Honeywell AQ2002 User Manual

Page 1
FEATURES
AQ2002
Room unit (optional)
APPLICATION
Aquatrol 2002 is a straightforward, versatile controller which forms the basis of an outside compensated control system for single or dual zone low pressure hot water heating systems. The controller offers build-in optimizer and many other advanced featured whilst still retaining simple user adjustments.
It provides self adaptive heating curve, optimum start/stop operation, outside air compensated mixed water control using a 3-port motorized valve and pump, boiler, and domestic hot water control using a valve and/or pump.
A wide range of compatible sensors, a remote unit, valves and actuators complement the control system.
AQ2002
OPTIMISER/COMPENSATOR
CONTROLLER
PRODUCT SPECIFICATION SHEET
Digital control technology with easy to understand
analogue installation adjustments
Outside compensated control of low pressure hot
water heating system
Fixed or self-adaptive heating curve (with optional
remote unit)
Two independent heating curves for 1st and 2nd
heating zone
Heating time programme offering switching between
comfort and economy operation up to 6 times per day, independently for each day of the week (selectable night off period is also available)
Optimum Start/Stop (with optional space sensor) or
Heating Boost on start-up (without space sensor)
Domestic Hot Water (DHW) time programme offering
up to 6 switching points per day independently for each day of the week
DHW programme can alternatively be used as the
heating programme for second heating zone
Holiday mode with programmable 1 to 99 day holiday
period and dynamic countdown display
Automatic, DHW only, Holiday or Standby operation
LED’s indicate control output status
Pump and valve exercise which helps prevent
sticking during long periods of inactivity
Frost protection of the pipework, hot water cylinder
and the building fabric (with optional space sensor)
Automatic summer heating mode changeover (user
adjustable)
Automatic heating shutdown under minimal load
conditions
Softstart to help prevent pipe expansion noise
Service switch to assist installer on start-up and
technician during service
Intelligent pump control with energy efficient pump
overrun
Built-in user programme
Optional remote unit providing space temperature
sensing, space temperature adjustment, comfort/economy override switch and 3 hour comfort extension button with confirmation LED
1 EN0R8527R0
Page 2
AQ2002 Optimiser/Compensator Controller
: IP40 (with base fitted and when installed
: 144 x 96 x 107 mm (with standard base)
SPECIFICATIONS
SYSTEM SELECTION CHART
Radiator or
With
On/Off Burner
Radiator
Single
Without
Pumped
Diverting
Radiator or
Radiator and
Single
Dual
On/Off Burner
On/Off Burner
With
With
Without
With
With
Pumped
Pumped
67134
5
2
Without
Without
APPLICATIONS
Supply voltage: 230 V~, +10% -15%, 50 Hz Power
: 8 W
Consumption Relay ratings : Pumps and boiler:
3 A, 230 V~ @ 0.6 pf - 400,000 oper. Mixing valve:
0.25 A, 230 V~ @ 0.4 pf - 1,000,000 oper
Sensor accuracy : Water sensors: 20°C to 90°C ±2 K
Outside sensor: -20°C to +20°C ±2 K Room sensor: 10°C to 25°C ±0.5 K
Ambient temp.
: 0 to 50°C
rating
The chart can be used to determine the system number (1-7) corresponding to the required application.
Systems 1, 2 and 3 are typical Radiator applications without mixing valve.
Systems 4 and 5 are Radiator OR Underfloor applications with mixing valve.
Systems 6 and 7 are Dual loop Radiator AND Underfloor applications.
Loop Systems
Humidity rating: 0 to 90% rh (non-condensing) Storage/shipping
: -30°C to +70°C
temperature Electromagnetic
compatibility
: Emissions to EN55014-1
Immunity to EN55014-2
Protection class
to EN60529)
Dimensions (w x h x d)
Panel cut-out
144 x 153 x 109 mm (with wiring centre)
: 138 x 92 mm
(w x h) Weight : 600 g
AQ2002
Underfloor
Underfloor
Loop Systems
Loop Systems
Underfloor
SYSTEM 1
Application
This system offers intelligent ON/OFF burner and pump control for radiator heating.
