Hitachi WJ-0007H, WJ-0002S, WJ-0022S, WJ-0015S, WJ-0015H User Manual

...
Pursuing the Ideal Compact Inverter
Pursuing the Ideal Compact Inverter
Series
Designed for excellent performance and user friendliness
Hitachi Solar Water Pump
Inverter System
Hitachi Solar Water Pump
Inverter System
KHKSCO GROUP
Ii
Objective of this Manual:
The objective of this manual is to educate the user for proper installation and for putting the system into use.
Scope Statement:
The scope of this manual covers only installation, commissioning and general operations of the Solar Water Pump Inverter
How-ever, some information on primary maintenance can be found in this manual.
Ii
ii
Operation Manual
Table of Contents:
Chapter
Page
About the System
1
Overview
1-1
Solar Power and Irrigation
1-1
Safety
2
Definitions And Symbols
2-1
General Warnings and Cautions
2-2
UL Cautions, Warnings And Instructions
2-3
Installation Preparation & Requirements
3
Terminal Screw and Wire size
3-1
Fuse Size
3-2
Mounting Location
3-3
Electrical Wiring
3-4
Connection to Solar Water Pump System
4
4
Power Wire For Solar Inverter
4-1
Control Wiring For Solar Inverter
2-8
2-9
Keypad Description
2-10
Key and Indicator Legend
2-11
Operating Principle And Hardware
5
Principle of Solar Water Pump Inverter
5-1
MPPT Over view
5-2
Motor Requirement
5-3
System Start-Up
6
Parameter Settings
6-1
Steps for setting Inverter for System
6-4
Fault Code
6-5
Monitoring System Data
6-6
PC Tools for Monitoring
6-9
Maintenance And Inspection
7
Modbus Network Communication
8
Introduction
8-1
Connecting Inverter to Modbus Network
8-2
Modbus Parameter Setting
8-3
Common Fault and Remedies
9
Contacts
About the System 1
In this chapter
Page
About the System
Over View
1-1
Solar Power and Irrigation
1-1
For the purpose of this manual and the product the following symbols are used.
Overview:
The system operates on power generated using solar PV (photovoltaic) system. The photovoltaic array converts the solar energy into electricity, which is used for running the motor pump set. The pumping system draws water from the open well, bore well, stream, pond, canal etc. The system requires a shadow-free area for installation of the Solar Panel. Of all the ways solar electricity benefits the people on Earth, none makes as much difference in the daily lives as pumping water. By providing water for irrigation or potable water have obvious benefits for people in rural areas and especially for those in developing nations. The proper choice is determined by application specific factors like how much water is required and whether the water should be available at night or just during high sun hours.
Solar Power and Irrigation:
Irrigation is best utilisation of Solar powerUsually area which require more water have high solar irradiationDuring summer time when more water is require, there is more sun lightWater need not be available at nightMaintenance facilities are lacking, Solar pump run maintenance free.Solar tracking can use.
Safety 2
In this chapter
Page
Introduction
2-1
Definition and Symbol
2-3
General warning and Cautions
2-3
UL Cautions, Warning and Instructions
2-1 Safety Information
Definitions and Symbols
HAZARDOUS HIGH VOLTAGE: Motor control equipment and electronic
controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housing or protrusions at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
WARNING: This equipment should be installed, adjusted, and serviced by qualified
electrical maintenance personnel familiar with the construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury.
WARNING: For equipment protection, install a ground leakage type breaker with a
fast response circuit capable of handling large currents. The ground fault protection circuit is not designed to protect against personal injury.
WARNING: HAZARDOUS OF ELECTRICAL SHOCK. DISCONNECT INCOMING
POWER BEFORE WORKING ON THIS CONTROL.
WARNING: Wait at least five (5) minutes after turning OFF the input power supply
before performing maintenance or an inspection. Otherwise, there is the danger of electric shock.
CAUTION: Proper grounds, disconnecting devices and other safety devices and
their location are the responsibility of the user and are not provided by Hitachi Industrial Equipment Systems Co., Ltd.
HIGH VOLTAGE: Dangerous voltage exists until power light is OFF. Wait at least
five (5) minutes after input power is disconnected before performing maintenance
Ii
WARNING: This equipment has high leakage current and must be permanently
(fixed) hard-wire to earth ground via two independent cables.
WARNING: Rotating shafts and above-ground electrical potentials can be
hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Installation, alignment and maintenance should be performed only by qualified personnel.
CAUTION:   b) Any motor used must be of a suitable rating.  c) Motors may have hazardous moving path. In this event suitable protection must be
provided.
CAUTION: Hazardous (main) terminals for any interconnection (motor, contact
breaker, filter, etc.) must be inaccessible in the final installation.
CAUTION: This equipment should be installed in IP54 or equivalent enclosure.
CAUTION: Connection to field wiring terminals must be reliably fixed having
two independent means of mechanical support. Use a termination with cable support (figure below), or strain relief, cable clamp, etc.
Ii
General Warnings and Cautions
WARNING: Never modify the unit. Otherwise, there is a danger of electric shock and/or injury. CAUTION: Withstand voltage test and insulation resistance tests (HIPOT) are executed before
the units are shipped, so there is no need to conduct these tests before operation.
CAUTION: Do not attach or remove wiring or connectors when power is applied. Also, do not
check signals during operation.
CAUTION: Be sure to connect the grounding terminal to earth ground. CAUTION: When inspecting the unit, be sure to wait five minutes after turning OFF the power
supply before opening the cover.
UL Cautions, Warnings and Instructions
Warnings and Cautions for Troubleshooting and Maintenance The warnings and instructions in
this section summarizes the procedures necessary to ensure an inverter installation complies with
delines.
