Honeywell AQ254 Catalog Page

Honeywell AQ254 Catalog Page

AQUATROL Zoning System

 

 

 

 

 

 

 

 

Type of Zoning

Number of Zones

Boiler Pump

 

 

Product Number

Devices Controlled

Controlled

Output Rating

Replacement Parts

 

 

 

 

 

 

*

AQ25242B/U

Zone pumps or 2-wire

4

120 Vac/250 Vac 5A,

AQ15200B universal injection/mixing boiler reset module;

 

 

valves (line voltage)

 

1/3HP

AQ12C11 supply/return/mixed loop sensor;

 

 

 

 

 

AQ12C10 outdoor sensor; AQ10X38 24 Vac 38 VA transformer;

 

 

 

 

 

AQ15540B 4-zone pump expansion module

 

 

 

 

 

 

*

AQ25244B/U

Zone valves with end

4

120 Vac/250 Vac 5A,

AQ15200B universal injection/mixing boiler reset module;

 

 

switches

 

1/3HP

AQ15740B 4-zone valve with end switch expansion module;

 

 

 

 

 

AQ12C11 supply/return/mixed loop sensor; AQ12C10 outdoor sensor;

 

 

 

 

 

AQ10X38 24 Vac 38 VA transformer

 

 

 

 

 

 

* TRADELINE models • SUPER TRADELINE models

 

 

 

 

 

 

 

 

 

AQ254 Add-a-Temperature Injection/Mixing Expansion Control Panel for Hydronic Zoning System

expands the total network capacity by up to 16 zones when used with AQ255 and/or AQ257 zoning panels.

 

• Acts as an add-on Control panel to the Main (AQ250, AQ25A,

 

AQ251, AQ252) Control panel.

 

• Allows each of the 16 zones connected to it to be assigned to the

 

system's primary or secondary loop.

 

• Up to 3 AQ254 panels can be added to a Main (AQ250, AQ25A,

 

AQ251 or AQ252) Control panel.

 

• Mixed loop temperature is controlled by a variable speed injection

 

pump or motorized mixing valve connected to the AQ254.

 

• Intuitive programming interface and armchair programming (can be

 

programmed at your desk and taken to the job site “ready-to-install”)

The AQ254 Add-a-Temperature Expansion Control Panel is used in

• Customizable mixing control settings allow for greater level of control

and comfort.

conjunction with an AQ250, AQ25A, AQ251 or AQ252 Control

• Zone synchronization through Zone of Greatest Demand control.

Panel. It provides one additional loop temperature control

• Integral 38 VA transformer with self resetting electronic fuse.

capability for the AQ2000 control panel it is connected to and

 

Application: Expanded zone control and mixed loop temperature control in a hydronic zoning system

Mixed loop target temperature is reset by either outdoor temperature or calculated system load based on indoor temperature feedback Mixing is target controlled by a variable speed injection pump or motorized mixing valve

Dimensions, Approximate: 9 1/2 in wide x 8 in. high x 3 3/8 in. deep (24 cm wide x 20.3 cm high x 8.5 cm deep)

Power Supply: 120V/60Hz

User Interface (Setting, Programming): (LCD Display and a 3 button Key Pad)

Electrical Connections (Line Voltage): Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals

Control and Zoning Panel Temperature Rating: 32 F to 130 F (0 C to 55 C)

Thermostat Compatibility: AQ1000 Series 2-wire communicating thermostats and most digital thermostats

Variable Speed Injection Pump Output: Triac modulated; 120 Vac, 2.1A, 1/6HP

Secondary Pump Output Rating: 120 Vac 5A, 1/3HP

Auxiliary Pump Output Rating: Dry contact output, 120 Vac/250 Vac 5A, 1/3 HP

Sensor Temperature Rating: -58 F to +230 F (-50 C to +110 C) Secondary Loop Mixing (Supply) Design Temp Range: 70 F to 210

F (21 C to 99 C)

Secondary Loop Mixing (Supply) Max Control Temp Range: 80 F to 210 F (27 C to 99 C)

Secondary Loop Return Min Control Temp Range: 80 F to 180 F (27 C to 82 C)

Secondary Loop Mixing (Supply) Min Control Temp Range: 35 F to 150 F (2 C to 66 C)

B-B Communication Bus Terminals: Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules.

R-C Input (on Control and Zoning Modules): 24 Vac Class II (input on Control and Zoning Modules)

R-C Output (on transformer): 38 VA, 24 Vac Class II

Operating Humidity Range (% RH): 5 to 90% RH, non-condensing

Weight: 3.9 lbs (1.8 kg)

Approvals

Canadian Standards Association: CSA C/US Certified to CSA and UL Standards, File No. LR76030

 

 

 

 

 

Product Number

Mixing Valve Floating Output (Com,O,C)

Replacement Parts

 

 

 

 

*

AQ25400B

24Vac rated dry contacts

AQ15400B Add-A-Temperature expansion control module;

 

 

 

AQ12C11 supply/return/mixed loop sensor;

 

 

 

AQ10X38 24 Vac 38 VA transformer

 

 

 

 

* TRADELINE models • SUPER TRADELINE models

 

 

 

 

 

<![if ! IE]>

<![endif]>Hydronic

<![if ! IE]>

<![endif]>Controls

70-6910

 

 

 

189

 

 

Loading...