Honda Power Equipment GA3.6HA, GA3.6H, GA-3.6HZ User Manual

OPERATION AND PARTS MANUAL
MODEL GA3.6H Series
GA-3.6HZ
GA3.6H
Portable Generators
(HONDA GASOLINE ENGINE)
Revision #0 (11/01/05)
THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.
PAGE 2 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
NOTE PAGE
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 3
TABLE OF CONTENTS
Multiquip GA-3.6H Series AC Portable Generators
Proposition 65 Warning ............................................. 2
Table Of Contents ..................................................... 4
Parts Ordering Procedures ....................................... 5
Safety Message Alert Symbols .............................. 6-7
Rules for Safe Operation ..................................... 8-10
Specifications (Generator/Engine) .......................... 11
Dimensions ............................................................. 12
General Information ................................................ 13
Load Application ..................................................... 14
Controls and Indicators ...................................... 15-17
Generator Refueling ............................................... 18
Installation .......................................................... 19-20
Pre-Inspection ......................................................... 21
Pre-Inspection (Engine) .......................................... 22
Initial Start-up (Engine) ........................................... 23
Initial Start-up/Generator Operation ....................... 24
Generator Operation/Shutdown.............................. 25
Preparation For Long Term Storage ....................... 26
Maintenance (Engine)........................................ 27-28
Wiring Diagram (GA-3HZ Generator) ..................... 29
Wiring Diagram (GA-3H Generator) ....................... 30
Wiring Diagram (GA-3HA Generator) ..................... 31
Troubleshooting (Engine) ...................................32-33
Troubleshooting (Generator) .................................. 34
Explanation of Code In Remarks Column ............... 36
Suggested Spare Parts ........................................... 37
HONDA GX240K1EDN2 ENGINE
Air Cleaner Assembly ......................................... 54-55
Camshaft Assembly ........................................... 56-57
Carburetor Assembly ......................................... 58-59
Control Assembly ............................................... 60-61
Crankcase Cover Assembly ............................... 62-63
Crankshaft Assembly ......................................... 64-65
Cylinder Barrel Assembly ................................... 66-67
Cylinder Head Assembly .................................... 68-69
Fan Cover Assembly .......................................... 70-71
Flywheel Assembly ............................................ 72-73
Ignition Coil Assembly ........................................ 74-75
Piston Assembly ................................................. 76-77
Recoil Starter Assembly..................................... 78-79
Solenoid Assembly ............................................. 80-81
Label Assembly .................................................. 82-83
Terms and Conditions Of Sale — Parts .................. 84
NOTE
Specification and part number are subject to change without notice.
Component DrawingsComponent Drawings
Component Drawings
Component DrawingsComponent Drawings
Nameplate and Decals....................................... 38-39
Generator Assembly .......................................... 40-41
Control Box Assembly (GA-3HZ) .......................42-43
Control Box Assembly (GA-3H) ......................... 44-45
Control Box Assembly (GA-3HA) ....................... 46-47
Muffler Assembly .............................................. 48-49
Pipe Frame Assembly (GA-3HZ) ....................... 50-51
Pipe Frame Assembly (GA-3H/GA-3.6HA) ........ 52-53
PAGE 4 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
Effective: June 1st, 2005
Ordering parts has never been easier!
PARTS ORDERING PROCEDURES
Choose from three easy options:
Best Deal!
Order via Internet (Dealers Only):
Order parts on-line using Multiquip’s SmartEquip website!
View Parts Diagrams
Order Parts
Print Specification Information
Goto www.multiquip.com and click on
Order Par ts
to log in and save!
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax.
Domestic (US) Customers dial:
1-800-6-PARTS-7 (800-672-7877)
Order via Phone:
Non-Dealer Customers:
Contact your local Multiquip Dealer for parts or call 800-427-1244 for help in locating a dealer near you.
If you have an MQ Account, to obtain a Username and Password, E-mail us at:
parts@multiquip.com.
To obtain an MQ Account, contact your District Sales Manager for more information.
internet
Use the on
Standard orders
complete part numbers.*
Fax
your order in and qualify for a 3% Discount
on
Standard orders
complete part numbers.*
Domestic (US) Dealers Call:
1-800-427-1244
and qualify for a 5% Discount
for all orders which include
for all orders which include
International Customers
their local Multiquip Representatives for Parts Ordering information.
Note: Discounts Are Subject To Change
Note: Discounts Are Subject To Change
should contact
When ordering parts, please supply:
❒❒
Dealer Account Number
❒❒
❒❒
Dealer Name and Address
❒❒
❒❒
Shipping Address (if different than billing address)
❒❒
❒❒
Return Fax Number
❒❒ ❒❒
Applicable Model Number
❒❒
❒❒
Quantity, Part Number and Description of Each Part
❒❒
NOTE
www.multiquip.com
Unless otherwise indicated by customer, all orders are treated as within 24 hours. We will make every effort to ship if received prior to 2PM PST.
WE ACCEPT ALL MAJOR CREDIT CARDS!