-001L, -002L, -004L, -007L, -015S, -
022S, -004H, -007H, -015H, -022H and -030H)
WARNING: Use 75 -001S, -002S, -004S, -007S, -015L, -
022L, -037L, -055L, -075L, -110L, -150L, -040H, -055H, -075H, -110H and -150H) WARNING: Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes, 240 or 480V maximum.
WARNING: When protected by CC, G, J, or R class Fuses, or when Protected By A Circuit
Breaker Having An Interrupting Rating Not Less Than 100,000 rms Symmetrical Amperes, 240 or 480 Volts Maximum.
WARNING: Install device in pollution degree 2 environment.   WARNING: Solid state motor overload protection is provided in each model WARNING: Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electric Code and any additional local codes
Installation Preparation 3
And Requirements
In this chapter
Page
Installation Preparation
3-1
Mounting Location
2-3
Electrical Wiring
2-3
Ii
Installation Preparation
Terminal Screw and Wire Size
Inverter Model
Screw Size
Required
Torque (N-m)
Wire Range
WJ-0001S
M3.5
1.0
AWG16
(1.3mm2)
WJ-0002S
WJ-
007S
M4
1.4
AWG14
(2.1mm2)
WJ-0015S
M4
1.4
AWG12
(3.3mm2)
WJ-0022S
M4
1.4
AWG10
(5.3mm2)
WJ-0004H WJ-0007H WJ-0015H
M4
1.4
AWG16
(1.3mm2)
WJ-0022H WJ-0030H
M4
1.4
AWG14
(2.1mm2)
WJ-0040H
M4
1.4
AWG12
(3.3mm2)
WJ-0055H WJ-0075H
M5
3.0
AWG10
(5.3mm2)
WJ-0110H WJ-0150H
M6
5.9 to 8.8
AWG6 (13mm2)
Ii
Fuse Size
The unit shall be connected with a Listed Cartridge Nonrenewable fuse or Inverse time circuit breaker, rated 600 Vac with the current ratings as shown in the table below
Model No.
Fuse
Inverse Time
Circuit Breaker
Type E CMC
Type
Rating(Maximum A)
Rating (Maximum
A)
WJ-0001S
Class
J
10 A, AIC 200 kA
30A
MMS-32H,
240V,40A
WJ-0002S
Class
J
10 A, AIC 200 kA
WJ-0004S
Class
J
10 A, AIC 200 kA
WJ-0007S
Class
J
15 A, AIC 200 kA
WJ-0015S
Class
J
15 A, AIC 200 kA
WJ-0022S
Class
J
20 A, AIC 200 kA
WJ-0004H
Class
J
10 A, AIC 200 kA
20A
MMS-32H,
480V,40A or
MMS-63H,
480V,52A
WJ-0007H
Class
J
10 A, AIC 200 kA
WJ-0015H
Class
J
10 A, AIC 200 kA
WJ-0022H
Class
J
10 A, AIC 200 kA
WJ-0030H
Class
J
15 A, AIC 200 kA
WJ-0040H
Class
J
15 A, AIC 200 kA
WJ-0055H
Class
J
30 A, AIC 200 kA
40A
WJ-0075H
Class
J
30 A, AIC 200 kA
WJ-0110H
Class
J
50 A, AIC 200 kA
WJ-0150H
Class
J
50 A, AIC 200 kA
Ii
Mounting location
Hardware installation
Study the following caution messages associated with mounting the inverter. This is the time when mistakes are most likely to occur that will result in expensive rework, equipment damage, or personal injury.
CAUTION: Be sure to install the unit on flame-resistant material such as steel plate.
Otherwise, there is the danger of fire.
CAUTION: Be sure not to place any flammable materials near the inverter.
Otherwise, there is the danger of fire.
CAUTION: Be sure not to let the foreign matter enter vent openings in the inverter housing, such as wire clippings, spatter from welding, metal shavings, dust, etc. Otherwise, there is the danger of fire.
CAUTION: Be sure to install the inverter in a place that can bear the weight according to the specifications in the text. Otherwise, it may fall and cause injury to personnel.
CAUTION: Be sure to install the unit on a perpendicular wall that is not subject to vibration. Otherwise, it may fall and cause injury to personnel.
CAUTION: Be sure not to install or operate an inverter that is damaged or has missing parts. Otherwise, it may cause injury to personnel.
CAUTION: Be sure to install the inverter in a well-ventilated room that does not have direct exposure to sunlight, a tendency for high temperature, high humidity or dew condensation, high levels of dust, corrosive gas, explosive gas, inflammable gas, grinding­fluid mist, salt damage, etc. Otherwise, there is the danger of fire. Ensure Adequate Ventilation To summarize the caution messages – you will need to find a solid, non-flammable, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, it is recommended to maintain the specified clearance and the inverter specified in the below diagram.
CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.
Ii
Ensure Adequate Ventilation
To summarize the caution messages – you will need to find a solid, non-flammable, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, it is recommended to maintain the specified clearance and the inverter specified in the below diagram
CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.
Electrical Wiring
You will connect wiring to the input of the inverter. First, you must determine whether the inverter model you have required three-phase power only, or single-phase power only. All models have the same power connection terminals [R/L1], [S/L2], and [T/L3]. So you must refer to the specifications label (on the side of the inverter) for the acceptable power source types! For inverters that can accept single-phase power and are connected that way, terminal [S/L2] will remain unconnected. Note the use of ring lug connectors for a secure connection.
