HITACHI WJ200 User Manual

WJ200
Series Inverter
Quick Reference Guide
Single-phase Input 200V class
Three-phase Input 200V class
Three-phase Input 400V class
Manual Number: NT3251X
May 2010
Refer to the user manual for detail
UL Cautions, Warnings and Instructions xii Warnings and Cautions for Troubleshooting and Maintenance
The warnings and instructions in this section summarizes the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories
WARNING: Use 60/75C Cu wire only. (for models: WJ200-001L, 002L, 004L, 007L, 015S, 022S,
004H, 007H, 015H, 022H, 030H)
WARNING: Use 75C Cu wire only. (for models: WJ200-001S, -002S, -004S, -007S, -015L, -022L,
-037L, -055L, -075L, -110L, -150L, -040H, -055H, -075H, -110H and -150H)
WARNING: Suitable for use on a circuit capable of delivering not more than 100,000 rms
Symmetrical Amperes, 240 or 480V maximum.
WARNING: When protected by CC, G, J, or R class Fuses, or when Protected By A Circuit Breaker
Having An Interrupting Rating Not Less Than 100,000 rms Symmetrical Amperes, 240 or 480 Volts Maximum.
WARNING: Install device in pollution degree 2 environment.
WARNING: Maximum Surrounding Air Temperature 50C
WARNING: Solid state motor overload protection is provided in each model
WARNING: Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electric Code and any additional local codes
guidelines.
1
Terminal symbols and Screw size
Inverter Model Screw Size
WJ200-001S WJ200-002S
M3.5 1.0 AWG16 (1.3mm
Required
Torque (N-m)
Wire range
2
) WJ200-004S WJ200-007S M4 1.4 AWG12 (3.3mm2) WJ200-015S WJ200-022S
M4 1.4 AWG10 (5.3mm
2
)
WJ200-001L WJ200-002L WJ200-004L
M3.5 1.0 AWG16 (1.3mm
2
)
WJ200-007L WJ200-015L M4 1.4 AWG14 (2.1mm2) WJ200-022L M4 1.4 AWG12 (3.3mm2) WJ200-037L M4 1.4 AWG10 (5.3mm2)
WJ200-055L
WJ200-075L
M5 3.0 AWG6 (13mm
2
)
WJ200-110L M6 3.9 to 5.1 AWG4 (21mm2)
WJ200-150L M8 5.9 to 8.8 AWG2 (34mm2) WJ200-004H
WJ200-007H
M4 1.4 AWG16 (1.3mm
2
) WJ200-015H WJ200-022H WJ200-030H
M4 1.4 AWG14 (2.1mm
2
)
WJ200-040H M4 1.4 AWG12 (3.3mm2) WJ200-055H WJ200-075H WJ200-110H WJ200-150H
M5 3.0 AWG10 (5.3mm
M6 3.9 to 5.1 AWG6 (13mm
2
)
2
)
2
Fuse Sizes
The inverter shall be connected with a UL Listed Cartridge Nonrenewable fuse, rated 600Vac with the current ratings as shown in the table below.
Inverter Model Type Rating
WJ200-001S WJ200-002S WJ200-004S WJ200-007S 15A, AIC 200kA
WJ200-015S WJ200-022S
WJ200-001L WJ200-002L WJ200-004L
WJ200-007L WJ200-015L WJ200-022L 20A, AIC 200kA
WJ200-037L 30A, AIC 200kA WJ200-055L WJ200-075L
WJ200-110L WJ200-150L
WJ200-004H WJ200-007H WJ200-015H WJ200-022H WJ200-030H WJ200-040H WJ200-055H WJ200-075H WJ200-110H WJ200-150H
Class J
10A, AIC 200kA
30A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
40A, AIC 200kA
80A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
20A, AIC 200kA
40A, AIC 200kA
3
A
_
Inverter Specification Label
The Hitachi WJ200 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, and application safety requirements.
Model name
Input ratings
Output ratings
MFG number
Inverter Specification Label
05A
-001SF 200-240
200-240
T12345_A_-001
Ver:2.0
2.0/1.3
1.2 /1. 0 1005
The model number for a specific inverter contains useful information about its operating characteristics. Refer to the model number legend below:
WJ200
Series name
001 S F
Configuration type
F=with keypad
Input voltage:
S=Single-phase 200V class L=Three-phase 200V class H=Three-phase 400V class
pplicable motor capacity in kW
001=0.1kW 037=3.7kW 002=0.2kW 040=4.0kW 004=0.4kW 055=5.5kW 007=0.75kW 075=7.5kW 015=1.5kW 110=11kW 022=2.2kW 150=15kW 030=3.0kW
4
WJ200 Inverter Specifications
Model-specific tables for 200V and 400V class inverters
The following tables are specific to WJ200 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page in this chapter class groups. Footnotes for all specification tables follow the table below.
Item Single-phase 200V class Specifications WJ200 inverters, 200V models 001SF 002SF 004SF 007SF 015SF 022SF Applicable motor size
*2
HP
Rated capacity (kVA)
240V
Rated input voltage Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Starting torque *6 200% at 0.5Hz Braking
DC braking Variable operating frequency, time, and braking force
Without resistor
With resistor 150% 100%
VT 0.2 0.4 0.55 1.1 2.2 3.0 kW CT 0.1 0.2 0.4 0.75 1.5 2.2 VT CT VT 0.4 0.6 1.2 2.0 3.3 4.1 200V CT 0.2 0.5 1.0 1.7 2.7 3.8 VT 0.4 0.7 1.4 2.4 3.9 4.9 CT 0.3 0.6 1.2 2.0 3.3 4.5
VT 1.2 1.9 3.5 6.0 9.6 12.0 Rated output current (A) CT 1.0 1.6 3.0 5.0 8.0 11.0
kg 1.0 1.0 1.1 1.6 1.8 1.8 Weight lb 2.2 2.2 2.4 3.5 4.0 4.0
1/4 1/2 3/4 1.5 3 4 1/8 1/4 1/2 1 2 3
Single-phase: 200V-15% to 240V +10%, 50/60Hz 5%
100%:
50%:
50Hz
60Hz
apply to both voltage
70%:50Hz
50%:
60Hz
20%:50Hz
20%:
60Hz
5
WJ200 Inverter Specifications, continued…
Item Three-phase 200V class Specifications WJ200 inverters, 200V models Applicable motor size *2
HP
Rated capacity (kVA)
240V
Rated input voltage Rated output voltage *3 Three-phase: 200 to 240V (proportional to input voltage)
Starting torque *6 200% at 0.5Hz Braking
DC braking Variable operating frequency, time, and braking force
Without resistor
With resistor 150% 100%
VT 0.2 0.4 0.75 1.1 2.2 3.0 kW CT 0.1 0.2 0.4 0.75 1.5 2.2 VT CT VT 0.4 0.6 1.2 2.0 3.3 4.1 200V CT 0.2 0.5 1.0 1.7 2.7 3.8 VT 0.4 0.7 1.4 2.4 3.9 4.9 CT 0.3 0.6 1.2 2.0 3.3 4.5
VT 1.2 1.9 3.5 6.0 9.6 12.0 Rated output current (A) CT 1.0 1.6 3.0 5.0 8.0 11.0
kg 1.0 1.0 1.1 1.2 1.6 1.8 Weight lb 2.2 2.2 2.4 2.6 3.5 4.0
Item Three-phase 200V class Specifications WJ200 inverters, 200V models Applicable motor size *2
HP
Rated capacity (kVA)
240V
Rated input voltage Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Starting torque *6 200% at 0.5Hz
Without resistor
With resistor 150%
DC braking Variable operating frequency, time, and braking force
VT 5.5 7.5 11 15 18.5 kW CT 3.7 5.5 7.5 11 15 VT CT VT 6.7 10.3 13.8 19.3 20.7 200V CT 6.0 8.6 11.4 16.2 20.7 VT 8.1 12.4 16.6 23.2 24.9 CT 7.2 10.3 13.7 19.5 24.9
VT 19.6 30.0 40.0 56.0 69.0 Rated output current (A) CT 17.5 25.0 33.0 47.0 60.0
Kg 2.0 3.3 3.4 5.1 7.4 Weight lb 4.4 7.3 7.5 11.2 16.3
001LF 002LF 004LF 007LF 015LF 022LF
1/4 1/2 1 1.5 3 4 1/8 1/4 1/2 1 2 3
Three-phase: 200V-15% to 240V +10%, 50/60Hz 5%
60Hz
60Hz
20%: 20%:
100%:
50%:
037LF 055LF 075LF 110LF 150LF
7.5 10 15 20 25 5 7.5 10 15 20
Single-phase: 200V-15% to 240V +10%, 50/60Hz 5%
100%:
50%:
50Hz
60Hz
50Hz
60Hz
70%:50Hz 50%:
70%:50Hz 50%:
 
Braking
50Hz 60Hz
6
WJ200 Inverter Specifications, continued…
Item Three-phase 400V class Specifications WJ200 inverters, 400V models Applicable motor size *2
HP
Rated capacity (kVA)
480V
Rated input voltage Rated output voltage *3 Three-phase: 200 to 240V (proportional to input voltage)
Starting torque *6 200% at 0.5Hz
Without resistor
With resistor 150%
DC braking Variable operating frequency, time, and braking force
VT 0.75 1.5 2.2 3.0 4.0 5.5 kW CT 0.4 0.75 1.5 2.2 3.0 4.0 VT 1 2 3 4 5 7.5 CT 1/2 1 2 3 4 5 VT 1.3 2.6 3.5 4.5 5.7 7.3 380V CT 1.1 2.2 3.1 3.6 4.7 6.0 VT 1.7 3.4 4.4 5.7 7.3 9.2 CT 1.4 2.8 3.9 4.5 5.9 7.6
VT 2.1 4.1 5.4 6.9 8.8 11.1 Rated output current (A) CT 1.8 3.4 4.8 5.5 7.2 9.2
kg 1.5 1.6 1.8 1.9 1.9 2.1 Weight lb 3.3 3.5 4.0 4.2 4.2 4.6
Item Three-phase 400V class Specifications WJ200 inverters, 400V models Applicable motor size *2
HP
Rated capacity (kVA)
480V
Rated input voltage Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Starting torque *6 200% at 0.5Hz
Without resistor
With resistor 150%
DC braking Variable operating frequency, time, and braking force
VT 7.5 11 15 18.5 kW CT 5.5 7.5 11 15 VT 10 15 20 25 CT 7.5 10 15 20 VT 11.5 15.1 20.4 25.0 380V CT 9.7 11.8 15.7 20.4 VT 14.5 19.1 25.7 31.5 CT 12.3 14.9 19.9 25.7
VT 17.5 23.0 31.0 38.0 Rated output current (A) CT 14.8 18.0 24.0 31.0
kg 3.5 3.5 4.7 5.2 Weight lb 7.7 7.7 10.4 11.5
004HF 007HF 015HF 022HF 030HF 040HF
Three-phase: 200V-15% to 240V +10%, 50/60Hz 5%
100%:
50%:
055HF 075HF 110HF 150HF
Single-phase: 200V-15% to 240V +10%, 50/60Hz 5%
100%:
50%:
50Hz
60Hz
50Hz
60Hz
70%:50Hz
60Hz
50%:
Braking
Braking
7
The following table shows which models need derating.
1-ph 200V class Need
derating
WJ200-001S WJ200-002S WJ200-004S WJ200-007S WJ200-015S WJ200-022S
9need derating
−:need no derating
9 9
Use the following derating curves to help determine the optimal carrier frequency setting for your inverter and find the output current derating. Be sure to use the proper curve for your particular WJ200 inverter model number.
3-ph 200V class Need
derating
WJ200-001L WJ200-002L WJ200-004L WJ200-007L WJ200-015L WJ200-022L WJ200-037L WJ200-055L WJ200-075L WJ200-110L WJ200-150L
9 9
9
9 9 9
3-ph 400V class Need
derating
WJ200-004H WJ200-007H WJ200-015H WJ200-022H WJ200-030H WJ200-040H WJ200-055H WJ200-075H WJ200-110H WJ200-150H
9 9
9
9 9 9
8
Basic System Description
A motor control system will obviously include a motor and inverter, as well as a circuit breaker or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now. But a system can also have a variety of additional components. Some can be for noise suppression, while others may enhance the inverter’s braking performance. The figure and table below show a system with all the
optional components you might need in your finished application.
L1 L2 L3
+1
Inverter
GND
T1 T2 T3
Breaker, MCCB or GFI
+
From power supply
Name Function
Breaker / disconnect
Input-side AC Reactor
Radio noise filter
EMC filter (for CE applications, see Appendix D)
Radio noise filter (use in non-CE applications) DC link choke
Radio noise filter
Output-side AC Reactor
LCR filter
A molded-case circuit breaker (MCCB), ground fault interrupter (GFI), or a fused disconnect device. NOTE: The installer must refer to the NEC and local codes to ensure safety and compliance. This is useful in suppressing harmonics induced on the power supply lines and for improving the power factor.
WARNING: Some applications must use an input-side AC
Reactor to prevent inverter damage. See Warning on next page. Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on output). Reduces the conducted noise on the power supply wiring between the inverter and the power distribution system. Connect to the inverter primary (input) side. This capacitive filter reduces radiated noise from the main power wires in the inverter input side.
Suppress harmonics generated by the inverter. However, it will not protect the input diode bridge rectifier. Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on input). This reactor reduces the vibration in the motor caused by the inverter’s switching waveforms, by smoothing the waveform to approximate commercial power quality. It is also useful to reduce harmonics when wiring from the inverter to the motor is more than 10m in length. Sine wave shaping filter for output side.
Motor
Thermal switch
9
Determining Wire and Fuse Sizes
The maximum motor currents in your application determines the recommended wore size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other components shown in the “Basic System Description” on page 2-7. The “Signal Lines” column applies to any wire connecting to the two green connectors just inside the front cover panel.
Motor Output Wiring
kW HP
VT CT VT CT
0.2 0.1 ¼ 1/8
0.4 0.2 ½ ¼
0.55
0.4 ¾ ½
1.1
0.75
1.5 1
2.2 1.5 3 2
3.0 2.2 4 3
0.2 0.1 ¼ 1/8
0.4 0.2 ½ ¼
0.75
0.4 1 ½
1.1
0.75
1.5 1
2.2 1.5 3 2
3.0 2.2 4 3
5.5 3.7 7.5 5
7.5 5.5 10 7.5 11 7.5 15 10
15 11 20 15
18.5
15 25 20
0.75
0.4 1 ½
1.5
0.75
2 1
2.2 1.5 3 2
3.0 2.2 4 3
4.0 3.0 5 4
5.5 4.0 7.5 5
7.5 5.5 10 7.5 11 7.5 15 10
15 11 20 15
18.5
15 25 20
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
Note 2: Be sure to consider the capacity of the circuit breaker to be used. Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m). Note 4: Use 18 AWG / 0.75mm
Inverter Model
Power Lines Signal Lines
WJ200-001SF WJ200-002SF WJ200-004SF
WJ200-007SF
WJ200-015SF WJ200-022SF
AWG16 / 1.3mm
(75C only)
AWG12 / 3.3mm
(75C only)
AWG10 / 5.3mm
WJ200-001LF WJ200-002LF WJ200-004LF
AWG16 / 1.3mm
WJ200-007LF
WJ200-015LF
WJ200-022LF
WJ200-037LF
WJ200-055LF WJ200-075LF
WJ200-110LF
WJ200-150LF
AWG14 / 2.1mm
(75C only)
AWG12 / 3.3mm
(75C only)
AWG10 / 5.3mm
(75C only)
AWG6 / 13mm
(75C only)
AWG4 / 21mm
(75C only)
AWG2 / 34mm
(75C only)
WJ200-004HF WJ200-007HF
AWG16 / 1.3mm WJ200-015HF WJ200-022HF WJ200-030HF
WJ200-040HF
WJ200-055HF WJ200-075HF
WJ200-110HF
WJ200-150HF
AWG14 / 2.1mm
AWG12 / 3.3mm
(75C only)
AWG10/ 5.3mm
(75C only)
AWG6 / 13mm
(75C only)
AWG6 / 13mm
(75C only)
connector sized for the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector manufacturer.
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
terminals).
Applicable equipment
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
2
10A
2
20A
2
30A
2
2
2
10A
15A
20A
2
30A
60A
80A
2
2
2
18 to 28
AWG / 0.14
to 0.75 mm2
shielded wire
(see Note 4)
80A
2
2
2
2
2
2
10A
15A
30A
50A
50A
10
RB
-
RB
-
Wire the Inverter Input to a Supply
Step 6: In this step, you will connect wiring to the input of the inverter. First, you must
6
determine whether the inverter model you have required three-phase power only, or
single-phase power only. All models have the same power connection terminals [R/L1],
[S/L2], and [T/L3]. So you must refer to the specifications label (on the side of the inverter) for the acceptable power source types! For inverters that can accept single-phase power and are connected that way, terminal [S/L2] will remain unconnected.
Note the use of ring lug connectors for a secure connection.
Single-phase 200V 0.1 to 0.4kW
Three-phase 200V 0.1 to 0.75kW
L1
Single-phase 200V 0.75 to 2.2kW
Three-phase 200V 1.5, 2.2kW Three-phase 400V 0.4 to 3.0kW
Chassis Ground (M4)
Chassis Ground (M4)
N U/T1 V/T2 W/T3
Power input Output to Motor
L1
Power input Output to Motor
Single-phase Three-phase
+1
+
R/L1
S/L2 T/L3 U/T1 V/T2 W/T3
Power input Output to Motor
Single-phase Three-phase
+1
+
N U/T1 V/T2 W/T3
R/L1
S/L2 T/L3 U/T1 V/T2 W/T3
Power input Output to Motor
RB
RB
PD/+1
PD/+1
P/+ N/
P/+ N/
-
-
11
Three-phase 200V 3.7kW Three-phase 400V 4.0kW
PD/+1
P/+
N/-
W/T3 V/T2 U/T1
W/T3 V/T2 U/T1
G G RB
S/L2
S/L2
P/+
RB
T/L3
T/L3
N/
-
Chassis Ground (M4)
Three-phase 200V 5.5, 7.5kW Three-phase 400V 5.5, 7.5kW
R/L1
Power input Output to Motor
R/L1
PD/+1
Power input Output to Motor
12
Three-phase 200V 11kW
Three-phase 400V 11, 15kW
Three-phase 200V 15kW
NOTE: An inverter powered by a portable power generator may receive a distorted power
waveform, overheating the generator. In general, the generator capacity should be five times that of the inverter (kVA).
R/L1
PD/+1
Power input Output to Motor
R/L1
PD/+1
Power input Output to Motor
S/L2
P/+
S/L2
P/+
T/L3
N/
T/L3
N/
-
-
W/T3 V/T2 U/T1
G G RB
W/T3 V/T2 U/T1
G G RB
13
Hz A
Using the Front Panel Keypad
Please take a moment to familiarize yourself with the keypad layout shown in the figure below. The display is used in programming the inverter’s parameters, as well as monitoring specific parameter values during operation.