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 5
❒❒
Specify Preferred Method of Shipment:
❒❒
Fed Ex/UPS
Next Day
Stock Orders
DHL Priority One Ground
Second/Third Day
Tr u c k
Standard Orders
Air Shipments
must be noted on fax or web order form.
the same day the order is received,
and will ship
GA-3.6H Series — SAFETY MESSAGE ALERT SYMBOLS
FOR YOUR SAFETY AND THE SAFETY OF OTHERS!
Safety precautions should be followed at all times when operating this equipment. Failure to read and understand the Safety Messages and Operating Instructions could result in injury to yourself and others.
This Owner's Manual has been developed to provide complete instructions for the safe and efficient
NOTE
Before using these generators, ensure that the operating individual has read and understands all instructions in this manual.
SAFETY MESSAGE ALERT SYMBOLS
The three (3) Safety Messages shown below will inform you about potential hazards that could injure you or others. The Safety Messages specifically address the level of exposure to the operator, and are preceded by one of three words: DANGER,
operation of the MQ Model GA-3.6
Series
Portable Generators
the engine manufacturers instructions for data relative to its safe operation.
. Refer to
HAZARD SYMBOLS
Potential hazards associated with the operation of the
GA-3.6H Series Portable Generators
Hazard Symbols which appear throughout this manual, and will be referenced in conjunction with Safety Message Alert Symbols.
Engine exhaust gases contain poisonous carbon monoxide. This gas is colorless and odorless, and can cause death if inhaled. NEVER operate this equipment in a confined area or enclosed structure that does not provide ample free flow air.
Gasoline is extremely flammable, and its vapors can cause an explosion if ignited. DO NOT start the engine near spilled fuel or combustible fluids.
Lethal Exhaust Gases
WARNINGWARNING
WARNING
WARNINGWARNING
WARNINGWARNING
WARNING
WARNINGWARNING
Lethal Exhaust Gas Hazards
Explosive Fuel Hazards
MQ
will be referenced with
DANGERDANGER
DANGER
DANGERDANGER
You WILL be if you DO NOT follow these directions.
WARNINGWARNING
WARNING
WARNINGWARNING
You CAN be KILLED or you DO NOT follow these directions.
CAUTICAUTI
CAUTION
CAUTICAUTI
You CAN be these directions.
KILLED
INJURED
if you DO NOT follow
or
SERIOUSLY INJURED
SERIOUSLY INJURED
if
DO NOT fill the fuel tank while the engine is running or hot. DO NOT overfill tank, since spilled fuel could ignite if it comes into contact with hot engine parts or sparks from the ignition system. Store fuel in approved containers, in well-ventilated areas and away from sparks and flames.
WARNINGWARNING
WARNING
WARNINGWARNING
Engine components can generate extreme heat. To prevent burns, DO NOT touch these areas while the engine is running or immediately after operations. Never operate the engine with heat shields or heat guards removed.
WARNINGWARNING
WARNING
WARNINGWARNING
ALWAYS wear approved protection when required.
Burn Hazards
Respiratory Hazards
respiratory
PAGE 6 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3H/GA-3HA — SAFETY MESSAGE ALERT SYMBOLS
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
NEVER operate equipment with covers, or guards removed. Keep fingers, hands, hair and clothing away from all moving parts to prevent injury.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
ALWAYS place the power source, circuit breakers or ON/OFF switch in the OFF position, when the generators is not in use, unless connected to transfer switch.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
ALWAYS wear approved eye and hearing protection.
Rotating Parts Hazards
Accidental Starting Hazards
Eye and Hearing Hazards
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Other important messages are provided throughout this manual to help prevent damage to your portable generator, other property, or the surrounding environment.
Equipment Damage
Hazards
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 7
GA-3.6H Series — RULES FOR SAFE OPERATION
DANGERDANGER
DANGER
DANGERDANGER
Failure to follow instructions in this manual may lead to serious injury or even death! This equipment is to be operated by trained and qualified personnel only! This equipment is for industrial use only.
The following safety guidelines should always be used when operating the GA-3.6H Series Portable Generator:
GENERAL SAFETY
DO NOT operate or service this equipment before reading this entire manual.
This equipment should not be operated by persons under 18 years of age.
NEVER operate this equipment without proper protective clothing, shatterproof glasses, steel-toed boots and other protective devices required by the job.
Read this manual!
NEVER touch the hot exhaust
manifold, muffler or cylinder. Allow these parts to cool before servicing engine or generators.
The engine section of this generators requires an adequate free flow of cooling air. any enclosed or narrow area where free flow of the air is restricted. If the air flow is restricted it will cause serious damage to the generator or engine and may cause injury to people. Remember the generator's engine gives off monoxide gas.
NEVER
operate the generator in
DEADLY
carbon
NEVER operate this equipment when not feeling well due to fatigue, illness or taking medicine.
NEVER operate this equipment under the influence of
drugs
ALWAYS wear proper respiratory (mask), hearing and eye protection equipment when operating the generator.