Ii
Single-phase 200V 0.1 to 0.4kW Three-phase 200V 0.1 to 0.75kW
Ii
Ii
Solar Water System 4
Wiring details
Ii
Connection to Solar Water Pump System
DC PV Power AC Grid Power
All Type Induction motor pump and PMAC motor Pump
Hitachi Solar
Water Pump
Inverter
Ii
Power Wiring For Solar Power in Solar Water Pump Inverter
( DC Input )
SOLAR PV
MODULE DC
POWER
DC Power
Hitachi Solar Water Pump Inverter
R S T
U V W M E
Water Submersible Pump AC
and PMAC Motor
+
-
+
-
Ii
Power Wiring For Solar Power Or Grid Power in Solar Water Pump Inverter AC Or DC Input
Note :
When AC Grid Power and DC PV Power use with change over switch,
Alternatively AC and DC power use in Inverter
AC Grid
Power
SOLAR PV
MODULE DC
POWER
AC / DC Power Change Over Switch, AC MCB, DC Fuses
Hitachi Solar Water Pump Inverter
R
S
T
+
-
U V W M E
Water Submersible Pump AC
and PMAC Motor
Option
+
-
Ii
Power Wiring For Solar Power and Grid Power
in Solar Water Pump Inverter AC & DC Input
When AC Grid and DC PV Power use together In Inverter Where DC PV Module Total
Vmp Value should be higher than AC Grid Voltage x 1.414
AC Grid
Power
SOLAR PV
MODULE DC
POWER
Switch, AC MCB, DC Fuses
Hitachi Solar Water Pump Inverter
R
S
T
+
-
U V W M E
Water Submersible Pump AC
and PMAC Motor
Fuses And Diodes For Reverse Polarity Protection
Note :
+
-
Ii
Control Wiring for Solar Water Pump Inverter:
For Rating 0.75KW to 15KW ( WJ200 )
For Rating above 15Kw ( SJ700 )
Note:
1. For Rating 0.75kw to 15Kw, Make switch between terminal L and 1 for giving Start command to pump and for above 15kw, It is require to put start switch between P24 and FW terminal of Control board.
2. Customer can use Push button for reset error of inverter for getting immediate restart command.
3. There is delay restart timer inside inverter for error come while dark cloud or suddenly power changes in PV panel. Like undervoltage
For Rating above 15Kw ( SJ700D )
Ii
Using the Front Panel Keypad
Inverter Keypad Description
Key and Indicator Legend
Items
Contents
(1) POWER LED
Turns ON (Green) while the inverter is powered up.
(2) ALARM LED
Turns ON (Red) when the inverter trips.
(3) Program LED
Turns ON (Green) when the display shows changeable
parameter.
Blinks when there is a mismatch in setting.
(4) RUN LED
Turns ON (Green) when the inverter is driving the motor.
(5) Monitor LED [Hz]
Turns ON (Green) when the displayed data is frequency related.
(6) Monitor LED [A]
Turns ON (Green) when the displayed data is current related.
(7) Run command LED
Turns ON (Green) when a Run command is set to the operator. (Run key is effective.)
(8) 7-seg LED
Shows each parameter, monitors etc.
(9) Run key
Makes inverter run.
(10) Stop/reset key
Makes inverter decelerates to a stop.Reset the inverter when it is in trip situation
(11) ESC key
Go to the top of next function group, when a function mode is
shown
Cancel the setting and return to the function code, when a
data is shown
Moves the cursor to a digit left, when it is in digit-to-digit
setting mode
Pressing for 1 second leads to display data of d001,
regardless of current display.
(12) Up key (13) Down key
Increase or decrease the data.Pressing the both keys at the same time gives you the digit-to-
digit edit.
(14) SET key
Go to the data display mode when a function code is shownStores the data and go back to show the function code, when
data is shown.
Moves the cursor to a digit right, when it is in digit-to-digit
display mode
(15) USB connector
Connect USB connector (mini-B) for using PC communication
Ii
SJ700 series Inverter Keypad description
Key and Indicator Legend
Name Function
Name Function
POWER lamp
Lights when the control circuit power is on.
ALARM lamp
Lights to indicate that the inverter has tripped. RUN (operation) lamp
Lights to indicate that the inverter is operating.
PRG (program) lamp
Lights when the monitor shows a value set for a function. This lamp starts blinking to indicate a warning (when the set value is invalid).
Monitor
Displays a frequency, output current, or set value.
Monitor lamps
Indicates the type of value and units displayed on the monitor. "Hz" (frequency), "V" (voltage), "A" (current), "kW" (electric power), and "%" (percentage)
RUN key enable LED
Lights up when the inverter is ready to respond to the RUN key. (When this lamp is on, you can start the inverter with the RUN key on the digital operator.)
RUN key
Starts the inverter to run the motor. This key is effective only when the operating device is the digital operator. (To use this key, confirm that the operating device indicator lamp is on.)
STOP/RESET key
Decelerates and stops the motor or resets the inverter from alarm status.
FUNC (function) key
Makes the inverter enter the monitor, function, or extended function mode.
STR (storage) key
Stores each set value. (Always press this key after changing a set value.)
1 (up) or 2 (down) key
Switches the inverter operation mode (among monitor, function, and extended function modes) or increases or decreases the value set on the monitor for a function.
Operating Principle 5
And Hardware
Ii
Operating Principal and Hardware:
Solar Water Pump Inverter :
WJ200 & SJ700 Series of Hitachi Inverter is low voltage range AC drive and it
available for 0.4Kw to 400Kw Motor rating which is design for drawing maximum power from PV module (Photovoltaic Cell).
Inverter has design to operate in Dual power supply AC power and DC power.
It is operating Maximum power point tracking algorithm to derive maximum power
from PV cell at any instant while in cloudy or sunny weather.
This inverter series specifically design for pump application which has special
reduce torque control mode with energy saving technology.
It is design for meet requirement of pump manufacturer and OEM to customize
application as per their requirements.