(5) Monitor LED [Hz]
(4) RUN LED
(8) 7-seg LED
(6) Monitor LED [A]
RUN
PWR
(7) Run command LED
(9) RUN key
(11) Escape key
8888
RUN
1
STOP/
RESET
ALM
PRG
ESC
2
SET
(13) Down key (12) Up key
(14) Set key
Key and Indicator Legend
Items Contents
(1) POWER LED Turns ON (Green) while the inverter is powered up. (2) ALARM LED Turns ON (Red) when the inverter trips.
(3) Program LED
(4) RUN LED Turns ON (Green) when the inverter is driving the motor. (5) Monitor LED [Hz] Turns ON (Green) when the displayed data is frequency related. (6) Monitor LED [A] Turns ON (Green) when the displayed data is current related. (7) Run command LED Turns ON (Green) when a Run command is set to the operator. (Run key is effective.) (8) 7-seg LED Shows each parameter, monitors etc.
(9) Run key Makes inverter run. (10) Stop/reset key
(11) ESC key
(12) Up key (13) Down key
(14) SET key
(15) USB connector Connect USB connector (mini-B) for using PC communication (16) RJ45 connector Connect RJ45 jack for remote operator
¾ Turns ON (Green) when the display shows changeable parameter. ¾ Blinks when there is a mismatch in setting.
¾ Makes inverter decelerates to a stop. ¾ Reset the inverter when it is in trip situation ¾ Go to the top of next function group, when a function mode is shown ¾ Cancel the setting and return to the function code, when a data is shown ¾ Moves the cursor to a digit left, when it is in digit-to-digit setting mode ¾ Pressing for 1 second leads to display data of d001, regardless of current display. ¾ Increase or decrease the data. ¾ Pressing the both keys at the same time gives you the digit-to-digit edit. ¾ Go to the data display mode when a function code is shown ¾ Stores the data and go back to show the function code, when data is shown. ¾ Moves the cursor to a digit right, when it is in digit-to-digit display mode
(1) POWER LED
(2) ALARM LED
(3) Program LED
(15) USB connector
(10) Stop/reset key
(16) RJ45 connector
14
Keys, Modes, and Parameters
The purpose of the keypad is to provide a way to
change modes and parameters. The term function
applies to both monitoring modes and parameters.
These are all accessible through function codes that are
primary 4-character codes. The various functions are separated into related groups identifiable by the left-most character, as the table shows.
Function
Group
“D” Monitoring functions Monitor “F” Main profile parameters “A” Standard functions “B” Fine tuning functions “C” Intelligent terminal functions “H” Motor constant related functions “P” Pulse train input, torque, EzSQ, and
“U” User selected parameters “E” Error codes
Type (Category) of Function Mode to Access
communication related functions
You can see from the following page how to monitor and/or program the parameters.
Keypad Navigation Map
8888
RUN
ESC
Program Program Program Program Program
Program
Program
STOP/
1
RESET
2
SET
PRG LED
Indicator
z z z z z
z
z
RUN
Hz A
PWR
ALM
PRG
The WJ200 Series inverter drives have many programmable functions and parameters. Chapter 3 will cover these in detail, but you need to access just a few items to perform the powerup test. The menu structure makes use of function codes and parameter codes to allow programming and monitoring with only a 4-digit display and keys and LEDs. So, it is important to become familiar with the basic navigation map of parameters and functions in the diagram below. You may later use this map as a reference.
15
Group "d"
Func. code display
d001
V U
d002
d104
Group "F"
Func. code display
F001
V U
SET
SET
Func. code display
SET
Func. code display
ESC
: Moves to data display
ESC
: Jumps to the next group
ESC
Save
SET ESC
0.00
50.00
Func. code display
F002
F004
Group "A"
A001
V U
A002
SET
ESC
SET ESC
Data display (F001 to F003) Data does not blink because of real time synchronizing
: Saves the data in EEPROM
SET
and returns to func. code display.
ESC
: Returns to func. code display without saving data.
SET ESC
Group "b"
A165
b001
ESC
Data display When data is changed, the display starts blinking, which means that new data has not been activated yet.
SET ESC
: Saves the data in EEPROM and
SET
returns to func. code display.
: Cancels the data change and
ESC
returns to func. code display.
50.01
00
01
U V
Press the both up and down key at the same
time in func. code or data display, then
single-digit edit mode will be enabled.
Refer to 2-34 for further information.
NOTE: Pressing the [ESC] key will make the display go to the top of next function group,
regardless the display contents. (e.g. A021 Æ [ESC] Æ b001)
16
[Setting example]
After power ON, changing from 0.00 display to change the b083 (carrier frequency) data.
d Press [ESC] key to show
the function code
d001
ESC
ESC
SET
c Data of d001 will be shown on the
display after the first power ON
0.00
e Press [ESC] key to move
F001
on to the function group F001
ESC
V
f Press [ESC] key twice to move
on to the function group b001.
b001
g Press Up key to change increase
function code (b001
U
h Press SET key to display the data of b083
SET
Æ b083)
b083
i Press up key to increase the
data (5.0 Æ 12.0)
Display is solid lighting.
5.0
ESC
U
V
i Press SET key to set
and save the data
When data is changed, the display starts blinking, which means that new data has not been activated yet.
SET
12.0
:Cancels the change and moves back to the function code
ESC
:Fix and stores the data and moves back to the function code
SET
Function code dxxx are for monitor and not possible to change.
Function codes Fxxx other than F004 are reflected on the performance just after changing the data (before pressing SET key), and there will be no blinking.
17
ESC key
SET key
U key
V key
Note Keep pressing for more than 1 second leads to d001 display, regardless the display situation. But note that the display will circulates while keep pressing the [ESC] key because of the original function of the key. (e.g. F001 Æ A001 Æ b001 Æ C001 ÆÆ displays 50.00 after 1 second)
When a function
code is shown…
Move on to the next function group
Move on to the data display
Increase function code Decrease function code
When a data is shown…
Cancels the change and moves back to the function code Fix and stores the data and moves back to the function code
Increase data value
Decrease data value
18
Connecting to PLCs and Other Devices
Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configuration. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device. In a simple application such as single-conveyor speed control, a Run/Stop switch and potentiometer will give the operator all the required control. In a sophisticated application, you may have a
programmable logic controller (PLC) as the system controller, with several connections to
the inverter.
It is not possible to cover all the possible types of application in this manual. It will be necessary for you to know the electrical characteristics of the devices you want to connect to the inverter. Then, this section and the following sections on I/O terminal functions can help you quickly and safely connect those devices to the inverter.
CAUTION: It is possible to damage the inverter or other devices if your application
exceeds the maximum current or voltage characteristics of a connection point.
The connections between the inverter and other devices rely on the electrical input/output characteristics at both ends of each connection, shown in the diagram to the right. The inverter’s configurable inputs accept either a sourcing or sinking output from an external
Other device
Input
circuit
Output
circuit
signal return
signal return
WJ200 inverter
Output
circuit
Input
circuit
device (such as PLC). This chapter shows the inverter’s internal electrical component(s) at each I/O terminal. In some cases, you will need to insert a power source in the interface wiring.
Other device WJ200 inverter
24V
P24
+ -
In order to avoid equipment damage and get your application running smoothly, we recommend drawing a schematic of each connection between the inverter and the other device. Include the internal components of each device in the schematic, so that it makes a complete circuit loop.
1
2
3
Input
circuits
After making the schematic, then:
1. Verify that the current and voltage for each
connection is within the operating limits of
GND
7
L
each device.
2. Make sure that the logic sense (active high or active low) of any ON/OFF connection is correct.
3. Check the zero and span (curve end points) for analog connections, and be sure the scale factor from input to output is correct.
4. Understand what will happen at the system level if any particular device suddenly loses power, or powers up after other devices.
19
A
r
(L1)
(L2)
A
A
Example Wiring Diagram
The schematic diagram below provides a general example of logic connector wiring, in addition to basic power and motor wiring converted in Chapter 2. The goal of this chapter is to help you determine the proper connections for the various terminals shown below for your application needs.
Breaker, MCCB or GFI
Power source, 3-phase or 1-phase, per inverter model
Intelligent inputs,
NOTE: For the wiring of intelligent I/O and analog inputs, be sure to use twisted pair / shielded cable. Attach the shielded wire for each signal to its respective common terminal at the inverter end only. Input impedance of each intelligent input is
4.7k
7 terminals
Thermistor
Short bar (Source type)
GND for logic inputs
Forward
R
S
T
N(L3)
P24
1
2
3/GS1 4/GS2 5/PTC
6
7/EB
PLC
L
Input
circuits
[5] configurable as discrete input or thermistor input
L
24V
+ -
WJ200
Output circuit
U(T1)
V(T2)
W(T3)
PD/+1
P/+
RB
N/-
AL1
AL0
AL2
11/EDM
Relay contacts, type 1 Form C
Open collector output
12
DC reactor (optional)
Brake resistor (optional)
Freq. arrival signal
Load
Load
Braking
unit (optional)
+
Moto
Meter
Meter
nalog reference
0~10VDC
4~20mA
Pulse train input 24Vdc 32kHz max.
GND for analog signals
EO
AM
H
O
OI
EA
L
L
L
pprx.10k
pprx.100
Termination resistor (200) (Change by slide switch)
RS485
transceiver
L
10Vdc
+
L
L
RS485
transceiver
L
USB
transceiver
L
Option port
controller
L
CM2
GND for logic outputs
SP
Serial communication port (RS485/ModBus)
SN
NOTE: Common for
RJ45 port (Optional operator port)
USB (mini-B) port (PC communication port) USB power: Self power
Option port connector
RS485 is “L”.
20
p
p
p
put
5 4 6 SN 7
OI L H O EA SP EO
A
Control Logic Signal Specifications
The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below.
Relay contacts
L2 AL1 AL0
RS485
comm.
Logic inputs
12 11 AM CM2
PLC
P24 1 L 3 2
Short bar
ut
Logic
out
ut
Pulse
RS485 comm.
Pulse
Train
out
Train
input
Analog
ut
in
Analog
out
Terminal Name Description Ratings
P24 +24V for logic inputs 24VDC, 100mA. (do not short to terminal L) PLC Intelligent input common Factory set: Source type for –FE and –FU
models (connecting [P24] to [1]~[7] turns each input ON). To change to sink type, remove the short bar between [PLC] and [L], and connect it between [P24] and [L]. In this case, connecting [L] to [1]~[7] makes each
input ON. 1 2 3/GS1 4/GS2 5/PTC 6 7/EB GS1(3) Safe stop input GS1 GS2(4) Safe stop input GS2 PTC(5) Motor thermistor input Connect motor thermistor between PTC and
EB(7) Pulse train input B 2kHz max.
EA Pulse train input A 32kHz max.
L (in upper row) *1 GND for logic inputs Sum of input [1]~[7] currents (return) 11/EDM Discrete logic outputs [11]
12 Discrete logic outputs [12] 50mA max. ON state current,
CM2 GND for logic output 100 mA: [11], [12] current return AM Analog voltage output 0~10VDC 2mA maximum EO Pulse train output 10VDC 2mA maximum
L (in bottom row) *2 GND for analog signals Sum of [OI], [O], and [H] currents (return)
Discrete logic inputs
(Terminal [3],[4],[5] and [7] have dual function. See following description and related pages for the details.)
(Terminal [11] has dual function. See following description and related pages for the details.)
27VDC max. (use PLC or an external supply
referenced to terminal L)
Functionality is based on ISO13849-1
See appendix for the details.
L terminal to detect the motor temperature.
Set 19 in C005.
Common is [PLC]
Common is [L]
50mA max. ON state current,
27 VDC max. OFF state voltage
Common is CM2
In case the EDM is selected, the functionality
is based on ISO13849-1
4VDC max. ON state voltage depression
27 VDC max. OFF state voltage
Common is CM2
32kHz maximum
21
(
(
)
Terminal Name Description Ratings
OI Analog current input 4 to 19.6 mA range, 20 mA nominal,
input impedance 100 O Analog voltage input 0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k H +10V analog reference 10VDC nominal, 10mA max. SP, SN Serial communication terminal For RS485 Modbus communication.
AL0, AL1, AL2 *3 Relay common contact 250VAC, 2.5A (R load) max.
250VAC, 0.2A (I load, P.F.=0.4) max.
100VAC, 10mA min.
30VDC, 3.0A (R load) max.
30VDC, 0.7A (I load, P.F.=0.4) max.
5VDC, 100mA min.
Note 1: The two terminals [L] are electrically connected together inside the inverter. Note 2: We recommend using [L] logic GND (to the right) for logic input circuits and [L]
analog GND (to the left) for analog I/O circuits.
Note 3: Refer to page 39 for details of trip signals.
Wiring sample of control logic terminal (source logic)
       
SN 7/EB 6 5/PTC 4/GS2 3/GS1
SP EO EA H O OI L AM CM2 12 11/EDM
      
Variable resistor for freq. setting
1k-2k)
Freq. meter
Note: If relay is connected to intelligent output, install a diode across the relay coil
(reverse-biased) in order to suppress the turn-off spike.
 
Short bar
source logic
1 L PLC P24
RY
RY
22
1 2
 
Sink/source logic of intelligent input terminals
Sink or source logic is switched by a short bar as below.
  
Sink logic
L 1 2
PLC P24
 
Short bar
Wire size for control and relay terminals
Use wires within the specifications listed below. For safe wiring and reliabi li ty, it is recommended to use ferrules, but if solid or stranded wire is used, stripping length should be 8mm.
Relay output terminal
Solid
Control logic terminal
Relay terminal
2
mm
(AWG)
0.2 to 1.5
(AWG 24 to 16)
0.2 to 1.5
(AWG 24 to 16)
mm2 (AWG)
(AWG 24 to 17)
(AWG 24 to 17)
Source logic
Stranded
0.2 to 1.0
0.2 to 1.0
PLC P24 L
Short bar
Control logic terminal
8mm
Ferrule
mm2 (AWG)
0.25 to 0.75
(AWG 24 to 18)
0.25 to 0.75
(AWG 24 to 18)
23
Recommendedferrule
For safe wiring and reliability, it is recommended to use following ferrules.
Wire size
2
mm
(AWG)
0.25 (24) AI 0.25-8YE 12.5 0.8 2.0
0.34 (22) AI 0.34-8TQ 12.5 0.8 2.0
0.5 (20) AI 0.5-8WH 14 1.1 2.5
0.75 (18) AI 0.75-8GY 14 1.3 2.8
* Supplier: Phoenix contact
Crimping pliers: CRIPMFOX UD 6-4 or CRIMPFOX ZA 3
Howtoconnect?
(1) Push down an orange actuating lever by a slotted screwdriver (width 2.5mm max.).
(2) Plug in the conductor. (3) Pull out the screwdriver then the conductor is fixed.
Model name of
ferrule *
L [mm] Φd [mm] ΦD [mm]
Push down an orange actuating lever.
Plug in the conductor.
Φd
8
L
ΦD
Pull out the screwdriver to fix the conductor.
24
Intelligent Terminal Listing
Intelligent Inputs
Use the following table to locate pages for intelligent input material in this chapter.
Input Function Summary Table
Symbol Code Function Name Page
FW 00 Forward Run/Stop
RV 01 Reverse Run/Stop CF1 02 Multi-speed Select, Bit 0 (LSB) CF2 03 Multi-speed Select, Bit 1 CF3 04 Multi-speed Select, Bit 2 CF4 05 Multi-speed Select, Bit 3 (MSB)
JG 06 Jogging
DB 07 External DC braking SET 08 Set (select) 2nd Motor Data 2CH 09 2-stage Acceleration and Deceleration FRS 11 Free-run Stop EXT 12 External Trip
USP 13 Unattended Start Protection
CS 14 Commercial power source switchover SFT 15 Software Lock
AT 16 Analog Input Voltage/Current Select
RS 18 Reset Inverter
PTC 19 PTC thermistor Thermal Protection
STA 20 Start (3-wire interface)
STP 21 Stop (3-wire interface)
F/R 22 FWD, REV (3-wire interface) PID 23 PID Disable
PIDC 24 PID Reset
UP 27 Remote Control UP Function
DWN 28 Remote Control Down Function UDC 29 Remote Control Data Clearing OPE 31 Operator Control
SF1~SF7 32~38 Multi-speed Select,Bit operation Bit 1~7
OLR 39 Overload Restriction Source Changeover
TL 40 Torque Limit Selection TRQ1 41 Torque limit switch 1 TRQ2 42 Torque limit switch 2
BOK 44 Brake confirmation
LAC 46 LAD cancellation
PCLR 47 Pulse counter clear
ADD 50 ADD frequency enable
F-TM 51 Force Terminal Mode
ATR 52 Permission for torque command input
KHC 53 Clear watt-hour data
MI1~MI7 56~62 General purpose input (1)~(7)
AHD 65 Analog command hold
CP1~CP3 66~68 Multistage-position switch (1)~(3)
ORL 69 Limit signal of zero-return
ORG 70 Trigger signal of zero-return
SPD 73 Speed/position changeover GS1 77 STO1 input (Safety related signal) GS2 78 STO2 input (Safety related signal)
485 81 Starting communication signal
PRG 82 Executing EzSQ program
HLD 83 Retain output frequency
ROK 84 Permission of Run command
EB 85 Rotation direction detection (phase B)
25
Use the following table to locate pages for intelligent input material in this chapter.
Symbol Code Function Name Page
DISP 86 Display limitation
NO 255 No assign
Intelligent Outputs
Use the following table to locate pages for intelligent output material in this chapter.
Symbol Code Function Name Page
RUN 00 Run Signal
FA1 01 Frequency Arrival Type 1–Constant Speed FA2 02 Frequency Arrival Type 2–Over frequency
OL 03 Overload Advance Notice Signal
OD 04 PID Deviation error signal
AL 05 Alarm Signal
FA3 06 Frequency Arrival Type 3–Set frequency
OTQ 07 Over/under Torque Threshold
UV 09 Undervoltage
TRQ 10 Torque Limited Signal
RNT 11 Run Time Expired ONT 12 Power ON time Expired THM 13 Thermal Warning
BRK 19 Brake Release Signal
BER 20 Brake Error Signal
ZS 21 Zero Hz Speed Detection Signal
DSE 22 Speed Deviation Excessive POK 23 Positioning Completion
FA4 24 Frequency Arrival Type 4–Over frequency FA5 25 Frequency Arrival Type 5–Set frequency OL2 26 Overload Advance Notice Signal 2
ODc 27 Analog Voltage Input Disconnect Detection OIDc 28 Analog Voltage Output Disconnect Detection
FBV 31 PID Second Stage Output NDc 32 Network Disconnect Detection
LOG1~3 33~35 Logic Output Function 1~3
WAC 39 Capacitor Life Warning Signal WAF 40 Cooling Fan Warning Signal
FR 41 Starting Contact Signal
OHF 42 Heat Sink Overheat Warning
LOC 43 Low load detection
MO1~3 44~46 General Output 1~3
IRDY 50 Inverter Ready Signal
FWR 51 Forward Operation
RVR 52 Reverse Operation
MJA 53 Major Failure Signal
WCO 54 Window Comparator for Analog Voltage Input WCOI 55 Window Comparator for Analog Current Input FREF 58 Frequency Command Source
REF 59 Run Command Source
SETM 60 2nd Motor in operation
EDM 62 STO (Safe Torque Off) Performance Monitor
OP 63 Option control signal
no 255 Not used
Input Function Summary Table
Input Function Summary Table
(Output terminal 11 only)
26
Using Intelligent Input Terminals
Terminals [1], [2], [3], [4], [5], [6] and [7] are identical, programmable inputs for general use.
