Holip hlp-c+, HLPC+00D423B, HLPC+0D7543B, HLPC+01D543B, HLPC+0D7523B Instruction

...
- 1 -
HLP-C
+
Inverters
Contents
Ⅰ.Introduction………………………………………… 1
2.Nameplate Information of HLP-C+ Series……………………3
Ⅱ. Safety Precautions ……………………………… 4
1.Before the Power Up ………………………………………… 4
2.During the Power Up………………………………………… 6
3.Duing the Operation …………………………………………… 6
Ⅲ. Standard Specifications ………………………… 8
1.Particular Specications …………………………………… 8
2.General Specifications ……………………………………… 8
Ⅳ. Storage and Installation………………………… 10
1.Storage………………………………………………………… 10
2.Installation Locationand Environment …………………… 10
3.Installation Space and Direction …………………………… 10
Ⅴ. Wiring ……………………………………………… 12
1.Main Circuit Schematic Diagram ………………………… 12
3.Basic Connection Diagram ………………………………… 14
Ⅵ. Instruction of the digital operator……………… 18
1.Description Of The Digital Operator ……………………… 18
2.Display Description of Indication Status ………………… 18
3.Operation Instruction ………………………………………19
Ⅶ. Commissioning ………………………………… 20
1.Important Checks Before the Commissioning …………… 20
2.Commissioning Methods …………………………………… 20
- 2 -
HLP-C
+
Inverters
Ⅷ. Function List ……………………………………… 21 Ⅸ. Descriptions of Functions ………………………28 Ⅹ. Care & Maintenance, Fault Information and Troubleshooting ……………………………… 80
1.Precautions about Inspection and Maintenance ………… 80
2.Periodical Inspection and Maintenance items…………… 80
3.Fault indication and troubleshooting ……………………… 81
4.Faults and Analysis ………………………………………… 85
Ⅺ. Selection of Peripheral Devices and Disposition………………………………………… 88
1.Options ……………………………………………………… 88
2.D isposition ………………………………………………… 89
Ⅻ. Appendices ……………………………………… 91
Appendix 1:
Application demonstrations ………………… 91
Appendix 2:
External Appearance and
Installation Dimensions …………………… 93
Appendix 3:
User’s Records and Feedback ……………… 95
- 1 -
HLP-C
+
Inverters
I.Introduction
Thank you for purchasing and using the general-purpose inverter of HLP- C+ Series of multi-functions and high performance. The inverter of HLP- C+ Series has been developed on basis of HLP-A Series keeping the main functions of HLP-A Series and with additional functions on request of customers as well as smaller size. So the inverter of HLP- C+ Series features more compact and more powerful functions. Please read caref ully t he ope ration manual before put t he inverter to use so as to correctly install and operate the inverter, give full play to its functions and ensure the safety. Please keep the operation manual handy for future reference, maintenance, inspection and repair. Due to the inverter of a kind of electrical and electronic product it mu st be installed, tested and adjusted with parameters by specialized engineering persons of motor. The marks of and other simbols in the manual remind you of the safet y and prevention caustions during the tra nsportat ion, instal lation, r unning and inspect ion. Please follow the se instructions to make sure the safe use of the inverter. In case of any doubt please contact our local agent for consultation. Our professional persons are willing and ready to serve you. The manual is subject to change without notice.
Danger
Caution
Danger
indicates wrong use may kill or injure people.
Caution
indicates wrong use may damage the inverter
or mechanical system.
Danger
● Be sure to turn off the input power supply before wiring.
● Do not touch any internal ecectrical circuit or component
when the charging lamp is still on after the AC power supply is disconnected, which means the inver ter still has high voltage inside and it is very dangerous.
- 2 -
HLP-C
+
Inverters
● Do not check components and signals on the circuit boards.
● Do not dissemble or modify the any internal connecting
cord, wiring or component of the inverter by yourself.
● Be sure to make correct ground connection of the ear th
terminal of the inverter.
● Neve r remo d e l it or exc h a nge c ont r ol bo a rd s and
components by yourself. It may expose you to an electrical shock or explosion, etc.