Whenever necessary, replace nameplate, operation and safety decals when they become difficult read.
Manufacturer does not assume responsibility for any accident due to equipment modifications.
NEVER use accessories or attachments, which are not recommended by Multiquip for this equipment. Damage to the equipment and/or injury to user may result.
or
alcohol
.
ALWAYS refuel in a well-ventilated area, away from sparks and open flames.
ALWAYS use extreme caution when working with flammable liquids. When refueling, stop the engine and allow it to cool. DO NOT machine. Fire or explosion could result from fuel vapors, or if fuel is spilled on a hot engine.
NEVER operate the generators in an explosive atmosphere or near combustible materials. An explosion or fire could result causing severe
smoke
around or near the
bodily
harm or even death.
NEVER disconnect any
These devices are intended for operator safety. Disconnection of these devices can cause severe injury, bodily harm or even death! Disconnection of any of these devices will void all warranties.
"emergency or safety devices"
.
PAGE 8 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series — RULES FOR SAFE OPERATION
ALWAYS be sure the operator is familiar with proper safety precautions and operation techniques before using generators.
NEVER leave the generators unattended, turn off engine when unattended.
Unauthorized equipment modifications will void all warranties.
ALWAYS ensure generators are on level ground before use.
DO NOT place hands or fingers inside generators engine compartment when engine is running.
NEVER run engine without air cleaner. Severe engine damage
may occur.
NEVER change or adjust the engine speed which has been
set at the factory prior to shipping.
Power Cord Safety
NEVER let power cables or cords
NEVER is being transfer to a load.
NEVER use a defective or frayed power cable. Check the cable for cuts in the insulation.
NEVER use a extension cord that is frayed or damaged where the insulation has been cut.
ALWAYS make certain that proper power or extension cord has been selected for the job See Table 4.
stand in water
while AC power from the generators
lay in wate
r.
Grounding Safety
ALWAYS make sure that electrical circuits are properly
grounded
local codes before operating generator. Severe
death!
ungrounded generator.
per the
National Electrical Code
(NEC) and
injury
by electrocution can result from operating an
Maintenance Safety
ALWAYS replace any worn or damaged warning decals.
or
NEVER lubricate components or attempt service on a running machine.
High Temperatures – Always stop engine and allow the engine to cool before adding fuel, oil or performing service and maintenance
hot!
functions. Contact with cause serious burns.
Keep the machinery in proper running condition. Fix damage to the machine immediately and replace any
broken parts immediately.
ALWAYS store equipment properly when it is not being used. Equipment should be stored in a clean, dry location out of the reach of children and unauthorized personnel.
The electrical voltage required to operate the generators can cause severe injury or even death through physical contact with live circuits. performing maintenance on the generator.
Dispose of hazardous waste properly. Examples of potentially hazardous waste are used motor oil, fuel and fuel filters.
DO NOT use food or plastic containers to dispose of hazardous waste.
DO NOT pour waste, oil or fuel directly onto the ground, down a drain or into any water source.
Removing the engine oil drain plug while the engine is hot will result in hot oil to gush out of the oil drain plug, therefore causing severe scalding to any persons in the general area of the generator.
Turn all circuit breakers OFF before
components can
ALWAYS make sure the generators are properly grounded to a suitable earth ground (GROUND ROD). See installation in this manual.
NEVER use
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 9
gas piping
as an electrical ground.
GA-3.6H Series— RULES FOR SAFE OPERATION
DANGERDANGER
DANGER
DANGERDANGER
During operation of this generation, there exists the possibility of
electrical shock or burn
cause
DEATH!
To avoid these hazards:
severe bodily harm
NEVER use
ELECTROCUTION HAZARDSELECTROCUTION HAZARDS
-
ELECTROCUTION HAZARDS
ELECTROCUTION HAZARDSELECTROCUTION HAZARDS
damaged
or
electrocution
, which can
or even
worn
cables when connecting
,
equipment to the generator. Make sure power
Emergencies
ALWAYS know the location of the
nearest
ALWAYS know the location of the nearest
first aid kit
connecting cables are securely connected to the generator’s output receptacles, incorrect connections may cause damage to the generators and electrical shock.
NEVER grab or touch a live power cord with wet hands, the possibility exist of electrical shock, electrocution, and even
death!
fire extinguisher
.
In emergencies
nearest phone or Also know the phone numbers of the nearest
ambulance, doctor
information will be invaluable in the case of an emergency.
always
.
know the location of the
keep a phone on the job site
and
fire department
.
. This
NEVER insert any objects into the output receptacles during operation. This is extremely dangerous. ALWAYS turn-off the generators and place all circuit breakers in the “OFF” position when contact with the output receptacles is required. There exist the possibility of
electrocution, electrical shock or burn, which can
cause severe bodily harm or even death
Backfeed to a utility system can cause
electrocution
NEVER connect the generators to a
building's electrical system without a transfer switch or other approved device. All installations should be performed by
licensed electrician
a with all applicable laws and electrical codes. Failure to do so could result in electrical shock or burn causing serious injury or even death!
and or property damage.
in accordance
!