The input circuits can use the inverter’s internal (isolated) +24V field supply or an external power supply. This section describes input circuits operation and how to connect them properly to switches or transistor outputs on field devices.
The WJ200 inverter features selectable sinking or sourcing inputs. These terms refer to the
connection to the external switching device–it either sinks current (from the input to GND) or sources current (from a power source) into the input. Note that the sink/source naming
convention may be different in your particular country or industry. In any case, just follow the wiring diagrams in this section for your application.
The inverter has a short bar (jumper) for
Logic inputs
configuring the choice of sinking or sourcing inputs. To access it, you must remove the
7 6
5 4 3 2 1 L
PLC P24
front cover of the inverter housing. In the figure to the top right, the short bar is shown as attached to the logic terminal block (connector). For EU and US version (suffix
Short bar
Sink logic connection
–xFE, and –xFU), it is originally located as source type logic. If you need to change to the sink type connection, remove the short bar and connect it as shown in the figure at the bottom right.
7 6
5 4 3 2 1 L
Short bar
Source logic connection
PLC P24
CAUTION: Be sure to turn OFF power to the inverter before changing the short circuit bar
position. Otherwise, damage to the inverter circuitry may occur.
[PLC] Terminal Wiring – The [PLC]
terminal (Programmable Logic Control terminal) is named to include various devices that can connect to the inverter’s logic inputs. In the figure to the right, note the [PLC] terminal and the short bar (jumper). Locating the short bar between [PLC] and [L] sets the input logic source type, which is the default setting for EU and US versions. In this case, you
Short bar for sink logic
P24
PLC
Input common
1
Input circuits
WJ200 inverter
24V
+
-
connect input terminal to [P24] to make it active. If instead you locate the short bar
7
between [PLC] and [P24], the input logic will be sink type. In this case, you connect the input terminal to [L] to make it active.
Short bar for source logic
Logic GND
L
The wiring diagram on the following pages show the four combinations of using sourcing or
sinking inputs, and using the internal or an external DC supply.
27
The two diagrams below input wiring circuits using the inverter’s internal +24V supply.
Each diagram shows the connection for simple switches, or for a field device with transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L] only when using the field device with transistors. Be sure to use the correct connection of the short bar shown for each wiring diagram.
Sinking Inputs, Internal Supply
Short bar = [PLC] – [P24] position
Field device
GND
Short bar
Logic GND
P24
Input common
PLC
L
WJ200
24V
+
1
7
Open collector outputs, NPN transistors
Sourcing Inputs, Internal Supply
Short bar = [PLC] – [L] position
Field device
Common to [P24]
1
7
to PNP bias circuits
GND
Input switches
Short bar
Logic GND
Input switches
1
7
P24
Input common
PLC
L
1
7
Input circuits
WJ200
24V
+
Input circuits
PNP transistor sousing outputs
28
f
The two diagrams below show input wiring circuits using an external supply. If using the “Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the short bar, and use a diode (*) with the external supply. This will prevent a power supply contention in case the short bar is accidentally placed in the incorrect position. For the “Sourcing Inputs, External Supply”, please connect the short bar as drawn in the diagram below.
Sinking Inputs, External Supply
Short bar = Removed
Field device
+
24V
GND
24V
+
Logic GND
WJ200
P24
*
Input common
PLC
L
24V
+
1
7
Open collector outputs, NPN transistors
Sourcing Inputs, External Supply
Short bar = [PLC] – [L]
PNP transistor sourcing outputs
Field device
1
7
+
24V
GND
1
Input circuits
7
Input switches
* Note: Make sure to remove the short circuit bar in case o using an external power supply.
Short bar
WJ200
24V
+
Input switches
P24
Input common
PLC
L
1
7
Input circuits
24V
+
29
CAUTION: Be sure to diode in between "P24" and "PLC" when connecting plural
inverters with digital input wiring in common.
The power to the inverter control part can be supplied externally as shown below. Except driving motor, it is possible read and write the parameters by keypad and via communication even the drive itself is not powered.
By having ability inverter doesn’t block the current flowing into itself when it is not powered. This may cause the closed circuit when two or more inverters are connected to common I/O wiring as shown below to result in unexpected turning the on the input. To avoid this closed circuit, please put the diode (rated:50V/0.1A) in the path as described below.
Switch
OFF
Short
bar
Short
OFF
Short
bar
Short
bar
bar
Power ON
PLC
L
1
Power OFF
PLC
L
1
P24
PLC
L
1
P24
PLC
L
1
Input
ON
Inserting
diode
In case of Source logic
Input
ON
Switch
OFF
Switch
OFF
P24
PLC
L
P24
PLC
L
1
P24
PLC
L
1
P24
PLC
L
1
Power ON
Input
OFF
Power OFF
Input
OFF
Switch
30
Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low).
Option
Code
00
01
Valid for inputs: Required settings
Notes:
 When the Forward Run and Reverse Run
 When a terminal associated with either [FW] or
Terminal
Symbol
FW Forward Run/Stop
RV Reverse Run/Stop
commands are active at the same time, the inverter enters the Stop Mode.
[RV] function is configured for normally closed,
the motor starts rotation when that terminal is disconnected or otherwise has no input voltage.
Function Name State Description
ON Inverter is in Run Mode, motor runs forward
OFF Inverter is in Stop Mode, motor stops
ON Inverter is in Run Mode, motor runs reverse
OFF Inverter is in Stop Mode, motor stops
C001~C007 A002 = 01
Example (default input configuration shown
– see page 3-49)
7654321L
See I/O specs on page 4-6.
RV FW
PLC
PCS
P24
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run
key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.
31
Multi-Speed Select ~Binary Operation
The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are accessible through programming four of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right. These can be any of the six inputs, and in any order. You can use fewer inputs if you need eight or fewer speeds.
NOTE: When choosing a subset of speeds to use,
always start at the top of the table, and with the least-significant bit: CF1, CF2, etc.
[CF1]
[CF2]
[CF3]
[FW]
3rd
7th 5th
2nd
1st 6th 4th 0th
1 0
1 0
1 0
1 0
Speed
Option
Code
02
03
04
05
Valid for inputs: Required settings
Notes:
 When programming the multi-speed settings,
be sure to press the SET key each time and then set the next multi-speed setting. Note that when the key is not pressed, no data will be set.
 When a multi-speed setting more than 50Hz
(60Hz) is to be set, it is necessary to program the maximum frequency A004 high enough to allow that speed
Terminal
Symbol
Function Name State Description
CF1 Multi-speed Select,
Bit 0 (LSB)
CF2 Multi-speed Select,
Bit 1
CF3 Multi-speed Select,
Bit 2
CF4 Multi-speed Select,
Bit 3 (MSB)
C001~C007 F001, A001=02, A020 to A035
Multi-
speed
CF4 CF3 CF2 CF1 Speed 0 0 0 0 0 Speed 1 0 0 0 1 Speed 2 0 0 1 0 Speed 3 0 0 1 1 Speed 4 0 1 0 0 Speed 5 0 1 0 1 Speed 6 0 1 1 0 Speed 7 0 1 1 1 Speed 8 1 0 0 0 Speed 9 1 0 0 1
Speed 10 1 0 1 0
Speed 11 1 0 1 1 Speed 12 1 1 0 0 Speed 13 1 1 0 1 Speed 14 1 1 1 0 Speed 15 1 1 1 1
Input Function
The example with eight speeds in the figure below shows how input switches configured for CF1–CF3 functions can change the motor speed in real time.
NOTE: Speed 0 depends on A001
parameter value.
ON Binary encoded speed select, Bit 0, logical 1
OFF Binary encoded speed select, Bit 0, logical 0
ON Binary encoded speed select, Bit 1, logical 1
OFF Binary encoded speed select, Bit 1, logical 0
ON Binary encoded speed select, Bit 2, logical 1
OFF Binary encoded speed select, Bit 2, logical 0
ON Binary encoded speed select, Bit 3, logical 1
OFF Binary encoded speed select, Bit 3, logical 0
Example (some CF inputs require input configuration; some are default inputs):
7654321L
See I/O specs on page 4–6.
CF4 CF3 CF2 CF1
PCS
PLC
P24
32
q
Two Stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the inverter changes the rate of acceleration and
deceleration from the initial settings (F002 and
F003) to use the second set of acceleration/
deceleration values. When the terminal is turned OFF, the inverter is returned to the original acceleration and deceleration time
(F002 acceleration time 1, and F003 deceleration time 1). Use A092 (acceleration time 2) and A093 (deceleration time 2) to set
the second stage acceleration and deceleration times.
In the graph shown above, the [2CH] becomes active during the initial acceleration. This causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
Option
Code
09
Valid for inputs: Required settings
Notes:
 Function A094 selects the method for second
stage acceleration. It must be set = 00 to select the input terminal method in order for the [2CH] terminal assignment to operate.
Terminal
Symbol
2CH Two-stage Accelera-
Function Name State Description
tion and Deceleration
C001~C007 A092, A093, A094=00
ON Frequency output uses 2nd-stage acceleration and
deceleration values
OFF Frequency output uses the initial acceleration 1 and
deceleration 1 values Example (default input configuration shown—see
page 3–49):
See I/O specs on page 4–6.
Target fre
Output frequency
[2CH]
[FW,RV]
2CH
7654321L
second
initial
1 0 1 0
uency
PCS
PLC
P24
t
33
Unattended Start Protection
If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that
automatic startup, so that the inverter will not run without outside intervention. When USP
is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key.
In the figure below, the [USP] feature is enabled. When the inverter power turns ON, the motor does not start, even though the Run command is already active. Instead, it enters
the USP trip state, and displays E 13 error code. This requires outside intervention to reset the alarm by turning OFF the Run command per this example (or applying a reset). Then the Run command can turn ON again and start the inverter output.
Run command [FW,RV]
[USP] terminal
Alarm output terminal
Inverter output frequency
Inverter power supply
Events:
1 0 1 0 1 0
0 1 0
E13
Alarm
cleared
Run
command
t
Option
Code
13
Valid for inputs: Required settings
Notes:
 Note that when a USP error occurs and it is
canceled by a reset from a [RS] terminal input, the inverter restarts running immediately.
 Even when the trip state is canceled by turning
the terminal [RS] ON and OFF after an under voltage protection E09 occurs, the USP function
will be performed.
 When the running command is active
immediately after the power is turned ON, a USP error will occur. When this function is used, wait for at least three (3) seconds after the powerup to generate a Run command.
Terminal
Symbol
USP Unattended Start
Function Name State Description
Protection
C001~C007
(none)
ON On powerup, the inverter will not resume a Run
OFF On powerup, the inverter will resume a Run
command (mostly used in the US)
command that was active before power loss Example (default input configuration shown for
–FE and –FU models; –F models require input configuration—see page 3–49):
See I/O specs on page 4–6.
7654321L
USP
PCS
PLC
P24
34
Reset Inverter
The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The alarm output will be cleared within 30 ms after the onset of the
Alarm signal
[RS]
1 0
Approx. 30 ms
1 0
Reset command.
WARNING: After the Reset command is given and the alarm reset occurs, the motor will
restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.
Option
Code
18
Valid for inputs: Required settings
Notes:
 While the control terminal [RS] input is ON, the
keypad displays alternating segments. After RS turns OFF, the display recovers automatically.
 Pressing the Stop/Reset key of the digital
operator can generate a reset operation only when an alarm occurs.
Terminal
Symbol
RS Reset Inverter
Function Name State Description
C001~C007
(none)
ON The motor output is turned OFF, the Trip Mode is
cleared (if it exists), and powerup reset is applied
OFF Normal power ON operation
Example (default input configuration shown):
7654321L
See I/O specs on page 4–6.
RS
12 ms
minimum
PCS
P24
PLC
t
 A terminal configured with the [RS] function can only be configured for normally open operation. The
terminal cannot be used in the normally closed contact state.
 When input power is turned ON, the inverter performs the same reset operation as it does when a
pulse on the [RS] terminal occurs.
 The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when
a hand-held remote operator is connected to the inverter.
 If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).  If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS]
terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS] input causes the motor output and the logic outputs to turn OFF together, immediately. However, when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 1 sec. period (approximate) before turning OFF.
35
Run Signal
When the [RUN] signal is selected as an intelligent output terminal, the inverter outputs a signal on that terminal when it is in Run Mode. The output logic is active low, and is the open collector type (switch to ground).
Option
Code
00
Valid for inputs: Required settings
Notes:
 The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082. The start
frequency is the initial inverter output frequency when it turns ON.
 The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the negative going turn-off spike generated by the coil from damaging the inverter’s output transistor.
Terminal
Symbol
RUN Run Signal
Function Name State Description
11, 12, AL0 – AL2 (none)
[FW,RV]
Output frequency
Run signal
ON when inverter is in Run Mode
OFF when inverter is in Stop Mode
Example for terminal [11] (default output configuration shown – see page 3-54):
1 0
B082
Inverter output terminal circuit
CM2 11
start freq.
RY
ON
t
RUN
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54):
Inverter logic circuit board
See I/O specs on page 4-6
AL0 AL2
Power
supply
RUN
AL1
Load
36
Frequency Arrival Signals
The Frequency Arrival group of outputs helps coordinate external systems with the current
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output
frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on
programmable accel/ decel thresholds for increased flexibility. For example, you can have an output turn ON at one frequency during acceleration, and have it turn OFF at a different frequency during deceleration. All transitions have hysteresis to avoid output chatter if the output frequency is near one of the thresholds.
Option
Code
Valid for inputs: Required settings
Notes:
 For most applications you will need to use
 For each frequency arrival threshold, the
 The output turns OFF as the output
 The example circuit for terminal [11] drives a
Terminal
Symbol
01
02
06
24
25
only one type of frequency arrival outputs (see examples). However, it is possible assign both output terminals to output functions [FA1] and [FA2]
output anticipates the threshold (turns ON early) by 1.5Hz
frequency moves away from the threshold, delayed by 0.5Hz
relay coil. Note the use of a diode to prevent the negative going turn-off spike generated by the coil from damaging the inverter’s output transistor
FA1 Frequency Arrival
FA2 Frequency Arrival
FA3 Frequency Arrival
FA4 Frequency Arrival
FA5 Frequency Arrival
Function Name State Description
ON when output to motor is at the constant frequency Type 1 – Constant Speed
Type 2 – Over frequency
Type 3 – Set frequency
Type 4 – Over frequency (2)
Type 5 – Set frequency (2)
11, 12, AL0 – AL2
C042, C043, C045, C046,
OFF when output to motor is OFF, or in any acceleration or
ON when output to motor is at or above the set frequency
OFF when output to motor is OFF, or during accel or decel
ON when output to motor is at the set frequency
OFF when output to motor is OFF, or in any acceleration or
ON when output to motor is at or above the set frequency
OFF when output to motor is OFF, or during accel or decel
ON when output to motor is at the set frequency
OFF when output to motor is OFF, or in any acceleration or
deceleration ramp
thresholds for, even if in acceleration or decel ramps
before the respective thresholds are crossed
deceleration ramp
thresholds for, even if in acceleration or decel ramps
before the respective thresholds are crossed
deceleration ramp Example for terminal [11] (default output configuration
shown – see page 3-54):
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 54):
See I/O specs on page 4-6
Inverter output terminal circuit
CM2 11
Inverter logic circuit board
AL0 AL2
Power
supply
FA1
RY
FA1
AL1
Load
37
Frequency arrival output [FA1] uses the standard output frequency (parameter F001) as the threshold for switching. In the figure to the right, Frequency Arrival [FA1] turns ON when the output
frequency gets within Fon Hz below or Fon Hz above the target constant frequency, where Fon is 1% of the set maximum frequency and Foff is 2% of
the set maximum frequency. This provides hysteresis that prevents output chatter near the threshold value. The hysteresis effect causes the output to
turn ON slightly early as the speed
approaches the threshold. Then the
turn-OFF point is slightly delayed. Note
the active low nature of the signal, due to the open collector output.
Frequency arrival output [FA2/FA4] works the same way; it just uses two separate thresholds as shown in the figure to the right. These provide for separate acceleration and deceleration thresholds to provide more flexibility than
for [FA1]. [FA2/FA4] uses C042/C045 during acceleration for the ON threshold,
and C043/C046 during deceleration for the OFF threshold. This signal also is active low. Having different accel and decel thresholds provides an asymmetrical output function. However, you can use equal ON and OFF thresholds, if desired.
Frequency arrival output [FA3/FA5] works also the same way, only difference is arriving at set frequency.
Output
freq.
0
FA1
signal
Output
freq.
thresholds
C042/C045
C043/C046
FA2/FA4
signal
Output
freq.
thresholds
C042/C045
C043/C046
Fon
Fon=1% of max. frequency Foff=2% of max. frequency
0
Fon=1% of max. frequency Foff=2% of max. frequency
F001
Fon
ON
Foff
Fon
Fon
ON
Foff
Fon
F001
Foff
ON
Foff
Foff
0
FA3/FA5
signal
Fon=1% of max. frequency Foff=2% of max. frequency
ON ON
38
A
A
A
Alarm Signal
The inverter alarm signal is active when a fault has occurred and it is in the Trip Mode (refer to the diagram at right). When the fault is cleared the alarm
Run Stop
STOP RESET
RUN
signal becomes inactive.
We must make a distinction between the alarm signal AL and the alarm relay contacts [AL0], [AL1] and [AL2].
Fault
Trip
The signal AL is a logic function, which you can assign to the open collector output terminals [11], [12], or the
larm signal active
relay outputs. The most common (and default) use of the relay is for AL, thus the labeling of its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic signal interface or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum).
Option
Code
05
Valid for inputs: Required settings
Notes:
 By default, the relay is configured as normally
closed (C036=01). Refer to the next page for an explanation.
 In the default relay configuration, an inverter
power loss turns ON the alarm output. the alarm signal remains ON as long as the external control circuit has power.
 When the relay output is set to normally
closed, a time delay of less than 2 seconds occurs after powerup before the contact is closed.
 Terminals [11] and [12] are open collector
outputs, so the electric specifications of [AL] are different from the contact output terminals [AL0], [AL1], [AL2].
 This signal output has the delay time (300 ms
nominal) from the fault alarm output.
 The relay contact specifications are in “Control
Logic Signal Specifications” on page 4–6. The
contact diagrams for different conditions are on the next page.
