Honeywell AC-140-7 User Manual

February 2008
P/N 32-0228
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
FOR
FP-4 FREEZE PROTECTION KIT
P/N 83-0763
FOR TURBO-COOL AFTERCOOLERS
MODELS
(230V-3PH-60Hz & 460V-3PH-60Hz)
BEFORE STARTING INSTALLATION OR MAINTENANCE PROCEDURES, TURN OFF ELECTRICAL POWER AND COMPLETELY DEPRESSURIZE THE AFTERCOOLER. FAILURE TO HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE UNIT.
NEVER REMOVE, REPAIR, OR REPLACE ANY ITEM ON THE AFTERCOOLER WHILE IT IS PRESSURIZED.
WHEN INSTALLING THIS KIT, ALWAYS COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES.
AC-140-7 thru AC-220-7
WARNING
REV . B
SECTION 1 INTRODUCTION
1.1 DESCRIPTION OF OPERATION
The FP-4 freeze protection kit is designed to prevent aftercooler freeze up when the ambient temperature is near or below freezing, 32oF (0oC).
The FP-4 has a two stage solid state temperature controller. The controller is mounted inside a Nema 4 enclosure. The controller is used to energize a control relay which is rated to handle the load of the aftercooler fan at the various voltages.
The linear platinum temperature sensor and thermowell mount into the piping between the outlet manifold of the aftercooler and the separator. When the temperature of the com­pressed air system at the aftercooler outlet falls to 35OF, the controller will automatically turn off of the fan. The controller is set for a 10oF dead band to prevent rapid cycling (fan will turn off at 35OF and on at 45oF).
A 12 foot heat tape and 30 feet of insulation wrap are provided to wrap around the separator. The heat tape is equipped with its own internal temperature control. The heat tape and insula­tion will provide additional freeze up protection.
1.2 THIS KIT INCLUDES:
Control box
1. 12' long heat tape, w/ thermostat
2. 30' long roll of insulation wrap
3. Copper 1/2" NPT thermowell w/clip
4. Cord grip connector
5. Linear platinum sensor
6. 2' of 3/8" flexible conduit
7. Three (3) seal fittings for connectors
8. 3/8" conduit straight connector
9. 3/8" 90 degree elbow connector
10. 1" x 1/2" NPT bushing
11. Four (4) #12-14 x 1" self tapping screws
12. Heat Condictive Compound
13.
FIGURE 1-A ITEMS INCLUDED WITH THIS KIT
PAGE 1
SECTION 2 INSTALLATION
2.1 MOUNTING THE CONTROL BOX
The control box should be mounted near the outlet manifold of the aftercooler. Make sure that the control box is close enough so that all components can reach the box when in­stalled.
Drill the four pilot holes in the mounting surface using a 1/8" drill. Reference Figure 2­A for dimensions.
The control box will be mounted with the hinged side of the enclosure on the bottom.
Fasten the controller in place using the four (4) #12-14 x 1" long self-tapping screws supplied with the kit.
2.2 INSTALLING THE SENSOR AND THERMOWELL
A 1/2" NPT or larger connection in the system piping between the outlet of the aftercooler and the inlet of the separator is required for the thermowell and sensor.
Thread the thermowell and the 1" x 1/2" bushing (if required) into a connection between the aftercooler outlet and the separator.
FIGURE 2-A MOUNTING THE CONTROL BOX
FIGURE 2-B MOUNTING THE THERMOWELL
Place some heat conductive compound into the thermowell. Place the sensor into the thermowell and fasten it in place using the clip supplied with the thermowell. Reference Figure 2-B.
Install the cord grip connector into the control box as shown in Figure 2-B. Push the sensor cable through the connector. Wire the sensor cable to the controller circuit board terminals as shown in Figure 2-F. Tighten the grip nut on the connector.
2.3 INSTALLING THE HEAT TAPE AND INSULATION
Install the cord grip on the control box as shown in Figure 2-C.
Cut the plug end off the heat tape. Strip back the wires.
Push the wire end of the heat tape through the connector. Allow enough cord inside the box for wiring. Connect the heat tape to the proper terminals in the control box as shown in FIGURES 2-F. Tighten the grip nut on the connector.
FIGURE 2-C INSTALLING THE HEAT TAPE AND INSULATION
Run the heat tape to the separator. Wrap the heat tape around the separator as shown in Figure 2-C. Do not overlap the tape.
Wrap the insulation around the piping and heat tape as shown in Figure 2-C.