Caution
● Do not make any voltage with standing test with any
component inside the inverter. These semi-conductor parts are subject to the damange of high voltage.
● Never connect the AC main circuit power supply to output
terminals U.V W. of the inverter.
● The main electric circuit boards of CMOS and IC of the
inver ter are subject to the effect and damage of static electricity. Donn’t touch the main circuit boards.
● Installation, testing and maintenance must be performed by qualied professional personnel.
● The inverter should be discarded as industrial waste. Avoid
burning.
( 1 ) Checks upon Delivery
The inverter has been strictly and well packed before ex-work. In consideration of various factors during the transportation special attention should be paid to the following points before the assembly and installation. If there is anything abnormal please notify the dealer or the relevant people of our company.
● Check if the inverter has got any damage or defor mation
during the transportation.
● Check if there is one piece of HLP-C+ series inverter and one
copy of the instruction manual available after unpacking it.
● C heck t h e information on t h e namepla t e to s ee if t he
specifications meet your order (Operating voltage and KAV value).
- 3 -
HLP-C
+
Inverters
MODE: HLPC+01D543B
INPUT: 3PH380V50Hz/60Hz
OUTPUT: 3PH380V4.0A1.5KW
Freq Range: 0.1-600Hz
HLP ELECTRONICS CO., LTD
Type:HLP C
+
01D5 43 B
Hardware Version
Voltage Rating,
43 means 3-phase380V
Inverter Capacity, 01D5 means 1.5KW
Series No.
Trade Mark
● Check if there is something wrong on the inner parts, wiring
and circuit board.
● Check if each terminal is tightly locked andif there is any
foreign article insie the inverter.
● Check if the operator buttons are all right.
● Check if the optional components you ordered is contained in
it.
● Check if there is a certicate of qualication and a warranty
card.
( 2 ) Nameplate Information of HLP-C+ Series
- 4 -
HLP-C
+
Inverters
Caution
● Check to be sure that the voltage of the main circuit AC
power supply matches the input voltage of the inverter.
Caution
E
symbol is the ground terminal. Be sure to make correct
ground connection of the earth terminals of the motor and the inverter for safety. E can't be connected to Line zero.
● No contactor should be installed between the power supply
and theinverter to use it for sta rting or stopping of the inverter. Otherwise it will affect the service life of the inverter.
Danger
● R.S.T terminals are power input terminals, never mixed with
U.V.W terminals. Be sure that the wiring of the main circuit is correct. Otherwise it will cause damages of the inverter when the power is delivered to it.
● Do not carry the front cover of the inverter directly when
handling, It should be handled with the base to prevent the fall off of the front cover and avoid the dropping of the inverter,which may possibly cause the injuries to people and the damages to the inverter.
● Mount the inver ter on a metal or ot her noncombustible material to avoid the risk of re.
● Install the inverter in a safe site, avoid high temperature,
direct sunlight, humid air or water.
● Keep the inverter from the reach of children or persons not
concerned.
II.Safety Precautions
⑴ Before the Power Up
Caution
- 5 -
HLP-C
+
Inverters
● The inverter can only be used at the places accredited by
our company. Any unauthorized working environment may
have the risks of re, gas explosion, electric shock and other
incidents.
● Install a cooling fan or other cooling device when installing
more than one inverters in the same enclosure so that the temperature inside the enclosure be kept below 40℃ to
avoid overheat or the risk of re. .
● Be sure to turn off the power supply before dissembling or
assembling the operation keyboard and fxing the front cover to avoid bad contact causing faults or non-display of the operator.
● Do not install the inverter in a space with explosive gas to
avoid the risk of explosion.
● If the inverter is used at or above 1000m above seal level,
the cooling efficiency will be worse, so please run it by changing down.
● Do not install any contactor and other components of related
capacitor o var istor on the out put side of the inverter. Other wise it will cause malfunctions and damages of components of the inverter.