Terminal
Symbol
Function Name State Description
AL Alarm Signal
11, 12, AL0 – AL2
C031, C032, C036
ON when an alarm signal has occurred and has not
been cleared
OFF when no alarm has occurred since the last clearing
of alarm(s) Example for terminal [11] (default output
configuration shown – see page 3-54):
Inverter output terminal circuit
L
CM2 11
RY
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54):
Inverter logic circuit board
L
AL1
AL0 AL2
Power supply
Load
See I/O specs on page 4-6
STOP RESET
Fault
39
The alarm relay output can be configured in two main ways:
 Trip/Power Loss Alarm – The alarm relay is configured as normally closed (C036=01)
by default, shown below (left). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay (< 2 seconds), the relay energizes and the alarm circuit is OFF. Then, either an inverter trip event or an inverter power loss will de-energize the relay and open the alarm circuit
 Trip Alarm – Alternatively, you can configure the relay as normally open (C036=00),
shown below (right). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an inverter trip event occurs, opening the alarm circuit. However, in this configuration, an inverter power loss does not open the alarm circuit.
Be sure to use the relay configuration that is appropriate for your system design. Note that the external circuits shown assume that a closed circuit = no alarm condition (so that a broken wire also causes an alarm). However, some systems may require a closed circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2] from the ones shown.
N.C. contacts (C036=01) N.O. contacts (C036=00)
During normal operation When an alarm occurs or
when power is OFF
supply
AL1
AL0 AL2
Power
Power Run Mode AL0-AL1 AL0-AL2 Power Run Mode AL0-AL1 AL0-AL2
ON Normal Closed Open ON Normal Open Closed
ON Trip Open Closed ON Trip Closed Open
OFF – Open Closed OFF – Open Closed
Load
AL1
AL0 AL2
Power supply
Load
During normal operation
or when power is OFF
AL1
AL0 AL2
Power supply
Load
When an alarm occurs
AL1
AL0 AL2
Power supply
Load
40
A
g
-
-
Analog Input Operation
The WJ200 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector, which provide for Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L].
If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type. Refer to the table on next page showing the activation of
AM H O OI L
+V Ref.
Voltage input
Current input
GND
V/I input select
[AT]
A001
Freq. settin
each analog input by combination of A005 set parameter and [AT] terminal condition. The [AT] terminal function is covered in “Analog Input
AM H O OI L
Current/Voltage Select” in section 4. Remember
that you must also set A001 = 01 to select analog
input as the frequency source.
Å
4-20 mA
+
0-10 V
NOTE: If no logic input terminal is configured for the [AT] function, then inverter recognizes
that [AT]=OFF and MCU recognizes [O]+[OI] as analog input.
Using an external potentiometer is a common way to control the inverter output frequency (and a good way to learn how to use the analog inputs). The potentiometer uses the built-in 10V reference [H] and the analog ground [L] for excitation, and the voltage input [O] for the signal. By default, the [AT] terminal selects the voltage input when it is OFF. Take care to use the proper resistance for the potentiometer, which is 1~2 k
, 2 Watts.
Voltage Input – The voltage input circuit uses
terminals [L] and [O]. Attach the signal cable’s shield wire only to terminal [L] on the inverter. Maintain the voltage within specifications (do not apply negative voltage).
Current Input – The current input circuit uses
terminals [OI] and [L]. The current comes from a
sourcing type transmitter; a sinking type will not
work! This means the current must flow into terminal [OI], and terminal [L] is the return back to the transmitter. The input impedance from [OI] to [L] is 100 Ohms. Attach the cable shield wire only to terminal [L] on the inverter.
AM H O OI L
1 to 2k, 2W
AM H O OI L
0 to 9.6 VDC, 0 to 10V nominal
AM H O OI L
4 to 19.6 mA DC, 4 to 20mA nominal
See I/O specs on page 4-6.
+
Å
41
The following table shows the available analog input settings. Parameter A005 and the input terminal [AT] determine the External Frequency Command input terminals that are available, and how they function. The analog inputs [O] and [OI] use terminal [L] as the reference (signal return).
A005
00
02
03
[AT] Input Analog Input Configuration
ON [O]
OFF [OI]
ON [O]
OFF Integrated POT on external panel
ON [OI]
OFF Integrated POT on external panel
Other Analog Input-related topics:
· “Analog Input Settings”
· “Additional Analog Input Settings”
· “Analog Signal Calibration Settings”
· “Analog Input Current/Voltage Select”
· “ADD Frequency Enable”
· “Analog Input Disconnect Detect”
42
Analog
outpu
output Sho
bar
Analog
pu
co
co
5 4 6 SN 7
AM
H O EA SP EO
Pulse Train Input Operation
The WJ200 inverter is capable of accepting pulse train input signals, that are used for frequency command, process variable (feedback) for PID control, and simple positioning. The dedicated terminal is called “EA” and “EB”. Terminal “EA” is a dedicated terminal, and the terminal “EB” is an intelligent terminal, that has to be changed by a parameter setting.
Relay contact
AL2
AL1
AL0
RS485
mm.
RS485
mm.
Pulse
Train
output
Pulse
Train
input
Logic input
in
t
t
CM2 OI L
PLC
12 11
Logic
P24 1 L 3 2
rt
Terminal Name Description Ratings
EA Pulse train input A For frequency command, 32kHz max.
Reference voltage: Common is [L] EB (Input terminal 7)
Pulse train input B (Set C007 to 85 )
27Vdc max.
For frequency command, 2kHz max.
Reference voltage: Common is [PLC]
(1) Frequency Command by pulse train input
When using this mode, you should set A001 to 06. In this case the frequency is detected by input-capture, and calculated based on the ratio of designated max. frequency (under 32kHz). Only an input terminal “EA” will be used in this case.
(2) Using for process variable of PID control
You can use the pulse train input for process variable (feedback) of PID control. In this case you need to set A076 to 03. Only “EA” input terminal is to be used.
(3) Simple positioning by pulse train input
This is to use the pulse train input like an encoder signal. You can select three types of
operation.
43
A
A
Analog Output Operation
In inverter applications it is useful to monitor the inverter operation from a remote location or from the front panel of an inverter enclosure. In some cases, this requires only a panel-mounted volt meter. In other cases, a controller such as a PLC may provide the inverter’s frequency command, and require inverter feedback data (such as output frequency or output current) to confirm actual operation. The analog output terminal [AM] serves these purposes.
nalog Voltage Output
10VDC full scale, 1mA max
See I/O specs on page 4-6
AM H O OI L
+-
GND
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog GND reference. The [AM] can output inverter frequency or current output value. Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or reverse motor
rotation. Use C028 to configure terminal [AM] as indicated below.
Func. Code Description
Inverter output frequency Inverter output current Inverter output torque Digital output freqnency Inverter output goltage Inverter input power Electronic Thermal Load LAD frequency Digital current monitor Cooling fin temperature General purpose Pulse train Option
C028
00 01 02 03 04 05 06 07 08 10 12 15 16
44
A
A
The [AM] signal offset and gain are adjustable, as indicated below.
Func. Description Range Default
C106 C109
The graph below shows the effect of the gain and offset setting. To calibrate the [AM] output for your application (analog meter), follow the steps below:
1. Run the motor at the full scale speed, or most common operating speed.
[AM] output gain 0.~255. 100. [AM] output offset 0.0~10.0 0.0
a. If the analog meter represents output frequency, adjust offset (C109) first, and then
use C106 to set the voltage for full scale output.
b. If [AM] represents motor current, adjust offset (C109) first, and then use BC106 to set
the voltage for full scale output. Remember to leave room at the upper end of the range for increased current when the motor is under heavier loads.
AM output offset adjustment
M output
10V
C109=0~10
5V
Parallel movement
AM output gain adjustment
M output
10V
5V
C106=0~255
0
1/2 FS
Full scale (FS) Hz or A
0
1/2 FS
Full scale (FS) Hz or A
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise the
required performance cannot be obtained because of the parallel movement of the offset adjustment.
45
Monitoring functions
NOTE:. Mark “9” in b031=10 shows the accessible parameters when b031 is set “10”, high
level access.
Func.
Code
D001
D002
D003
D004
D005
Output frequency monitor Real time display of output frequency
Output current monitor Filtered display of output current to
Rotation direction monitor Three different indications:
Process variable (PV), PID feedback monitor
Intelligent input terminal status
Name Description
“d” Function
to motor from
0.0 to 400.0Hz If b163 is set high, output frequency (F001) can be changed by up/down
key with d001 monitoring.
motor, range is 0 to 655.3 ampere (~99.9 ampere for
1.5kW and less)
FForward “oStop “rReverse Displays the scaled PID process variable (feedback) value (A075 is
scale factor),
0.00 to 10000 Displays the state of the intelligent input terminals:
ON
Run
Mode
Edit
Units
Hz
A
% times
constant
D006
Intelligent output terminal status
OFF
3
7 6 5 4
Terminal numbers
Displays the state of the intelligent output terminals:
2 1
Relay
ON
OFF
12 11
46
Func.
Code
D007
d008
d009
d010
d012
D013
d014
d015
D016
D017
D018
d022
d023
d024
d025
d026
d027
d029
d030
d050
d060
“d” Function
Name Description
Scaled output frequency monitor
Actual frequency monitor Displays the actual frequency, range
Torque command monitor Displays the torque command, range
Torque bias monitor Displays the torque bias value, range
Output torque monitor Displays the output torque, range is
Output voltage monitor Voltage of output to motor,
Input power monitor Displays the input power, range is 0
Watt-hour monitor Displays watt-hour of the inverter,
Elapsed RUN time monitor Displays total time the inverter has
Elapsed power-on time monitor
Heat sink temperature monitor Temperature of the cooling fin, range
Life check monitor Displays the state of lifetime of
Program counter monitor [EzSQ]
Program number monitor [EzSQ]
User monitor 0 [EzSQ] User monitor 1 [EzSQ] User monitor 2 [EzSQ] Positioning command monitor Displays the positioning command,
Current position monitor Displays the current position, range
Dual monitor Displays two different data
Inverter mode monitor Displays currently selected inverter
Displays the output frequency scaled by the constant in B086. Decimal point indicates range:
0 to 3999
is -400 to 400 Hz
is -200 to 200 %
is -200 to 200 %
-200 to 200 %
Range is 0.0 to 600.0V
to 999.9 kW
range is 0 to 9999000
been in RUN mode in hours. Range is 0 to 9999 / 1000 to 9999 / 100 to 999 (10,000 to 99,900)
Displays total time the inverter has been powered up in hours. Range is 0 to 9999 / 1000 to 9999 / 100 to 999 (10,000 to 99,900)
is -20~150
electrolytic capacitors on the PWB and cooling fan.
Range is 0 to 1024
Range is 0 to 9999
Result of EzSQ execution, range is –2147483647~2147483647 Result of EzSQ execution, range is –2147483647~2147483647 Result of EzSQ execution, range is –2147483647~2147483647
range is –268435455~+268435455
is –268435455~+268435455
configured in b160 and b161.
mode : I-C:IM CT mode/I-v:IM VT mode/ P:PM
Cooling fan
Lifetime expired
Normal
Electrolytic caps
47
Run
Mode
Edit
Units
Hz times
constant
C
Hz
%
%
%
V
KW
hours
hours
Func.
Code
D080
D081
D082
D083
d084
d085
d086
d090
D102
d103
D104
“d” Function
Name Description
Trip counter Number of trip events,
Range is 0. to 65530
Trip monitor 1
Trip monitor 2
Trip monitor 3
Trip monitor 4
Trip monitor 5
Trip monitor 6
Warning monitor Displays the warning code
DC bus voltage monitor Voltage of inverter internal DC bus,
BRD load ratio monitor Usage ratio of integrated brake
Electronic thermal monitor Accumulated value of electronic
Displays trip event information:
 Error code  Output frequency at trip point  Motor current at trip point  DC bus voltage at trip point  Cumulative inverter operation
time at trip point
 Cumulative power-ON time at
trip point
Range is 0.0 to 999.9
chopper, range is 0.0~100.0%
thermal detection, range is from
0.0~100.0%
Run
Mode
Edit
Units
events
V
%
%
48
Main Profile Parameters
NOTE:. Mark “9” in b031=10 shows the accessible parameters when b031 is set “10”, high
level access.
Func.
Code
F001
F002
F202
F003
F203
F004
Output frequency setting Standard default target frequency
Acceleration time (1)
Acceleration time (1),
nd
2
motor
Deceleration time (1)
Deceleration time (1),
nd
2
motor
Keypad RUN key routing Two options; select codes:
Name Description
“F” Function Defaults
that determines constant motor speed, range is 0.0 / start frequency to maximum frequency (A004) Standard default acceleration, range is 0.01 to 3600 sec.
Standard default deceleration, range is 0.01 to 3600 sec.
00 Forward 01 Reverse
Run
Mode
Edit
9
9
9
9
9
U
Lnitial data Units
0.0 Hz
10.0 sec.
10.0 sec.
10.0 sec.
10.0 sec.
00
49
Standard Functions
NOTE:. Mark “9” in b031=10 shows the accessible parameters when b031 is set “10”, high
level access.
Func.
Code
A001
A201
A002
A202
A003
A203
Frequency source
Frequency source,
nd
motor
2
Run command source
Run command source,
nd
motor
2
Base frequency Settable from 30 Hz to the
Base frequency,
nd
2
motor
Name Description
“A” Function Defaults
Eight options; select codes:
00 POT on ext. operator 01 Control terminal 02 Function F001 setting 03 ModBus network input 04 Option 06 Pulse train input 07 via EzSQ 10 Calculate function output
Five options; select codes:
01 Control terminal 02 Run key on keypad,
or digital operator
03 ModBus network input 04 Option
maximum frequency(A004)
Settable from 30 Hz to the 2 maximum frequency(A204)
nd
Run
Mode
Edit
Lnitial data Units
U
U
U
U
U
U
60.0 Hz
60.0 Hz
02
02
02
02
A004
A204
A005
A011
A012
A013
A014
Maximum frequency Settable from the base
frequency to 400 Hz
Maximum frequency,
nd
motor
2
[AT] selection Three options; select codes:
[O] input active range start frequency
[O] input active range end frequency
[O] input active range start voltage
[O] input active range end voltage
Settable from the 2 frequency to 400 Hz
00...Select between [O] and [OI] at [AT] (ON=OI, OFF=O)
02...Select between [O] and external POT at [AT] (ON=POT, OFF=O)
03...Select between [OI] and external POT at [AT] (ON=POT, OFF=OI)
The output frequency corresponding to the analog input range starting point, range is 0.00 to 400.0 The output frequency corresponding to the analog input range ending point, range is 0.0 to 400.0 The starting point (offset) for the active analog input range, range is 0. to 100. The ending point (offset) for the active analog input range, range is 0. to 100.
nd
base
50
U
U
U
U
U
U
U
60.0 Hz
60.0 Hz
00
0.00 Hz
0.00 Hz
0. %
100. %
Func.
Code
A015
A016
A017
a019
A020
A220
A021
to
A035
A038
A039
A041
A241
“A” Function Defaults
Name Description
[O] input start frequency enable
Analog input filter Range n = 1 to 31,
Multi-speed operation selection
Multi-speed freq. 0 Defines the first speed of a
Multi-speed freq. 0,
nd
motor
2
Multi-speed freq. 1 to 15 (for both motors)
Jog frequency Defines limited speed for jog,
Jog stop mode Define how end of jog stops the
Torque boost select
Torque boost select, 2nd motor
Two options; select codes:
00Use offset (A011 value) 01Use 0Hz
1 to 30 : ×2ms filter 31: 500ms fixed filter with ±
0.1kHz hys.
Select codes:
00...Binary operation (16 speeds selectable with 4 terminals)
01...Bit operation (8 speeds
selectable with 7 terminals)
multi-speed profile, range is 0.0 / start frequency to 400Hz
A020 = Speed 0 (1st motor) Defines the first speed of a multi-speed profile or a 2nd motor, range is 0.0 / start frequency to 400Hz A220 = Speed 0 (2nd motor) Defines 15 more speeds, range is 0.0 / start frequency to 400 Hz.
A021=Speed 1 ~ A035=Speed15 A021 ~ A035
range is from start frequency to
9.99 Hz
motor; six options: 00Free-run stop (invalid during
run)
01Controlled deceleration
(invalid during run)
02DC braking to stop(invalid
during run)
03Free-run stop (valid during
run)
04Controlled deceleration
(valid during run)
05DC braking to stop(valid
during run)
Two options:
00Manual torque boost 01Automatic torque boost
Run
Mode
Edit
U
U
9
U
9
9
9
9 9
U
U
U
Lnitial data Units
01
8. Spl.
00 -
00 -
0.0 Hz
0.0 Hz
See next
row
0.0 Hz
6.00 Hz
04
00
00
Hz
A042
Manual torque boost value Can boost starting torque
between 0 and 20% above
51
9
1.0 %
Func.
Code
A242
A043
A243
A044
A244
A045
A245
a046
a246
a047
a247
A051
A052
A053
A054
“A” Function Defaults
Name Description
Manual torque boost value, 2nd motor
Manual torque boost frequency
Manual torque boost frequency,
2nd motor
V/f characteristic curve
V/f characteristic curve,
nd
motor
2
V/f gain
V/f gain, 2nd motor
Voltage compensation gain for automatic torque boost
Voltage compensation gain for automatic torque boost,
motor
Slip compensation gain for automatic torque boost
Slip compensation gain for automatic torque boost,
motor
DC braking enable Three options; select codes:
DC braking frequency The frequency at which DC
DC braking wait time The delay from the end of
DC braking force for deceleration
2nd
2nd
normal V/f curve, range is 0.0 to 20.0%
Sets the frequency of the V/f breakpoint A in graph (top of previous page) for torque boost, range is 0.0 to 50.0%
Six available V/f curves;
00Constant torque 01Reduced torque (1.7) 02Free V/F 03Sensorless vector (SLV)
Sets voltage gain of the inverter, range is 20. to 100.%
Sets voltage compensation gain under automatic torque boost, range is 0. to 255.
Sets slip compensation gain under automatic torque boost, range is 0. to 255.
00Disable 01Enable during stop 02Frequency detection
braking begins, range is from the start frequency
(B082) to 60Hz
controlled deceleration to start of DC braking (motor free runs until DC braking begins), range is 0.0 to 5.0 sec. Level of DC braking force, settable from 0 to 100%
Run
Mode
Edit
9
9
9
U
U
9
9
9
9
9
9
U
U
U
U
Lnitial data Units
1.0 %
5.0 %
5.0 %
00
00
100. %
100. %
100.
100.
100.
100.
00
0.5 Hz
0.0 sec.
50. %
A055
A056
a057
DC braking time for deceleration
DC braking / edge or level detection for [DB] input
DC braking force at start Level of DC braking force at
Sets the duration for DC braking, range is from 0.0 to 60.0 seconds Two options; select codes:
00Edge detection 01Level detection
start, settable from 0 to 100%
52
U
U
U
0.5 sec.
01
0. %
Func.