PAGE 2
SECTION 2 INSTALLATION
2.4 INSTALLING THE CONDUIT
Install the straight conduit connector on the control box. Reference Figure 2-D.
The supplied conduit will be used to run between the aftercooler and the control box. Connect the conduit to the straight connector.
Install the 90 degree elbow connector on the aftercooler. Reference Figure 2-D.
FIGURE 2-D INSTALLING THE CONDUIT
2.5 INSTALLING THE TRANSFORMER JUMPERS
WARNING
BEFORE STARTING THIS PROCEDURE, TURN OFF ELECTRICAL POWER. FAILURE TO HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE UNIT.
This kit was designed to operate at 230V-3PH-60Hz or 460V-3PH-60Hz. Two jumpers were shipped inside the control box. They must be installed on the transformer before connecting the power to the control box. Install the jumper(s) as shown in Figure 2-E for the desired voltage.
CAUTION
It is important that this procedure be properly completed before continuing with installation. This kit will not operate without the jumpers. Damage to the control box will occur if the jumpers are improperly installed.
FIGURE 2-E INSTALLING THE TRANSFORMER JUMPERS
2.6 ELECTRICAL CONNECTIONS
WARNING
BEFORE STARTING INSTALLATION PROCEDURES OR ATTEMPTING TO MAKE ANY WIRING CHANGES, TURN OFF ELECTRICAL POWER. FAILURE TO HEED THIS WARNING MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR DAMAGE TO THE UNIT.
WHEN INSTALLING THIS KIT ALWAYS COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES.
A 7/8" hole in the top right side of the control box is provided for incoming power conduit. The hole can be enlarged if necessary.
The control box is designed for 230V-3PH-60Hz or 460V­3PH-60Hz operation. The transformer jumpers must be installed as outlined in Section 2.5 for the desired voltage.
Make the necessary wiring runs and connections for the main power supply.
Remove the junction box cover on the aftercooler for access to the junction box. Make the necessary wiring runs through the conduit from the aftercooler to the control box. Fasten the
conduit to the connector on the aftercooler. Reference FIGURE 2-D.
Make the wire connections at the junction box on the aftercooler. Reference FIGURE 2-F. Fasten the junction box cover to the aftercooler.
Complete the wire connections inside the controller as shown in FIGURE 2-F.
Once all wiring connections have been properly made, the rotation of the fan should be checked. The fan must rotate in the proper direction for maximum performance. Reference the operator's manual supplied with the aftercooler for the correct rotation direction. Also, check the aftercooler for a rotation direction label.
To check the rotation, turn on the power supply to the aftercooler. If the fan does not rotate in the proper direction, any two of the power leads to the motor can be switched.
PAGE 3
SECTION 2 INSTALLATION
FIGURE 2-F CONTROL BOX COMPONENT LAYOUT and WIRING DIAGRAM
IMPORTANT
THE FAN MOTOR MUST ROTATE IN THE CORRECT DIRECTION. REFERENCE THE AFTERCOOLER OPERATOR'S MANUAL FOR PROPER ROATION DIRECTION. IF IT DOES NOT, THE ROTATION CAN BE CORRECTED BY SWITCHING TWO OF THE POWER LEADS TO THE MOTOR.
PAGE 4
SECTION 2 INSTALLATION
2.7 SETTING THE CONTROLLER
The controller was factory set for normal operation. The factory settings are as follows:
RELAY 1
O
SET POINT 35 DIFFERENTIAL 10 MODE COOLING
Turn on the main power to the FP-4 control. If the settings have been changed, set them to the factory
settings following the procedures below . The controller will retain the setting if the power is disconnected.
PROGRAMMING PROCEDURES
1. Press MENU key, then press RIGHT arrow key three times. Use the UP and DOWN arrow to select the SETPOINT. Press the RIGHT arrow to store the setpoint in memory.
2. Press the RIGHT arrow to set the DIFFERENTIAL. Use the UP and DOWN arrow to set the differential. Press the RIGHT arrow to store the differential in memory.
3. Press the RIGHT arrow key to set the HEATING / COOL- ING mode. Use the UP or DOWN arrow to select the desired mode. Press the RIGHT arrow to store the mode in memory.
F
O
F
FIGURE 2-G CONTROLLER DISPLAY
4. Press RIGHT arrow three times to exit the program mode.
SECTION 3 OPERATION
3.1 OPERATION
Once the kit is installed and set properly, just energize the controller and it will operate automatically.
The controller will turn off half of the aftercooler fan when the temperature of system air at the outlet of the aftercooler falls to 35OF. The fan will turn on when the system temperature rises to 45oF. Reference chart in Figure 3-A .
