L8124A,C,E,L and M
Aquastat® Relays
INSTALLATION INSTRUCTIONS

APPLICATION

These immersion type controllers are used with forced hydronic heating systems that include domestic hot water service. All models provide high limit, low limit and circulator control. Table 1 lists the various models and their applications.
These Aquastat® relays have a diaphragm powerhead and MicroSwitch™ assembly that respond to temperature changes in the boiler water. L8124 can provide multizone control by using a separate circulator and R845 Relay for each zone. L8124E and L have large transformers and extra terminals for supplying power to low voltage valves. L8124L includes a large transformer and extra terminals for low voltage zone valves. L8124M is for use in a wood-coal/gas-oil multifuel heating system. Circulator is independently controlled by the thermostat.
Do not use these Aquastat® Relays where the pressure can exceed 100 psi (690 kPa) on the bulb if inserted directly or 200 psi (1380 kPa) when using an immersion well, or where the ambient temperature can exceed 150°F (66°C) at the case or 265°F (129°C) at the sensing element.
Table 1. Model Descriptions.
Model
Number
L8124A 120V Yes Same as L8124A,C,L
L8124C
L8124L 3
L8124E 24V 2 1.25A at 24 Vac; 30 VA
L8124M 120V Same as L8124A. None.
a
Multizone control can be provided by using a separate circulator and R845 Relay for each zone.
Burner
Control
Circuit
Can Be Used For
Multizone With
Circulators
No. of V8043 Zone
Valves Powered
Without Additional
a
Transformer

SPECIFICATIONS

Low Limit:
Setting: 110°F to 220°F (43°C to 104°C), adjustable. Differential: 10°F to 25°F (6°C to 14°C), adjustable.
High Limit:
Setting: 130°F to 240°F (54°C to 116°C), adjustable. Differential: 10°F (6°C), fixed.
WARNING
Explosion Hazard. Can cause serious injury, death or property damage.
Use this product only in systems with a pressure relief valve.
Electrical Ratings
Burner Circuit Circulator Circuit
circulator rating.
(total load) B
1-B2
120 Vac: 7.4A (full load),
44.4A (locked rotor). 240 Vac: 3.7A (full load),
22.2A (locked rotor).
, Tv-Z.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
95- 6571- 11
Page 2
L8124A,C,E,L AND M AQUASTAT® RELAYS

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
WARNING
Electrical Shock Hazard. Can cause severe injury, death or equipment damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
IMPORTANT
1. Terminals on these Aquastat Relays are
approved for copper wire only.
2. Immersion well must fit sensing element and
bulb must rest against bottom of well.
Bend the tubing, if necessary, to hold the bulb against the bottom of the well. Do not make a sharp bend in the tubing. A sharp bend can produce a break in the tubing and cause loss of fill. This condition will cause the high and low limit controllers to be continuously made.
Select models have an adjustable capillary length. See Fig. 1.
3
1
CAUTION: EXCESSIVE HANDLING OR SHARP BENDS CAN DAMAGE THE CAPILLARY.
SENSING ELEMENT IS FACTORY FORMED FOR 1.5 IN.
1
INSULATION WELL ASSEMBLIES.
FOR 3 IN. INSULATION WELL ASSEMBLIES, PULL OUT
2
SUFFICIENT CAPILLARY TO ASSURE THAT THE CAPSULE BOTTOMS IN THE WELL.
STRAIGHTEN CAPILLARY SUFFICIENTLY SO IT DOES NOT
3
INTERFERE WITH INSERTION OF THE CAPSULE INTO THE WELL.
Fig. 1. Adjusting the capillary length.

Mounting

Each relay is suitable for use with an immersion well for insertion into the boiler. (Check individual OS number specifications to determine whether a well is supplied
2
M8882
with the relay.) Refer to form 68-0040, Wells and Fittings for Temperature Controllers, to order well. A compression fitting is available for applications where direct immersion of the sensing bulb is desired. A 124904 Well Adapter (see Fig. 2) can be ordered separately to adapt some other wells to the mounting clamp. The boiler must be provided with a tapping that allows horizontal mounting of the well. It should be located where boiler water of average temperature can circulate around the well.
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare one, properly
sized and threaded, at the selected location.
3. Install the immersion well in the boiler tapping and tighten securely.
NOTE: Do not use the case as a handle to tighten.
4. Refill boiler and check for water leakage.
5. Loosen but do not remove the clamp screw on
the bottom (L8124A,E) or on top (L8124C,L,M) of case.
6. Insert the element in the well until it bottoms. See Fig. 2.
7. Fit the case onto the well so that the clamp on the case slides over the flange on the well. Securely tighten clamp screw.