Code
a058
a059
A061
A261
A062
A262
A063 A065 A067
A064 A066 A068 A069
A070
A071
“A” Function Defaults
Name Description
DC braking time at start Sets the duration for DC braking,
range is from 0.0 to 60.0
seconds Carrier frequency during DC braking
Frequency upper limit Sets a limit on output frequency
Frequency upper limit, 2nd motor
Frequency lower limit Sets a limit on output frequency
Frequency lower limit, 2nd motor
Jump freq. (center) 1 to 3 Up to 3 output frequencies can
Jump freq. width (hysteresis) 1 to 3
Acceleration hold frequency Sets the frequency to hold
Acceleration hold time Sets the duration of acceleration
PID enable Enables PID function,
Carrier frequency of DC braking
performance, range is from 2.0 to
15.0kHz
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
be defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
acceleration, range is 0.0 to
400.0Hz
hold, range is 0.0 to 60.0
seconds
three option codes:
00PID Disable
01PID Enable
02PID Enable with reverse
output
Run
Mode
Edit
U
U
U
U
U
U
U
U
U
U
U
Lnitial data Units
0.0 sec.
5.0 sec.
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.0
0.0
0.0
0.5
0.5
0.5
0.00 Hz
0.0 sec.
00
Hz
Hz
53
Func.
Code
A072
A073
A074
A075
A076
A077
A078
a079
A081
a281
A082
a282
“A” Function Defaults
Name Description
PID proportional gain Proportional gain has a range of
0.00 to 25.00
PID integral time constant Integral time constant has a
range of 0.0 to 3600 seconds
PID derivative time constant Derivative time constant has a
range of 0.0 to 100 seconds
PV scale conversion Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99 PV source Selects source of Process
Variable (PV), option codes:
00[OI] terminal (current in)
01[O] terminal (voltage in)
02ModBus network
03Pulse train input
10Calculate function output
Reverse PID action Two option codes:
00PID input = SP-PV
01PID input = -(SP-PV)
PID output limit Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0% PID feed forward selection Selects source of feed forward
gain, option codes:
00Disabled
01[O] terminal (voltage in)
02[OI] terminal (current in)
AVR function select
AVR function select,
nd
2
motor
AVR voltage select
AVR voltage select,
nd
2
motor
Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00AVR enabled
01AVR disabled
02AVR enabled except during
deceleration
200V class inverter settings:
200/215/220/230/240
400V class inverter settings:
380/400/415/440/460/480
Run
Mode
Edit
9
9
9
U
U
U
U
U
U
U
U
U
Lnitial data Units
1.0
1.0 sec
0.00 sec
1.00
00
00
0.0 %
00
02
02
200/
400
200/
400
V
V
a083
a084
A085
A086
AVR filter time constant Define the time constant of the
AVR filter, range is 0 to 10 sec.
AVR deceleration gain Gain adjustment of the braking
performance, range is 50 to
200% Energy-saving operation mode Two option codes:
00Normal operation
01Energy-saving operation
Energy-saving mode tuning Range is 0.0 to 100 %.
54
U
U
U
U
0.300 sec
100. %
00
50.0 %
Func.
Code
A092
A292
A093
A293
A094
A294
A095
A295
A096
A296
“A” Function Defaults
Name Description
Acceleration time (2)
Acceleration time (2),
nd
2
motor
Deceleration time (2)
Deceleration time (2),
nd
2
motor
Select method to switch to Acc2/Dec2 profile
Select method to switch to Acc2/Dec2 profile, 2
Acc1 to Acc2 frequency transition point
Acc1 to Acc2 frequency transition point, 2
Dec1 to Dec2 frequency transition point
Dec1 to Dec2 frequency transition point, 2
nd
nd
motor
nd
motor
motor
nd
Duration of 2
acceleration, range is:
0.01 to 3600 sec.
Duration of 2nd segment of
deceleration, range is:
0.01 to 3600 sec.
Three options for switching from
1st to 2nd accel/decel:
segment of
002CH input from terminal
01Transition frequency
02Forward and reverse
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
Run
Mode
Edit
9
9
9
9
U
U
U
U
U
U
Lnitial data Units
10.00 sec
10.00 sec
10.00 sec
10.00 sec
00
00
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
A097
A098
A101
A102
A103
A104
A105
Acceleration curve selection Set the characteristic curve of
Acc1 and Acc2, five options:
00linear
01S-curve
02U-curve
03Inverse U-curve
04EL S-curve
Deceleration curve selection Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097) [OI] input active range start frequency
[OI] input active range end frequency
[OI] input active range start current
[OI] input active range end current
[OI] input start frequency select
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00Use offset (A101 value)
01Use 0Hz
U
U
U
U
U
U
U
00
00
0.00 Hz
0.0 Hz
20. %
100. %
00
55
Func.
Code
a131
a132
A141
A142
A143
A145
A146
a150
“A” Function Defaults
Name Description
Acceleration curve constant Range is 01 to 10.
Deceleration curve constant Range is 01 to 10.
A input select for calculate function
B input select for calculate function
Calculation symbol Calculates a value based on the
ADD frequency An offset value that is applied to
ADD direction select Two options:
Curvature of EL-S-curve at the start of acceleration
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
A input source (A141 selects) and
B input source (A142 selects).
Three options:
00ADD (A input + B input)
01SUB (A input - B input)
02MUL (A input * B input)
the output frequency when the
[ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
00Plus (adds A145 value to the
output frequency setting)
01Minus (subtracts A145 value
from the output frequency setting)
Range is 0 to 50%
Run
Mode
Edit
U
U
U
U
U
9
U
U
Lnitial data Units
02
02
02
03
00
0.00 Hz
00
10. %
a151
a152
a153
a154
a155
Curvature of EL-S-curve at the end of acceleration
Curvature of EL-S-curve at the start of deceleration
Curvature of EL-S-curve at the end of deceleration
Deceleration hold frequency Sets the frequency to hold
Deceleration hold time Sets the duration of deceleration
Range is 0 to 50%
Range is 0 to 50%
Range is 0 to 50%
deceleration, range is 0.0 to
400.0Hz
hold, range is 0.0 to 60.0
seconds
56
U
U
U
U
U
10. %
10. %
10. %
0.0 Hz
0.0 sec.
Func.
Code
a156
a157
A161
A162
A163
A164
A165
“A” Function Defaults
Name Description
PID sleep function action threshold
PID sleep function action delay time
[VR] input active range start frequency
[VR] input active range end frequency
[VR] input active range start % The starting point (offset) for the
[VR] input active range end % The ending point (offset) for the
[VR] input start frequency select
Sets the threshold for the action,
set range 0.0~400.0 Hz
Sets the delay time for the
action, set range 0.0~25.5 sec
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
current input range,
range is 0. to 100.%
current input range,
range is 0. to 100.%
Two options; select codes:
00Use offset (A161 value)
01Use 0Hz
Run
Mode
Edit
U
U
U
U
U
U
U
Lnitial data Units
0.00 Hz
0.0 sec
0.00 Hz
0.00 Hz
0. %
100. %
01
57
Fine Tuning Functions
Func.
Code
B001
B002
B003
B004
B005
b007
b008
b010
b011
Restart mode on power failure / under-voltage trip
Allowable under-voltage power failure time
Retry wait time before motor restart
Instantaneous power failure / under-voltage trip alarm enable
Number of restarts on power failure / under-voltage trip events
Restart frequency threshold Restart the motor from 0Hz if the
Restart mode on over voltage / over current trip
Number of retry on over voltage / over current trip Retry wait time on over voltage / over current trip
Name Description
“b” Function Defaults
Select inverter restart method,
Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume operation after
frequency matching
03Resume previous freq. after
freq. matching, then decelerate to stop and display trip info
Run
Mode
Lnitial data Units
Edit
U
00
04Resume operation after active
freq. matching The amount of time a power input under-voltage can occur without tripping the power failure alarm. Range is 0.3 to 25 sec. If under-voltage exists longer than this time, the inverter trips, even if the restart mode is selected. Time delay after under-voltage condition goes away, before the inverter runs motor again. Range is 0.3 to 100 seconds.
Three option codes:
00Disable 01Enable 02Disable during stop and
decelerates to a stop
Two option codes:
00Restart 16 times 01Always restart
frequency becomes less than this set value during the motor is coasting, range is 0 to 400Hz Select inverter restart method, Five option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz 02Resume operation after
frequency matching 03Resume previous freq. after
active freq. matching, then
decelerate to stop and display
trip info 04Resume operation after active
freq. matching Range is 1 to 3 times
Range is 0.3 to 100 sec.
U
U
U
U
U
U
U U
1.0 sec.
1.0 sec.
00
00
0.00 Hz
00
3
1.0 sec
times
58
Func.
Code
B012
B212
B013
B213
b015
b016
b017
b018
b019
b020
B021
B221
B022
B222
B023
B223
b024
“b” Function Defaults
Name Description
Level of electronic thermal
Level of electronic thermal,
nd
motor
2
Electronic thermal characteristic Electronic thermal characteristic, 2
Free setting electronic thermal ~freq.1 Free setting electronic thermal ~current1 Free setting electronic thermal ~freq.2 Free setting electronic thermal ~current2 Free setting electronic thermal ~freq.3 Free setting electronic thermal ~current3 Overload restriction operation mode Overload restriction operation mode, 2
Overload restriction level
Overload restriction level, 2
Deceleration rate at overload restriction Deceleration rate at overload restriction, 2 Overload restriction operation mode 2
nd
motor
nd
motor
nd
motor
nd
motor
Set a level between 20% and 100% for the rated inverter current.
Select from three curves, option codes:
00Reduced torque 01Constant torque 02Free setting
Range is 0 to 400Hz
Range is 0 to inverter rated current Amps Range is 0 to 400Hz
Range is 0 to inverter rated current Amps Range is 0 to 400Hz
Range is 0 to inverter rated current Amps Select the operation mode during overload conditions, four options, option codes:
00Disabled 01Enabled for acceleration and
constant speed
02Enabled for constant speed
only 03Enabled for acceleration and
constant speed, increase speed
at regen. Sets the level of overload restriction, between 20% and 200% of the rated current of the inverter, setting resolution is 1% of rated current
Sets the deceleration rate when inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
Select the operation mode during overload conditions, four options, option codes:
00Disabled 01Enabled for acceleration and
constant speed
02Enabled for constant speed
only 03Enabled for acceleration and
constant speed, increase speed
at regen.
Run
Mode
Lnitial data Units
Edit
U
current for
U
U U
U U U U U U U U
U
U
U U U
Rated
each
inverter
model *1
01
01
0.0 Hz
0.00
0.0 Hz
0.00
0.0 Hz
0.00
01
01
Rated
current
x 1.5
Rated
current
x 1.5
1.0 sec.
1.0 sec.
01
A
A
Amps
Amps
Amps
Amps
Amps
59
Func.
Code
b025
b026
b027
B028
B029
B030
B031
B033
b034
B035
b036
“b” Function Defaults
Name Description
Overload restriction level 2 Sets the level of overload restriction,
between 20% and 200% of the rated current of the inverter, setting resolution is 1% of rated current
Deceleration rate 2 at overload restriction
OC suppression selection * Two option codes:
Current level of active freq. matching
Deceleration rate of active freq. matching
Start freq. of active freq. matching
Software lock mode selection Prevents parameter changes, in five
Motor cable length parameter Set range is 5 to 20.
Run/power ON warning time Range is,
Rotation direction restriction Three option codes:
Reduced voltage start selection
Sets the deceleration rate when inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
00Disabled 01Enabled
Sets the current level of active freq. matching restart, range is
0.1*inverter rated current to
2.0*inverter rated current, resolution
0.1 Sets the deceleration rate when active freq. matching restart, range is 0.1 to 3000.0, resolution 0.1 Three option codes:
00freq at previous shutoff 01start from max. Hz 02start from set frequency
options, option codes: 00all parameters except B031 are
locked when [SFT] terminal is ON
01all parameters except B031 and
output frequency F001 are locked when [SFT] terminal is ON
02all parameters except B031 are
locked
03all parameters except B031 and
output frequency F001 are locked
10High level access including
B031
See appendix C for the accessible parameters in this mode.
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
00No restriction 01Reverse rotation is restricted 02Forward rotation is restricted Set range, 0 (disabling the function), 1 (approx. 6ms) to 255 (approx.
1.5s)
Run
Mode
Lnitial data Units
Edit
U
U
U
U
U
U
U
U U
U
U
Rated
current
x 1.5
1.0 sec.
01
Rated
current
0.5 sec.
00
01
10.
0.
00
2
A
Hrs.
60
Func.
Code
b037
b038
B039
B040
B041
b042
B043
B044
b045
b046
b049
B050
B051
B052
B053
B054
“b” Function Defaults
Name Description
Function code display restriction
Initial display selection
Automatic user parameter registration
Torque limit selection Four option codes:
Torque limit 1 (fwd/power) Torque limit level in forward
Torque limit 3 (rev/power) Torque limit level in reverse
Torque limit 4 (fwd/regen.) Torque limit level in forward regen.
Torque LAD STOP selection Two option codes:
Reverse run protection Two option codes:
Dual Rating Selection
Controlled deceleration on power loss
DC bus voltage trigger level of ctrl. decel.
Over-voltage threshold of ctrl. decel.
Deceleration time of ctrl. decel. Range is 0.01 to 3600.0
Initial freq. drop of ctrl. decel. Setting of initial freq. drop.
Seven option codes:
00Full display 01Function-specific display 02User setting (and b037) 03Data comparison display 04Basic display 05Monitor display only 000Func. code that SET key
pressed last displayed.(*)
001~030d001~d030 displayed 201F001 displayed 202B display of LCD operator
Two option codes:
00Disable 01Enable
00Quadrant-specific setting mode 01Terminal-switching mode 02Analog voltage input mode(O)
powering quadrant, range is 0 to 200%/no(disabled)
powering quadrant, range is 0 to 200%/no(disabled)
quadrant, range is 0 to 200%/no(disabled)
00Disable 01Enable
00No protection 01Reverse rotation is protected 00 (CT mode) / 01 (VT mode)
Four option codes:
00Trips 01Decelerates to a stop 02Decelerates to a stop with DC
bus voltage controlled
03Decelerates to a stop with DC
bus voltage controlled, then
restart Setting of DC bus voltage to start controlled decel. operation. Range is
0.0 to 1000.0 Setting the OV-LAD stop level of controlled decel. operation. Range is
0.0 to 1000.0
Range is 0.0 to 10.0 Hz
Run
Mode
Lnitial data Units
Edit
U
U
U
U
U
U
U
U
U
U U
U
U
U U
04
001
00
00
200 %
200 %
200 %
00
01
00
00
220.0/
440.0
360.0/
720.0
1.0 sec
0.0 Hz
V
V
61
Func.
Code
B060
B061
B062
B063
B064
b065
b070
b071
b075
B078
b079
B082
B083
B084
B085
B086
“b” Function Defaults
Name Description
Maximum-limit level of window comparator (O)
Minimum-limit level of window comparator (O)
Hysteresis width of window comparator (O)
Maximum-limit level of window comparator (OI)
Minimum-limit level of window comparator (OI)
Hysteresis width of window comparator (OI)
Operation level at O disconnection Operation level at OI disconnection Ambient temperature setting Set range is,
Watt-hour clearance Two option codes:
Watt-hour display gain Set range is,
Start frequency Sets the starting frequency for the
Carrier frequency Sets the PWM carrier (internal
Initialization mode (parameters or trip history)
Country for initialization Select default parameter values for
Frequency scaling conversion factor
Set range, {Min.-limit level (b061) + hysteresis width (b062)x2} to 100 %
(Minimum of 0%) Set range, 0 to {Max.-limit level (b060) - hysteresis width (b062)x2} % (Maximum of 0%) Set range, 0 to {Max.-limit level (b060) - Min.-limit level (b061)}/2 % (Maximum of 10%)
Set range, {Min.-limit level (b064 + hysteresis width (b065)x2} to 100 %
(Minimum of 0%) Set range, 0 to {Max.-limit level (b063) - hysteresis width (b065)x2} % (Maximum of 0%) Set range, 0 to {Max.-limit level (b063) - Min.-limit level (b064)}/2 % (Maximum of 10%) Set range, 0 to 100%, or “no” (ignore) Set range, 0 to 100%, or “no” (ignore)
-10~50 C
00OFF 01ON (press STR then clear)
1.~1000.
inverter output, range is 0.10 to 9.99 Hz
switching frequency), range is 2.0 to
15.0 kHz Select initialized data, five option codes:
00Initialization disabled 01Clears Trip history 02Initializes all Parameters 03Clears Trip history and
initializes all parameters 04Clears Trip history and
initializes all parameters and
EzSQ program
country on initialization, two option codes:
00area A 01area B Specify a constant to scale the displayed frequency for D007 monitor, range is 0.01 to 99.99
Run
Mode
Lnitial data Units
Edit
U
9
9
9
9
9
U U
9 9
9
U
U
U
U
U
100. %
0. %
0. %
100. %
0. %
0. %
no -
no -
40
00 -
1.
0.50 Hz
2.0 kHz
00
00
1.00
C
62
Func.
Code
B087
B088
b089
b090
B091
B092
B093
b094
b095
“b” Function Defaults
Name Description
STOP key enable Select whether the STOP key on the
keypad is enabled, three option codes:
00Enabled 01Disabled always 02 Disabled for stop
Restart mode after FRS Selects how the inverter resumes
operation when free-run stop (FRS) is cancelled, three options:
00Restart from 0Hz 01Restart from frequency
detected from real speed of
motor (freq. matching) 02Restart from frequency
detected from real speed of
motor (active freq. matching)
Automatic carrier frequency reduction
Dynamic braking usage ratio Selects the rate of use (in %) of the
Stop mode selection Select how the inverter stops the
Cooling fan control Selects when the fan is ON during
Clear elapsed time of cooling fan
Initialization target data Select initialized parameters, four
Dynamic braking control (BRD) selection
Three option codes:
00Disabled 01Enabled, depending on the
output current 02Enabled, depending on the
heat-sink temperature
regenerative braking resistor per 100 sec. intervals, range is 0.0 to 100%. 0%: Function disabled >0%: Enabled, per value
motor, two option codes:
00DEC (decelerate to stop) 01FRS (free-run to stop)
inverter operation, four options:
00Fan is always ON 01Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF) 02Fan is temperature controlled Two option codes:
00Count 01Clear
option codes:
00All parameters 01All parameters except in/output
terminals and communication.
02Only registered parameters in
Uxxx. 03All parameters except
registered parameters in Uxxx
and b037. Three option codes:
00Disable 01Enable during run only 02Enable always
63
Run
Mode
Lnitial data Units
Edit
U
U
U
U
U
U
U
U
U
00
00
01 -
0.0 %
00
01 -
00 -
00 -
01 -
Func.
Code
b096
b097
B100
b101
b102
b103
b104
b105
b106
b107
b108
b109
“b” Function Defaults
Name Description
BRD activation level Range is:
330 to 380V (200V class) 660 to 760V (400V class)
BRD resistor value Min.Resistance to 600.0
Free V/F setting, freq.1 Set range, 0 ~ value of b102
Free V/F setting, voltage.1 Set range, 0 ~ 800V
Free V/F setting, freq.2 Set range, value of b100 ~b104
Free V/F setting, voltage.2 Set range, 0 ~ 800V
Free V/F setting, freq.3 Set range, value of b102 ~b106
Free V/F setting, voltage.3 Set range, 0 ~ 800V
Free V/F setting, freq.4 Set range, value of b104 ~b108
Free V/F setting, voltage.4 Set range, 0 ~ 800V
Free V/F setting, freq.5 Set range, value of b108 ~b110
Free V/F setting, voltage.5 Set range, 0 ~ 800V
Run
Mode
Lnitial data Units
Edit
U
Min.