NOTE
In keeping with Multiquip's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
PAGE 10 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series— SPECIFICATIONS (GENERATOR/ENGINE)
snoitacificepS.1elbaT
LEDOMZH6.3-AG/AH6.3-AG/H6.3-AG
epyT dleiFgnivloveRepyTsselhsurB,elop-2
tuptuO.xaMsttaW0063
egatloVdetaRV042/021
C/.xaM6.62/03
rotareneGzH06
esahPesahPelgniS
ycneuqerFzH06
deepSd
etaRMPR0063
rotcaFrewoP%001
thgieWteNyrD
V021@spmA.tno
V042@spmA.tnoC/.xaM3.31/51
rekaerBtiucriCniaMspmA5.31eloP-2
yticapaCknaTleuF )sretiL91(snollaG.S.U0.5.xorppA
47(.sbl071
AH6.3AG/H6.3AG).gK
ZH6.3AG).gK18(.sbl871
enignE
emiD
noisn
)HxWxL(
thgieWteNyrD
Effects of Altitude and Heat
ledoM2NDE1K042XGADNOH
epyT
ekort
SXeroB
tnemecalpsiDcc18.41
tuptuOxaM.M.P.R0063/.P.H0.8
leuF enilosaGelibomotuAde
daelnU
yticapaCliOebuLstnip33.2
dohteMlortnoCdeepS epyTthgiew-ylFlagufirtneC
dohteMgnitratStratSlioceR
SNOITACIFICEPSENIGNE.2elbaT
,VHO,rednilyCelgniS,ekorts4delooc-riA
enignEenilosaGtfahSlatnoziroH
.ni03.2X.ni09.2
).mm85xmm37(
.ni1.61X9.61x0.41
).mm014X034X553(
).gK52(sbl1.55
The maximum output of the engines listed above are applicable to supplying electrical power for continuous service at ambient conditions in accordance with SAE Test cord J607. The above ambient conditions are at standard sea level, with a barometric reading of 29.92 inches and a temperature of 60 degrees fahrenheit.
°°
°
°°
Generally, the engine's output power will decrease 3-1/2% for each 1000 feet of altitude above sea level, and 1% for each 10
°°
°
Fahrenheit above the standard temperature of 60
°°
F
F
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 11
GA-3.6H Series— DIMENSIONS
Figure 2. Dimensions
PAGE 12 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series — GENERAL INFORMATION
Excitation System
WARNINGWARNING
WARNING
WARNINGWARNING
Before connecting this generators to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch.
Serious injury or death may result without this transfer switch.F
GA-3.6H Series Familiarzation Generator
The Multiquip GA-3.6H series generators have been designed as a portable dual purpose power source for 60 Hz (single phase) lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
These generators are mounted on rubber vibration isolators that have a steel base backplate which is attached to the protective steel pipe carrying frame. The protective carrying frame is made of steel tubing and fully wraps around the generators to protect against damage. See Figures 2A through 2E for the basic controls and indicators for the GA-
3.6H Series generators. These portable generators are supplied with a electrical
control box
control box is also placed on rubber isolators.
Control Box
The control box is provided with the following:
NEMA L14-20R, twist-lock receptacle,125/250V, 20 amps.
. To reduce vibration caused by the engine, the
The GA-3.6H series generators use a magnet attached to a flywheel to produce AC voltage from a lamp coil beneath the flywheel. As the magnetic passes the coil it produces approximately 19-22 AC volts.
This voltage (19-22 VAC) is then sent to the control box that contains three rectifying diodes:
z
Excitation (diode 1)
z
Battery (diode 2)
z
Slow Down (diode 3)
The AC voltage will pass through the excitation diode that converts the voltage to DC power.
This DC power is then sent to the excitation windings housed within the main windings commonly called the "stator".
This voltage is then transferred into the rotor through induction. The rotor contains two diodes within it which rectify the DC voltage and send it out through the main windings, as AC voltage.
Alternator
The alternator, a brushless revolving-field type, is permanently aligned to the engine through rigid coupling.
Engine
These generators are powered by a 8.0 HP, air-cooled, 4­stroke
HONDA gasoline engine. Reference Table 2, for
engine specifications.
NEMA L5-20R, twist-lock receptacle, 125V, 20 amps.
NEMA L6-30R, twist-lock receptacle, 250V, 30 amps. (GA-3.6HZ only)
NEMA L5-30R, twist-lock receptacle, 125V, 30 amps.
NEMA 5-20R, GFCI duplex receptacle,125V, 20 amps
(GA-3.6HA has two).
13.5 amp main circuit breaker.
AC Voltmeter
G.F.C.I. Ground Terminal (GA-3.6HZ only)
Full Power Switch
Idle Control Switch
Operation Switch
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 13
GA-3.6H Series— LOAD APPLICATION
Single Phase Load — 60 Hz
Always be sure to check the nameplate on the generators and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generators for operating the equipment.
Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.
