Honeywell AQ2000 User Manual

The
single zone low pressure hot water heating system. It
FEATURES
provides self adaptive heating curve, optimum start/stop operation, sequence control of two boilers, outside air compensated mixed water control using a 3-port motorised valve and pump, and domestic hot water control using a valve and/or pump.
A wide range of compatible sensors, a remote unit, valves and actuators complement the control system.
AQ2000
OPTIMISER/COMPENSATOR
CONTROLLER
PRODUCT DATA
Digital control technology with easy-to understand
analogue installation adjustments
Outside compensated control of low pressure hot
water heating system
Multiple system applications
Automatic system recognition from connected
sensors
Fixed or self-adaptive heating curve (with optional
space sensor)
Optimum Start/Stop (with optional space sensor) or
Boost on start-up (without space sensor)
Room temperature compensation (with optional
space sensor)
Heating time programme offering switching between
comfort and economy operation up to 6 times per day, independently for each day of the week (selectable economy off is also available)
Manual override switch
Domestic Hot Water Service (DHWS) time
programme offering up to 6 switching points per day, independently for each day of the week
Frost protection of the pipework , hot water cylinder
and the building fabric (with optional space sensor)
Automatic summer heating mode changeover (user
adjustable)
Automatic heating shutdown under minimal load
conditions
Soft start to help prevent pipe expansion noise
Service switch to assist installer on start-up and
technician during service
Intelligent pump control with energy efficient pump
overrun
Built-in user programme
System temperature and parameter inquiry
Optional remote unit providing space temperature
sensing, space temperature adjustment, comfort/economy override switch and 3-hour comfort extension button with confirmation LED
Optional space sensor
Holiday mode with programmable 1 to 99 day
holiday period and dynamic countdown display
Automatic, DHWS only, Holiday or Standby
operation
Minimum boiler flow temperature
Control of one, or two boilers in sequence with
automatic lead boiler rotation
LED's indicate control output status
EN0R 8441
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
Supply voltage
: 230 V~, +10% -15%, 50 Hz
Sensor accuracy
Humidity rating
: 0 to 90%
rh (non-condensing)
144 x 153 x 109 mm (with wiring centre)
BASIC SYSTEMS
SPECIFICATIONS
Power Consumption
Relay ratings : Pumps and boilers:
Ambient temperature rating
: 8 W
3 A, 230 V~ @ 0.6 pf - 400,000 operations Mixing valve:
0.25 A, 230 V~ @ 0.4 pf - 1,000,000 operations
: Water sensors: 20°C to 90°C ±2 K
Outside sensor: -20°C to +20°C ±2 K Room sensor: 10°C to 25°C ±0.5 K
: 0 to 50°C
System 1
Boiler control for radiator systems
DHWS priority control when DHWS sensor connected. Optimisation and self-learning heating curve when
optional space sensor or remote unit connected.
One or two boiler control in sequence.
Storage/shipping temperature
Electromagnetic compatibility
Protection class : IP40 (with base fitted and when installed
Dimensions (w x h x d)
Panel cut-out (w x h)
Weight : 600 g
: -30°C to +70°C
: Emissions to EN55014
Susceptibility to EN50082-1
to EN60529)
: 144 x 96 x 105 mm (with standard base)
: 138 x 92 mm
System 2
Boiler and mixing valve control for radiator or underfloor heating systems
Versatile DHWS control when sensor connected.
Separate or combined operation available. Combined can be shifting priority or parallel operation. (see DHWS Operation on page 3)
Optimisation and self-learning heating curve when
optional space sensor or remote unit connected.
One or two boiler control in sequence. Continuous temperature boiler loop
EN0R 8441 2
System 3
DHWS OPERATION
Mixed flow control for radiator or underfloor heating systems.
DHWS separate when DHWS sensor connected. Optimisation and self-learning heating curve when
optional space sensor or remote unit connected.
System 4
Optimiser control for systems with existing controls and requiring optimisation only.
DHWS separate when DHWS sensor connected.
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
Key
P1 = Heating pump P2 = DHWS pump B1 = Boiler 1 B2 = Boiler 2 T1 = Space sensor/Remote Unit
Separate DHWS
The DHWS operation is completely independent and has no effect on the demand for heat from the boiler(s). This is useful when DHWS is being supplied from a separate heat source. The DHWS output is active when the DHWS temperature falls 5 K below the DHWS setpoint.
Combined DHWS
There are three variants for combined DHWS; DHWS priority, shifting priority and parallel operation. In all three cases a demand for DHWS occurs when the DHWS temperature falls 5 K below the DHWS setpoint.
1. DHWS Priority
In heating circuits with no mixing valve (and no mixed flow temperature sensor), the DHWS has priority over the heating.