U
Resistanc e
U U U U U U U U U U
360/
720
0. Hz
0.0 V
0. Hz
0.0 V
0. Hz
0.0 V
0. Hz
0.0 V
0. Hz
0.0 V
V
Oh m
b110
b111
b112
b113
B120
b121
b122
b123
b124
b125
b126
b127
B130
B131
b132
Free V/F setting, freq.6 Set range, value of b108 ~b112
Free V/F setting, voltage.6 Set range, 0 ~ 800V
Free V/F setting, freq.7 Set range, b110 ~ 400
Free V/F setting, voltage.7 Set range, 0 ~ 800V
Brake control enable Two option codes:
00Disable 01Enable
Brake Wait Time for Release Set range: 0.00 to 5.00 sec
Brake Wait Time for Acceleration Brake Wait Time for Stopping Set range: 0.00 to 5.00 sec
Brake Wait Time for Confirmation Brake release freq. Set range: 0 to 400Hz
Brake release current Set range: 0~200% of inverter rated
Braking freq. setting Set range: 0 to 400Hz
Deceleration overvoltage suppression enable
Decel. overvolt. suppress level DC bus voltage of suppression.
Decel. overvolt. suppress const.
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
current
00Disabled 01Enabled 02Enabled with accel.
Range is: 200V class330 to 395 400V class660 to 790 Accel. rate when b130=02. Set range: 0.10 ~ 30.00 sec.
64
U U U U U
U U
U U
U U
U U
U
U
0. Hz
0.0 V
0. Hz
0.0 V
00 -
0.00 Sec
0.00 Sec
0.00 Sec
0.00 Sec
0.00 Sec
(rated
current)
0.00 Hz
00
380
/760
1.00 sec
A
V
Func.
Code
B133
B134
b145
b150
b160
b161
b163
b164
b165
b166
b171
b180
b190
b191
b192
b193
“b” Function Defaults
Name Description
Decel. overvolt. suppress proportional gain Decel. overvolt. suppress integral time GS input mode Two option codes:
Display ex.operator connected When an external operator is
1st parameter of Dual Monitor Set any two "d" parameters in b160
2nd parameter of Dual Monitor
Frequency set in monitoring Two option codes:
Automatic return to the initial display
Ex. operator com. loss action Five option codes:
Data Read/Write select
Inverter mode selection Three option codes:
Initialization trigger (*)
Password Settings A 0000(Invalid Password)
Password authentication A 0000-FFFF
Password Settings B 0000(Invalid Password)
Password authentication B 0000-FFFF
Proportional gain when b130=01. Range is: 0.00 to 5.00 Integration time when b130=01. Range is: 0.00 to 150.0
00No trip (Hardware shutoff only) 01Trip
connected via RS-422 port, the built-in display is locked and shows only one "d" parameter configured in: d001 ~ d030
and b161, then they can be monitored in d050. The two parameters are switched by up/down keys.
Set range: d001 ~ d030
00Freq. set disabled 01Freq. set enabled
10 min. after the last key operation, display returns to the initial parameter set by b038. Two option codes:
00Disable 01Enable
00Trip 01Trip after deceleration to a stop 02Ignore 03Coasting (FRS) 04Decelerates to a stop 00 Read/Write OK 01 Protected
00No function 01Std. IM (Induction Motor) 03PM(Permanent Magnet Motor)
This is to perform initialization by parameter input with b084, b085 and
b094. Two option codes: 00Initialization disable 01Perform initialization
0001-FFFF(Password)
0001-FFFF(Password)
Run
Mode
Lnitial data Units
Edit
9 9
U
U
U
U
9
9
9
U U
U
U U
U U
0.20
1.0 sec
00 -
001
001
002
00 -
00 -
02 -
00 -
00 -
00 -
0000 -
0000 -
0000 -
0000 -
65
Intelligent Terminal Functions
“C” Function Defaults Func. Code
C001
C002
C003
C004
C005
C006
C007
C011 C012 C013 C014 C015 C016 C017 C021
C022
C026
C027
Input [1] function Select input terminal [1] function,
Input [2] function Select input terminal [2] function,
Input [3] function
[GS1 assignable]
Input [4] function
[GS2 assignable]
Input [5] function
[PTC assignable]
Input [6] function Select input terminal [6] function,
Input [7] function Select input terminal [7] function,
Input [1] active state
Input [2] active state
Input [3] active state
Input [4] active state
Input [5] active state
Input [6] active state
Input [7] active state
Output [11] function
[EDM assignable]
Output [12] function
Alarm relay function 48 programmable functions
[EO] terminal selection (Pulse/PWM output)
Name Description
68 options (see next section)
68 options (see next section)
Select input terminal [3] function, 68 options (see next section)
Select input terminal [4] function, 68 options (see next section)
Select input terminal [5] function, 68 options (see next section)
68 options (see next section)
68 options (see next section) Select logic conversion, two option codes:
00normally open [NO] 01normally closed [NC]
48 programmable functions available for logic (discrete) outputs (see next section)
available for logic (discrete) outputs (see next section) 13 programmable functions:
00Output frequency (PWM) 01Output current (PWM) 02Output torque (PWM) 03Output frequency (Pulse train) 04Output voltage (PWM) 05Input power (PWM) 06Electronic thermal load ratio
(PWM)
07LAD frequency (PWM) 08Output current (Pulse train) 10Heat sink temperature (PWM) 12General output (PWM) 15Pulse train input monitor 16Option(PWM)
Run
Mode
Edit
U U
U U U U
U U
U U U U U U U
U U
U
Lnitial data Units
00
[FW]
01
[RV]
02
[CF1]
03
[CF2]
09
[2CH]
18
[RS]
13
[USP]
00
00
00
00
00
00
00
01
[FA1]
00
[RUN]
05
[AL]
07
      
66
Func. Code
C028
C030
C031 C032 C036 C038
C039
C040
C041
C241
C042
C043
C044
C045
C046
“C” Function Defaults
Name Description
[AM] terminal selection (Analog voltage output
0...10V)
Digital current monitor reference value
Output [11] active state
Output [12] active state
Alarm relay active state
Output mode of low current detection
Low current detection level Set the level of low load detection,
Output mode of overload warning
Overload warning level Sets the overload warning signal
Overload warning level, 2nd motor
Frequency arrival setting for acceleration
Frequency arrival setting for deceleration
PID deviation level Sets the allowable PID loop error
Frequency arrival setting 2 for acceleration Frequency arrival setting 2 for deceleration
11 programmable functions:
00Output frequency 01Output current 02Output torque 04Output voltage 05Input power 06Electronic thermal load ratio 07LAD frequency 10Heat sink temperature 11Output torque (with code) 13General output 16Option
Current with digital current monitor output at 1,440Hz Range is 20%~200% of rated current Select logic conversion, two option codes:
00normally open [NO] 01normally closed [NC]
Two option codes: 00During acceleration,
deceleration and constant speed 01During constant speed only
range is 0.0 to 2.0*inverter rated current Two option codes:
00During accel., decel. and constant speed
01During constant speed only
level between 0% and 200% (from 0 to two time the rated current of the inverter) Sets the overload warning signal level between 0% and 200% (from 0 to two time the rated current of the inverter) Sets the frequency arrival setting threshold for the output frequency during acceleration, range is 0.0 to 400.0 Hz Sets the frequency arrival setting threshold for the output frequency during deceleration, range is 0.0 to 400.0 Hz
magnitude (absolute value), SP-PV, range is 0.0 to 100% Set range is 0.0 to 400.0 Hz
Set range is 0.0 to 400.0 Hz
Run
Mode
Edit
U
9
U U U U
U
U
U
U
U
U
U
U U
Lnitial data Units
07
[LAD]
Rated current
00
00 -
01
01
INV rated
current
01
Rated current
x 1.15
Rated current
x 1.15
0.0 Hz
0.0 Hz
3.0 %
0.00 Hz
0.00 Hz
A
 
A
A
A
67
Func. Code
C047
C052
C053
C054
C055
C056
C057
C058
C059
C061
C063 C064 C071
C072
C074
C075
“C” Function Defaults
Name Description
Pulse train input/output scale conversion
PID FBV output high limit
PID FBV output low limit
Over-torque/under-torque selection
Over/under-torque level (Forward powering mode) Over/under-torque level (Reverse regen. mode) Over/under-torque level (Reverse powering mode) Over/under-torque level (Forward regen. mode) Signal output mode of Over/under-torque
Electronic thermal warning level Zero speed detection level Set range is 0.0 to 100.0Hz
Heat sink overheat warning
Communication speed Eight option codes:
Modbus address Set the address of the inverter on
Communication parity Three option codes:
Communication stop bit Two option codes:
If EO terminal is configured as pulse train input (C027=15), scale conversion is set in C047. Pulse-out = Pulse-in (C047) Set range is 0.01 to 99.99 When the PV exceeds this value, the PID loop turns OFF the PID second stage output, range is 0.0 to 100% When the PV goes below this value, the PID loop turns ON the PID second stage output, range is
0.0 to 100% Two option codes:
00Over-torque 01Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes: 00During accel., decel. and
constant speed 01During constant speed only
Set range is 0 to 100% Setting 0 means disabled.
Set range is 0 to 110 C
032,400 bps 044,800 bps 059,600 bps 0619,200 bps 0738,400 bps 0857,600 bps 0976,800 bps 10115,200 bps
the network. Range is 1 to 247
00No parity 01Even parity 02Odd parity
11 bit 22 bit
Run
Mode
Edit
9
U
U
U
U U U U U
U U
U U
U U
U
Lnitial data Units
1.00
100.0 %
0.0 %
00 -
100. %
100. %
100. %
100. %
01 -
90 %
0.00 Hz
100.
05 baud
1.
00
1 bit
C
68
Func. Code
C076
C077
C078
C081
C082
C085
C091
C096
C098 C099 C100
C101
“C” Function Defaults
Name Description
Communication error select
Communication error time-out
Communication wait time Time the inverter waits after
O input span calibration Scale factor between the external
OI input span calibration Scale factor between the external
Thermistor input (PTC) span calibration Debug mode enable * Displays debug parameters.
Communication selection
EzCOM start adr. of master 01-08
EzCOM end adr. of master 01-08
EzCOM starting trigger
Up/Down memory mode selection
Selects inverter response to communications error. Five options:
00Trip 01Decelerate to a stop and trip 02Disable 03Free run stop (coasting) 04Decelerates to a stop
Sets the communications watchdog timer period. Range is 0.00 to 99.99 sec
0.0 = disabled
receiving a message before it transmits. Range is 0. to 1000. ms
frequency command on terminals L–O (voltage input) and the frequency output, range is 0.0 to 200%
frequency command on terminals L–OI (voltage input) and the frequency output, range is 0.0 to 200% Scale factor of PTC input. Range is 0.0 to 200%
Two option codes:
00Disable 01Enable <Do not set>
(for factory use)
00Modbus-RTU 01 EzCOM 02 EzCOM<administrator>
00 Input terminal 01 Always
Controls speed setpoint for the inverter after power cycle. Two option codes:
00Clear last frequency (return to default frequency F001)
01Keep last frequency adjusted
by UP/DWN
Run
Mode
Edit
U
U
U
9
9
9 9
U
U U U
U
Lnitial data Units
02
0.00 sec.
0. msec.
100.0 %
100.0 %
100.0 %
00
00
01
01
00
00
  
69
Func. Code
C102
C103
C104
C105 C106 C109 C111
C130 C131 C132 C133 C140 C141 C142 C143
C144
C145 C146
“C” Function Defaults
Name Description
Reset selection Determines response to Reset
input [RS]. Four option codes:
00Cancel trip state at input signal
ON transition, stops inverter if in Run Mode
01Cancel trip state at signal OFF
transition, stops inverter if in Run Mode
02Cancel trip state at input ON
transition, no effect if in Run Mode
03Clear the memories only
related to trip status
Restart mode after reset Determines the restart mode after
reset is given, three option codes:
00Start with 0 Hz 01Start with freq. matching 02Start with active freq. matching
UP/DWN clear mode Freq. set value when UDC signal is
given to the input terminal, two option codes:
000 Hz 01Original setting (in the
EEPROM memory at power on)
EO gain adjustment Set range is 50 to 200%
AM gain adjustment Set range is 50 to 200%
AM bias adjustment Set range is 0 to 100%
Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from 0 to two time the rated current of the inverter)
Output [11] on delay
Output [11] off delay
Output [12] on delay
Output [12] off delay
Relay output on delay
Relay output off delay
Logic output 1 operand A
Logic output 1 operand B
Logic output 1 operator Applies a logic function to calculate
Logic output 2 operand A
Logic output 2 operand B
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
All the programmable functions available for logic (discrete) outputs except LOG1 to LOG3, OPO, no
[LOG] output state, Three options:
00[LOG] = A AND B 01[LOG] = A OR B 02[LOG] = A XOR B
All the programmable functions available for logic (discrete) outputs except LOG1 to LOG3, OPO, no
Run
Mode
Edit
U
U
U
9 9 9 9
U U U U U U U U
U
U U
Lnitial data Units
00
00 -
00 -
100. %
100. %
0. %
Rated current
x 1.15
0.0 Sec.
0.0 Sec.
0.0 Sec.
0.0 Sec.
0.0 Sec.
0.0 Sec.
00 00
00
00
00
A
 
 
70
Func. Code
C147
C148 C149
C150
C160 C161 C162 C163 C164 C165 C166 C169
“C” Function Defaults
Name Description
Logic output 2 operator Applies a logic function to calculate
[LOG] output state, Three options:
00[LOG] = A AND B 01[LOG] = A OR B 02[LOG] = A XOR B
Logic output 3 operand A
Logic output 3 operand B
Logic output 3 operator Applies a logic function to calculate
Input [1] response time
Input [2] response time
Input [3] response time
Input [4] response time
Input [5] response time
Input [6] response time
Input [7] response time
Multistage speed/position determination time
All the programmable functions available for logic (discrete) outputs except LOG1 to LOG3, OPO, no
[LOG] output state, Three options:
00[LOG] = A AND B 01[LOG] = A OR B 02[LOG] = A XOR B
Sets response time of each input terminal, set range: 0 (x 2 [ms]) to 200 (x 2 [ms]) (0 to 400 [ms])
Set range is 0. to 200. (x 10ms)
Run
Mode
Edit
U
U U
U
U U U U U U U U
Lnitial data Units
00
00 01
00
1.
1.
1.
1.
1.
1.
1.
0. ms
 
      
Input Function Summary Table – This table shows all thirty-one intelligent input functions
at a glance. Detailed description of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4-8.
Input Function Summary Table
Option
Code
Terminal
Symbol
FW FORWARD Run/Stop
00
RV Reverse Run/Stop
01
CF1 *1
02
CF2
03
CF3
04
CF4
05
JG Jogging
06
DB External DC braking
07
SET
08
Function Name Description
Multi-speed Select, Bit 0 (LSB)
Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB)
Set (select) 2nd Motor Data
ON Inverter is in Run Mode, motor runs forward OFF Inverter is in Stop Mode, motor stops ON Inverter is in Run Mode, motor runs reverse OFF Inverter is in Stop Mode, motor stops ON Binary encoded speed select, Bit 0, logical 1 OFF Binary encoded speed select, Bit 0, logical 0 ON Binary encoded speed select, Bit 1, logical 1 OFF Binary encoded speed select, Bit 1, logical 0 ON Binary encoded speed select, Bit 2, logical 1 OFF Binary encoded speed select, Bit 2, logical 0 ON Binary encoded speed select, Bit 3, logical 1 OFF Binary encoded speed select, Bit 3, logical 0
ON
OFF Inverter is in Stop Mode ON DC braking will be applied during deceleration OFF DC braking will not be applied
ON
OFF
Inverter is in Run Mode, output to motor runs at jog parameter frequency
The inverter uses 2nd motor parameters for generating frequency output to motor The inverter uses 1st (main) motor parameters for generating frequency output to motor
71
2CH
09
FRS Free-run Stop
11
EXT External Trip
12
USP
13
CS
14
SFT Software Lock
15
AT
16
RS Reset Inverter
18
PTC
19
2-stage Acceleration and Deceleration
Unattended Start Protection
Commercial power source switchover
Analog Input Voltage/Current Select
PTC thermistor Thermal Protection (C005 only)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON Motor can be driven by commercial power OFF Motor is driven via the inverter
ON
OFF The parameters may be edited and stored ON OFF
ON
OFF Normal power-ON operation
ANLG
OPEN
Frequency output uses 2nd-stage acceleration and deceleration values Frequency output uses standard acceleration and deceleration values Causes output to turn OFF, allowing motor to free run (coast) to stop Output operates normally, so controlled deceleration stop motor When assigned input transitions OFF to ON,
inverter latches trip event and displays No trip event for ON to OFF, any recorded trip events remain in history until reset On powerup, the inverter will not resume a Run command (mostly used in the US) On powerup, the inverter will resume a Run command that was active before power loss
The keypad and remote programming devices are prevented from changing parameters
Refer to “Analog Input Settings” on page 3-13.
The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted
When a thermistor is connected to terminal [5] and [L], the inverter checks for over-temperature and will cause trip event and turn OFF output to motor A disconnect of the thermistor causes a trip event, and the inverter turns OFF the motor
E 12
Option
Code
20
21
22
23
24
27
Terminal
Symbol
STA Start
STP Stop
F/R FWD, REV
PID PID Disable
PIDC PID Reset
UP Remote Control UP
Function Name Description
(3-wire interface)
(3-wire interface)
(3-wire interface)
Function (motorized speed pot.)
Input Function Summary Table
ON Starts the motor rotation OFF No change to present motor status ON Stops the motor rotation OFF No change to present motor status ON Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction
OFF Selects the direction of motor rotation: OFF = REV.
While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction
ON Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active (A071=01)
OFF Has no effect on PID loop operation, which operates
normally if PID Enable is active (A071=01)
ON Resets the PID loop controller. The main
consequence is that the integrator sum is forced to
zero OFF No effect on PID controller ON Accelerates (increases output frequency) motor from
current frequency OFF Output to motor operates normally
72
Option
Code
28
29
31
32
33
34
35
36
37
38
39
40
41
42
Option
Code
44
46
47
50
51
Input Function Summary Table
Terminal
Symbol
DWN Remote Control Down
UDC Remote Control Data
OPE Operator Control
SF1 Multi-speed Select,
SF2 Multi-speed Select,
SF3 Multi-speed Select,
SF4 Multi-speed Select,
SF5 Multi-speed Select,
SF6 Multi-speed Select,
SF7 Multi-speed Select,
OLR Overload Restriction
TL Torque Limit Selection
TRQ1 Torque limit switch 1
TRQ2 Torque limit switch 2
Terminal
Symbol
BOK Brake confirmation
LAC LAD cancellation
PCLR Pulse counter clear
ADD ADD frequency enable
F-TM Force Terminal Mode
Function Name Description
Function (motorized speed pot.)