● Do not install any switching component like air breaker
or contactor on the output side of the inverter. If any of such components must be installed because of process and other needs, it must be ensured that the inverter has no output when the switch takes actions. In addition, it is forbidden to install any for improvement of power factors or varistors against thunder on the output side. Otherwise it
Inverter
X
X
- 6 -
HLP-C
+
Inverters
⑵ During the Power Up
Danger
● Do not plug the connectors (CONNECTOR)of the inverter
when it is in the delivery of current to avoid any surge into the main control board due to plugging, which might cause the damage of the inverter.
● Always have the protective cover in place before delivery of
current to avoid electrical shock injury.
⑶ During the Operation
will cause malfunctions, tripping protecton and damages of components of the inverter. Please remove them as shown in the above diagram.
● The function of STOP switch is only valid after it is set. Its
use is different with the emergency stop switch. Be careful when using it.
● It will affect the service life of the inverter if a contact is
connected to the front end of input of the inverter to control its starting and stopping. Generally it is required to control it through FOR or REV terminals. Special attention should be paid to its use in the case of frequent starts and stops.
● Please use an independent power supply for the inverter.
Do avoid using the common power supply with an electric welder and other equipment. Otherwise it will cause the protection or damage of the inverter.
Danger
● Never connect or disconnect the motor set while the inverter
is in running. Otherwise it will cause overcurrent trip and even burn up the main circuit of the inverter.
● Never remove the front cover of t he inver ter while t he
inverter is powered on to avoid any injury of electric shock..
● Do not come close to the machine when the fault restart
function is used to avoid anything unexpected. The motor may automatically restart after stopping running
- 7 -
HLP-C
+
Inverters
Caution
● Do not touch the heat sink, braking resistor, or other heat
elements. These can become very hot.
● Be sure that the motor and machine is within the applicable
speed ranges before starting operation because the inverter is quite easy to run from lower speed to higher speed.
● Do not check the signals on circuit boards while the inverter
is running to avoid danger.
● Be careful when changing the inverter settings. The inverter
has been adjusted and set before ex-work. Do not adjust it wantonly. Please make proper adjustments according to the required functions.
● Do consider the vibration, noise and the speed limit of the
motor bearings and the mechanical devices when the inverter is running at or above the frequency of 50Hz.
- 8 -
HLP-C
+
Inverters
III. Standard Specifications
⑴ Particular Specifications
Type Input Voltage
Power
(KW)
Inverter
Capacity
KVA
Output
Current
(A)
Suitable
Motor
KW
HLPC+0D7543B
3φ380V
50/60Hz
0.75 2.2 2.7 0.75 HLP C+01D543B 1.5 3.2 4.0 1.5 HLP C+02D243B 2.2 4.0 5.0 2.2 HLP C+00D423B
Single &
Three Phase
220V 50/60Hz
0.4 1.0 2.5 0.4 HLP C+0D7523B 0.75 2.0 5.0 0.75 HLP C+01D523B 1.5 2.8 7.0 1.5
⑵ General Specifications
Descriptions HLP- C
+
Control Type SPWM
Input Power
400V class:345~440V
230V class:170~230V
Range 0.1~600.0Hz
Acuracy
Digital:0.01%(-10~40
℃);
Analogue:0.1%(25±10
℃)
Setting Resolution
Digital:0.1Hz;Analogue:1‰ of Max.
Operating Frequency Output Resolution 0.1Hz Operator Setting
Method
Press directly ∧ or ∨ to set.
Analog Setting Method
External Voltage 0-5V,0-10V,4-20mA
0-20mA
Other Functions
Frequency lower limit, starting frequency,
stopping frequency, three skip frequencies
can be individually set and so on.
Acceleration/
Deceleration time Control
Four selectable combinations of
independent acceleration and deceleration
settings (0.1-6500s).
V/FCurve Set V/F curve at will
Frequency Control
- 9 -
HLP-C
+
Inverters
Torgue Control
Torque increase settable by max. 10.0%.
The star ting torque ca n reach 150% at
1.0Hz.
Multi-function input terminals
6 multi-input terminals for 8–speed steps
cont rol , prog r a m operation, switch of
4-steps Accel/Decel, UP/DOWN function,
counter, external emergency stop and other
functions.