Control Mode: Reduce Torque technology is mostly utilized in pump application
where load on motor shaft have very high inertia / momentum. It operates on starting torque is normal and afterword torque is going to reduce and increase speed of motor. So, less power require to achieve higher speed of motor. It operate Energy saving function while reaching nearly constant speed where optimizing input power by reduce of output voltage and current.
Ii
MPPT overview
The Hitachi solar inverter uses maximum power pint tracking control software to
operate solar panel (PV) at maximum power generation level.
Hitachi solar inverter internal MPPT algorithm is used to derive maximum power
form PV cell at any instant and it is happen by changing output voltage and current in PV cell until maximum power is obtained.
When inverter is in stop command then PV cell generating short circuit current and if
the PV cells are not connected to any load, then output voltage of cell is same as open circuit voltage of PV.
See below I-V characteristic
The I-V curve is not constant for all instant, the intensity of sun ray and temperature
changes during a day time. The current changes linearly with Intensity and voltage change very small with temperature changes. So, for constant temperature, Maximum power varies proportionally with intensity of sun rays. The Maximum power is obtain at knee point of I-V curve.
System Start-up 6
Ii
Parameter setting
WJ200 series Inverter parameter setting for solar water pump inverterThere are six buttons available for setting parameters.
Run button : use for start motor form operator panel/ keypadStop/Reset button: use for stop motor form operator panel / keypad and also to reset
alarm
ESC button: use for going back to parameter group number. Use for go out from
parameters
SET button: use for going inside of parameter and setting change value of
parameters in eeprom memory
1 UP arrow and 2 DOWN arrow button: use for changing digit value, Means change
parameter number as well as value inside parameters
Ii
WJ200 series Inverter parameter setting for solar water pump inverter
After giving power to inverter, It show 0000 value of d001 parameter (output motor Hz)
Make b049 = 01 for making inverter in Variable torque mode (Specially pump application)
Check A017 = 02 For enabling MPPT algorithm, 00 means stop, 01 means for
terminal enabling
First to set motor data inside of inverter like KW, Hz, RPM, Current, VotlageA003 = Hz of motorH003 = KW of motorH004 = Pole of motor which come from RPM of motor.A002 = 01 Terminal Run commandF002 = 100 Sec , Acceleration TimeF003 = 1 Sec , Deceleration timeA020 = Put Total Vmp of connect PV cells,C001 = 56, Terminal 1 as Forward Run commandC006 = 18, Terminal 6 as Reset inverterP101 = 3 min,
Auto restart delay time after inverter get any alarm, Change as per requirements
P102 = 3000, Water level sensitivity,
For 1-PHASE (2-WIRE) PUMPS MAKE : 1- P129 = 00 2- A082 = MAX
For 60Hz Pump Make :
1- A017 = 00 2- P117 = 6000 3- A061 = 60 4- A003 = 60 5- A017 = 02
Note : Make B037 = 00
Ii
SJ700 series Inverter parameter setting for solar water pump inverter
After giving power to inverter, It show 0000 value of d001 parameter (output motor Hz)
Check A017 = 01 For enabling MPPT algorithm, 00 means stop, 01 means for
terminal enabling.
And Check Short link between terminal P24 and FW where Short link seen between
PLC and CM1 terminal.
First to set motor data inside of inverter like KW, Hz, RPM, Current, VotlageA003 = Hz of motorH003 = KW of motorH004 = Pole of motor which come from RPM of motor.A002 = 01 Terminal Run commandF002 = 100 Sec , Acceleration TimeF003 = 1 Sec , Deceleration timeA020 = Put Total Vmp of connect PV cells,C001 = 56, Terminal 1 as Forward Run commandC006 = 18, Terminal 6 as Reset inverterP101 = 3 min,
Auto restart delay time after inverter get any alarm, Change as per requirements
P130 = 3000, Water level sensitivity,
For 60Hz Pump Make :
1- A017 = 00
2- Remove FW 3- P111 = 6000
Note : Make B037 = 00
4- A061 = 60 5- A003 = 60 6- A017 = 01 7- FW Back
Ii
SJ700D series Inverter parameter setting for solar water pump inverter
After giving power to inverter, It show 0000 value of d001 parameter (output motor
Hz)
Check A017 = 02 For enabling MPPT algorithm, 00 means stop, 02 means for
terminal enabling.
First to set motor data inside of inverter like KW, Hz, RPM, Current, VotlageA003 = Hz of motorH003 = KW of motorH004 = Pole of motor which come from RPM of motor.A002 = 01 Terminal Run commandF002 = 100 Sec , Acceleration TimeF003 = 1 Sec , Deceleration timeA020 = Put Total Vmp of connect PV cells,C001 = 56, Terminal 1 as Forward Run commandC006 = 18, Terminal 6 as Reset inverterP101 = 3 min,
Auto restart delay time after inverter get any alarm, Change as per requirements
P130 = 3000, Water
level sensitivity,
For 60Hz Pump Make : A017 = 00 P111 = 6000
Note : Make B037 = 00
A061 = 60 A003 = 60 A017 = 02
Ii
Fault Codes
All fault come in parameters D081 to d086, means Hitachi drive can store last 6 fault
history.
Error Code
Name
Cause(s)
E01
Over-current event while at constant speed
The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly.
E02
Over-current event during deceleration
E03
Over-current event during acceleration
E04
Over-current event during other conditions
E05
Overload protection
When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.
E06
Braking resistor overload protection
When the BRD operation rate exceeds the setting of "b090", this protective function shuts off the inverter output and displays the error code.
E07
Over-voltage protection
When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.
E08
EEPROM error
When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.
E09
Under-voltage error
A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its output.
E10
Current detection error
If an error occurs in the internal current detection system, the inverter will shut off its output and display the error code.
E11
CPU error
A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.
