If this control is replacing a control that contains
mercury in a sealed tube, do n
control in the trash
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.
ot
place your old
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
24 Vac single or multistage heat pump or conventional
heating and cooling systems. Select models have terminals for LEDs and remote temperature sensors. Refer to
Table 1. All Q7300 Thermostat Subbases require a
common wire to the supply power.
Maximum Stages
a
Location
Subbase without Remote-Mounted
Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Subbase with Remote-Mounted
Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used
to sense and control room temperature, then install the
thermostat in an area that is accessible for setting and
adjusting the temperature and settings.
If both the subbase and remote-mounted temperature
sensor(s) are used to sense and control room temperature, then install the subbase about 5 ft above the floor in
an area with good air circulation.
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
NO
NO
Fig. 1. Typical location of thermostat or remote-mounted sensor.
Install the remote-mounted sensor(s) about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.
Do not mount the sensor(s) where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
If more than one remote sensor are required, they must be
arranged in a temperature averaging network consisting of
two, three, four, five or nine sensors. See Fig. 2 through 6.
IMPORTANT
To avoid electrical interference, which can cause
erratic performance, keep wiring runs as short as
possible and do not run thermostat wires
adjacent to the line voltage electrical distribution
systems. Use shielded cable (Belden type 8762
or equivalent for 2-wire and Belden type 8772 or
equivalent for 3-wire). The cable shield must be
grounded only at the controlled equipment case.
SUBBASE
TT
YES
5 FEET
(1.5 METERS)
Fig. 3. Two T7047C Sensors and one T7047G Sensor
providing temperature averaging network for
NO
M4823A
SUBBASE
TT
T7047C
TT
T7047G
T7047C
TT
TT
M4839
T7300/Q7300 Thermostat/Subbase.
SUBBASE
TT
T7047C
TT
T7047C
TT
T
T
Fig. 2. Two T7047G Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
62-0135
T7047GT7047G
T
T
M4838
T7047C
TT
Fig. 4. Four T7047C Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
T7047C
TT
M4840
2
T7047G
T
T7047G
SUBBASE
TT
T7047G
T
T
T7047G
Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
WALL
WIRES
THROUGH WALL
T
T7047G
WALL
ANCHORS
T
T
(2)
T
T7047C
T7047C
T7047C
T
T
SUBBASE
TT
T7047C
TT
T7047C
TT
T7047C
TT
M4841
TT
TT
TT
M4842
T
Fig. 5. Five T7047G Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
T7047C
TT
T7047C
TT
T7047C
TT
Fig. 6. Nine T7047C Sensors providing
temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
Mounting Subbase
The subbase mounts horizontally on the wall or a 2 in. x 4 in.
wiring box. Position the subbase horizontally on the wall or
on a 2 in. x 4 in. wiring box.
쐃 Position and level the subbase or wallplate (for
appearance only). The thermostat functions properly
even when not level.
쐇 Use a pencil to mark the mounting holes. See Fig. 7.
쐋 Remove the subbase or wallplate from the wall and
drill two 3/16 inch holes in the wall (if drywall) as
marked. For firmer material such as plaster or wood,
drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
쐏 Position the subbase over the holes, pulling wires
through the wiring opening.
쐄 Loosely insert the mounting screws into the holes.
쐂 Tighten mounting screws.
MOUNTING
HOLES
MOUNTING
SCREWS
LEDS
M10237
Fig. 7. Mounting the subbase.
WIRING SUBBASE
All wiring must comply with local electrical codes and
ordinances. Follow equipment manufacturer wiring
instructions when available. Refer to Fig. 9 through 17 for
typical hookups. A letter code is located near each
terminal for identification.
CAUTION
Disconnect power before wiring to prevent
electrical shock or equipment damage.
쐃 Loosen the terminal screws on the subbase and
connect the system wires. See Fig. 8.
IMPORTANT
Use 18-gauge, solid-conductor color-coded
thermostat cable for proper wiring. If using 18gauge stranded wire, no more than ten wires can
be used. Do not use larger than 18-gauge wire.
쐇 Securely tighten each terminal screw.
쐋 Push excess wire back into the hole.
쐏 Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
FOR STRAIGHT
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
Fig. 8. Proper wiring technique.
INSERTION STRIP
5/16 IN. (8 MM).
M4826
3
62-0135
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.