Multi-function Onput terminals
2 multi-function output terminals for the
displaying and warning of running, zero
speed, counter, external fault, program
operation and other information.
Other Functions
AVR (auto voltage regulation), Deceleration
stop or self-st op, DC brake, auto reset
and restart, speed search, PLC, traverse
function, drawing control, auto energy-
savings, carrier adjustable by max. 16KHz,
etc.
4-Ddigits Display & Status Lamp
Display frequency, curre nt, revolution,
voltage, counter, temperature, pressure,
forward or reserve running, and fault, etc.
Communication Control RS485 Operation Temperature -10~40
Humidity 0~95% Relative Humidity(without dew
Viobration Below 0.5G
Over Voltage
230V class:DC Voltage>400V400V class
DC Voltage>800V
Low Voltage
230V cla s s:DC Volta g e<20 0V400V
class:DC Voltage<400V Instant Stop
and Restart
Restarted by speed search after
instantaneous stop. Stall Prevention Anti-stall in Acc/Dec Run Output Eend
Shorts
Electronic circuit protecting
Other Functions
Fin over-heat protection, restriction of reverse
running, fault reset, parameter lock, etc.
General Control
Protection Functions
- 10 -
HLP-C
+
Inverters
IV.Storage & Installation
⑴ Storage
The inverter must be kept in its original package box before installation. Pay attention to the followings when keeping it in storage if the inverter is not used for the time being:
● It must be stored in a dry place without rubbish or dust.
● The suitable temperature for storage is between -20℃ and
+65℃.
● The relative humidity required is 0-95%, no condensation.
● There is no corrosive gas or liquid in the storage ambience..
● It’s better to lay the inverter on a rack and keep it in a proper
ipackage.
● It is bet ter not to store t he inver ter for long time. Long
time storage of the inverter will lead to the deterioration of electrolytic capacity. If it needs to be stored for long time be sure to power it one time within a yearand the power on time should be at least above five hours. When powered In input the voltage must be increased slowly with a voltage regulator to the rated voltage value.
⑵ Installation Locationand Environment
Attention: The ambient conditions of the inverter will affect its service life.
● Ambient operating temperature -10℃ to 40℃ wit h good
ventilation.
● No water drop and low moisture.
● Free from direct sunshine, high temperature and heavy dust
fall.
● Free from corrosive gas or liquid.
● Less dust, oil gas and metallic particles
● Free from vibration and easy for service and inspection.
● Free from the inteference of electromagnetic noise.
⑶ Installation Space and Direction
● There must be enough space left around the inverter for easy
maintenance and cooling. See Diagram 1.
- 11 -
HLP-C
+
Inverters
● The inverter must be installed vertically and to ensure the
smooth ventilation for effective cooling.
● If there is any instability when installing the inverter, please
put a f lat board under the inverter bottom base and install again. If the inverter is installed on a loose surface, stress may cause damage in main circuit so as to damage the inverter.
● The inverter should be installed on non-combustible materials,
such as iron plates.
● If several inverters are installed together in one cabinet, please
add heat dissipation plates and leave enough space between the inverters. See Diagram.
- 12 -
HLP-C
+
Inverters
V. Wiring
⑴ Main Circuit Schematic Diagram
Power supply:
Verify that the inverter’s rated voltage coincides with AC power supply voltage to avoid a damage of the inverter.
No fuse breaker:
Refer to the related list.
Ground fault circuit interrupter
Use one of anti-high harmonic.
Magnetic contactor: Note:
Do not use the magnetic contactor as the
power supply on/off button for the inverter.
AC reactor:
It is recommended to install a AC reactor for power factor improvement if the intput capacity is more than 1000KVA.
Inverter:
● Be sure to make correct connections of the
main circuit wires and control signal wires of the inverter.
● Be sure to make correct setting of parameters
for the inverter.