WIRING

WARNING
Electrical Shock Hazard. Can cause severe injury, death or equipment damage.
Disconnect power before wiring to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances. The limits given in the Specifications section must not be exceeded when applying this control. Terminals on these Aquastat Relays are approved for copper wire only.
Refer to the insert on the inside of the Aquastat Relay cover or to Table 1 for electrical ratings and maximum load information. Use manufacturer instructions when wiring controlled equipment or refer to typical hookups in Fig. 3 through 11.
WARNING
Explosion Hazard. Can cause severe injury, death or property damage.
Use this product only in systems with a pressure relief valve.
If the B1 terminal on the device being replaced is a 1/4 in. (6 mm) tab terminal, use the existing wiring harness terminals to install the replacement device. If the B1 terminal on the device being replaced is a screw terminal, insert the provided tab terminal to screw terminal adapter on the 1/4 in. (6 mm) tab terminal of the replacement device. After the adapter is installed, the existing wraparound wire end may be reused to make an electrical connection to the B1 terminal.
95-6571—11 2
Page 3
L8124A,C,E,L AND M AQUASTAT® RELAYS
BACK OF
IMMERSION
D
CONTROLLER CASE
IMMERSION WELL CLAMP
IMMERSION
CAPILLARY TUBE
SETSCREW
WELL SPUD
ADAPTER
)
2
IMMERSION
1
SHORT TUBE FITS IN CENTRAL
Fig. 2. Position of bulb in immersion well and use of well adapter when required.
LOW VOLTAGE THERMOSTAT
T
T
1K
W
LOW LIMIT/ CIRCULATOR
1K2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
2
USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 3. L8124A,C single zone connections
L8124A,C
G
1
2
R
B
1K1
ZR
ZC
B
HIGH LIMIT
R
and internal schematic.
3
B1
B2
C1
C2
BOILER
2
L1 (HOT)
L2
1
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
LINE VOLTAGE CIRCULATOR
M8802
CONTROLLER
CASE
IMMERSION OLD IMMERSION WELL ASSEMBLY
(A)
HEAT-CONDUCTIVE COMPOUND
1
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).
2
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (
TV
1
2
3
WELL CLAMP
SCREW
LOW VOLTAGE THERMOSTAT
T
Z
1K
R
W
LOW LIMIT/ CIRCULATOR
HIGH LIMIT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 4. L8124E single zone connections
and internal schematic.
WELL CLAMP
ADAPTER
L8124E
1K2
B
R
B
3
SENSING BULB
G
1
2
1K1
C1
C2
B1
B2
(D)
(B)
2
L1 (HOT)
L2
LINE VOLTAGE CIRCULATOR
LOW VOLTAGE GAS VALVE (eg, VR8300)
M8803
1
TR
TH
3 95-6571—11
Page 4
L8124A,C,E,L AND M AQUASTAT® RELAYS
T87F
L8124A
TT
2
G
L1
L2
L2
L1 (HOT)
1
PUMP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
ZC
ZR
3
C1
B1
C2
B2
R8184
T
T
BLACK
WHITE
TT
123
PUMP
F
F
T87F
ORANGE
R845 RELAY
45
C554
T87F
R845 RELAY
TT
123
6
PUMP
BURNER AND IGNITION
M8822
Fig. 5. L8124A in an oil-fired, forced hot water, tankless, zoned, pump system.
TO ADDITIONAL
L2
L1
R845A RELAYS
1
FOR OTHER ZONES
R845A RELAY ZONE 2
6
5
3
4
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
T
LOW VOLTAGE THERMOSTAT
1K
W
1K2
T
R
LOW LIMIT/ CIRCULATOR
B
R
L8124A,C
B
HIGH LIMIT
(HOT)
2
G
1
2
1K1
ZR
ZC
3
B1
B2
C1
C2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
LINE VOLTAGE CIRCULATOR
Fig. 6. L8124A,C multizone system with circulator connections and internal schematic.
45
6
ZONE 2 CIRCULATOR
ZONE 2 LOW VOLTAGE THERMOSTAT
M8827
95-6571—11 4
Page 5
L8124A,C,E,L AND M AQUASTAT® RELAYS
ZONE 1 THERMOSTAT
V8043F
TH TR
2
1
2
3
4
Fig. 7. L8124 multizone system with zone valve
TR
TH
T
1K
W
LOW LIMIT/ CIRCULATOR
1K2
Z
R
HIGH LIMIT
TV
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
UP TO TWO V8043F ZONE VALVES CAN BE POWERED WITH L8124G,L. ADD ADDITIONAL TRANSFORMER FOR EVERY TWO OR LESS VALVES.
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
B1 IS 1/4 IN. TAB TERMINAL.
connections and internal schematic.
TH TR
L8124G,L
B
B
ZONE 2 THERMOSTAT
V8043F
TR
TH
ZR
ZC
4
B1R
B2 C2
C1
G
1
2
1K1
3
L1 (HOT)
1
L2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
LINE VOLTAGE CIRCULATOR
M1795B
1 L1 (HOT)
L2
2
G
L2 L1
C1 C2
CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 8. L8124E in a 24Vac, gas-fired,
forced hot water, tankless system.
TT
3
B1
B2
LOW VOLTAGE GAS VALVE (eg, VR8300)
TH
T87F
L8124E
TR
M1796A
5 95-6571—11
Page 6
L8124A,C,E,L AND M AQUASTAT® RELAYS
T87F
R845 RELAY
TT
123
1
L1 (HOT)
L2
2
L8124E AQUASTAT® RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
PUMP PUMP
G
L2 L1
TT
C1 C2
B2
B1
45
3
6
TH
TR
TT
123
LOW VOLTAGE GAS VALVE (eg, VR8300)
T87F
R845 RELAY
45
T87F
TT
6
123
PUMP
Fig. 9. L8124E in a 24 Vac, gas-fired, forced hot water, tankless, zoned pump system.
1
TO ADDITIONAL R845A RELAYS
L1
L2
L8124E
T
1K
W
LOW LIMIT/ CIRCULATOR
Z
1K2
R
B
R HIGH LIMIT
B
TV
G
1
2
1K1
C1
C2
3
B1
B2
2
TR
THTR TH
LOW VOLTAGE GAS VALVE (eg, VR8300)
(HOT)
FOR OTHER ZONES
R845A RELAY ZONE 1
6
5
3
4
1
2
ZONE 1 CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 10. L8124E multizone system with circulator connections and internal schematic.
R845 RELAY
45
M1794A
6
ZONE 1 LOW VOLTAGE THERMOSTAT
M8828
95-6571—11 6
Page 7
L8124A,C,E,L AND M AQUASTAT® RELAYS
LOW VOLTAGE THERMOSTAT ZONE 1
TV
T
1K
W
LOW LIMIT/ CIRCULATOR
1K2
L8124L
Z
R
B
B HIGH LIMIT
G
1
2
1K1
ZR
ZC
3
B1R
B2 C2
C1
1
L2
L1 (HOT)
2
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
LINE VOLTAGE CIRCULATOR ZONE 1
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
R845A RELAY ZONE 2
6
5
3
4
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 11. L8124L multizone system with circulator connections and internal schematic.
ZONE 2 CIRCULATOR
ZONE 2 LOW VOLTAGE THERMOSTAT
M8829

