AQ2000 Series
AQUATROL THERMOSTAT WIRING
INSTALLATION INSTRUCTIONS
Aquatrol zoning modules are compatible with any digital thermostat. The AQ1000 digital communicating thermostats have been
designed to enhance the Aquatrol system functionalities. Non-communicating dry-contact thermostats provide the needed heat
signals for operation.
AQ1000TN2 and AQ1000TP2
Connect TH terminals of the thermostat
to Rh and W terminals of the zone
module (no polarity to observe).
Aquatrol zoning modules are compatible with any digital thermostat. The AS1000 digital communicating thermostats have been
The AQ panels are equipped with a 38 VA transformer which leaves between 27 and 34 VA available (depending on the panel
model) to power thermostats or valves. Honeywell's VisionPRO, FocusPRO and PRO thermostat lines draw less than 0.5 VA for
each thermostat. Honeywell's Prestige HD thermostat draws 2.7 VA each under normal usage. If additional VA is needed for the
system, use a second transformer.
Connect Rh and W terminals of the
thermostat to Rh and W terminals of
the zone module.
Battery-powered/
Dry-contact Thermostats 24-VAC Thermostats
1. If any, remove jumper between Rc
and R on thermostat.
2. Connect 24 VAC from transformer to
C and Rc terminals of thermostat.
3. Connect Rh and W terminals of the
thermostat to Rh and W terminals of
the zone module.
69-2394—02
AQ2000 SERIES
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
69-2394—02 T.W. Rev. 06-10
Printed in China