- 13 -
HLP-C
+
Inverters
⑵ Function Description of Circuit Terminals
1. Main Circuit Terminals Arrangement
2. Control Circuit Terminals Arrangement
FA FB FC DRV FOR REV RST SPL SPM SPH GND AM VI AI +10V
3. Function description of main circuit terminals
4、Function description of control circuit terminals
Symbol Function Description
R.S.T
Input terminals of AC line power.(230V class, for
both single/three phase, single phase connected to
any two phases)
U.V.W Output terminals to motor.
P.P.r External braking resistor terminals.
E
Ground terminals: the third kind of grounding for 230V and special grounding for 400 V of Electrical Engineering Regulations.
Symbol Function Description Factory setting
FOR Multi-function input 1 Forward run
REV Multi-function input 2 Reverse run
RST Multi-function input 3 Reset SPH Multi-function input 4 High speed
SPM Multi-function input 5 Intermediate Speed
SPL Multi-function input 6 Low Speed
GND
Common end for digit control signals
- 14 -
HLP-C
+
Inverters
Mark: The pin denitions of RS485 communication interface
are as follows:
Pin1 Pin6
Pin1:GND; Pin2:+5V; Pin3:RS+; Pin4:RS-; Pin5:GND; Pin6:GND
⑶ Basic Wiring Diagram
The whole wiring of the inverter is divided into two parts, main circuit terminal connections and control circuit terminal connections. Users can see the main circuit terminals, and the control circuit terminals after removing the outer cover. The terminals must be connected correctly as the following wiring circuit diagrams.
Symbol Function Description Factory setting
+10
Power supply for analog freqency
+10V
VI
A n a l o g f r e q u e n c y reference input (voltage)
0~+10V corresponding to the highest operating frequency
AI
A n a l o g f r e q u e n c y reference input (current)
4 ~20 m A co r r e s p o n d i n g to t he h i g he s t op e rat i ng frequency
DRV
Mu lti-function out put terminal (Optical couple output)
DC24V/100mA
FA FB FC
Mu lti-function out put
terminal 3 (N/O or N/C)
3A/250VAC3A/30VDC
AM
D i g i t a l f r e q u e n c y outputtermina
0-10V
RS485 communication
interface
- 15 -
HLP-C
+
Inverters
The following diagram shows the factory standard connection of Model HLP-C+
(4) Precautions on Wiring
a:For main circuit wiring:
● While wiring the sizes and specications of wires should be
selected and the wiring should be executed according to the electrical engineering regulations to ensure the safety.
● It is better to use shield wire or wire and tube for power cord
and ground the shield layer or two ends of wire tube.
● Be sure to install a No Fuse Breaker (NFB) between the power
supply and the input terminals (R.S.T). (If using ground fault circuit interrupter, please choose the one cor responding to high frequency)
● The power line and the cont rol line should be arranged
separately and should not be laid in the same ducts..
● Never connect AC power to the output terminals (U.V.W) of
the inverter.
● Output wires mustn’t be in touch of the metal part of the outer
cover, or it will cause earth short-circuit.
● Phase-shifting capacitor, LC, RC noise lters, etc, can never
- 16 -
HLP-C
+
Inverters
Model
HLPC+00
D423B
HLPC+0 D7523B
HLPC+0 1D523B
HLPC+0 2D223B
HLPC+0
D7543B
HLPC+0
1D543B
HLPC+0 2D243B
NFB
Capacity
16A 16A 32A 32A 16A 16A 16A
Wire
Size
2.5mm² 2.5mm² 2.5mm² 4mm² 2.5mm² 2.5mm² 2.5mm²
Screw M4 M4 M4 M4 M4 M4 M4
Note: The parameters above are only for reference, not a standard.
be connected between the motor and the output terminals (U.V.W) of the inverter.
● The main circuit wire must be enough far away from other
control equipments.
● When the wiring between the inverter and the motor exceeds
15 meters for 230V class or 30 meters for 440V class, much
higher dV/dT will be produced inside the coil of motor, which
will cause the destroy to the interlayor insulation of motor. Please change it to a special AC motor for the inverter or add a reactor on the side of the inverter.
● Please lower the carrier frequency if there is longer distance
betweent the inerter and the motor. Because the higher carrier frequency will result in the bigger leakage current of high­order harmonics of the cables the leakage current will have unfavorable effect on the inverter and other equipment.