E12
External trip
A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.
E13
USP
When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode until the error is cleared.
E14
Ground fault
The inverter is protected by the detection of ground faults between the inverter output and the
motor upon during powerup tests. This feature protects the inverter, and does not protect humans.
E15
Input over-voltage
The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state. After the fault is cleared, the inverter can enter Run Mode again.
E21
Inverter thermal trip
When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF.
E22
CPU communication error
When communication between two CPU fails, inverter trips and displays the error code.
E25
Main circuit error (*3)
The inverter will trip if the power supply establishment is not recognized because of a malfunction due to noise or damage to the main circuit element.
E30
Driver error
An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. The inverter has turned OFF the IGBT module output.
E35
Thermistor
When a thermistor is connected to terminals [5] and [L] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output.
E36
Braking error
When "01" has been specified for the Brake Control Enable (b120), the inverter will trip if it cannot receive the braking confirmation signal within the Brake Wait Time for Confirmation (b124) after the output of the brake release signal.
E37
Safe Stop
Safe stop signal is given.
E38
Low-speed overload protection
If overload occurs during the motor operation at a very low speed, the inverter will detect the overload and shut off the inverter output.
E40
Operator connection
When the connection between inverter and operator keypad failed, inverter trips and displays the error code.
E41
Modbus communication error
When ―trip‖ is selected (C076=00) as a
behavior in case of communication error, inverter trips when timeout happens.
E43
EzSQ invalid instruction
The program stored in inverter memory has been destroyed, or the PRG terminal was turned on without a program downloaded to the inverter.
E44
EzSQ nesting count error
Subroutines, if-statement, or for-next loop are nested in more than eight layers
E45
EzSQ instruction error
Inverter found the command which cannot be executed.
E50 to E59
EzSQ user trip (0 to 9)
When user –defined trip happens, inverter trips and displays the error code.
E60
Option error (DeviceNet Communications error)
If the disconnection due to the Bus-Off signal or timeout occurs during the operation using DeviceNet commands, the inverter will shut off its
output and display the error code shown on the right. (The inverter will trip according to the settings of "p45" and "P048".)
E61
Option error (duplicated MACID)
If two or more devices having the same MAC ID are detected in the same network, the inverter will display the error code shown on the right.
E62
Option error (External trip)
If the Force Fault/Trip bit of Attribute 17 in the Instance 1 of the Control Supervisory object is set to "1", the inverter will shut off its output and display the error code shown on the right.
E63 to E68
Option error
The inverter detects errors in the option board mounted in the optional slot. For details, refer to the instruction manual for the mounted option board.
E69
Option error (inverter communication error)
If timeout occurs during the communication between the inverter and DeviceNet option board, the inverter will shut off its output and display the error code shown on the right.
E80
Encoder disconnection
If the encoder wiring is disconnected, an encoder connection error is detected, the encoder fails, or an encoder that does not support line driver output is used, the inverter will shut off its output and display the error code shown on the right.
E81
Excessive speed
If the motor speed rises to "maximum frequency (A004) x over-speed error detection level (P026)" or more, the inverter will shut off its output and display the error code shown on the right.
E83
Positioning range error
If current position exceeds the position range (P072-P073), the inverter will shut off its output and display the error code.
Ii
Motor requirement
The all type induction and submersible motor can work under Hitachi solar
inverter
200VAC Hitachi inverter can work for 0VAC to 240VAC motor400VAC Hitachi inverter can work for 0 VDC to 460VAC motorMotor should be three phase three wire inputDC motor can’t be workFor PMDC motor, Please contact concern Hitachi Person.
Ii
Monitoring System Data :
“D” Group parameter is use for monitor inverter data
D001 = output Hz of inverter / Speed of motor in HzD002 = output current to motorD102 = DC voltage level at DC bus inside inverterD013 = Output voltage to motor, It may be less as per energy saving mode compare
to V/F ratio
D014 = input KW power consumptionD015 = Total KW power consume by inverter/motorD016 = Total Run time of motor in HrD017 = Total power on time of inverter in HrD018 = Heat sink temperature of inverter
PC tool for monitoring :
Ii
Maintenance and Inspection
Daily and Yearly Inspection Chart
Item Inspected
Check for…
Inspection
Cycle
Inspection
Method
Criteria
Daily
Year
Overall
Ambient environment
Extreme temperatures & humidity
Thermometer, hygrometer
Ambient temperature between – Humidity 90% or less non-condensing
Major devices
Abnormal noise & vib.
Visual and aural
Stable environment for electronic controls
Power supply voltage
Voltage tolerance
Digital volt meter, measure between inverter terminals [L1], [L2], [L3]
200V class: 50/60 Hz 200 to 240V (-15/+10%) 400V class: 50/60 Hz 380 to 460V (-15/+10%)
Main
circuit
Ground Insulation
Adequate resistance
5 Mohm or greater
Mounting
No loose screws
Torque wrench
M3.5: 1.0Nm M4: 1.4Nm M5: 3.0 M6: 3.9 to
5.1Nm M8: 5.9 to 8.8Nm
Components
Overheating
Thermal trip events
No trip events
IGBT
Resistance value
Terminal block
Secure connections
Visual
No abnormalities
Smoothing capacitors
Leaking, swelling
Visual
No abnormalities
Relay(s)
Chattering
Aural
Single click when switching ON or OFF
Resistors
Cracks or discoloring
Visual
Check Ohms of optional braking res.
Control circuit Function
Voltage balance between phases
Measure voltage between U,V,W
Difference must be 2% or less.
Protection circuit
e.g. Input Ex.trip signal and check inverter behavior and alarm signal.