To determine the running wattage for your load, multiply the running wattage as indicated by steps 1, 2, and 3 below:
1. INCANDESCENT LOADS Lights, heaters and similar appliances. Total the running wattage and multiply by 1. Example: 29 light bulbs @ 100W each = 2.9 KW use a 3 KW generator.
2. SMALL MOTORS Drills and other small power tools. Total the running wattage and multiply by 2. Example:
NOTE
If wattage is not given on the equipment's name plate, approximate wattage may be
A 1 inch drill runs at 1 KW use a 2 KW generator.
determined by multiplying nameplate voltage by the nameplate amperage.
3. LARGE MOTORS Submersible pumps, table saws etc.
WATTS = VOLTAGE x AMPERAGE The power factor of this generators is 1.0 See Table 3 below
when connecting loads.
Total the running wattage and multiply by 3. Example: A conveyor belt runs at 8 KW use a 24 KW generator.
spmal
spmal
NOTE
daoLfOepyTrotcaFrewoP
srotomnoitcudniesahp-elgniS57.0-4.0
tnecsednacni,sretaehcirtcelE
ltnecseroulF
yrucem,spma
,secivedcinortcelE
tnempiuqenoitacinummoc
slootrewopnommoC8.0
When using a combination of dual receptacles, total load
exceed
the rated capacity of the
generator.
daoLyBrotcaFrewoP.3elbaT
0.1
9.0-4.0
0.1
should not
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Motors and motor-driven equipment draw much greater current for starting than during operation. adequate size
extension cable
Always
use an
which can carry the
required load.
Extension Cables
When electric power is to be provided to various tools or loads at some are normally used.
distance
from the generator, extension cords
Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generators and point of use (load) is held to a minimum
. Use the cable selection chart (Table 3)
as a guide for selecting proper cable size.
The idle control device is operated at a
NOTE
minimum load capacity of 100W. If the load capacity is less than 100W, place the idle control switch in the OFF position.
PAGE 14 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series— CONTROLS AND INDICATORS
Figure 2A. Generators Components
1. Lifting Bail Eye – Attach a rope or chain to this lifting eye when lifting of the generators is required. Never stand underneath the generators while it is being lifted. Place lifting eye in down position when not in use.
2. AC-Voltmeter – This voltmeter indicates (with a mark) the rated 60 Hz (single-phase) output voltage. In addition the voltmeter can also be used as a diagnostic tool. If the voltmeter indicator (needle) is below the rated voltage, engine problems may exist (low/high RPM's). To prevent damage to the generators or power tools turn the generators OFF and consult your authorized Multiquip service dealer.
3. Idle Control Switch – The generators are provided with an automatic idle control device for noise suppression and reduced fuel consumption. The automatic idle control automatically engages under a no-load condition. With the automatic idle control switched “ON”, the engine revolutions will automatically drop to about 2600 rpm (low-speed operation) within 3 seconds after the load stops. When the operation is resumed, the engine speed is automatically increased to about 3600 rpm (high-speed operation) as soon as the load is connected.
5. GFCI Duplex Receptacle – NEMA 5-20R, GFCI receptacle
6. 120V Output Receptacle –
7. 120V Output Receptacle – NEMA L5-30R twist-lock
8. 120V/240V Output Receptacle – NEMA L14-30R twist-
9. Main Breaker – This 2-pole circuit breaker (120/240V,
10. Ground – This ground connection point should be
will provide 120V, 20 amps. (GA-3.6HA has two.)
NEMA L5-20R twist-lock
receptacle will provide 120V, 20 amps, 60 Hz.
receptacle will provide 120V, 30 amps, 60 Hz.
lock receptacle will provide (120V, 50 amps, or 240V, 25 amps, 60 Hz.)
13.5 amps) protects the generators from short circuiting or overloading. When starting the generators the circuit breaker placed in the "OFF" position.
connect to a good earth ground (ground rod). GA-3.6H and GA3.6HA models only
always
have
4. Operation Switch – Place this position (up) for normal operation. To turn-off the generators, place the operation switch in the "OFF" position (down).
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 15
rocker
switch in the "ON"
NOTE
GA-3.6H Series— CONTROLS AND INDICATORS
Model GA3.6HZ shown. Location of Full Power Switch for Models GA3.6H and
GA-3.6HA, is on front control panel.
Figure 2B. Generators Components
11. Full Power Switch – The generators are provided with a full power switch. Figures 2C and 2D show simplified wiring diagrams of the dual voltage system.
When the full power switch is in the 120 volt (up) position, you can access the 120 volts from the GFCI duplex receptacle and the120V twist-lock receptacle, or a combination of both receptacles as long as the total load does not exceed the generating set capacity.
Figure 3C. 120V Full Power Switch
Simplified Diagram (Up Position)
NOTE
full rated power
When the
full power switch
of the generators at
is in the 120V position, the 240V twist-lock receptacle
cannot be used
.
