONS
Output Rating
at 100 Percent
Power Factor
RESET BUTTON
Mounting
Foot Mounting
Mount the transformer using screws (not included) through the four 3/16 in. x 3/8 in. holes in the mounting feet. See Fig. 1. Make line voltage primary connections within an approved enclosure.
® U.S. Registered Trademark Copyright © 1996 Honeywell Inc. • All Rights Reserved
X-XX UL
MOUNTING FOOT (2)
Fig. 1. Foot mounting.
M6905
69-1014-1
AT150F, AT175F UNVIVERSAL CIRCUIT BREAKER TRANSFORMERS
Conduit/Panel Mounting
Mount the transformer on a plate or panel (not included) with a 7/8 in. knockout. The transformer has a 1/2-14 NPSM conduit connector and lock nut.
1. With the conduit connector side of the transformer facing the plate, thread the leadwires through the plate knockout.
2. Insert the connector in the knockout.
3. While holding the plate in place, assemble and tighten the lock nut to fasten the transformer securely. See Fig. 2. Avoid damaging the leadwires with the screwdriver.
4. Make line voltage primary connections within an approved enclosure.
MOUNTING PLATE (NOT INCLUDED)
LEADWIRES FOR PRIMARY AND SECONDARY CONNECTIONS
CONDUIT CONNECTOR
LOCK NUT
END BELL
RESET BUTTON
M6906
Fig. 2. Conduit/panel mounting (plate not included).
Wiring
1. All wiring must comply with local codes and ordi­nances. Disconnect power before making wiring connections to prevent electrical shock or equipment damage.
2. Make the primary connections to the line voltage power supply. Be sure to use the correct leadwires for the available power supply. See Fig. 3.
3. Insulate the ends of the unused leadwires using wire nuts or capping with a solderless connector.
4. Make the secondary connections to the 24 Vac control circuit.
120/208/240 VAC MODELS
COMMON
PRIMARY
PRIMARY
1 SECONDARY LEADWIRES ARE BLUE AND YELLOW LEADWIRES.
BLACK IS COMMON WITH RESPECT TO THE TRANSFORMER
2
WINDING ONLY AND NOT THE EXTERNAL CIRCUIT.
120V
208V
240V
208/277/480 VAC MODELS
COMMON
208V
277V
480V
BLACK
WHITE
RED
ORANGE
BLACK
RED
BROWN
BLACK/RED
2
SECONDARY
1
2
SECONDARY
1
M6907
Fig. 3. Transformer schematics.
CHECKOUT
V oltage Check
After the installation is complete, turn on the power supply and perform a voltage check.
1. Place the controlled equipment in operation and observe through one complete cycle.
2. Using a voltmeter, verify the proper primary and secondary voltages.
3. If the voltage readings are incorrect, make sure the primary voltage connections are made properly.
4. Measure the voltage again.
a. If the proper primary voltage is measured and
the secondary voltage is significantly less than the voltage shown in Table 1, the transformer winding is damaged. Replace the transformer and repeat the checkout procedures.
b. If the primary voltage is 0V, make sure the
power supply is connected properly or repair if necessary. Repeat the checkout procedures.
5. Do not put the system into operation unless the correct primary and secondary voltages are measured.
Circuit Breaker
Overloading the transformer results in tripping the circuit breaker. If the secondary side of the transformer is short circuited, the circuit breaker trips in less than one minute. Reset the circuit breaker by pressing the reset button on the side of the transformer. It can take up to one hour for the transformer to cool, allowing it to reset. If the circuit breaker continues to trip, thoroughly check the system for short circuits and the current draw.
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
69-10141 C.H. Rev. 9-96 Printed in China
69-1014
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9
Helping You Control Your World®
2
Loading...