Honeywell AT140A, AT175A, AT150A, AT120A User Manual

AT120A, AT140A, AT150A, AT175A Universal Transformers
INSTALLATION INSTRUCTIONS

APPLICATION

These transformers are for use in 24 Vac nominal control circuits. They are typically used in heating/cooling control systems but can be used in any application that does not exceed the load ratings. They meet National Electrical
Table 1. Model Specifications.
Primary Secondary
Model
Number
AT120A 120/208/
AT140A 120 9 in. leads 27.0 24.0 Screw
AT150A 120/208/
AT175A 120/208/
Input
Vol tag e
(60 Hz)
240
120/208/ 240
120/240
208/240
240
240
Wiring
Connections
9 in. leads 27.0 24.0 Screw
9 in. leads 27.5 24.0 Screw
9 in. leads 27.5 24.0 Screw
Open
Circuit
Code Class 2 “not wet” and Class 3 “wet” requirements and are Underwriters Laboratories (UL) Inc. listed under UL 1585. They can be mounted through a 7/8 in. knock­out on the accessory mounting plate (included), or with the integral mounting feet. See Table 1 for additional specifications.
Vol tag e
At Rated
Power
Output
Wiring
connections
terminals
terminals
terminals
terminals
Output Rating at
100 Percent Power
20 VA
40 VA
50 VA
75 VA
Factor

INSTALLATION

When Installing this Product …

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before beginning installation.
69-0251-3
AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS

Mounting

The transformer can be mounted in one of three ways: — foot mounting. — plate mounting. — mounting through outlet box knockout hole.
Foot Mounting
1. Mount the transformer using screws (not supplied) through the four 3/16 in. x 3/8 in. holes in the mounting feet.
2. Make line voltage primary connections within an approved enclosure. See Fig. 1.
3. Discard the mounting plate.
USE SCREWS OR BOLTS THROUGH SLOTS (4) IN MOUNTING FEET
LEADWIRES FOR PRIMARY CONNECTIONS
SCREW TERMINALS FOR SECONDARY CONNECTIONS
LEADWIRES FOR PRIMARY CONNECTIONS
CLAMP SCREW AND CLAMP
LEADWIRES FOR PRIMARY CONNECTIONS
PLATE MOUNTED AT CLAMP ON PRIMARY END BELL
MOUNTING PLATE
SCREW
END BELL
RAISED PORTION OF LARGE CENTER KNOCKOUT
TERMINALS FOR SECONDARY CONNECTIONS
PLATE MOUNTED AT THE LAMINATIONS
MOUNTING PLATE
MOUNTING SCREW
SCREW TERMINALS FOR SECONDARY CONNECTIONS
1
MOUNTING FOOT (2)
M9161
Fig. 1. Foot mounting.
Plate Mounting
MOUNTING PLATE TO TRANSFORMER
Mount the plate to the transformer in either of two positions (see Fig. 2):
• at clamp on primary end bell.
• at laminations.
69-0251-3 2
1
1
MOUNTING FEET ON "A" MODELS ONLY.
Fig. 2. Mounting plate to transformer in either
of two positions.
MOUNTING PLATE AT CLAMP ON PRIMARY END BELL
1. Turn the screw on the clamp almost all the way out.
2. Hold the mounting plate with the keyhole slots up
and the raised portion of the large center knockout away from you.
3. From the back, thread the primary leadwires through the round center hole in the plate.
4. Fit the clamp and screw through the round hole.
5. While holding the plate in place, tighten the
setscrew securely against the rim of the hole. See Fig. 3. Avoid damaging the leadwires with the screwdriver.
M9162
AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS
WITH RAISED PORTION OF KNOCKOUTS FACING YOU:
PRY UP TOP SECTION OF LARGE KNOCKOUT
1. BY INSERTING SCREWDRIVER FIRST AT ONE SIDE OF SLOT AND THEN AT THE OTHER SIDE.
M12126
Fig. 3. When screw is tightened, clamp holds
plate on transformer.
MOUNTING PLATE AT LAMINATIONS
1. Remove the large rectangular knockout in the mounting plate as shown in Fig. 4.
2. Hold the transformer so the clamp on the end bell faces you.
3. With the keyhole slots up, fit the mounting plate over the primary leadwires and end bell. Insert small tab at the bottom of the plate into the slot in the transformer mounting foot.
4. Insert the mounting screw (supplied) through the holes as shown in Fig. 5. Secure the plate to the transformer, but do not overtighten the screw.
MOUNTING TRANSFORMER AND PLATE ON OUTLET BOX
The mounting plate can be mounted on 4 in. square boxes, 2 x 4 in. rectangular boxes, and on 4 in. octagonal boxes. See Fig. 4.
1. Align the plate with the box to determine the correct mounting holes. The mounting feet and secondary terminals are outside the box.
2. Remove the mounting hole knockouts, if necessary. Mount the plate on the outlet box using two screws (obtained locally).
Mounting Through Outlet Box Knockout Hole
The transformer can be mounted on an outlet box using the clamp on the primary end bell. The mounting plate is not used. To mount the transformer on an outlet box:
1. Turn the clamp screw almost all the way out.
2. From outside box, thread the primary leadwires
through suitable 7/8 in. knockout. Fit the clamp and screw through the knockout. Do not mount the transformer through a plastic knockout.
3. Tighten the clamp screw securely against the rim of the knockout. Avoid damaging the leadwires with the screwdriver.
THEN PRY UP BOTTOM SECTION OF KNOCKOUT.
2.
REMOVE BOTH SECTIONS OF KNOCKOUT WITH PLIERS.3.
SHADED AREAS REPRESENT KNOCKOUTS AND SCREW SLOTS USED WITH 2 X 4 INCH OR OCTAGONAL OUTLET BOXES.
Fig. 4. Use screwdriver to pry out both
sections of knockout.
TRANSFORMER
IMPORTANT MOUNT TRANSFORMER OTHER SIDE
M9188A
PLATE
M9163
Fig. 5. Mounting screw and tab hold plate on
transformer.
3 69-0251-3
AT120A, AT140A, AT150A, AT175A UNIVERSAL TRANSFORMERS
Mounting Through Outlet Box Knockout
The transformer can be mounted on an outlet box using the clamp on the primary end bell. The mounting plate is not used. To mount the transformer on an outlet box:
1. Turn the clamp screw almost all the way out.
2. From outside box, thread the primary leadwires
through suitable 7/8 in. knockout. Fit the clamp and screw through the knockout. Do not mount the transformer through a plastic knockout.
3. Tighten the clamp screw securely against the rim of the knockout. Avoid damaging the leadwires with the screwdriver.