Specications for NFB and Wire
b:For control circuit wiring (signal line)
● The signal line should be separately laid in a different duct
with the main circuit wire to avoid any possible interference.
● Please use the shielded cable with the size of 0.5-2mm2 for
signal lines and make one end grounding. while the shielded cable with the size of 1 mm² is recommended for the control line.
● Use the control terminals correctly according to your needs.
c:Grounding
● Ground i ng t er m i nal : T he t h i rd g rounding me t hod
E
- 17 -
HLP-C
+
Inverters
⑴ Good ⑵ Good ⑶ Not good
(Grounding resistance should be 100. or lower.)
● Choose grounding wires according to the basic length ans
size of the technical requirements of the electric equipment.
● Do avoid shar ing grounding wire with other large power
equipment such as electric welder, dynamic machine, etc. The grounding wire should be kept away from the power supply wires.
● The-grounding method for several inverters together should
be done as the first and second diagrams. Avoid the third diagram.
● The grounding wire must be as shorter as possible.
Never connect it to zero line.
- 18 -
HLP-C
+
Inverters
VI. Description of Digital Operator
⑴ Description of Digital Operator
⑵ Display Status
1
.During stopping: STOP on.
2.
During operation
a: In case of output, RUN on, STOP dark; in case of forward
rotating, FWD on, in case of reverse rotatying, REV on.
b:Run→Stop, then RUN on, STOP ashing→RUN dark, STOP
on.
c:Forward→Reverse, then FW D on, R EV flashing→FWD
ashing, REV on.
d:When the inverter is operated in 0.00HZ, RUN ashing and
STOP off.
e:In jogging, RUN on, STOP ashing.
- 19 -
HLP-C
+
Inverters
⑶ Operation instruction
A. Description: Displaying Contents
1、
Output Frequency 50.0Hz
2、
Set Frequency 50.0Hz
3、
Output Current 2.0A
4、
Output Voltage 220V
5、
DC Voltage 540V
6、
Temperature 39
7、
Counter
8、
PID feedback is 50%
9、
Revolution
10、
Forward Moving
11、
Reverse Moving
B. DC voltage, the temperature, counter, PID feedback and revolution can only be displayed af ter set ting. For specific parameter refer to C121.
C. Show the interface content before power off at power on
D. Under the status of FOR, REV, CXXX and parameter content, it can automatically ret u r n to the i nterfaces of f requency, voltage, electric current, etc. automatically after several seconds.
E. Under the status of Running and Stopping, it continues to display the original interface. But the corresponding contents will change with the running situation and the indicator lamp will indicate the corresponding status. During the operation the fan is running and when stopping the fan stops running.
- 20 -
HLP-C
+
Inverters
VII. Commissioning
(1) Important Checks Before the Commissioning
● If there is any wrong connected wires? Pay special attention to
the terminals: U.V.W; Make sure the power supply wires are connected to R.S.T, not U.V.W.
● If there is any metal powder or other wires left on the base
plate of the inverter or at the terminals, which might cause short circuit.
● If the scews are tightly locked and if the connecting parts are
loose.
● If there is any short circuit or earth fault in the output parts.
(2)Commissioning Methods
The procedure of the operator is factory set up for the control method of HLP series. The commissioning can be carried out through the digital operator. Generally, the commissioning can be conducted at 5.00 Hz.
Procedures Display Indicator Lamp POWER ON F000 FOR、STOP on Press 00.00 FOR、STOP on Press 05.00 FOR、STOP on Press RUN F05.0 FOR、RUN on. The fan operates. Press STOP F05.0 FOR、STOP on. The fan stops.
Note: The fan runs whe n the i nver ter is ope r ating or the temperature is reached within the inverter. In the process the inverter shuts down with the operation frequency dropping to
0.00HZ, STOP indicator lamp glimmer and will be on when the inverter stops.
