Mixing Valves

AMX300 Series DirectConnect™ Thermostatic Mixing Valve and Kits

U P C

®

Application: Domestic Hot Water

Mixed Water Supply Temperature Range: 100 F to 145 F (38 C to 63 C)

Operating Temperature Range:

33 F to 80 F (cold water inlet); 100 F to 212 F (hot water inlet) (0.5 C to 27 C (cold water inlet)); (38 C to 100 C) (hot water inlet))

AMX300 kits reduce installation time to an minimum while still providing Honeywell's industry leading mixing valve technology

Excellent temperature stability and control

Effectively minimizes scalding risk to building occupants

Kit includes mixing valve, cold water tee fitting and flexible stainless steel connector

Mixing valve and cold water tee both connect directly to water heater; flexible stainless steel connector joins the cold water tee directly to the cold inlet port of the mixing valve

Fits virtually all water heaters up to 1 in. (all necessary adapters included)

Increased user comfort for more available hot water.

Constant water temperature under different operating conditions

Proportional valve (control of hot and cold water)

Flow reduction in seconds if cold water supply is interrupted

Temperature adjustable with easy “Push-Twist-Release” locking hand wheel design

Recirculation port option for fast delivery of heated water to furthest fixtures

Alternate hot port for bypass of hot water directly from tank to nonmixed temperature applications (dishwashers, clothes washers, etc.)

Brass/stainless construction

Teflon coated wear surfaces for extended service

IAPMO listed (cUPCus)

Complies with ASSE 1017 when used with check valve on supply (not included)

Lead free part numbers end in LF

Minimum Flow Rate: 0.25 gpm; Recirculation Port: 1/2 in. NPT; Alternate Hot Port: 1/2 in. NPT (0.95 lpm; Recirculation Port: 1/2 in. NPT; Alternate Hot Port: 1/2 in. NPT)

Maximum Working Pressure: 150 psi

 

 

 

 

 

 

 

 

Pipe Size

 

Capacity

 

 

 

 

 

 

 

 

 

Product Number

(inch)

DN

Connection Type

(Cv)

Description

Comments

 

 

 

 

 

 

 

AMX300/U

3/4 in.

DN20

Cold Inlet - 7/8 in.-14 SAE J513,

2.1 Cv

3/4 in. mixing valve (Replacement valve tor

 

 

 

45 degree flare fitting; Mixed Outlet -

 

AMX300T and AMX302T DirectConnect

 

 

 

 

Male NPT; Hot Inlet - Female NPT

 

mixing valve kits.)

 

 

 

 

 

 

 

 

AMX300LF/U

3/4 in.

DN20

Cold Inlet - 7/8 in.-14 SAE J513,

2.1 Cv

3/4 in. mixing valve (Replacement valve tor

Low lead Content

 

 

 

45 degree flare fitting; Mixed Outlet -

 

AMX300T and AMX302T DirectConnect

<.25% by weighted

 

 

 

Male NPT; Hot Inlet - Female NPT

 

mixing valve kits.)

average

 

 

 

 

 

 

 

AMX300T/U

3/4 in.

DN15

Mixed Outlet - Male NPT; Hot Inlet -

2.1 Cv

DirectConnect water heater kit with 3/4 in.

 

 

 

Female NPT

 

mixing valve, 3/4 in. cold water tee, and 8-in.

 

 

 

 

 

 

SS flex connector

 

 

 

 

 

 

 

 

AMX300TLF/U

3/4 in.

DN15

Mixed Outlet - Male NPT; Hot Inlet -

2.3 Cv

DirectConnect water heater kit with 3/4 in.

Low lead Content

 

 

 

Female NPT

 

mixing valve, 3/4 in. cold water tee, and 8-in.

<.25% by weighted

 

 

 

 

 

SS flex connector

average

 

 

 

 

 

 

 

AMX302T/U

3/4 in.

DN25

Mixed Outlet - Male NPT; Hot Inlet -

2.1 Cv

DirectConnect water heater kit with 3/4-in.

 

 

 

Female NPT

 

mixing valve, 3/4-in. cold water tee, and 11-in.

 

 

 

 

 

 

SS flex connector

 

 

 

 

 

 

 

 

AMX302TLF/U

3/4 in.

DN25

Mixed Outlet - Male NPT; Hot Inlet -

2.3 Cv

DirectConnect water heater kit with 3/4-in.

Low lead Content

 

 

 

Female NPT

 

mixing valve, 3/4-in. cold water tee, and 11-in.

<.25% by weighted

 

 

 

 

 

SS flex connector

average

 

 

 

 

 

 

 

Pressure Drop Chart

 

25.0

<![if ! IE]>

<![endif]>(PSI)

20.0

15.0

<![if ! IE]>

<![endif]>DROP

10.0

<![if ! IE]>

<![endif]>PRESSURE

5.0

 

 

0

0

PRESSURE DROP VS. FLOW RATE

 

 

 

 

 

 

F

 

 

100

F

 

 

120

 

 

 

AMX300T

@

 

AMX300T

@

 

 

 

 

 

 

 

 

 

 

3.0 6.0 9.0 12.0

FLOW RATE (US GPM)

M34701

 