The heat tape is controlled by its own internal thermostat. Power is supplied to the heat tape as long as the control box is energized.
The temperature controller is equipped with a LCD display. During normal operation when the fan are operating, (temperature above set points) the sensor temperature and RELAYS 1 ON will be displayed on the controller.
NOTE: The cover on the control box must be opened to view the temperature controller display.
FIGURE 3-A OPERATION SEQUENCE
PAGE 5
SECTION 4 TROUBLESHOOTING
4.1 TROUBLESHOOTING PROCEDURES
PROBLEM POSSIBLE CAUSES
1. Aftercooler fan motor continues to operate, system temperature below 35
O
F.
Controller not set properly
Control relay faulty
Check the controller settings as outlined in Section 2.7. The controller may be set in the heat mode or the set points set too low. Set the controller to the recommended settings.
Check the control relay. Replace if faulty.
SOLUTIONS
2. Aftercooler fan motor not operating, system temperature above 45OF.
No power to the control box
No power to the controller
Controller not set properly
Controller failure
Sensor failure
Control relay faulty
Check main electrical power source.
Check the transformer. Make sure that the jumpers on the transformer are properly installed. Reference Section 2.5. Check the fuses on the transformer.
Check the controller settings as outlined in Section 2.7. The controller may be set in the heat mode or the set points set too high. Set the controller to the recommended settings.
Check the controller settings. If the controller is properly set, check the main power source.
Check the controller display for error codes. Section 4.2 outlines what the error codes indicate and the necessary steps.
If the sensor is faulty a "--" will be displayed for the temperature on the controller display. Refer to Section 4.2 for further details. If the sensor is faulty, it must be replaced.
Check the control power at the relay coil. Check the relay for proper operation. Replace if faulty.
4.2 CONTROLLER ERROR CODES
The controller display panel is used to display error codes in the event of problems with the controller. The four error codes are listed below.
-- -SENSOR FAILURE
The "--" displayed for the temperature indicates that there is a problem with the sensor. The sensor is open or shorted. All relays will be de-energized in the event of a sensor failure. If the sensor is damaged, it must be replaced.
EE-EEPROM FAILURE
The "EE" error code indicates that there is a problem with EEPROM. The values read back from the EEPROM are not the same as what was written into the EEPROM. This error cannot be field repaired. The controller must be replaced.
-60°F or 270°F (-51°C or 132°C) Blinking - TEMPERATURE OUT OF RANGE
The temperature display blinks when the sensed temperature is outside of the display range, below -60°F (-51°C) or above 270°F (132°C). The displayed value remains at the display limit and the controller continues to function unless an open or shorted condition is detected.
BLINKING RELAY STATUS
This occurs when the Relay Minimum Off Time is active. The (ñ ) blinks while the relay's minimum off time is active.
PAGE 6
SECTION 5 REPLACEMENT PARTS
5.1 REPLACEMENT PARTS
ITEM NO.
1 2 3 4 5 6 7 8
9 11 12 13 14 15 16 17 18 19 20 21 22 23
DESCRIPTION
12' LONG HEAT TAPE
30' ROLL OF INSULATION WRAP
1/2" NPT THERMOWELL w/CLIP
CORD GRIP CONNECTOR
SENSOR
3/8" FLEXIBLE CONDUIT
SEAL FITTING FOR CONNECTOR
3/8" CONDUIT STRAIGHT CONNECTOR
3/8" 90O ELBOW CONDUIT CONNECTOR
1" X 1/2" NPT BUSHING
#12-14 x 1" SELF TAPPING SCREW
TEMPERATURE CONTROLLER
MOTOR RELAY
TRANSFORMER
1 AMP FUSE
.6 AMP FUSE
GRAY TERMINAL
YELLOW TERMINAL
GREEN TERMINAL
END CLAMP TERMINAL
JUMPER FOR TERMINAL
JUMPER FOR TRANSFORMER
QTY
1 1 1 2 1
2 FT
3 1 1 1 4 1 1 1 1 2 2 2 2 2 2 2
PART NO.
26-8151 26-0712 29-0325 26-5618 26-7186 26-0875 26-0883 26-1068 26-1078 14-0402 28-1286 26-7185 26-0919 26-5637 26-5336 26-5638 26-0380 26-0382 26-0384 26-0388 26-0686 26-5663
PAGE 7
SECTION 6 WARRANTY
PER VAN AIR TERMS AND CONDITIONS OF SALE
PAGE 8
YOUR VAN AIR REPRESENTATIVE IS:
NAME:
COMPANY:
ADDRESS:
CITY: STATE: ZIP:
PHONE: FAX:
ATTACH BUSINESS CARD HERE
MAKING COMPRESSED AIR AND GAS WORK BETTER SINCE 1944.