Functions properly. Overall
No odor, discoloring, corrosion
Visual
No abnormalities Capacitor
Leaking, swelling
Visual
Undistorted appearance
Cooling Cooling fan
Noise
Power down, manually rotate
Rotation must be smooth
Dust
Visual
Vacuum to clean
Mounting
Visual
Mounted firmly Heat sink
Dust
Visual
Vacuum to clean
Display
LEDs
Legibility
Visual
All LED segments work
Ii
Note 1: The life of a capacitor is affected by the ambient temperature.
Note 2: Designed life of a cooling fan is.10 years. However, it is affected by the ambient
temperature and other environmental conditions.
Note 3: The inverter must be cleaned periodically. If dust accumulates on the fan and heat sink,
it can cause overheating of the inverter.
Network Communication 7
Ii
Modbus Network Communication
Introduction
WJ200 Series inverters have built-in RS-485 serial communications, featuring the Modbus RTU protocol. The inverters can connect directly to existing factory networks or work with new networked applications, without any extra interface equipment. The specifications are in the following table.
Item
Specifications
User-selectable
Transmission speed
2400 / 4800 / 9600 / 19.2k / 38.4k /
57.6k / 76.8k / 115.2k bps
Communication mode
Asynchronous
Character code
Binary
LSB placement
Transmits LSB first
Electrical interface
RS-485 differential transceiver
Data bits
8-bit (Modbus RTU mode)
Parity
None / even / odd
Stop bits
1 or 2 bits
Startup convention
One-way start from host device
Wait time for response
0 to 1000 msec.
Connections
Station address numbers from 1 to 32
Connector
Terminal connector
Error check
Overrun, Framing block check code, CRC-16, or horizontal parity
Cable length
500m maximum
Connecting the Inverter to Modbus
Modbus connector is in control terminal block as below. Note that RJ45 connector (RS-422) is used for external operator only.
Ii
Inverter Parameter Setup –
The inverter has several settings related to Modbus communications. The table below lists them together. The Required column indicates which parameters must be set properly to allow communications. You may need to refer to the host computer documentation in order to match some of its settings.
Func.
Code
Name
Required
Settings
A001
Frequency source
03
00…Keypad potentiometer 01…Control terminal 02…Function F001 setting 03…Modbus network input
10…Calculate function output
A002
Run command source
03
01…Control terminal
02…Run key on keypad, or digital
operator 03…Modbus network input
C071
Communication speed
05
03 2400 bps 04 4800 bps 05 9600 bps 06 19.2k bps 07 38.4k bps 08 57.6k bps 09 76.8k bps 10 115.2k bps
C072
Modbus Address
1
Network address, range is 1 to 247
C074
Communication parity
00
00…No parity
01…Even parity
02…Odd parity
C075
Communication stop bit
1
Range is 1 or 2
C076
Communication error
select
00
00…Trip (Error code E60) 01…Decelerate to a stop and trip
02…Disable
03…Free run stop (coasting)
04…Decelerate to a stop
C077
Communication error
time-out
1.00
Comm. Watchdog timer period, range is 0.00 to 99.99 sec.
C078
Communication wait
time
10
Time the inverter waits after receiving a message before it transmits. Range is 0. to 1000. ms
Ii
NOTE:
When you change any of the parameters above, the inverter power must be rebooted in order to activate new parameters. Instead of rebooting, turning ON/OFF of reset terminal works as same.
For Modbus data Listing, Please refer detail manual come with inverter
Common Fault and Remedies
Fault: During running pump Find E09.x – Under Voltage Alarm
Remedies: First to check x value, Suppose E09.2, E09.3 and E09.4 means during deceleration, Constant speed and acceleration condition Then Check following parameters F002 – 50second F003 – 10 second A017 – 02 MPPT enable D004 – DC voltage of PV input power
Fault: If find E07.x – Over Voltage Alarm
Remedies: First to check PV module Open circuit Voltage (Voc) value and no of PV connected in series connection. If Total Voc value is higher than 800VDC then Inverter will show over voltage alarm. then try to reduce PV qty in series. Now, Best selection as below for series and parallel connection Example: If, Pump motor voltage is 415VAC, Then try to make Total Vmp value of connected near to 585 to 600VDC. It should be 1.414 time of Pump motor voltage
Fault: If find E01, E02, E03, E04 and E05 during starting of pump
Remedies: Check following parameters F002 – 50 second (Up to 90kw inverter) B021 – 03 overload restriction enable A044 – 01 Pump control mode Try to change B049 – 01 VT mode, B022 – max value and B023 – 0.1sec
Fault: If find E14 – Ground fault
Remedies: Check motor wires and its earth cable. Inverter has two screw terminal One cable for incoming and other for motor earth cable If Earthing cable is properly connected then check inverter to pump motor distance, if it more than 100meter, please try to use output line reactor (output choke) with minimum 3% impedance. If there is no any motor cable and only DC power input, then asked to service person from company.