T2 = Mixed flow water sensor T3 = Outside sensor T4 = DHWS sensor T5 = Boiler water sensor M = Motor/Actuator
2. DHWS Shifting Priority
In heating circuits with a mixing valve where the boiler temperature is less than 10 K above the DHWS setpoint the mixing valve will be closed giving DHWS priority. If there is extra heat available and the boiler temperature is more than 20 K above the DHWS setpoint, the mixing valve will be controlled at the calculated setpoint. The mixed water temperature setpoint is reduced when the boiler temperature lies between these two values.
3. DHWS Parallel
In heating circuits with a mixing valve the heating circuit will operate normally during a demand for DHWS.
EN0R 84413
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
within the range 40 to 70°C.
CONTROLLER FEATURES
If a fixed value of the heating curve ratio
within the range 4 to 40 using this
will act on T5 (boiler temperature) or T2
Output
Indicators
User
Comfort Setpoint
LCD Display
Installer Adjustments
The desired space Comfort temperature can be set within the range 12 to 28°C.
Override
System Selection
Cycle Rate Adjustment
The cycle rate adjustment allows the cycle rate as recommended by the boiler manufacturer to be set directly on the controller.
Programming/Operating Buttons
Status
User Adjustment
Installer Adjustment
Economy Setpoint
The desired Economy temperature can be set within the range 8 to 22°C. Economy OFF can be selected by turning the knob to the OFF position.
Domestic Hot Water Setpoint
The DHWS temperature can be set
Automatic Summer/Winter Changeover Temperature Setpoint
This can be set within the range 10 to 30°C. When the average daily outdoor temperature is above the automatic Summer/Winter setpoint the heating will be turned off.
Boiler/Mixed Flow Temperature High Limit
The flow temperature high limit can be set within the range 20 to 90°C and this
(mixed flow temperature) depending on the system selected.
Heating Curve Ratio Adjustment
is required then this value can be set potentiometer.
To determine the heating curve required refer to the graph displayed below.
Ratio
EN0R 8441 4
Outside Air Temperature oC (T3)
A boiler/mixed flow differential of between 6 and 16 K
A boiler minimum flow temperature setpoint of between 60
Boiler/Mixed Flow Differential
Boiler Minimum Flow Temperature
Boiler temperature Setpoint Adjustment
The Boiler Setpoint operates in a different manner depending on the position of System Selector Switch S8.
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
(Switch S8 in position A)
Boiler
Boiler/Flow Water Temperature oC
Temperature
Boiler/Mixed Flow Differential (adjustable)
Outside Temperature oC
Mixed Flow Temperature
can be set using the Boiler Setpoint knob. The boiler calculated setpoint will be the mixed flow
calculated setpoint plus the set differential.
System Selection
System selection is achieved in two manners:
Automatic System Selection System Selector Switches
System Selection Switches
(Switch S8 in position B)
Boiler Calculated Setpoint
Mixed Flow Calculated Setpoint
Boiler/Mixed Flow Differential (Fixed 10K)
Boiler/Flow Water Temperature oC
Boiler Flow Temperature
Outside Air Temperature oC
and 90°C can be set using the Boiler Setpoint knob. When the controller is in automatic mode the boiler low limit will be active from the beginning of the first comfort period to the end of the last comfort period each day.
Automatic System Selection
If a mixed flow water sensor (T2) is connected, the
controller assumes that a mixing valve is present.
If a Remote Unit and/or a Space Sensor (T1) is present
the controller activates the space temperature compensation, the self-adaptive heating curve and the optimum Start/Stop.
If a DHWS sensor (T4) is present then combined or
separate temperature control of the DHWS will be available. If no DHWS sensor (T4) is present only time control is available on the DHWS output.
Automatic system detection takes place during the first minute after powering the controller.
Switch Description Position A Position B S1 Actuator speed 1 minute 4 minute S2 DHWS type combined separate S3 DHWS programme programmed continuous S4 DHWS operation priority operation parallel S5 Boilers one two S6 Type of heating radiator underfloor S7 Adaptive heat curve yes no S8 Boiler setpoint boiler/mixed flow
boiler minimum flow
diff.
EN0R 84415
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
Outside
Remote
Mixed
Space
DHWS
Boiler
Boiler
Boiler
Mixing
Heating
DIMENSIONS AND MOUNTING
Important
Panel Mounting
Standard Base
AQ2000 Panel
Standard Base Mounting
Cover
Standard Base Mounting
Surface Mounting
The Aquatrol 2000 controller can be surface mounted in either a control panel or directly on the wall.
Panel Mounting
The controller can be panel mounted in a control panel door and features integral panel mounting clips for ease of installation.
Electrcal Connections for a Typical Aquaplan System
Line
Voltage
Low
Voltage
Tamperproofing
The controller can be made tamperproof, if required, by inserting a wire link through the hole in the front clear cover and the front housing at the top centre of the front panel and twisting or crimping to fix the front panel permanently shut, thus preventing unauthorised adjustment.