OPERATION

High Limit Controller

The high limit opens and turns off the burner when the water temperature reaches the setpoint. The high limit automatically resets after the water temperature drops past the setpoint and through the 10°F (6°C) differential.
WARNING
Explosion Hazard. Can cause serious injury, death or equipment damage.
Use this product only in systems with a pressure relief valve.

Low Limit and Circulator Controllers

On a temperature rise, with the adjustable differential at the minimum setting of 10°F (6°C), the burner circuit (R-B) breaks and the circulator circuit (R-W) makes at the control setpoint. On a temperature drop of 10°F (6°C) below the setpoint, the R-B circuit makes and the R-W circuit breaks. See Fig. 12.
At any differential setting greater than 10°F (6°C), the R-B make temperature and the R-W break temperature remain the same (control setting minus 10°F [6°C]). The R-B break and R-W make temperature are the setpoint temperature plus the difference between the differential setting and 10°F (6°C).
EXAMPLE: Setpoint of 140°F (60°C), differential set at 25°F (14°C). On a temperature rise, R-B breaks and R-W makes at 155°F (68°C). On a temperature fall, R-B makes and R-W breaks at 130°F (54°C).
SWITCH BREAKS ON TEMPERATURE RISE.
BURNER TURNS OFF. HIGH LIMIT SETTING
LOW LIMIT AND CIRCULATOR SETTING
1
WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
CIRCULATOR OPERATES
ON A CALL FOR HEAT.
SWITCH MAKES ON
TEMPERATURE FALL.
BURNER OPERATES ON A
CALL FOR HEAT.
SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.
SWITCH MAKES R-W
AND BREAKS R-B ON
TEMPERATURE RISE.
SWITCH MAKES R-B AND
BREAKS R-W ON
TEMPERATURE FALL.
BURNER IS ON TO
MAINTAIN MINIMUM
WATER TEMPERATURE.
CIRCULATOR IS OFF.
M1523
Fig. 12. Relationship of setpoints and differential.
7 95-6571—11
1
Page 8
L8124A,C,E,L AND M AQUASTAT® RELAYS
On the L8124M, the burner and circulator circuits are separately controlled; the low limit controls the burner circuit (R-B) as described above, while the low voltage thermostat directly controls the circulator circuit. See Fig. 13.
LOW VOLTAGE THERMOSTAT
L8124M
TT
1K
R
W
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH
2
GROUND. USE GROUNDING SCREW PROVIDED.
3
B1 IS 1/4 IN. TAB TERMINAL.
Fig. 13. L8124M single zone connections
B
LOW LIMIT
B
R
and internal schematic.
HIGH LIMIT
1K1
ZC
G
L1
L2
C1
C2
B1
B2
3
2
L1 (HOT)
L2
1
LINE VOLTAGE CIRCULATOR
LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE
M8804

SETTING

Follow the boiler manufacturer recommendations when making the L8124 settings. The high limit setting must be at least 20°F (11°C) higher than the low limit setting. Set the indicators over the selected temperature marks. The low limit differential is set by turning the differential adjustment knob to the desired amount of differential. The thermostat heat anticipator should be set at 2.0A.

CHECKOUT