Application Notes
FOR Best Vmpp value to set in
A020 : D004 (VOC )/1.2 OR D004 (VOC )VOC/1.25
PV in Series PV in Parallel
Ii
Standard Specications
1-phase 200V class
Models WJ2 00- 00 1SF 002SF 004SF 007SF 0 15 S F 022SF
VT 0.2 0.4 0.55 1.1 2.2 3.0
kW
Applicable mot or size *
Rated capaci ty (kVA)
Input Rating
Output Rating
Minimum value of r esistor (Ω) 100 100 100 50 50 35
Weight
Rated input volt age (V ) 1-phase: 20 0V-15% to 240V +10%, 5 0/ 60Hz ±5%
Rated inpu t current (A)
Rated output voltage (V) *
Rated output current (A)
1
3-phase 200V class
Models WJ2 00- 001LF 002LF 004LF 007LF 015 LF 022LF 037LF 055LF 075LF 110 LF 150 LF
Applicable mot or size *
Rated capaci ty (kVA)
Input Rating
Output Rating
Minimum value of r esistor (Ω) 100 10 0 10 0 50 50 35 35 20 17 17 10
Weight
Rated input volt age (V ) 3-phase: 200V-15% to 240V +10%, 5 0/ 60Hz ±5%
Rated inpu t current (A)
Rated output voltage (V) *
Rated output current (A)
1
CT 0.1 0.2 0.4 0.75 1.5 2.2
VT 1/4 1/ 2 3/4 1. 5 3 4
HP
CT 1/8 1/4 1/2 1 2 3
VT 0.4 0.6 1.2 2.0 3.3 4.1
200V
CT 0.2 0.5 1.0 1.7 2.7 3.8
VT 0.4 0.7 1.4 2.4 3.9 4.9
240V
CT 0.3 0.6 1.2 2.0 3.3 4.5
VT 2.0 3.6 7.3 13.8 20.2 24.0
CT 1.3 3.0 6.3 11.5 16.8 22.0
2
VT 1. 2 1.9 3.5 6.0 9.6 12.0
CT 1.0 1.6 3.0 5.0 8.0 11.0
kg 1.0 1. 0 1.1 1.6 1.8 1.8
lb 2.2 2.2 2.4 3.5 4.0 4.0
VT 0.2 0.4 0.75 1.1 2.2 3.0 5.5 7. 5 11 15 18.5
kW
CT 0 .1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7. 5 11 15
VT 1/4 1/2 1 1.5 3 4 7.5 10 15 20 25
HP
CT 1/8 1/4 1/2 1 2 3 5 7.5 10 15 20
VT 0.4 0.6 1.2 2.0 3.3 4.1 6.7 10.3 13.8 19 .3 23.9
200V
CT 0.2 0.5 1.0 1.7 2.7 3.8 6.0 8.6 11. 4 16.2 20.7
VT 0.4 0.7 1. 4 2.4 3.9 4.9 8.1 12.4 16.6 23.2 28.6
240V
CT 0.3 0.6 1.2 2.0 3.3 4.5 7.2 10.3 13.7 19.5 24.9
VT 1.2 1.9 3.9 7. 2 10.8 13.9 23.0 3 7.0 48.0 68.0 72.0
CT 1.0 1.6 3.3 6.0 9.0 12.7 20.5 30.8 39.6 57.1 62.6
2
VT 1.2 1.9 3.5 6.0 9.6 12.0 19.6 30.0 40.0 56.0 69.0
CT 1.0 1.6 3.0 5.0 8.0 11.0 17.5 25.0 33.0 47.0 60.0
kg 1.0 1.0 1.1 1. 2 1. 6 1.8 2.0 3.3 3.4 5.1 7. 4
lb 2.2 2.2 2.4 2.6 3.5 4.0 4.4 7.3 7. 5 11. 2 16.3
3-phase: 200 to 240V (proportional to input voltage)
3-phase: 200 to 240V (proportional to input voltage)
Ii
3-phase 400V class
Models WJ2 00- 00 4HF 007HF 015HF 02 2HF 030HF 040HF 055HF 0 75HF 110HF 150HF
VT 0.75 1.5 2.2 3.0 4.0 5.5 7. 5 11 15 18.5
kW
Applicable mot or size *
Rated capaci ty (kVA)
Input Rating
Output Rating
Minimum value of r esistor (Ω) 180 18 0 180 100 100 100 70 70 70 35
Weight
Rated input volt age (V ) 3-phase: 380V-15% to 480 V +10%, 50 / 60Hz ±5%
Rated inpu t current (A)
Rated output voltage (V) *
Rated output current (A)
1
CT 0.4 0.75 1. 5 2.2 3.0 4.0 5.5 7.5 11 15
VT 1 2 3 4 5 7.5 10 15 20 25
HP
CT 1/2 1 2 3 4 5 7.5 10 15 20
VT 1. 3 2.6 3.5 4.5 5.7 7.3 11. 5 15 .1 20.4 25.0
200V
CT 1.1 2.2 3.1 3.6 4.7 6.0 9.7 11. 8 15.7 20.4
VT 1. 7 3.4 4.4 5.7 7. 3 9.2 14. 5 19 .1 25.7 31. 5
240V
CT 1.4 2.8 3.9 4.5 5.9 7.6 12. 3 14.9 19.9 25.7
VT 2.1 4.3 5.9 8.1 9.4 13. 3 20.0 24.0 38.0 4 4.0
CT 1. 8 3.6 5.2 6.5 7. 7 11.0 16.9 18. 8 29.4 35.9
2
VT 2.1 4.1 5.4 6.9 8.8 11.1 17.5 23.0 31.0 38.0
CT 1. 8 3.4 4.8 5.5 7. 2 9.2 14.8 18.0 24.0 31.0
kg 1. 5 1.6 1. 8 1.9 1. 9 2 .1 3.5 3.5 4.7 5.2
lb 3.3 3.5 4.0 4.2 4.2 4.6 7.7 7.7 10.4 11. 5
3-phase: 380 to 480 V (proportional to input voltage)
General Specications
Item General Specications
Protect ive housing *
3
Control method Sinusoidal Pulse Width Modulation (PW M) control Carrier frequency 2kHz to 15kHz (derating required depending on the model) Output f requency range *
4
Frequency accuracy
Frequency set ting resolut ion Digital: 0.01Hz; Analog: max . frequency / 1000
Volt ./ Freq. character istic
Overload capacity
Acceleration /deceleration time 0.01 to 3600 seconds, linear and S-curve accel /decel, second accel /decel setting available Start ing torque 200% @0.5Hz (sensorless vector control) DC braking Variable operating f requency, time, and braking force
Operator panel
Freq . setting
Ex ternal signal * Via network RS485 ModBus RTU, other net work option Operator panel Run /Stop (For ward /Rever se run change by command)
FW D/ REV run
Ex ternal signal * Via network RS485 ModBus RTU, other net work option Terminals 7 terminals, sink / source changeable by a short b ar
Intelligent input
Input signal
terminal
68 funct ions
Functions
assignable
Intelligent output terminal
Functions 48 f unctions assignable
Output signal
Moni tor output (analog) Output freq., output current, output torque, output voltage, input power, thermal load ratio, L AD freq., heat sink temperature, general ou tput (EzSQ)
Pulse train output (0 – 10VDC, 32 kHz max.)