When the switch is in the 240 volt (down) position, you can acess
half of the rated power
of the generating set at 120 volts from the GFCI duplex receptacle and up to half of the rated power of the set at 120 volts from 120V twist-lock receptacle; or full rated power of the set at 240 volts from the 240V twist-lock receptacle.
Figure 3D. 120/240V Full Power Switch
Simplified Diagram (Down Position)
12. 120V Output Receptacle – NEMA L6-20R twist-lock
receptacle will provide 240V, 20 amps, 60 Hz. GA-3.6HZ only.
13. GFCI Ground – This ground connection point should be
connected to a good earth ground (ground rod).
Applies
to GA3.6HZ only.
PAGE 16 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
NOTE
GA-3.6H Series— CONTROLS AND INDICATORS
Models GA3.6H and GA3.6HA shown. Componet location for GA3.6HZ is similar.
Figure 2E. Generators Components
14. Fuel Cock Lever – Turn this lever (down)the flow of fuel into the carburetor. Turn
stop (up)
15. Spark Plug – Provides spark to the ignition system. Set spark plug gap to 0.6 - 0.7 mm (0.028 - 0.031 inch) Clean spark plug once a week.
16. Muffler/Heat Shield – Used to reduce noise and emissions. NEVER touch this is in use. Always allow time for the generators to cool down before performing maintenance.
17. Choke Lever – Used for starting the engine. choke lever when starting a cold engine or in cold weather conditions. The choke enriches the fuel mixture. choke lever if starting a warm engine or in warm weather conditions.
18. Recoil Starter (pull rope) – Manual-starting method. Pull the starter grip until resistance is felt, then pull briskly and smoothly.
19. Engine Oil Filler Cap – Remove this cap/dipstick when the adding of engine oil is required. See Table 4 for recommended type engine oil.
the flow of fuel.
heat shield
downward
when the generator/welder
to
start
upward
Close
the
Open
the
20. Engine Oil Drain Plug – Remove this drain plug when
to
21. Air Cleaner – Prevents dirt and other debris from entering
22. Fuel Tank Cap – Remove this cap to add unleaded
23. Fuel Gauge – This gauge is located on top of the fuel tank.
24. Fuel Tank – Fuel tank capacity is 5 gallons (19 liters).
on level ground. Placing the generators on level ground will ensure that the low oil sensor will function properly.
draining of the oil from the engine crankcase is required. Fill with recommeded type oil as listed in Table 4.
the fuel system. Remove wing-nut on top of air filter cannister to gain access to filter element. NEVER run the engine without an air cleaner.
gasoline to the fuel tank. gasoline. Make sure cap is tightened securely. DO NOT over fill.
Read this gauge to determine when fuel is
NOTE
Replenish
This with a low oil shutdown capability. A built in sensor will automatically turn off the engine should the oil level fall
below a safe operating condition. Make sure the generators is placed
HONDA
with
clean unleaded
low
.
engine is equipped
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 17
GA-3.6H Series — GENERATOR REFUELING
DANGERDANGER
DANGER
DANGERDANGER
Adding fuel to the tank should be done only when the engine is stopped and has had an opportunity to cool down. In the event of a fuel spill, DO NOT attempt to start the engine until the fuel residue has been completely wiped up, and the area surrounding the engine is dry. If generators is placed in a truck bed with a plastic liner, REMOVE generators from truck bed and place on ground (Figure 3) to refuel. This possibility exist of to static electricity.
fire
or
explosion
due
Figure 3. Generators Refueling
PAGE 18 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series — INSTALLATION
Outdoor Installation
Install the generator/welder in a area that is free of
bystanders
generators is on secure level ground so that it cannot slide or shift around. Also install the generators in a manner so that the exhaust will not be discharged in the direction of nearby homes.
The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.
Pay close attention to ventilation when operating the generators inside tunnels and caves. The engine exhaust contains noxious elements.
, and
overhead obstructions
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
. Make sure the
debris
Indoor Installation
,
Exhaust gases from gasoline engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.
Eliminate the danger of deadly carbon monoxide gas. Remember that exhaust fumes from any gasoline engine are very poisonous if discharged in a closed room, but harmless if allowed to mix with the outside air. If the generators is installed indoors, you must make provisions for venting the engine exhaust to the outside of the building.
Generators Grounding
To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground. Always use the ground terminal on the generators to ground the generator. Ground the generators from its ground
connector so that the resistance to ground is 500 ohms or less.
Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.
Mounting
The generators should always be mounted on a flat level surface to isolate vibration of the generators when it is running. DO NOT place the generators on slopes, the possibility exists that the generators could slide.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
An electric shock is apt to happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from a short circuit.
NEC articles 250-64(b) and 250-66 set the following grounding requirements:
1. Use one of the following wire types to connect the generators to earth ground.
a. Copper - 10 AWG (5.3 mm2) or larger. b. Aluminum - 8 AWG (8.4 mm2) or larger.
2. When grounding the generators (Figure 3) connect the ground cable between the lock washer and the nut on the generators and tighten the nut fully. Connect the other end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 19
GA-3.6H Series — INSTALLATION
Connecting the Ground
The nut and ground terminal on the generators should always be used to connect the generators to a suitable ground. The ground cable should be #8 size wire minimum.