Wall Mounting using Wiring Centre (Optional)
For wall mounting the optional Wiring Centre K42007745­005 can be used for protection and termination of electrical conduits, MICC cable or Pirelli FP200 cable with suitable adaptors.
1. The installer must be a trained engineer
2. Disconnect the power supply before beginning installation
No. 2
Pump
EN0R 8441 6
valve
No. 1
Flow
Air
Unit
CONTROLLER ORDERING SPECIFICATION
Ordering specification: W6060C1067 with English literature
Specifications
Application
Application
Specifications
Wire dimensions
Specifications
Specifications
OTHER SYSTEM COMPONENTS
W6060C1083 with French literature W6060C1091 with Italian literature
(to be ordered separately)
Outside Temperature Sensor T7043E
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
The Outside Temperature Sensor consists of a thermistor element housed in a tough plastic case. It is mounted outside the building providing a temperature input signal to the controller.
Ordering Specification:
T7043E1008
Flow Temperature Sensor T7044C
The T7044C Strap-on Flow Water Temperature Sensor consists of a thermistor sensing element housed in a tough plastic case. It is strapped to the flow water pipe providing a temperature input signal to the controller.
Ordering Specification:
T7044C1002
Flow Temperature Sensor T7043F
Application
The T7043F Immersion Flow Water Temperature Sensor consists of a thermistor sensing element housed in an immersion pocket. It should be mounted on a bend on the flow water pipe providing a temperature input signal to the controller
Sensing range : -30 to +40°C Sensor : NTS type 10 kΩ @
25°C
Enclosure : Plastic with integral
Pg11 fitting
Dimensions : 72 ∅ x 45 mm
Sensing range : 0 to 115°C Sensor : NTS type 10 kΩ @
25°C
Enclosure : Plastic with integral
Pg11 fitting
Dimensions : 72 ∅ x 48 mm
Sensing range : 0 to 115°C Sensor : NTS type 10 kΩ @
25°C
Enclosure : Plastic with integral
Pg11 fitting
Housing dimensions
Well
: 72 ∅ x 45 mm
: ½" BSPT x 100
mm
Insertion Thermostat T7106A
Application
The T7106A Insertion Flow Water Temperature Sensor consists of a thermistor sensing element encapsulated in a metal casing. It can be inserted in a well to provide a temperature input signal to the controller.
Ordering Specification:
T7106A1001
Sensing range : 0 to +105°C Maximum
ambient Sensor : NTS type 10 k @
Dimensions : 6 Ø x 60 mm
Wire rating : -30 to +105° Insertion well : 6 mm Ø x 60 mm
: 105°C
25°C
: 4 mm dia. x 1.5 m
EN0R 84417
AQ2000 OPTIMISER/COMPENSATOR CONTROLLER
Specifications
RELATED LITERATURE
Ordering Specification:
T8102B1001 with English literature
Remote Unit T8102B
Application
The Remote Unit provides a space temperature sensor input signal to the AQ2000 for space temperature compensation and to enable the optimisation and adaptive ratio to function. Remote adjustment of the setpoint is also possible and an override switch gives the possibility of selecting permanent comfort or economy settings. A "party" button allows a three hour comfort extension to be selected.
T8102B1050 with French literature T8102B1068 with Italian literature
Sensor : NTC type 10 kO @
Housing : White plastic Weight : 70 g Dimensions : 70 x 75 x 31 mm
Setpoint adjustment
Space Sensor T8102B
Application
The Space Sensor provides a space temperature sensor input signal to AQ2000 for space temperature compensation and to enable the optimisation and adaptive ratio to function. The Space Sensor can be used in conjunction with the Remote Unit for added flexibility.
Specifications
Sensor : NTS type 10 k @
Housing : White Plastic Weight : 70g Dimensions : 70 x 75 x 31 mm
25°C
(w x h x d)
: ± 3 K
25°C
(w x h x d)
Ordering Specification:
Wiring Centre K42007745-005
Application
The Wiring Centre is an essential component when mounting the controller on a wall. It provides a number of conduit entries through the bottom, back and sides. In addition, it provides extra terminals to link multiple incoming cables such as line, neutral and earth.
Ordering Specification:
K42007745-005
Application Manual UK1C 0002 in English Installation and user Guide 42008356-001 in English
42008356-002 in French 42008356-003 in Italian (check availability)
Specifications
Housing : White plastic Cable entries : 17 x 19 mm
Dimensions : 144 x 154 x 72
conduit entries (9 bottom, 3 right side, 1 left side, 4 back)
mm (w x h x d)
Honeywell Control Systems Limited Helping You Control Your World Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0R 8441
Loading...