Clearing
Bit operation Bit 1
Bit operation Bit 2
Bit operation Bit 3
Bit operation Bit 4
Bit operation Bit 5
Bit operation Bit 6
Bit operation Bit 7
Source Changeover
Input Function Summary Table
Function Name Description
ON Decelerates (decreases output frequency) motor
from current frequency OFF Output to motor operates normally ON Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101 must be set=00 to enable this function to work OFF UP/DWN frequency memory is not changed ON Forces the source of the output frequency setting
A001 and the source of the Run command A002 to
be from the digital operator OFF
Source of output frequency set by A001 and source
of Run command set by A002 is used ON Bit encoded speed select, Bit 1, logical 1 OFF Bit encoded speed select, Bit 1, logical 0 ON Bit encoded speed select, Bit 2, logical 1 OFF Bit encoded speed select, Bit 2, logical 0 ON Bit encoded speed select, Bit 3, logical 1 OFF Bit encoded speed select, Bit 3, logical 0 ON Bit encoded speed select, Bit 4, logical 1 OFF Bit encoded speed select, Bit 4, logical 0 ON Bit encoded speed select, Bit 5, logical 1 OFF Bit encoded speed select, Bit 5, logical 0 ON Bit encoded speed select, Bit 6, logical 1 OFF Bit encoded speed select, Bit 6, logical 0 ON Bit encoded speed select, Bit 7, logical 1 OFF Bit encoded speed select, Bit 7, logical 0 ON Perform overload restriction OFF Normal operation ON
Setting of b040 is enabled OFF Max. torque is limited with 200%
ON
Torque limit related parameters of Powering/regen,
and FW/RV modes are selected by the combinations
OFF
of these inputs. ON
OFF
ON
Brake wait time (b124) is valid OFF
Brake wait time (b124) is not valid ON Set ramp times are ignored. Inverter output
immediately follows the freq. command. OFF Accel. and/or decel. is according to the
set ramp time ON Clear the position deviation data OFF Maintain the position deviation data ON
Adds the A145 (add frequency) value
to the output frequency OFF
Does not add the A145 value to the
output frequency ON Force inverter to use input terminals for output
frequency and Run command sources OFF
Source of output frequency set by A001 and source
of Run command set by A002 is used
73
Option
Code
52
53
56
57
58
59
60
61
62
65
66
67
68
69
70
73
Option
Code
77
78
81
82
83
84
85
86
255
Terminal
Symbol
ATR Enable torque
KHC Clear watt-hour data
MI1 General purpose input
MI2 General purpose input
MI3 General purpose input
MI4 General purpose input
MI5 General purpose input
MI6 General purpose input
MI7 General purpose input
AHD Analog command hold
CP1 Multistage-position
CP2 Multistage-position
CP3 Multistage-position
ORL Limit signal of homing
ORG Trigger signal of
SPD Speed/position
Terminal
Symbol
GS1 * GS1 input
GS2 * GS2 input
485 Start EzCOM
PRG Executing EzSQ
HLD Retain output
ROK Permission of Run
EB Rotation direction
DISP Display limitation
no No function
Function Name Description
command input
(1)
(2)
(3)
(4)
(5)
(6)
(7)
switch (1)
switch (2)
switch (3)
homing
changeover
Function Name Description
program
frequency
command
detection (C007 only)
Input Function Summary Table
ON Torque control command input is enabled OFF Torque control command input is disabled
ON Clear watt-hour data OFF No action ON General purpose input (1) is made ON under EzSQ OFF General purpose input (1) is made OFF under EzSQ ON General purpose input (2) is made ON under EzSQ OFF General purpose input (2) is made OFF under EzSQ ON General purpose input (3) is made ON under EzSQ OFF General purpose input (3) is made OFF under EzSQ ON General purpose input (4) is made ON under EzSQ OFF General purpose input (4) is made OFF under EzSQ ON General purpose input (5) is made ON under EzSQ OFF General purpose input (5) is made OFF under EzSQ ON General purpose input (6) is made ON under EzSQ OFF General purpose input (6) is made OFF under EzSQ ON General purpose input (7) is made ON under EzSQ OFF General purpose input (7) is made OFF under EzSQ ON Analog command is held OFF Analog command is not held
Multistage position commands are set according to
ON
the combination of these switches.
OFF ON OFF ON OFF ON Limit signal of homing is ON OFF Limit signal of homing is OFF ON Starts homing operation OFF No action ON Speed control mode OFF Position control mode
Input Function Summary Table
ON
EN60204-1 related signals:
Signal input of “Safe torque off” function.
OFF ON OFF ON Starts EzCOM OFF No execution ON Executing EzSQ program OFF No execution ON Retain the current output frequency OFF No retention ON Run command permitted OFF Run command is not permitted ON Forward rotation OFF Reverse rotation ON
Only a parameter configured in b038 is shown OFF All the monitors can be shown ON (input ignored) OFF (input ignored)
74
Option
Code
Output Function Summary Table – This table shows all functions for the logical outputs
(terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” in chapter 4.
Output Function Summary Table
00
01
02
03
04
05
06
07
09
10
11
12
13
19
20
21
Terminal
Symbol
RUN Run Signal
FA1 Frequency Arrival Type
FA2 Frequency Arrival Type
OL Overload Advance
OD Output Deviation for PID
AL Alarm Signal
FA3 Frequency Arrival Type
OTQ Over/under Torque
UV Undervoltage
TRQ Torque Limited Signal
RNT Run Time Expired
ONT Power ON time Expired
THM Thermal Warning
BRK Brake Release Signal
BER Brake Error Signal
ZS Zero Hz Speed
Function Name Description
ON When the inverter is in Run Mode OFF When the inverter is in Stop Mode ON When output to motor is at the set frequency
1–Constant Speed
2–Over frequency
Notice Signal 1
Control
3–Set frequency
Signal
Detection Signal
OFF When output to motor is OFF, or in any
acceleration or deceleration ramp
ON When output to motor is at or above the set freq,
even if in accel (C042) or decel (C043) ramps
OFF When output to motor is OFF, or at a level below
the set frequency
ON When output current is more than the set
threshold (C041) for the overload signal
OFF When output current is less than the set threshold
for the deviation signal
ON When PID error is more than the set threshold for
the deviation signal
OFF When PID error is less than the set threshold for
the deviation signal
ON When an alarm signal has occurred and has not
been cleared
OFF When no alarm has occurred since the last
cleaning of alarm(s)
ON When output to motor is at the set frequency,
during accel (C042) and decel (C043).
OFF When output to motor is OFF, or is not at a level of
the set frequency
ON Estimated motor torque exceeds the specified
level
OFF Estimated motor torque is lower than the specified
level ON Inverter is in Undervoltage OFF Inverter is not in Undervoltage ON Torque limit function is executing OFF Torque limit function is not executing ON Total running time of the inverter exceeds the
specified value OFF Total running time of the inverter does not exceed
the specified value ON Total power ON time of the inverter exceeds the
specified value OFF Total power ON time of the inverter does not
exceed the specified value ON
Accumulated thermal count exceeds the C061 set
value OFF Accumulated thermal count does not exceed the
C061 set value ON Output for brake release OFF No action for brake ON Brake error has occurred OFF Brake performance is normal ON Output frequency falls below the threshold
specified in C063
75
Option
Code
22
23
24
25
26
27
28
31
32
33
34
35
39
40
Output Function Summary Table
Terminal
Symbol
OFF Output frequency is higher than the threshold
DSE Speed Deviation
POK Positioning Completion
FA4 Frequency Arrival Type
FA5 Frequency Arrival Type
OL2 Overload Advance
ODc Analog Voltage Input
OIDc Analog Current input
FBV PID Second Stage
NDc Network Disconnect
LOG1 Logic Output Function 1
LOG2 Logic Output Function 2
LOG3 Logic Output Function 3
WAC Capacitor Life Warning
WAF Cooling Fan Warning
Function Name Description
specified in C063 ON Deviation of speed command and actual speed
Excessive
4–Over frequency
5–Set frequency
Notice Signal 2
Disconnect Detection
Disconnect Detection
Output
Detection
Signal
Signal
exceeds the specified value P027. OFF Deviation of speed command and actual speed
does not exceed the specified value P027. ON Positioning is completed OFF Positioning is not completed ON When output to motor is at or above the set freq.,
even if in accel (C045) or decel (C046) ramps OFF When output to motor is OFF, or at a level below
the set frequency ON When output to motor is at the set frequency,
during accel (C045) and decel (C046). OFF When output to motor is OFF, or is not at a level of
the set frequency ON When output current is more than the set
threshold (C111) for the overload signal OFF When output current is less than the set threshold
for the deviation signal ON
When the [O] input value < B070 setting (signal
loss detected) OFF When no signal loss is detected ON
When the [OI] input value < B071 setting (signal
loss detected) OFF When no signal loss is detected ON Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053) OFF Transitions to OFF when the PID Process Variable
(PV) exceeds the PID High Limit (C052), and
transitions to OFF when the inverter goes from
Run Mode to Stop Mode ON When the communications watchdog timer (period
specified by C077) has time out OFF When the communications watchdog timer is
satisfied by regular communications activity ON
When the Boolean operation specified by C143
has a logical “1” result OFF
When the Boolean operation specified by C143
has a logical “0” result ON
When the Boolean operation specified by C146
has a logical “1” result OFF
When the Boolean operation specified by C146
has a logical “0” result ON
When the Boolean operation specified by C149
has a logical “1” result OFF
When the Boolean operation specified by C149
has a logical “0” result ON Lifetime of internal capacitor has expired. OFF Lifetime of internal capacitor has not expired. ON Lifetime of cooling fan has expired.
76
Option
Code
Output Function Summary Table
Terminal
Symbol
OFF Lifetime of cooling fan has not expired.
Function Name Description
41
42
43
44
45
46
50
51
52
53
54
55
58
59
60
62
63
255
FR Starting Contact Signal
OHF Heat Sink Overheat
Warning
LOC Low load detection
MO1 General Output 1
MO2 General Output 2
MO3 General Output 3
IRDY Inverter Ready Signal
FWR Forward Rotation
RVR Reverse Rotation
MJA Major Failure Signal
WCO Window Comparator for
Analog Voltage Input
WCOI Window Comparator for
Analog Current Input
FREF Frequency Command
Source
REF Run Command Source
SETM 2nd Motor Selection
EDM STO (Safe Torque Off)
Performance Monitor (Output terminal 11 only)
OPO Option card output
no Not used
ON Either FW or RV command is given to the inverter OFF No FW or RV command is given to the inverter, or
both are given to the inverter ON Temperature of the heat sink exceeds a specified
value (C064) OFF Temperature of the heat sink does not exceed a
specified value (C064) ON Motor current is less than the specified value
(C039) OFF Motor current is not less than the specified value
(C039) ON General output 1 is ON OFF General output 1 is OFF ON General output 2 is ON OFF General output 2 is OFF ON General output 3 is ON OFF General output 3 is OFF ON Inverter can receive a run command OFF Inverter cannot receive a run command ON Inverter is driving the motor in forward direction OFF Inverter is not driving the motor in forward
direction ON Inverter is driving the motor in reverse direction OFF Inverter is not driving the motor in reverse
direction ON Inverter is tripping with major failure OFF Inverter is normal, or is not tripping with major
failure ON Analog voltage input value is inside of the window
comparator OFF Analog voltage input value is outside of the
window comparator ON Analog current input value is inside of the window
comparator OFF Analog current input value is outside of the
window comparator ON Frequency command is given from the operator OFF Frequency command is not given from the
operator ON Run command is given from the operator OFF Run command is not given from the operator ON 2nd motor is being selected OFF 2 ON STO is being performed
OFF STO is not being performed
ON (output terminal for option card) OFF (output terminal for option card) ON ­OFF -
nd
motor is not being selected
77
Motor Constants Functions
“H” Function Defaults
Func.
Code
H001
H002
H202
Auto-tuning selection Three option codes:
Motor constant selection
Motor constant selection,
nd
2
motor
Name Description
00Disabled 01Enabled with motor stop 02Enabled with motor rotation
Four option codes:
00Hitachi standard motor 02Auto tuned data
Run
Mode
Edit
U
U
U
Lnitial data Units
00 -
00 -
00 -
H003
H203
H004
H204
H005
H205
H006
H206
H020
H220
H021
H221
H022
H222
H023
H223
H024
H224
H030
H230
H031
Motor capacity
Motor capacity,
nd
motor
2
Motor poles setting
Motor poles setting,
nd
2
motor Motor speed response constant Motor speed response constant, 2nd motor Motor stabilization constant
Motor stabilization constant, 2nd motor Motor constant R1 (Hitachi motor) Motor constant R1, 2nd motor (Hitachi motor) Motor constant R2
(Hitachi motor)
Motor constant R2, 2nd motor Motor constant L
(Hitachi motor)
Motor constant L, 2nd motor Motor constant I0
(Hitachi motor)
Motor constant I0, 2nd motor Motor constant J
(Hitachi motor)
Motor constant J, 2nd motor
Motor constant R1
(Auto tuned data)
Motor constant R1, 2nd motor Motor constant R2
(Auto tuned data)
(Hitachi motor)
(Hitachi motor)
(Hitachi motor)
(Hitachi motor)
(Auto tuned data)
Eleven selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5
Four selections: 2 / 4 / 6 / 8 / 10
Set range is 1 to 1000
Motor constant (factory set), range is 0 to 255
0.001~65.535 ohms
0.001~65.535 ohms
0.01~655.35mH
0.01~655.35A
0.001~9999 kgm2
0.001~65.535 ohms
0.001~65.535 ohms
Specified by
U
the capacity of
each inverter
U
U U
9 9 9
9
Specified by
U
the capacity of
each inverter
U U U U U U U U U
Specified by
U
the capacity of
each inverter
U U
kW
model
4 poles
4 poles
100. -
100. -
100.
100.
mode
mode
kW
Ohm
Ohm
Ohm
Ohm
mH
mH
A
A
kgm
kgm
ohm
ohm
ohm
2
2
78
“H” Function Defaults
Func.
Code
H231
H032
H232
H033
H233
H034
H234
H050
H051
Motor constant R2, 2nd motor Motor constant L
(Auto tuned data)
Motor constant L, 2nd motor Motor constant I0
(Auto tuned data)
Motor constant I0, 2nd motor Motor constant J
(Auto tuned data)
Motor constant J, 2nd motor Slip compensation P gain for V/f control with FB Slip compensation I gain for V/f control with FB
Name Description
(Auto tuned data)
(Auto tuned data)
(Auto tuned data)
(Auto tuned data)
0.01~655.35mH
0.01~655.35A
0.001~9999 kgm
0.00-10.00
0.-1000.
PM Motor Constants Functions
“H” Function Defaults
Func.
Code
H102
H103
H104
H105
H106
H107
H108
H109
H110
H111
PM motor code setting
PM motor capacity
PM motor pole setting
PM Rated Current
PM const R(Resistance)
PM const Ld(d-axis inductance)
PM const Lq(q-axis inductance)
PM const Ke(Induction voltage constant)
PM const J(Moment of inertia)
PM const R (Resistance, Auto)
Name Description
00Hitachi standard
01Auto-Tuning
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0 /3.7/
4.0/5.5/7.5/11.0/15.0/18.5 2/4/6/8/10/12/14/16/18/20/22/24/26/ 28/ 30/32/34/36/38/40/42/44/46/48
(0.00-1.00)×Rated current of the
inverter [A]
0.001-65.535 [Ω]
0.01-655.35 [mH]
0.01-655.35 [mH]
0.0001-6.5535 [V/(rad/s)]
0.001-9999.000 [kgm2]
0.001-65.535 [Ω]
2
(Use H106-H110 at motor constants)
(Use H109-H110, H111-H113 at motor constants)
Run
Mode
Edit
U U U U U U U U U
Run
Mode
Edit
U
U
U
U U U U U U U
Lnitial data Units
0.2 Times
2. (s)
Lnitial data Units
00
kW
dependent
kW
dependent
kW
dependent
kW
dependent
kW
dependent
kW
dependent
kW
dependent
kW
dependent
kW
dependent
ohm
mH
mH
A
A
kgm
kgm
-
kW
Poles
A
Ohm
mH
mH
V/(rad/
s)
kgm^2
Ohm
2
2
79
Func.
Code
H112
H113
H116
H117
H118
H119
H121
H122
H123
H131
H132
H133
H134
“H” Function Defaults
Name Description
PM const Ld(d-axis inductance, Auto)
PM const Lq(q-axis inductance, Auto)
PM Speed Response
PM Starting Current
PM Starting Time
PM Stabilization Constant
PM Minimum Frequency
PM No-Load Current
PM Starting Method Select
PM Initial Magnet Position Estimation 0V Wait Times
PM Initial Magnet Position Estimation Detect Wait Times
PM Initial Magnet Position Estimation Detect Times
PM Initial Magnet Position Estimation Voltage Gain
0.01-655.35 [mH]
0.01-655.35 [mH]
1-1000 [%]
20.00-100.00 [%]
0.01-60.00 [s]
0-120 [%]
0.0-25.5 [%]
0.00-100.00 [%]
00 Normal 01 Initial Magnet Position
0-255
0-255
0-255
0-200
Estimation
Run
Mode
Edit
U U U U U U
9 9
U
U U
U U
Lnitial data Units
kW
dependent
kW
dependent
100
70.00[%]
1.00[s]
100[%]
8.0 [%]
10.00 [%]
0
10
10
30
100
mH
mH
%
%
s
%
%
%
-
-
-
-
-
80
Expansion Card Functions
“P” parameters will be appeared when the expansion option is connected.
“P” Function Default s
Func.
Code
P001
P003
P004
P011
P012
p015
P026
P027
P031
P033
P034 p036
p037 p038
p039
p040
Reaction when option card error occurs
[EA] terminal selection Three option codes:
Pulse train input mode selection for feedback
Encoder pulse setting Sets the pulse number (ppr) of the
Simple positioning selection Two option codes:
Creep Speed
Over-speed error detection level Speed deviation error detection level
Torque command input selection
Torque command level input Set range is 0~200%
Torque bias mode selection Five option codes:
Torque bias value setting Range is –200~200%
Torque bias polar selection Two option codes:
Speed limit of Torque control (Forward rotation) Speed limit of Torque control (Forward rotation)
Name Description
Two option codes:
00…Inverter trips 01…Ignores the error (Inverter
continues operation)
00…Speed reference (incl. PID) 01…For control with encoder
feedback 02…Extended terminal for EzSQ Four option codes:
00…Single-phase pulse [EA] 01…2-phase pulse (90 difference) 1
([EA] and [EB]) 02…2-phase pulse (90 difference) 2
([EA] and [EB]) 03…Single-phase pulse [EA] and
direction signal [EB]
encoder, set range is 32~1024 pulses
00…simple positioning deactivated 01…simple positioning activated
Set range is start frequency (b082) ~10.00 Hz Set range is 0~150%
Set range is 0~120 Hz
Six option codes:
00…Analog voltage input [O] 01…Analog current input [OI] 03…Operator, 06…Option
00…No bias 01…Operator
00…According to the sign 01…According to the rotation
direction 05…Option Set range is 0.00~120.00Hz
Set range is 0.00~120.00Hz
Run
Mode
Edit
U
U
U
U
U U
U U
U
9
U
9
U
9 9
Lnitial data Units
00
00
00
512.