- 21 -
HLP-C
+
Inverters
VIII. Function List
Parameter and Function List (Part 1)
Function
code
Function
Set Range & Function
Explanation
Factory
Setting C000 Main frequency 0.0~600.0Hz 0.00 C001 Accel. Time 0.1~6500S 5.0 C002 Decel. Time 0.1~6500S 5.0 C003 V/F Curve 0~16 00 C004 Max. voltage 0.1~255/510 220/380 C005 Base frequency 0.01~600 50/60
C006
Intermediate voltage
0.1~255/510 *
C007
Intermediate frequency
0.01~600 *
C008 Min. voltage 0.1~* * C009 Min. frequency 0.1~20.0Hz *
C010 Max. frequency 10.0~600.0 50.00
C011
Frequency lowe r limit
0.0~600 0.00
C012 Running control 0~2 0
C013
Running frequency select
0~2 0
C014
Starting mode select
0~1 0
C015 Stopping mode 0~1 0 C016 FOR/REV select 0~1 1 C017 STOP key select 0~1 1 C018 S-Curve Time 0~6500S 0 C019 Carrier frequency 0~15 09
C020 Starting Frequency 0.1~10 1.5
C021
Stopping Frequency
0.1~10 1.5
C022 Jog Frequency 0~600 5.0
C023
Jog Accel/Decel
Time
0.1~25.0 1.0
- 22 -
HLP-C
+
Inverters
Parameter and Function List (Part 2)
Function
code
Function
Set Range & Function
Explanation
Factory
Setting C024 PLC operation 0~5 0
C025
Auto PLC operation
0~3 0
C026
PLC rotation Direction
0~255 0
C027
PLC Accel/Decel
Time 1
0~255 0
C028
PLC Accel/Decel
Time 2
0~255 0
C029 Accel. Time 2 0.1~6500S 10.0
C030 Decel. Time 2 0.1~6500S 10.0 C031 Accel. Time 3 0.1~6500S 50.0 C032 Decel. Time 3 0.1~6500S 50.0 C033 Accel. Time 4 0.1~6500S 100.0
C034 Decel. Time 4 0.1~6500S 100.0
C035 Frequency 2 0.0~600.0Hz 15.0 C036 Frequency 3 0.0~600.0Hz 20.0 C037 Frequency 4 0.0~600.0Hz 25.0 C038 Frequency 5 0.0~600.0Hz 30.0 C039 Frequency 6 0.0~600.0Hz 35.0
C040 Frequency 7 0.0~600.0Hz 40.0
C041 Frequency 8 0.0~6500S 0.50
C042 PLC Timer 1 0.0~6500S 10.0
C043 PLC Timer 2 0.0~6500S 10.0 C044 PLC Timer 3 0.0~6500S 0.0 C045 PLC Timer 4 0.0~6500S 0.0 C046 PLC Timer 5 0.0~6500S 0.0 C047 PLC Timer 6 0.0~6500S 0.0 C048 PLC Timer 7 0.0~6500S 0.0 C049 PLC Timer 8 0.0~6500S 0.0
- 23 -
HLP-C
+
Inverters
Parameter and Function List (Part 3)
Function
code
Function
Set Range & Function
Explanation
Factory
Setting
C050 Multi-input FOR 0: I n v a lid ; 1:Ru n ; 3:
Fo r. rotation; 4: Rev. r o t a t i on ; 5: Sto p ; 5:
For/Rev.; 6: Jog; 7: Jog For rotation; 8: Jog Rev
Rotation; 9: Emergency s t o p; 10 : Re s e t ; 12 : O ve r he a t of r a di a t or or mot or; 13: Timer 1 start; 14: Timer 2 start;
17: Hi g h s p e e d ; 18 :
Intermediate speed; 19: Low speed; 20: Multi­Speed 1; 21: Multi-Speed 2; 22: Multi- Speed 3;
23: Accel/Decel select 1; 24: Accel/Decel select
2; 2 5: U P f u n c t i on ; DOWN f unc t ion; 27: 2 7: C o u n t e r p u l s e;
28: Count er reset; 29:
Drawing start; 31: Auto PLC Reset suspend; 32: PID valid
02 C051 Multi-input REV 03 C052 Multi-input RST 10 C053 Multi-input SPH 17
C054 Multi-input SPM 18
C055 Multi-input SPL 19
- 24 -
HLP-C
+
Inverters
Parameter and Function List (Part 4)
Function
code