At the generator, connect the terminal of the ground cable between the lock washer and the nut (Figure 4) and tighten the nut fully. Connect the other end of the ground cable to a suitable earth ground (ground rod).
Figure 4. Generators Grounding
PAGE 20 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
GA-3.6H Series — PRE-INSPECTION
General Inspection Prior to Operation
Ground Power Tools
When using power tools or electrical equipment requireing AC power from the generator, make sure connecting (power tool) cable has a ground as shown in Figure 5.
Extension Cable
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generators and point of use (load) is held to a minimum. Use the cable selection chart (Table 3) as a guide for selecting proper cable size.
NOTE
Main Circuit Breaker
To protect the generators from an overload always place the main circuit breaker in the "OFF" position prior to starting the
Figure 5. Ground Cables/Plugs
engine.
Never!
use power tools or equipment that do not have a ground capability, the possibility
of electrocution, electrical
exists
shock or burn severe bodily harm
, which can cause
or even
DEATH!
)noitarepOesahPelgniS,zH06(noitceleSelbaC.3elbaT
nitnerruC
serepmA
5.2003.tf0001.tf0
5006.tf005.tf003.tf002.tf521
5.7009.tf053.tf002.tf521.tf001
010021.tf052.tf051.tf001
510081.tf051.tf001.tf56
020
sttaWnIdaoLhtgneLelbaCelbawollAmumixaM
stloV021tAeriW01#eriW21#eriW41#eriW61#
06.tf573.tf052
042.tf521.tf57.tf05
.egatlovwolmorftlusernacegamadtnempiuqE:NOITUAC
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 21
GA-3H/HA Series — PRE-INSPECTION (ENGINE)
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
NEVER operate the generators in a confined area or enclosed area structure that does not provide ample
ALWAYS wear approved eye and hearing protection before operating the generator.
free flow of air
.
Figure 7. Engine Oil Dipstick (Oil Level)
epyTliO.4elbaT
Before Starting
1. Read safety instructions at the beginning of manual.
2. Clean the generator, removing dirt and dust, particularly the engine cooling air inlet, carburetor and air cleaner.
3. Check the air filter for dirt and dust. If air filter is dirty, replace air filter with a new one as required.
4. Check carburetor for external dirt and dust. Clean with dry compressed air.
5. Check fastening nuts and bolts for tightness.
Engine Oil Check
1. To check the engine oil level, place the generators on
secure level ground with the engine stopped.
2. Remove the filler dipstick from the engine oil filler hole
(Figure 6) and wipe clean.
Motor fuels are highly flammable and can be dangerous if mishandled. DO NOT smoke while refueling. DO NOT attempt to refuel the generators if the engine is
running or in the dark
Fuel Check
1. Close the fuel cock before filling the fuel tank.
2. Remove the fuel cap located on top of fuel tank.
3. Read the fuel gauge located on top of the fuel tank (Figure 8) to determin if the fuel level is low. If fuel is low, replenish with
clean unleaded fuel
nosaeS erutarepmeT epyTliO
remmuS rehgiHroC°52 03-W01EAS
llaF/gnirpS C°01~C°52 02/03-W01EAS
retniW rewoLroC°0 01-W01EAS
DANGER EXPLOSIVE FUELDANGER EXPLOSIVE FUEL
DANGER EXPLOSIVE FUEL
DANGER EXPLOSIVE FUELDANGER EXPLOSIVE FUEL
hot!
,
.
.
Figure 8. Fuel Gauge
Figure 6. Engine Oil Dipstick (Removal)
3. Insert and remove the dipstick without screwing it into the filler neck. Check the oil level shown on the dipstick.
4. If the oil level is low (Figure 7), fill to the edge of the oil filler hole with the recommended oil type (Table 4). Maximum oil capacity is 1.16 quarts (1.1 liters)
PAGE 22 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
4. When refueling, be sure to use a strainer for filtration. DO NOT top-off fuel.
Wipe up any spilled fuel
DO NOT fill the tank beyond capacity.
immediately!
GA-3.6H Series— INITIAL START-UP (ENGINE)
2. Place the
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
DO NOT attempt to operate this generators until the Safety, General Information and Inspection sections of this manual have been
thoroughly understood
This section is intended to assist the operator with the
start-up
this section be read carefully before attempting to use the generators in the field.
Before Starting the Engine
1. Be sure to
2. NEVER start the engine with the main
of the portable generator. It is extremely important that
disconnect all electrical loads
generators prior to starting the engine.
in the “ON" position. Always place this circuit breakers (Figure 9) in the OFF position before starting.
read and
.
initial
from the
circuit breaker
if starting a
3. Place the
if starting a
4. Place the
ON
"
choke lever
cold
Figure 11. Choke Lever
choke lever
warm engine
generator's operation switch
" position.
(Figure 11) in the "
engine.