2950 Mechanic Street
Lake City, PA 16423 USA
Phone: 800/840-9906
Service Fax: 814/774-0778
Order Entry Fax: 814/774-3482
www.vanairsystems.com
T775A/B/M Series 2000 Electronic Stand-Alone Controllers
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next generation of commercial and agricultural controls capable of remote sensing of temperature and providing switched and/or proportional outputs to various types of loads.
Five models have analog (modulating) outputs for actuator and motor control, and NEMA-4 weatherproof enclosures are available for wet environments.
IMPORTANT
Each T775A/B/M controller is an operating control, not a limit or safety control. If used in applications requiring safety or limit controls, a separate safety or limit control device is required.
Table 1. T775A/B/M Controller Configurations.
Controller
T775A2009 Standard T775A1001 1 None None 1 1 NEMA 1
T775B2016 Standard N/A 2 None 1 2 1 NEMA 4X
T775B2024 Standard T775C1009 T775D1008 4 None 2 2 1 NEMA 4X
T775B2032 Standard T775A1019 T775B1000 2 None 1 2 1 NEMA 1
T775B2040 Standard T775A1027 T775A1035
T775M2006 Modulating N/A None 2 N/A 2 1 NEMA 1
T775M2014 Modulating T775G1005 T775G1013
T775M2022 Modulating N/A 2 2 N/A
T775M2030 Modulating T775E1114 T775F1022
T775M2048 Modulating T775E1015 T775E1023
a
b
c
d
a
Model
All models include a digital input for use with the disable or setback option. The modulating (analog) outputs are 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable. Each floating output eliminates two SPDT relays. These models can support a high/low modulating limit at Sensor B for temperature control at Sensor A.
Description Replaces
T775B1018 T775B1026
T775B1042
T775G1021 T775G1039
T775F1055 T775F1089
T775E1056 T775E1064
T775E1098
SPDT Relay
Outputs
Analog
(Mod)
Outputs
4None 2 2 1NEMA 1
42N/A
42N/A
22N/A
Floating
b
Outputs
Sensor
c
Inputs
Nbr of
Sensors
Included Enclosure
d
2
d
2
d
2
d
2
1 NEMA 4X
1 NEMA 4X
1 NEMA 1
1 NEMA 1
E4436
62-0254-03
T775A/B/M SERIES 2000 CONTROLLER PRODUCT DESCRIPTION
Temperature Sensors
a
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all models except NEMA 4X models)
• T775-SENS-WR – Water resistant with 5 foot leads (included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031D2003 – 5 inch immersion sensor with wiring box (use immersion well; P/N 50001774-001)
• C7031J2009 – 12 foot duct averaging sensor with wiring box
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging sensor with flange
• C7130B1009 – Room mount sensor
a
See form 62-0265 – Temperature Sensors for the T775
Series 2000 Stand-alone Controller
Controller Dimensions
1 (25.5)
7/8 (22.5)
2 15/16 (74)
Accessories
• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304, 1/2 in. threading
TOP
4 1/16 (103.4)
4 1/16 (103.4)
7/8 (22.5)
1/64 (3.8)
2 11/16 (68.1)
4 13/32 (112.1)
LEFT RIGHT
8 5/32 (207.1)
7 23/32
(196)
7/8 (22.5)
1 (25.5)
3 31/32 (101)
FRONT VIEW
BOTTOM
1/2 (12.4)
Fig. 1. T775A/B/M dimensions in inches (mm).
2 13/16 (71.8)
7/8 (22.5)
M24279
62-0254–03 2
BEFORE INSTALLATION T775A/B/M SERIES 2000 CONTROLLER
BEFORE INSTALLATION
Review the “Specifications” on page 35 before installing the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for your appli­cation.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically performed in the order listed:
1. Mounting — see “Mounting” below.
2. Wiring — see “Wiring” on this page.
3. Checkout — see page 10.
4. Programming — see page 13.
5. Scheduling (optional) — see page 30.
Additional topics are:
• Temperature sensor calibration begins on page 10.
• Interface overview begins on page 11.
• Setup (for advanced options) begins on page 17.
• Summary menu begins on page 34.
• Troubleshooting begins on page 34.