Function
Set Range & Function
Explanation
Factory
Setting
C056 Multi-output DRV 0: I nvalid; 1: Run; 2:
Fa u lt S ig n al; 3: Z e r o Sp eed; 4: DC Bra king i n d i c a t i o n ; 5 : S e t Fr e q u e nc y r e a c h ; 6: U n i f o r m Fr e q u e n c y 1 re a ch ; 7: Un i fo r m
Frequency 2 reach; 8: In
Accel.; 9: In Decel.; 10: Inverter Overload alarm; 11: Mot o r Ov e r lo a d alarm; 12: Overtorque detect; 13: Undervoltage a l a r m ; 1 4 : S i n g l e stage end; 15: Process end ; 16: Set Cou n t er reach; 17: Inter mediate
C o u n t e r r e a c h ; 18 :
Externally c o nt r olled T i m e r 1 r e a c h ; 19 : Externally c o nt r olled T i m e r 2 r e a c h ; 2 0 4~20mA disconnected; 2 7 : D r a w i n g r e a c h ;
28: PI D Down L i m i t
alarm; 29: PID Up Limit alarm; 30: Fan run; 31: Electromagnetic Relay act; 32: Braking Resistor act
01
C057
Multi-output FABC
02
C058 Multi–Analog AM 0~7 0 C059 Analog output gain 0~100 100
C060 Up/down mode 0~1 0
C061 Reserved
- 25 -
HLP-C
+
Inverters
Function
code
Function
Set Range & Function
Explanation
Factory
Setting C062 Timer 1 time 0.0~10.0 00.0 C063 Timer 2 time 0~100 000 C064 Counter 0~9999 0
C065
Intermediate Counter
0~9999 0
C066 Skip Frequency 1 0~600 0.0 C067 Skip Frequency 2 0~600 00.00 C068 Skip Frequency 3 0~600 0.0
C069
Skip Frequency range
0.1~10.00 0.50
C070
Uniform Frequency 1
0.0~600 00.00
C071
Uniform Frequency 2
0.0~600 00.00
C072
Analog Quantity Select
0~4 0
C073
Low end frequency of analog quantity
0.0~600 00.00
C074
Bia s direction of low end frequency
0~1 0
C075
High end frequency of analog quantity
0.0~600 51.0
C076
Bia s direction of high end frequency
0~1 0
C077
N e g a t i v e b i a s reverse
0~1 0
C078
An a log Fi l t e r ing Constant
0~50 20
C079
Over voltage stal l prevention
0~1 1
C080
St a ll preve n tio n level during accel.
0~200 150
C081
St a ll preve n tio n level during running
0~200 000
Parameter and Function List (Part 5)
- 26 -
HLP-C
+
Inverters
Function
code
Function
Set Range & Function
Explanation
Factory
Setting
C082
St a ll preve n tio n level during decel.
0~200 180
C083
Over torque detect level
0~200 000
C084
Over torque detect time
0.1~20.0 01.0
C085
Rated Motor Voltage
* 220/380
C086
Rated Motor Current
* *
C087 Motor poles 02~60 04
C088
Rated Motor Revolution
0~9999 1440
C089
Motor no-load current
0~100 40
C090 Slip compensation 0~1.0 0.000
C091 DC braking voltage 0.0~20.0 2.0
C092
DC braking time at starting
0.0~25.0 0.0
C093
DC braking time at stopping
0.0~25.0 0.0
C094 Speed search time 0.0~20.0 5.0
C095
Speed search current level
0~200 150
C096
Restart after instantaneous stop
0~1 0
C097
Allowable power­off time
0.1~5.0 0.5
C098
Number of abnormal restart
00~10 00
C099
Auto voltage regulation function
0:Invalid 1:Effective 1
C100
Auto torgue compensation
0.0~10.0 2.0
Parameter and Function List (Part 6)
Loading...
+ 73 hidden pages