Control
DHW
DHW
DHW
Valve
Electrical Connections
Mixing Valve
DHW
Control
DHW
DHW
DHW
DHW
Temperature sensors
T3 Outside air T7043E T5 Boiler
supply
Optional T1 Remote
unit
Control
Mixing Valve
DHW
DHW
T7076D insertion or T7043F immersion
T8102B1001 Full function remote unit including wall plate.
EN0R 8527 R0 2
For potential free connection, please refer
to boiler connection section
Page 3
AQ2002 Optimiser/Compensator Controller
SYSTEM 2
SYSTEM 3
Application
This system offers intelligent ON/OFF burner and pump control for radiator heating.
This system also provides a second pump to meet the demands for domestic hot water.
Electrical Connections
For boiler potential free connection, please refer
to boiler connection section
Temperature sensors
T3 Outside air T7043E T4 Domestic hot water T7076D insertion or T7043F immersion T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
Application
This system offers intelligent ON/OFF burner and pumps control for radiator heating and uses a diverted valve to meet the demands of domestic hot water
Electrical Connections
For boiler potential free connection, please refer
to boiler connection section
Temperature sensors
T3 Outside air T7043E T4 Domestic hot water T7076D insertion or T7043F immersion T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
EN0R 8527 R03
Page 4
AQ2002 Optimiser/Compensator Controller
SYSTEM 4
with mixing valve control for radiator or underfloor heating.
with a mixing valve and a pump control without boiler control.
SYSTEM 5
with mixing valve control for radiator or underfloor heating.
Application
This system offers intelligent ON/OFF burner and pump control
This system can also be used for a single heating loop equipped
Electrical Connections
For boiler potential free connection, please refer
to boiler connection section
Temperature sensors
T2 Mixed water T7044C strap on or T7043F immersion T3 Outside air T7043E T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
Application
This system offers intelligent ON/OFF burner and pump control
This system also provides a second pump to meet the demands for domestic hot water.
Electrical Connections
For boiler potential free connection, please refer to
boiler connection section
Temperature sensors
T2 Mixed water T7044C strap on or T7043F immersion T3 Outside air T7043E T4 Domestic hot water T7076D insertion or T7043F immersion T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
EN0R 8527 R0 4
Page 5
AQ2002 Optimiser/Compensator Controller
SYSTEM 6
SYSTEM 7
Application
This dual loop system offers intelligent ON/OFF burner and pump control for radiator loop and mixing valve control for underfloor loop.
Electrical Connections
For boiler potential free connection, please refer to
boiler connection section
Temperature sensors
T2 Mixed water T7044C strap on or T7043F immersion T3 Outside air T7043E T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
Application
This dual loop system offers intelligent ON/OFF burner and pump control for radiator loop and mixing valve control for underfloor loop. This system also provides a third pump to meet the demands for domestic hot water.
Electrical Connections
For boiler potential free connection, please refer to boiler
connection section
Temperature sensors
T2 Mixed water T7044C strap on or T7043F immersion T3 Outside air T7043E T4 Domestic hot water T7076D insertion or T7043F immersion T5 Boiler supply T7076D insertion or T7043F immersion Optional
T1 Remote unit T8102B1001 Full function remote unit including wall plate.
EN0R 8527 R05
Page 6
AQ2002 Optimiser/Compensator Controller
within the range 40 to 70°C.
within the range 10 to 30°C. When the
CONTROLLER FEATURES
within the range 4 to 40 using this
Comfort Setpoint
LCD Display
User Adjustments
Installer Adjustments
The desired space Comfort temperature can be set within the range 12 to 28°C.
Override Buttons
System Selector Switches
Programming/Operating Buttons
Cycle Rate Adjustment
The cycle rate adjustment allows the cycle rate as recommended by the boiler manufacturer to be set directly on the controller.