(Figure 11) in the "
or the
temperature is warm.
CLOSED
OPEN
(Figure 12) in the
" position
" position
Figure 9. Main Circuit Breaker (OFF Position)
Starting the Engine
1. Place the engine position.
Figure 10. Engine Fuel Valve Lever (ON Position)
fuel valve lever
(Figure 10) to the "ON"
Figure 12. Generator Operation Switch (ON)
5. Grasp the starter grip (Figure 13) and slowly pull it out. The resistance becomes the hardest at a certain position, corre­sponding to the compression point. Pull the starter grip briskly and smoothly for starting.
Figure 13. Starter Grip
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
DO NOT pull the starter rope all the way to the end. DO NOT release the starter rope after pulling. Allow it to
rewind as soon as possible.
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 23
GA-3.6H Series— INITIAL START-UP/GENERATOR OPERATION
6. If the engine has started, slowly return the choke lever (Figure 11) to the started repeat steps 1 through 5.
7. Before the generator is placed into operation, run the engine for 3-5 minutes. Check for abnormal smells, fuel leaks, and noises that would associate with lose components.
8.
Place
the
“OPEN”
idle control switch
position. If the engine has not
(Figure 14) in the "OFF"
(down) position. This will allow the engine speed to run
2. Place the full power switch (Figure 17) in the 120V position (up).
Figure 17. Full Power Switch 120 V Position (Up)
at speed about 3600 RPM's
NOTE
3. Read the
Figure 14. Idle Control Switch (Off)
(Figure 18) and verify that120 VAC is present at the 120V twist-lock and GFCI duplex receptacles. For
Placing the the OFF position (Figure 14) allows
NOTE
the generators will run at idle speed (2200 RPM's) until a load is applied, at that time the engine speed will increase to 3600 RPM's as long as the load is being applied. When the load is not in use, the engine speed will drop back to the idle mode after about 3 seconds.
the engine to operate at a maximum speed of about 3600 RPM's. When the idle control switch is placed in the up position (ON) (Figure 15),
idle control switch
in
additional verification of voltage, an external voltmeter can be used to measure the output voltage as shown in Figure 18.
When the
full power switch
is in the 120 V
position, the 240V twist-lock receptacle
cannot be used.
voltmeter
on the front panel of the generator
Figure 15. Idle Control Switch (On)
Figure 18. 120 V and GFCI Receptacles
60 Hz Operation
1. Place main circuit breaker (Figure 16) in the ON position.
4. Place the full power switch (Figure 19) in the 240V position (down).
Figure 17. Main Circuit Breaker (ON)
PAGE 24 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
Figure 19. Full Power Switch 240/120 V Position (Down)
GA-3.6H Series— GENERATOR OPERATION/SHUTDOWN
5. Read the (Figure 20) and verify that 240 VAC is present at the 240V twist-lock receptacle. Using an external voltmeter verify that 120V is present at the 120V twist-lock and GFCI duplex receptacles.
voltmeter
on the front panel of the generator
Stopping the Engine
1. Place the main circuit breaker (Figure 21) in the OFF position.
Figure 21. Main Circuit Breakers (Off)
2. Place the position.
3. Let the engine run at idle with no load for 2-3 minutes.
idle control switch
Figure 22. Idle Control Switch (Off)
(Figure 22) in the OFF
4. To shut-down the engine, place the generator's operation switchg(Figure 23) in the OFF position.e
Figure 20. 60 Hz Output Receptacles
When the full power switch is in the 240
NOTE
receptacle and up to half of the rated power of the set at 120 volts from the 120V twist-lock receptacle; or full rated power of the genset at 240 volts from the 240V twist-lock receptacle.
NOTE
volt (down) position, you can take up to
half of the rated power
set at 120 volts from the GFCI duplex
When using a combination of dual receptacles, total load should not exceed the rated capacity of the generator.
of the generating
5. Place the engine
Figure 23. Generator Operation Switch (Off)
position.
fuel valve lever
(Figure 24) to the "OFF"
Connecting the Load
1. If small wattage power tools are required, connect them to the 60 Hz output receptacles at this time.
GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05) — PAGE 25
Figure 24. Engine Fuel Valve Lever (OFF Position)
6. Remove all
loads
from the generator.
GA-3.6H Series— PREPARATION FOR LONG TERM STORAGE
Generators Storage
For storage of the generating set for over 30 days, the following is required:
Drain the fuel tank completely, or add STA-BIL to the fuel.
Run the engine until the gasoline in the carburetor is completely consumed.
Completely drain the oil from the crankcase and refill with fresh oil.
Remove the spark plug, pour 2 or 3 cc of SAE 30 oil into the cylinder and crank slowly to distribute the oil.
Slowly rotate the engine a few times with the starter Rope and install a new plug.
Pull out the starter rope slowly and stop at the compression point.
Clean all external parts of the generating set with a cloth.
Cover the generating set and store in a clean, dry place.
PAGE 26 — GA-3.6H SERIES A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (11/01/05)
Loading...
+ 60 hidden pages