WIRING

All wiring must comply with local codes and ordinances. Disconnect power before making wiring connections to prevent electrical shock or equipment damage.
1. Make primary connections to the line voltage power supply. On multitap models, be sure to use correct leads for available power supply. See Fig. 6.
2. On multitap models, insulate the ends of the unused leads using wire nuts or capping with a solderless connector.
3. Make secondary connections to 24 Vac control circuit.

CHECKOUT

CAUTION
Voltage Check Hazard. Overload current protection is inherent on AT120, AT140, and AT150. A fused 3.5 Amp secondary is used on AT175.
Do not short transformer secondary terminals.

Voltage Check

After installation is complete, turn on power supply and perform a voltage check:
1. Place controlled equipment in operation and observe through one complete cycle.
2. Using a voltmeter, check for proper primary and secondary voltages.
3. If voltage readings are incorrect, be sure primary voltage connections are made correctly.
4. Measure voltage again: a. If correct primary voltage is measured and
secondary voltage is significantly less than the voltage shown on the regulation curves, transformer winding is damaged. Replace transformer and repeat checkout procedures.
b. If primary voltage is 0V, be sure power supply
is connected correctly or repair, if necessary. Repeat checkout procedures.
5. Do not put system into operation unless correct primary and secondary voltages are measured.
SINGLE VOLTAGE MODELS
2
COMMON
BLACK
3
VOLTAGE VAR IES WITH MODEL
120 V - WHITE 208 V - RED 240 V - ORANGE 277 V - BROWN 480 V - BLACK/RED
1
SECONDARY
PRIMARY
120/240 MODELS
2
COMMON
BLACK
PRIMARY
120 V
WHITE
3
240 V
ORANGE
1
SECONDARY
208/240 VAC MODELS
2
BLACK
RED
ORANGE
1
SECONDARY
PRIMARY
3
COMMON
208 V
240 V
120/208/240 VAC MODELS
COMMON
PRIMARY
3
1 SECONDARY CONNECTIONS ARE SCREW TERMINALS, 1/4 INCH
QUICK-CONNECTS OR BLUE AND YELLOW LEADWIRES.
2
BLACK IS COMMON WITH RESPECT TO THE TRANSFORMER WINDING ONLY AND NOT THE EXTERNAL CIRCUIT.
3
SOME MODELS AVAILABLE WITH 1/4 INCH QUICK CONNECTS.
120 V
208 V
240 V
Fig. 6. Schematics for single and multitap
2
BLACK
WHITE
RED
ORANGE
transformers.
1
SECONDARY
M22974
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2005 Honeywell International Inc. 69-0251-3 G.H. Rev. 06-05
Loading...