Output Status Indicators
User Adjustments
Installer Adjustments
Economy Setpoint
The desired Economy temperature can be set within the range 8 to 22°C. Economy OFF can be selected by turning the knob to the OFF position.
Domestic Hot Water Setpoint
The DHWS temperature can be set
Automatic Summer/Winter Changeover Temperature Setpoint
Boiler/Mixed Flow Temperature High Limit
In systems with no mixing valve (no T2 sensor) the maximum value of the boiler supply water temperature (T5) can be adjusted by this setting. In systems with T2 sensor and mixing valve the maximum mixed water temperature will be adjusted by this setting. In this case, the maximum boiler supply temperature is fixed at 90°C.
Heating Curve Ratio Adjustment
Two Heating Curve Ratio Adjustments are proposed, one for each loop.
If a fixed value of the heating curve ratio is required then this value can be set
potentiometer. To determine the heating curve required
refer to the graph displayed below.
Ratio
The automatic Summer/Winter changeover temperature can be set
average daily outdoor temperature is above the automatic Summer/Winter setpoint the heating will be turned off.
EN0R 8527 R0 6
Outside Air Temperature oC (T3)
Page 7
AQ2002 Optimiser/Compensator Controller
USER OPERATION
will operate at the economy space setpoint and the hot water
will be restarted in automatic mode and controlled according
Built-in Heating and DHW Program
Two different built programs are available, the first one is designed for the first heating loop, and the second one can be assigned either for second heating loop or DHW system (depending of switch S2 position).
Heating program offer switching between comfort and economy operation up to 6 times per day, independent for each day of the week.
DHW program offer switching between ON and OFF operation up to 6 times per day, independent for each day of the week.
Holiday Program
When the holiday mode of operation is selected, the heating control will be inactive (except for frost protection) until the set
number of days has elapsed. When the heating and hot water to the programmed data.
The return to automatic occurs at 0:00 the day the heating is required.
System Temperature Enquiry
By switching to the enquiry mode all system temperature and the adapted heating curve value (or the value of the heating curve compensation slope knob if fixed compensation is selected) can be displayed on the LCD.
Only the current temperature and parameter value will be displayed.
This facility is not available during the initial start-up procedure
REMOTE UNIT
Electrical connection
Room Unit
CONTROLLER OPERATION
Outside temperature compensation
The Aquatrol 2002 is an outside temperature controller compensated designed for most of heating systems composed by boiler, circuit with or without mixing valve, and domestic hot water.
Fixed or Self Adaptive Heating Curve
Room temperature compensation is available (in CH zone 1 only) when a remote room unit is connected. The fixed or self adaptive heating curve function is selected by switch S7.
Optimum Start/Stop
If a remote room unit is present, the controller automatically calculates the ideal times for starting the setback and heating-up phases defined by the heating program, in order to save energy without sacrificing comfort. Without a room sensor, optimum start/stop is not possible and a heating boost is implemented in advance of an upward heating setpoint change.
Note: optimum start and stop are applicable only to CH
zone 1 since only that zone can have a remote room unit.
The AQ2002 controller can be completed by a remote unit (optional) , its allow the user to adjust rapidly on controller setpoints without going to the boiler room.
The remote unit incorporates a space temperature sensor, a remote setpoint adjustment knob with adjustable range stops, a 3 hour extension push button with LED indication, and a manual switch to override the operating mode. The day or night flag will flash on controller when the mode is overridden. When used as a space temperature sensor, the same mounting directions for the space sensor temperature applies.
The unit is a 2 wire connection polarized.
Comfort/Economy Override Switch
Comfort Extension Button Remote Space
Temperature Adjustment
Comfort Extension Indicator (LED)
Frost Protection of the Pipework
Frost protection of the heating system applies at all times and in all operating modes of the controller.
Automatic Shutdown
During periods when there is no requirement for heat, the controller will shut down the system including turning off the heating pumps.
Automatic Summer/Winter Changeover
When the daily average outdoor temperature is high, then the heating is turned off (pumps off, boiler off, valve closed). The summer/winter changeover temperature is adjustable via a potentiometer.