MOUNTING
This section describes the mounting procedures for the controller and temperature sensor(s).
The controller may be mounted in any orientation. However, mounting in the orientation shown in Fig. 1 permits proper viewing of the LCD display and use of the keypad.
NEMA 4 Enclosure Mounting
For models with NEMA 4 enclosures, ensure that waterproof wire/conduit fittings are used at the knockouts for all wiring attachments. See Fig. 7 on page 6 for knockout locations.
IMPORTANT
For NEMA 4 enclosures, be sure to cover and seal all unused open knockouts.
Temperature Sensor(s) Mounting and Location
Temperature sensors may be located up to 1,000 feet (304 m) from the T775A/B/M controller. See Table 3 on page 10 for calibration guidelines.
The sensors may be mounted on a wall or panel for sensing space temperature, strapped to a pipe or inserted in an immersion well (see Fig. 2) for hot or cold water sensing, or taped to a standard cap or bulb holder for duct air sensing. To prevent moisture or condensation entering the sensor through the lead wire holes, mount the sensor with the lead wires exiting the bottom of the sensor.
NOTES:
1. The included sensor is not designed for very wet applications. For immersion applications, an immersion well is used.
2. Heat conductive compound must be used in immersion wells.
3. See “Temperature Sensors” on page 2 for this type of installation.
SENSOR
PLACED IN WELL
USE HEAT
CONDUCTIVE
COMPOUND
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller circuit board, or in areas where escaping gas or other explosive vapors are present.
IMPORTANT
The controller must be mounted in a position that allows clearance for wiring, servicing, and removal.
Use a screwdriver to pry out only the knockouts that you will use.
If mounting on DIN rail, be sure to remove the knockouts before mounting. See “Controller Wiring” on page 5 and Fig. 7 on page 6 for recommended knockout usage and locations. If you do not use an opened knockout be sure to cover it.
Mount the controller on any convenient interior location using the four mounting holes provided on the back of the enclosure using #6 or #8 screws (screws are not provided and must be obtained separately). Use controller dimensions in Fig. 1 on page 2 as a guide.
1/2 NPT
Fig. 2. Sensor inserted in immersion well.
NOTE: Multiple sensors may be parallel-series wired to
sense average temperatures in large spaces. See Fig. 3 on page 4.
IMMERSION WELL
M24470
WIRING
All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw terminal blocks located inside the device.
The remainder of this section describes the temperature sensor wiring and the T775A/B/M controller wiring.
3 62-0254–03
T775A/B/M SERIES 2000 CONTROLLER WIRING
Wiring Connections Access
To access the wiring connections, remove the two screws on the left side of the enclosure and gently swing open the top. Be careful to not stress the ribbon cables that connect the keypad and LCD display to the controller circuit board.
Temperature Sensor Wiring
CAUTION
Electrical Shock Hazard. Can short equipment circuitry.
Make sure that metal tube of sensor does not short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings from the sensor. Avoid the following to ensure proper operation:
• Do not route the temperature sensor wiring with building power wiring.
• Do not locate the temperature sensor wiring next to control contactors.
• Do not locate the temperature sensor wiring near electrical motors.
• Do not locate the temperature sensor wiring near welding equipment.
• Make sure good mechanical connections are made to both the sensor and the controller.
• Do not mount the sensor with the lead wire end pointing up in an area where condensation can occur.
If any of the above conditions cannot be avoided, use shielded cable.
NOTE: Each T775 controller must be wired to its own
sensor(s). However, a benefit of the T775 controller’s accuracy is that there is no more than a 2°F differential between any two T775 controllers.
Multiple Parallel Sensors
Multiple sensors can be parallel-series wired to sense average temperatures in large spaces. To maintain control accuracy, the number of sensors to be parallel­series wired must be of the n
2
power (for example, 4, 9,
16, etc.). See Fig. 3.
SENSORS
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
M24471
Fig. 3. Parallel-series wiring of sensors.
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded wire. For cable runs greater than 25 feet or where electrical interference may be a problem, shielded cable is recommended. See Fig. 4.
Refer to “Temperature Sensor Calibration” on page 10 for wire size selection where cable runs are longer than 25 feet.
T T
T T
SENSOR A AND SENSOR B TERMINAL WIRING IS POLARITY INSENSITIVE.
1
SENSOR A
1
SENSOR B
SHIELDED CABLE
Fig. 4. Sensor wiring — showing shielded cable connection to Sensor A.
SHIELDED CABLE
NOTE: SHIELDED CABLE MUST BE CONNECTED TO AN EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END.
