Mixing Valves
0 6.0 9.0 12.0
0
5.0
10.0
15.0
20.0
25.0
3.0
FLOW RATE (US GPM)
PRESSURE DROP (PSI)
AMX300T @ 100 F
AMX300T @ 120 F
M34701
PRESSURE DROP VS. FLOW RATE
AMX300 Series DirectConnect™ Thermostatic Mixing Valve and Kits
AMX300 kits reduce installation time to an minimum while still
providing Honeywell's industry leading mixing valve technology
• Excellent temperature stability and control
• Effectively minimizes scalding risk to building occupants
• Kit includes mixing valve, cold water tee fitting and flexible stainless
steel connector
• Mixing valve and cold water tee both connect directly to water
heater; flexible stainless steel connector joins the cold water tee
directly to the cold inlet port of the mixing valve
• Fits virtually all water heaters up to 1 in. (all necessary adapters included)
• Increased user comfort for more available hot water.
• Constant water temperature under different operating conditions
• Proportional valve (control of hot and cold water)
• Flow reduction in seconds if cold water supply is interrupted
• Temperature adjustable with easy “Push-Twist-Release” locking
hand wheel design
• Recirculation port option for fast delivery of heated water to
furthest fixtures
• Alternate hot port for bypass of hot water directly from tank to nonmixed temperature applications (dishwashers, clothes washers, etc.)
• Brass/stainless construction
• Teflon coated wear surfaces for extended service
• IAPMO listed (cUPCus)
• Complies with ASSE 1017 when used with check valve on supply
(not included)
• Lead free part numbers end in LF
Application: Domestic Hot Water
Mixed Water Supply Temperature Range: 100 F to 145 F (38 C to 63 C)
Operating Temperature Range:
33 F to 80 F (cold water inlet); 100 F to 212 F (hot water inlet)
(0.5 C to 27 C (cold water inlet)); (38 C to 100 C) (hot water inlet))
Minimum Flow Rate: 0.25 gpm; Recirculation Port: 1/2 in. NPT;
Alternate Hot Port: 1/2 in. NPT (0.95 lpm; Recirculation Port: 1/2 in.
NPT; Alternate Hot Port: 1/2 in. NPT)
Maximum Working Pressure: 150 psi
Pipe Size
Product Number
AMX300/U 3/4 in. DN20 Cold Inlet - 7/8 in.-14 SAE J513,
AMX300LF/U 3/4 in. DN20 Cold Inlet - 7/8 in.-14 SAE J513,
AMX300T/U 3/4 in. DN15 Mixed Outlet - Male NPT; Hot Inlet -
AMX300TLF/U 3/4 in. DN15 Mixed Outlet - Male NPT; Hot Inlet -
AMX302T/U 3/4 in. DN25 Mixed Outlet - Male NPT; Hot Inlet -
AMX302TLF/U 3/4 in. DN25 Mixed Outlet - Male NPT; Hot Inlet -
Connection Type
45 degree flare fitting; Mixed Outlet Male NPT; Hot Inlet - Female NPT
45 degree flare fitting; Mixed Outlet Male NPT; Hot Inlet - Female NPT
Female NPT
Female NPT
Female NPT
Female NPT
Pressure Drop Chart
Capacity
Description Comments(inch) DN (Cv)
2.1 Cv 3/4 in. mixing valve (Replacement valve tor
2.1 Cv 3/4 in. mixing valve (Replacement valve tor
2.1 Cv DirectConnect water heater kit with 3/4 in.
2.3 Cv DirectConnect water heater kit with 3/4 in.
2.1 Cv DirectConnect water heater kit with 3/4-in.
2.3 Cv DirectConnect water heater kit with 3/4-in.
AMX300T and AMX302T DirectConnect
mixing valve kits.)
AMX300T and AMX302T DirectConnect
mixing valve kits.)
mixing valve, 3/4 in. cold water tee, and 8-in.
SS flex connector
mixing valve, 3/4 in. cold water tee, and 8-in.
SS flex connector
mixing valve, 3/4-in. cold water tee, and 11-in.
SS flex connector
mixing valve, 3/4-in. cold water tee, and 11-in.
SS flex connector
—
Low lead Content
<.25% by weighted
average
—
Low lead Content
<.25% by weighted
average
—
Low lead Content
<.25% by weighted
average
254 customer.honeywell.com 70-6910