00
5.00
115.0
10.00
00
0.
00
0.
00
0.00
0.00
-
-
-
-
-
Hz
%
Hz
-
%
-
%
-
Hz
Hz
81
Func.
Code
p041
P044
P045
P046
P048
P049
p055
p056
p057 p058
P060
P061
P062
P063
P064
P065
P066
P067
P068
P069
P070 P071
“P” Function Default s
Name Description
Speed / Torque control switching time Communication watchdog
timer (for option)
Inverter action on communication error (for option)
DeviceNet polled I/O: Output instance number Inverter action on communication idle mode
Motor poles setting for RPM 0/2/4/6/8/10/12/14/16/18/20/22/24/26
Pulse train input frequency scale setting Pulse train input frequency filter time constant setting Pulse train input bias setting Set range is –100~100 %
Limitation of the pulse train input setting
Multistage position 0
Multistage position 1
Multistage position 2
Multistage position 3
Multistage position 4
Multistage position 5
Multistage position 6
Multistage position 7
Homing mode selection
Homing direction
Low speed homing freq. 0 to 10Hz
High speed homing freq. 0 to 400Hz
Set range is 0 to 1000 ms
Set range is 0.00 to 99.99s
00 (tripping), 01 (tripping after decelerating and
stopping the motor), 02 (ignoring errors), 03 (stopping the motor after
free-running), 04 (decelerating and stopping the
motor) 0-20
00 (tripping), 01 (tripping after decelerating and
stopping the motor), 02 (ignoring errors), 03 (stopping the motor after
free-running), 04 (decelerating and stopping the
motor)
/28/ 30/32/34/36/38/40/42/44/46/48 Sets the pulse numbers at max. frequency, set range is 1.0~32.0 kHz Set range is 0.01~2.00 sec.
Set range is 0~100 %
P073 to P072
(Displayed higher 4-digits only)
00…Low speed mode 01…High speed mode 00…Forward rotation side 01…Reverse rotation side
Run
Mode
Edit
U U
U
U
U
U U
U U U
9 9 9 9 9 9 9 9 9 9
9 9
Lnitial data Units
0.
1.00
00
1
00
0
25.0
0.10
0.
100.
0
0
0
0
0
0
0
0
00
01
5.00
5.00
ms
s
-
-
-
Poles
kHz
sec
%
%
Pulse
s
Pulse
s
Pulse
s
Pulse
s
Pulse
s
Pulse
s
Pulse
s
Pulse
s
-
-
Hz
Hz
82
Func.
Code
P072
P073
P075
P077
p100
~
P131 P140
P141 P142 P143 P144 P145 P146 P147 P148 P149 P150 P151 P152 P153 P154 P155
“P” Function Default s
Name Description
Position range (Forward)
Position range (Reverse)
Positioning mode selection
Encoder disconnection timeout EzSQ user parameter U(00) ~ U(31)
EzCOM number of data 1 to 5
EzCOM destination 1 adderss 1 to 247
EzCOM destination 1 register 0000 to FFFF
EzCOM source 1 register 0000 to FFFF
EzCOM destination 2 adderss 1 to 247
EzCOM destination 2 register 0000 to FFFF
EzCOM source 2 register 0000 to FFFF
EzCOM destination 3 adderss 1 to 247
EzCOM destination 3 register 0000 to FFFF
EzCOM source 3 register 0000 to FFFF
EzCOM destination 4 adderss 1 to 247
EzCOM destination 4 register 0000 to FFFF
EzCOM source 4 register 0000 to FFFF
EzCOM destination 5 adderss 1 to 247
EzCOM destination 5 register 0000 to FFFF
EzCOM source 5 register 0000 to FFFF
0 to +268435455(Higher 4-digits displayed)
–268435455 to 0(Higher 4-digits displayed)
00…With limitation 01…No limitation (shorter route)
P004 is to be set 00 or 01
0.0 to 10.0 s
Each set range is 0~65535
Run
Mode
Edit
9 9
U
9
9 9
9 9 9 9 9 9 9 9 9 9 9 9 9 9 9
Lnitial data Units
+2684354 55
-2684354 55
00
1.0
0.
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
Pulse
s
Pulse
s
-
s
-
5
1
2
3
4
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
83
CE-EMC Installation Guidelines
You are required to satisfy the EMC directive (2004/108/EC) when using an WJ200 inverter in an EU country.
To satisfy the EMC directive and to comply with standard, you need to use a dedicated EMC filter suitable for each model, and follow the guidelines in this section. Following table shows the compliance condition for reference.
Table 1. Condition for the compliance
Model Cat. Carrier f Motor cable
All WJ200 series C1 2kHz 20m (Shielded)
Table 2. Applicable EMC filter
Input class Inverter model Filter model (Schaffner)
WJ200-001SFE
FS24828-8-07
FS24828-27-07
FS24829-8-07
FS24829-16-07
FS24829-50-07
FS24830-6-07
FS24830-12-07
FS24830-29-07
FS24830-48-07
1-ph. 200V class
3-ph. 200V class
3-ph. 400V class
WJ200-110L and 150H needs to be installed in a metal cabinet and add ferrite core at the input cable to meet category C1. Unless otherwise category C2.
Important notes
1. Input choke or other equipment is required if necessary to comply with EMC directive
from the harmonic distortion point of view (IEC 61000-3-2 and 4).
2. If the motor cable length exceeds 20m, use output choke to avoid unexpected problem
due to the leakage current from the motor cable (such as malfunction of the thermal relay, vibration of the motor, etc..).
3. As user you must ensure that the HF (high frequency) impedance between adjustable
frequency inverter, filter, and ground is as small as possible.
 Ensure that the connections are metallic and have the largest possible contact
WJ200-002SFE WJ200-004SFE WJ200-007SFE WJ200-015SFE WJ200-022SFE WJ200-001LFU WJ200-002LFU WJ200-004LFU WJ200-007LFU WJ200-015LFU WJ200-022LFU WJ200-037LFU FS24829-25-07 WJ200-055LFU WJ200-075LFU WJ200-110LFU FS24829-70-07 WJ200-150LFU FS24829-75-07 WJ200-004HFE WJ200-007HFE WJ200-015HFE WJ200-022HFE WJ200-030HFE WJ200-040HFE FS24830-15-07 WJ200-055HFE WJ200-075HFE WJ200-110HFE WJ200-150HFE
84
areas (zinc-plated mounting plates).
4. Avoid conductor loops that act like antennas, especially loops that encompass large
areas.
 Avoid unnecessary conductor loops.  Avoid parallel arrangement of low-level signal wiring and power-carrying or
noise-prone conductors.
5. Use shielded wiring for the motor cable and all analog and digital control lines.
 Allow the effective shield area of these lines to remain as large as possible; i.e., do
not strip away the shield (screen) further away from the cable end than absolutely necessary.
 With integrated systems (for example, when the adjustable frequency inverter is
communicating with some type of supervisory controller or host computer in the same control cabinet and they are connected at the same ground + PE-potential), connect the shields of the control lines to ground + PE (protective earth) at both ends. With distributed systems (for example the communicating supervisory controller or host computer is not in the same control cabinet and there is a distance between the systems), we recommend connecting the shield of the control lines only at the end connecting to the adjustable frequency inverter. If possible, route the other end of the control lines directly to the cable entry section of the supervisory controller or host computer. The shield conductor of the motor cables always must connected to ground + PE at both ends.
 To achieve a large area contact between shield and ground + PE-potential, use a
PG screw with a metallic shell, or use a metallic mounting clip.
 Use only cable with braided, tinned copper mesh shield (type “CY”) with 85%
coverage.
 The shielding continuity should not be broken at any point in the cable. If the use of
reactors, contactors, terminals, or safety switches in the motor output is necessary, the unshielded section should be kept as short as possible.
 Some motors have a rubber gasket between terminal box and motor housing. Very
often, the terminal boxes, and particularly the threads for the metal PG screw connections, are painted. Make sure there is always a good metallic connection between the shielding of the motor cable, the metal PG screw connection, the terminal box, and the motor housing. If necessary, carefully remove paint between conducting surfaces.
6. Take measures to minimize interference that is frequently coupled in through
installation cables.
 Separate interfering cables with 0.25m minimum from cables susceptible to
interference. A particularly critical point is laying parallel cables over longer distances. If two cables intersect (one crosses over the other), the interference is smallest if they intersect at an angle of 90°. Cables susceptible to interference should therefore only intersect motor cables, intermediate circuit cables, or the wiring of a rheostat at right angles and never be laid parallel to them over longer distances.
7. Minimize the distance between an interference source and an interference sink
(interference- threatened device), thereby decreasing the effect of the emitted interference on the interference sink.
 You should use only interference-free devices and maintain a minimum distance of
0.25 m from the adjustable frequency inverter.
8. Follow safety measures in the filter installation.
 If using external EMC filter, ensure that the ground terminal (PE) of the filter is
properly connected to the ground terminal of the adjustable frequency inverter. An HF ground connection via metal contact between the housings of the filter and the adjustable frequency inverter, or solely via cable shield, is not permitted as a protective conductor connection. The filter must be solidly and permanently
85
connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs.
To achieve a protective ground connection for the filter:
 Ground the filter with a conductor of at least 10 mm  Connect a second grounding conductor, using a separate grounding terminal
parallel to the protective conductor. (The cross section of each single protective conductor terminal must be sized for the required nominal load.)
2
cross-sectional area.
86
(
)
g
Installation for WJ200 series (example of SFE models)
Model LFx (3-ph. 200V class) and HFx (3-ph. 400V class) are the same concept for the installation.
PE
(Foot-print)
Earth line is connected to the heatsink of the inverter
or PE terminal for bigger models
Power supply 1-ph. 200V
EMC filter
Metal plate (earth)
The filter is a footprint type, so it is located between the inverter and the metal plate.
Remove the insulation material coating of the earth contact portions so to obtain good
rounding condition.
L1,N
U,V,W
Cable clamp *
Metal plate (earth)
Shielded cable
Cable clamp *
M
*) Both earth portions of the shielded cable must be connected to the earth point by cable clamps.
Input choke or equipment to reduce harmonic current is necessary for CE marking (IEC 61000-3-2 and IEC61000-3-3) from the harmonic current point of view, even conducted emission and radiated emission passed without the input choke.
87
Hitachi EMC Recommendations
WARNING: This equipment should be installed, adjusted, and serviced by qualified
personal familiar with construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury.
Use the following checklist to ensure the inverter is within proper operating ranges and conditions.
1. The power supply to WJ200 inverters must meet these specifications:
 Voltage fluctuation ±10% or less  Voltage imbalance ±3% or less  Frequency variation ±4% or less  Voltage distortion THD = 10% or less
2. Installation measure:
 Use a filter designed for WJ200 inverter. Refer to the instruction of the applicable
external EMC filter.
3. Wiring:
 Shielded wire (screened cable) is required for motor wiring, and the length must be
20 meter or less.
 If the motor cable length exceeds the value shown above, use output choke to
avoid unexpected problem due to the leakage current from the motor cable.
 The carrier frequency setting must be 2 kHz to satisfy EMC requirements.  Separate the power input and motor wiring from the signal/process circuit wiring.
4. Environmental conditions—when using a filter, follow these guidelines:
 Ambient temperature: –10 to 50 °C (Derating is required when the ambient
temperature exceeds 40 °C)
 Humidity: 20 to 90% RH (non-condensing)  Vibration: 5.9 m/sec2 (0.6 G) 10 ~ 55Hz  Location: 1000 meters or less altitude, indoors (no corrosive gas or dust)
88
Functional Safety (Certification in Progress)
Introduction
The Gate Suppress function can be utilized to perform a safe stop according to the EN60204-1, stop category 0 (Uncontrolled stop by power removal). It is designed to meet the requirements of the ISO13849-1, PL=d only in a system in which EDM signal is monitored by an “external device monitor”.
Stop Category defined in EN60204-1
Category 0 : Uncontrolled stop by immediate (< 200 ms) shut-down of the power supply to
the actuators
Category 1 : Controlled stop by interrupting the power supply to the actuator level if, for
example, the hazardous movement has been brought to a standstill (time-delayed shut-down of the power supply).
Category 2 : Controlled stop. The power supply to the drive element is not interrupted.
Additional measures to EN 1037 (protection from unexpected restart) are necessary.
How it works
Interrupting the current to GS1 or GS2, for example removing the link between either GS1 or GS2 and PLC or both GS1/GS2 and PLC disables the drive output, i.e. the power supply to the motor is cut by stopping the switching of the output transistors in a safe way. EDM output is activated when GS1 and GS2 are given to the drive.
Always use both inputs to disable the drive. If for any reason only one channel is opened, the drive output is stopped but the EDM output is not activated. In this case the Safe Disable input wiring must be checked.
Activation
Turning on the safety switch automatically assign the GS1 input and GS2 input automatically.
Safetyfunction
switch
ONOFF
EDMfunction
OFF
(normal)
switch
ON
(EDM)
To assign EDM (external device monitor) output, please turn the EDM function switch on. EDM output is automatically assigned on intelligent output terminal 11.
89
(When safety switch or EDM switch is turned off, the intelligent input and output terminal assigned on will be set as "no" function, and contact will remain normally off.)
Always use both inputs to disable the drive. If for any reason only one channel is opened, the drive output is stopped but the EDM output is not activated. In this case the Safe Disable input wiring must be checked.
Installation
According to the safety standard listed above, please install referring to the example. Please be sure to use the both GS1 and GS2, and construct the system that GS1 andGS2 are both turned off when safety input is given to the inverter.
When the Gate Suppress function is utilized, connect the drive to a safety certified interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1 and GS2.
item
Input [3] and [4]
function
active state
Output [11] function C021 62
Output [11] active
state
GS input mode b145
Note 1) They are automatically set when safety switch is turned ON, cannot be changed.
Note 2) Those are automatically assigned when EDM switch is turned ON, cannot be
changed.
Note 3) Inverter trips with "E37". When competing with external trip (E12), E37 has priority.
Note 4) While the drive is the trip status "E037" and either GS1 or GS2 is activated, on the
safety by is not guaranteed.
Function
code C003 77 GS1: Safety input 1 (note 1) C004 78 C013 01 NC: Normally Closed (note 1) Input [3] and [4] C014 01 NC: Normally Closed (note 1)
C031 00 NO: Normally Open (note 2)
data description
GS2Safety input 2 (note 1)
EDMExternal Device Monitor(note2)
00 Output is shut off by hardware. No trip.
Output is shut off by hardware, and then,
01
trip. (note3) (note4)
90
A
Wiring example
When the Gate Suppress function is utilized, connect the drive to a safety certified interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1 and GS2.
Safety Switch (Example: emergency
push button)
Safety input
Reset Switch
T11 T12
G9SX-GS226-T15-RC
T21 T22
T31
EDM (feedback) input
+24V
T33
T32
A1
2
S14
S24
Fuse
+24V
Safety output
Safety Unit
Standard
(IEC61508,ISO13849) certified
CM2
EDM
GS1
GS2
PLC L
KM1
WJ200
M
By pressing the emergency stop button, the current to GS1 and GS2 is shut off, and the inverter output is shut off. By this, motor is free-running. This behavior is according to the stop category 0 defined in EN60204.
Note 1: Above is the example to use the intelligent input terminal with source logic. When
it is used with sink logic, the wiring is to be modified.
Note 2: The wire for safety relay and emergency input signal are to be shielded coaxial
cable for example RS174/U (produced by LAPP) by MIL-C17, or KX2B by NF C 93-550 with diameter 2.9mm with less than 2 meters. Please be sure to ground the shielding.
Note 3: All the inductance related parts such as relay and contactor are required to
contain the over-voltage protection circuit.
 
The arch extinguishing fuse with rated voltage AC250V, rated current 100mA complies
to either IEC6127 –2/-3/-4
Example)
SOCEQ series AC250V, 100mA (UL, SEMKO, BSI) Little216 series AC250V, 100mA (CCC, UL, CSA, SEMKO, CE, VDE)
91
As described on page 4-14 of this manual, inverter doesn’t block the current flowing into itself when it is not powered. This may cause the closed circuit when two or more inverters are connected to common I/O wiring as shown below to result in unexpected turning the on the input. This may lead to dangerous situation. To avoid this closed circuit, please put the diode (rated:50V/0.1A) in the path as described below.
In case of Source logic
Short
Short
bar
bar
Power ON P24 PLC
L
Input
1
Power OFF P24 PLC
L
ON
Power ON
P24
PLC
L
Inserting
diode
1
P24
PLC L
Input
OFF
Power OFF
1
1
Switch
OFF
Short bar
P24
PLC
L
1
Input
ON
Switch
OFF
P24
PLC
L
Input
1
OFF
Switch
OFF
Short
bar
P24 PLC
L
1
P24
Switch
OFF
PLC
L
1
92
Components to be combined
Followings are the example of the safety devices to be combined.
Series Model Norms to comply Certification date
GS9A 301 ISO13849-2 cat4, SIL3 06.06.2007
G9SX GS226-T15-RC IEC61508 SIL1-3 04.11.2004
NE1A SCPU01-V1 IEC61508 SIL3 27.09.2006
The configuration of and components used in any circuit other than an appropriately pre approved safety module that interfaces with the WJ200 GS1/GS2 and EDM ports MUST be at least equivalent to CAT 3 PLd under ISO 13849-1:2006 in order to be able to claim an overall CAT 3 PLd for the WJ200 and external circuit combination.
The EMI level that the external module has been assessed to must be at least equivalent to that of Appendix E IEC 62061.
Periodical check (proof test)
Proof test is essential to be able to reveal any dangerous undetected failures after a period of time, in this case 1 year. Carrying out this proof test at least one a year is the condition to comply the ISO13849-1 PLd.
- To activate (give current to) GS1 and GS2 simultaneously and separately to see output is allowed and EDM is conducting
Terminal Status
GS1 current OFF current ON current OFF current ON GS2 current OFF current OFF current ON current ON
EDM conducted not conducted Not conducted not conducted
(output) forbidden forbidden forbidden Allowed
- To activate (give current to) both GS1 and GS2 to see output is allowed and EDM is not conducting
- To activate (give current to) GS1, not to activate GS2 and see output is forbidden and EDM is not conducting
- To activate (give current to) GS2, not to activate GS1 and see output is forbidden and EDM is not conducting
- To deactivate (interrupt current to) both GS1 and GS2 to see output is forbidden and EDM is conducting
Precautions
1. To assure, that the Safe Disable function appropriately fulfills the safety requirements of the application, a throughout risk assessment for the whole safety system has to be carried out.
2. The Safe Disable function does not cut the power supply to the drive and does not provide electrical isolation. Before any installation or maintenance work is done, the drives power supply must be switched off and place a tag/lock-out.
3. The wiring distance for the Safe Disable inputs should be shorter than 30 m.
4. The time from opening the Safe Disable input until the drive output is switched off is less than 10 ms.
93
Loading...