Pump and Valve Exercise
In order to prevent sticking or jamming of components during long periods of inactivity, for example in the summer, then a pump/valve exercise will take place once a week at 12:00 on Fridays.
DHWS Operation
When a DHW temperature (T4) sensor is connected, the DHW temperature is controlled to a user-adjustable set point.
There are two variants for combined DHWS; DHWS Priority/Shifting or Parallel priority operation. In all two
EN0R 8527 R07
Page 8
AQ2002 Optimiser/Compensator Controller
DHWS Priority/Shifting Priority
In heating circuits with no mixing valve (and no mixed flow temperature sensor), the DHWS has priority over the heating.
In heating circuits with mixing valve, operation is as follows: While the boiler temperature is less than a differential of
10K above the DHW setpoint, the mixing valve will be closed giving DHW priority. However if there is surplus heat available and the boiler temperature is more than 20K (the differential plus a proportional-band of 10K) above the DHW setpoint then the mixed heating loop will control at its calculated setpoint, servicing the heating in parallel with the DHW. If the boiler temperature is between these two values then the mixed water setpoint is reduced.
Note: In dual loop systems, the CH zone 2 pump will be
switched off during a DHW service.
DHWS Parallel
In heating circuits with mixing valve when parallel operation has been selected central heating will continue to operate normally during a DHW service.
Note: In some systems selection of parallel operation may
result in extended DHW recovery times or in extreme cases DHW never being satisfied
Note: Any heating loop supplied directly from the boiler will
be shut down during DHW demand period no matter what is the position of S4 switch.
If a DHWS sensor (T4) is present then combined or separate temperature control of the DHWS will be available. If no DHWS sensor (T4) is present only time control is available on the DHWS output.
Automatic system detection takes place during the first minute after powering the controller.
System Selection Switches
SwitchDescription Position A Position B
S1 Boiler low limit 20°C 45°C S2 2nd time programme DHW CH zone 2 S3 DHWS program programmed continuous S4 DHWS operation
S5 DHW actuator device pump valve S6 Type of heating radiator underfloor S7 Adaptive heat curve 1 yes no
Priority/ Shifting
operation
parallel
INSTALLER START UP SEQUENCE
To initiate the installer start up sequence the service switch must be set to the "1" position with the power to the controller switched OFF.
When power is now switched ON the above sequence will start. The sequence can be stopped at any time by moving the service switch to the "0" position.
SYSTEM SELECTION
System selection is achieved in two manners:
Automatic System Selection
System Selector Switches
Automatic System Selection
The AQ2002 is able to recognize which temperature sensor is connected.
If a mixed flow water sensor (T2) is connected, the controller assumes that a mixing valve is present.
If a Remote Unit (T1) is present the controller activates the space temperature compensation, the optimum Start/Stop and the self-adaptive heating curve (if switch S7 on position A).
S8 Heating zones one/single loop two/dual loop
Shading indicates position as supplied from the factory
S1 Boiler Minimum Temperature
Allows to set the minimum boiler temperature:
- Position A: 20°C, no boiler temperature low limit
- Position B: 45°C NOTE: Low limit will apply also to the 2nd CH heating zone flow
temperature
S2 Second time program
See table
S3 DHW Time Programme
Allows to select the timed or continuous operation of DHW. If the S2 is in position B and S3 in position A, DHW will operate according to both heating zone programmes.
S4 DHW Operation
DHW demand can be served in one of the following modes:
- Position A: Priority or Shifting Priority. Please refer to “DHWS Operation” section
- Position B: parallel. Please refer to “DHWS Operation” section
S5 DHW Actuator Device
S5 allows you to configure AQ2002 for systems where diverting valve is used to switch the boiler output to CH or DHW installation. Use of diverting valve is only allowed in systems without mixing valve.
- Position A: on DHW demand the DHW pump will be switched
on.
- Position B: on DHW demand the diverting valve will be driven
to DHW position and CH pump will continue to run forcing the flow through the hot water heat exchanger.