SENSOR
NOTE: TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
M24472
62-0254–03 4
WIRING T775A/B/M SERIES 2000 CONTROLLER
Controller Wiring
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
CAUTION
Do not use 24 Vac power to power any external loads if 120 Vac or 240 Vac is used to power the T775A/B/M controller.
CAUTION
A separate earth ground is required.
Equipment damage can result if the earth ground is not connected. See Fig. 5 and Table 2 on page 6.
CAUTION
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling the unit.
See Fig. 7 on page 6 for locating the appropriate power input, remote sensors input, low voltage, contact closure, and load output terminals.
Access to the terminals can be gained through standard conduit knockouts (A through E in Fig. 7 on page 6) located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to the load relay output terminals and 120/240 Vac power wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power connection.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 14 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
Single wire – from 14 to 18 AWG solid or stranded
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one ter-
minal location, twist the wires together a minimum of three turns before inserting them to ensure proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and tighten­ing the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
1
2
IMPORTANT
Poor wiring practices can cause erratic readings from the sensor. To ensure proper operation, ensure that good mechanical connections are made to both the sensor and the controller.
IMPORTANT
When wiring the input power, only one source of power can be applied to the T775A/B/M control­ler (24 Vac or 120 Vac or 240 Vac).
1
W
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
EARTH GROUND TERMINAL MUST BE CONNECTED TO CONDUIT CLAMP LOCALLY.
C
+
2
M24296
Fig. 5. Earth Ground.
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
2. TWIST WIRES
TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
1/2 (13)
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M24473
Fig. 6. Attaching two or more wires at terminal blocks.
5 62-0254–03
T775A/B/M SERIES 2000 CONTROLLER WIRING APPLICATIONS (EXAMPLES)
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and are described in Table 2.
See Fig. 8 – Fig. 20 beginning on page 6 for typical T775A/B/M wiring applications.
KNOCKOUT A
NO
C
NC
KNOCKOUT E
T T
T T
NC
C
NO
120
NO
C
NC
MOD 1
2
MOD 2
DIGITAL
INPUT
KNOCKOUT B
POWER
3
24 VAC
OUTPUT RELAY 4
OUTPUT RELAY 1
KNOCKOUT C
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE POLARITY INSENSITIVE.
2
FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT, USE SIGNAL (+) & COMMON (-). FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
3
SOURCE (24, 120, OR 240 VAC).
B
R
+
W
B
R
+
W
– +
C
+
NC
C
NO
Fig. 7. T775A/B/M terminal and feature locations.
NOTE: Refer to Table 1 on page 1 for the specific con-
figuration of sensors and outputs supported by the model you are installing.
NOTE: For NEMA 4 enclosures, use waterproof fittings
for wiring/conduit connections at knockouts.
COM
240
SENSOR A
1
SENSOR B
OUTPUT RELAY 3
POWER 120/240 VAC
OUTPUT RELAY 2
KNOCKOUT D
M24474
Table 2. Description of Wiring
Terminal Connections. (Continued)
Connection Terminal Label Description
Input
DI + - Digital Input (dry
contact)
24 Vac Power
24V + + 24 Vac Hot
Common C 24 Vac Common
Ground
Earth Ground
b
120 or 240 Vac Power
120 Vac 120 120 Vac Power
Common COM Common
240 Vac 240 240 Vac Power
a
For Series 90 connections, you must insert a 340 Ohm resistor across terminals R and W. See Fig. 17 on page 8. The resistor is included with the controller.
b
A separate earth ground is required for all installations regardless of the power source (24, 120, or 240 Vac). See Fig. 5 on page 5.
WIRING APPLICATIONS (EXAMPLES)
Fig. 8 – 20 illustrate typical controller wiring for various applications.
SENSOR A
T T
L1
(HOT)
L2
24 VAC
LOAD 1
C
+
Table 2. Description of Wiring
Terminal Connections.
Connection Terminal Label Description
Sensors
Sensor A
Sensor B
T T
Outputs
Temperature Sensor; polarity insensitive
Fig. 8. Wiring for two-stage control – 24 Vac input and
Relay 1 Relay 2 Relay 3 Relay 4
Mod 1
Mod 2
62-0254–03 6
NO COM NC
+ - (Vdc or mA) W R B (Series 90)
120-240 Vac Relay Output
Modulating Output
a
LOAD 2
NO
COM
24 Vac load.
NO
C
NC
NO
C
NC
COM
NO
M24475A
Loading...
+ 30 hidden pages