EN0R 8527 R0 8
S6 Type of heating
Page 9
AQ2002 Optimiser/Compensator Controller
S6 Type of heating
See table
S7 Adaptive Heating Curve 1
To benefit from this feature a remote unit must be installed. During normal heating periods estimates are made for the heating curve ratio 1. Each day controller compares its performance to meet the criteria of achieving the day space temperature. A new value for the heating curve ratio 1 is stored daily in the controller’s memory such that within 4 to 6 days, from the initial start-up it will have changed the initial heating curve to one that more closely matches the building’s thermal characteristics. During this learning phase the room compensation will assist in providing comfortable space temperature conditions.
S8 Heating zones
See table
SYSTEM ON INDICATION
Each output is monitored by LED.
Fault
Description Controller Action
Code
F1 Dual loop ratio
setting fault
CH1 ratio has priority: set ratio 1 under ratio 2 following installation requirements
F2 T2 sensor fault Acts as system without mixing valve. F3 T3 sensor fault Heating on at or above frost protection
values.
F4 Not used F5 T4 sensor fault DHW output held off.
F6 T5 sensor fault If frost protection active: Boiler cycles at
20%. If no frost protection: Boiler off
F7 T1 remote unit.
Acts as system without remote unit.
fault F8 Internal fault Boiler cycles at 20%, valve opens. F9 Remote unit
Acts as system without remote unit.
fault
DIMENSIONS
Controller Dimension in mm
When the LED is illuminated it indicates that:
The mixing valve actuator is being driven closed,
reducing Heating.
The mixing valve actuator is being driven open, increasing Heating.
Heating pump 2 is ON.
The DHW is ON.
Heating pump 1 is ON.
Boiler output is ON.
FAULT CODES
Should a fault occur in the system a fault code will be displayed on the LCD. The table below gives details of the codes and the action taken by the controller.
Information:
The above table also indicates the priority of the fault. The lower the code the higher the priority.
An open circuit is used to automatically select the control system configuration for DHW, mixing systems and for the Remote Unit. A fault is not displayed if an open circuit is detected on the T2, T4 & T5 sensors or the Remote Unit terminals within the first minute after switching power on.
Surface Mounting
The Aquatrol 2000 controller can be surface mounted in either a control panel or directly on the wall.
Panel Mounting
The controller can be panel mounted in a control panel door and features integral panel mounting clips for ease of installation.
Panel cut-out (w x h) : 138 x 92 mm
EN0R 8527 R09
Page 10
AQ2002 Optimiser/Compensator Controller
INSTALLATION
wiring.
Important
1. The installer must be a trained engineer
2. Disconnect the power supply before beginning installation
The recommended wiring is as follow:
From Controller to … Maximum Length Type of wire
Temperature sensor 100m Remote unit 50m Boiler/Burner 100m Motorized valve 100m Pumps 100m Other devices 100m
To meet the
requirements of
local standards
Boiler connection
ON/OFF boilers can be connected and controlled by two different manners:
ON/OFF boiler supplied and controlled by line voltage
Tamper-Proofing
The controller can be made tamperproof, if required, by inserting a wire link through the hole in the front clear cover and the front housing at the top center of the front panel and twisting or crimping to fix the front panel permanently shut, thus preventing unauthorized adjustment.
Wall Mounting using Wiring Centre (Optional)
For wall mounting the optional Wiring Center K42007745­005 can be used for protection and termination of electrical conduits, MICC cable or Pirelli FP200 cables with suitable adapters.
CONNECTIONS
Controller Connection
The controller operates from a 230V 50Hz power supply. Cables providing power to the controller should be sized to match the individual installation requirements for distance and power consumption. The AQ2002 controller requires an effective earth directly from the building’s consumer unit in order to meet the same earthing requirements for the temperature sensors.
Each terminal within the controller is capable of accepting either two cables with a maximum cross sectional area of
1.5mm2 or one cable with a maximum cross sectional area
of 2.5mm2. Please refer to your system for the correct input/output
ON/OFF boiler supplied by the line voltage and control by a free voltage contact
Boiler relay ratings
Boiler: 3 A, 230 V~ @ 0.6 pf
EN0R 8527 R0 10
Page 11
CONTROLLER ORDERING SPECIFICATION
Ordering specification: W6060C1141 Belgium and French version
Specifications
water pipe providing a temperature input
water pipe, or inserted in a well, and
W6060C1158 English version
OTHER SYSTEM COMPONENTS (to be ordered separately)
Outside Temperature Sensor T7043E
Application
The Outside Temperature Sensor consists of a thermistor element housed in a tough plastic case. It is mounted outside the building providing a temperature input signal to the controller.
Ordering Specification: T7043E1008
Flow Temperature Sensor T7044C
Sensing range : -30 to +40°C Sensor : NTS type 10 k @ 25°C Enclosure : Plastic with integral
Pg11 fitting
Dimensions : 66 x 35 mm
AQ2002 Optimiser/Compensator Controller
Application
The T7044C Strap-on Flow Water Temperature Sensor consists of a thermistor sensing element housed in a tough plastic case. It is strapped to the flow
signal to the controller. Ordering Specification: T7044C1002
Flow Temperature Sensor T7043F
Application
The T7043F Immersion Flow Water Temperature Sensor consists of a thermistor sensing element housed in an immersion pocket. It should be mounted on a bend on the flow water pipe providing a temperature input signal to the controller
Ordering Specification: T7043F1006
Insertion Temperature Sensor T7076D
Application
The T7076D tape-on or insertion sensor consists of a thermistor sensing element encapsulated in plastic. It is designed for use in outside temperature compensated heating systems. It can be taped on to a hot
provides a temperature input signal to the controller. For tape-on installation, a polyester and an aluminium tape are supplied.
Ordering Specification: T7076D1001
Specifications
Sensing range : 0 to 115°C Sensor : NTS type 10 k @ 25°C Enclosure : Plastic with integral
Pg11 fitting
Dimensions : 72 x 48 mm
Specifications
Sensing range : 0 to 115°C Sensor : NTS type 10 k @ 25°C Enclosure : Plastic with integral
Pg11 fitting Dimensions : 72 x 45 mm Well : ½" BSPT x 100 mm
Specifications
Sensing range : 0 to 110°C Maximum
Ambient temp. : 115°C Wire dimensions : 1.3mm x 1.5m long. Sensor : NTS type 10 k @ 25°C Wire rating : -30 to +115°C Dimensions : 7 Ø x 25 mm
Temperature Sensor Characteristics
EN0R 8527 R011
Page 12
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
Specifications
RELATED LITERATURE
Remote Unit T8102B
Application
The Remote Unit provides a space temperature sensor input signal to the AQ2000 for space temperature compensation and to enable the optimization and adaptive ratio to function. Remote adjustment of the setpoint is also possible and an override switch gives the possibility of selecting permanent comfort or economy settings. A "party" button allows a three hour comfort extension to be selected.
Ordering Specification:
T8102B1001 with English literature T8102B1050 with French literature T8102B1068 with Italian literature
Sensor : NTS type 10 k @ 25°C Housing : White plastic Weight : 70 g Dimensions : 70 x 75 x 31 mm (w x h x
d) Setpoint : ± 3 K
adjustment
Wiring Centre K42007745-005
Application
The Wiring Centre is an essential component when mounting the controller on a wall. It provides a number of conduit entries through the bottom, back and sides. In addition, it provides extra terminals to link multiple incoming cables such as line, neutral and earth.
Ordering Specification:
K42007745-005
Specifications
Housing : White Plastic Cable entries : 17 x 19 mm conduit entries
Dimensions : 70 x 75 x 31 mm (w x h x d)
(9 bottom, 3 right side, 1 left side, 4 back)
AQ2002 Installation Guide 42010344-001 in English
42010344-002 in French
AQ2002 User Guide 42010345-001 in English
42010345-002 in French
Honeywell Control Systems Limited http://europe.hbc.honeywell.com Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0R 8527 R0
Loading...