Alar m output cont act ON for inverter alar m (1c contacts, both nor mally open or closed available.)
Other functions
Protect ive funct ion
Temperature Operating (ambient): -10 to 50
Operating environment
Humidity 20 to 90% humidity (non-condensing)
Vibration *
Location Altitude 1,000m or less, indoors (no corrosive gasses or dust)
Coat ing color Black Options Remote operator unit, cables for the units, braking unit, braking resistor, AC reactor, DC reactor, EMC lter
IP20
0.1 to 400Hz Digital command: ±0.01% of the maximum frequency
Analog command: ±0.2% of the maximum frequency (25
°
C ±10°C)
V/f control (constant torque, reduced torque, free-V /F): b ase freq. 3 0Hz – 400Hz adjustable, Sensorless vector control, Closed loop control with motor encoder feedback (only V/f control). Dual rating: CT (Heavy duty): 60 sec. @150%
VT (Normal duty): 60 sec. @120%
2
1
keys / Value set tings
6
0 to 10 VDC (input impedance 10kΩ), 4 to 20mA (input imp edance 100Ω), Potentiometer (1k to 2kΩ, 2W )
6
Forward r un /stop, Reverse run / stop
FW (forward run command), RV (reverse run command), CF1 – CF4 (multi-stage speed setting), JG (jog command), DB (external braking), SET (set second motor), 2CH (2-stage accel. /decel. command), FRS (free run stop command), E XT (exter nal trip), USP (st artup function), CS (commercial power switchover), SFT (soft lock), AT (analog input selection), RS (reset), PTC (thermistor thermal protection), STA (start), STP (stop), F/ R (forward /reverse), PID (PID disable), PIDC (PID reset), UP (remote control up function), DWN (remote control down function), UDC (remote control data clear), OPE (operator control), SF1– SF7 (multi-stage speed setting; bit operation), OLR (overload restriction), TL (torque limit enable), TRQ1 (torque limit changeover1), TRQ2 (torque limit changeover2), BOK (Braking conrmation), L AC (LAD cancellation), PCLR (position deviation clear), ADD (add frequency enable), F-TM (force terminal mode), ATR (permission of torque command input), KHC (Cumulative power clear), MI1– MI7 (general purpose inputs for EzSQ), AHD (analog command hold), CP1– CP3 (multistage-position switches), ORL (limit signal of zero-return), ORG (trigger signal of zero-return), SPD (speed/position changeover), GS1,GS2 (STO inputs, safety related signals), 485 (Starting communication signal), PRG (executing E zSQ program), HLD (retain output frequency), ROK (permission of run command), EB (rotation direction detection of B-phase), DISP (display limitation), NO (no function) RUN (run signal), FA1 –FA 5 (frequency arrival signal), OL,OL2 (overload advance notice signal), OD (PID deviation error signal), A L (alarm signal), OTQ (over / under torque thre shold), UV (under-voltage), TRQ (torque limit signal), RNT (run time expired), ONT (power ON time expired), THM (thermal warning), BRK (brake release), BER (brake error), ZS (0Hz detection), DSE (speed deviation excessive), POK (positioning completion), ODc (analog voltage input disconnection), OIDc (analog cur rent input disconnection), FB V (PID second stage output), NDc (network disconnec t detection), LOG1 – LOG3 (Logic output signals), WAC (capacitor life warning), WA F (cooling fan warning), FR (st arting contact), OHF (heat sink overheat warning), LOC (Low load), MO1 –MO3 (general outputs for EzSQ), IRDY (inver ter ready), FWR (forward operation), RVR (reverse operation), M JA (major failure), WCO (window comparator O), WCOI (window comparator OI), FREF (frequency command source), REF (run command sour ce), SETM (second motor in operation), EDM (STO (safe torque off ) per formance monitor), OP (option control signal), NO (no function)
[PW M output] Output fre q., output current, output torque, output voltage, input power, thermal load ratio, LAD freq., heat sink temperature, general output (EzSQ) [Pulse train output] Output frequency, output cur rent , pulse train input monitor
Free-V/f, manual / automatic torque boost, output voltage gain adjustment, AVR function, reduced voltage start, motor data selection, auto­tuning, motor stabilization control, reverse r unning protection, simple position control, simple torque control, torque limiting, automatic carrier frequency r educ tion, energy saving operation, PID function, non-stop operation at instantaneous power failure, brake control, DC inje ction braking, dynamic braking (BRD), f requency upper and lower limiters, jump frequencies, curve accel and decel (S, U, inversed U,EL-S), 16-stage speed prole, ne adjustment of st art frequency, accel and decel stop, process jogging, frequency calculation, frequency addition, 2-stage accel/decel, stop mode selection, start /end freq., analog input lter, window comparators, input terminal response time, output signal delay/ hold function, rotation direction restriction, stop key sele ction, sof tware lock, safe stop function, scaling function, display restriction, passwor d function, user p arameter, initialization, initial display selection, cooling fan control, warning, trip retry, frequency pull-in r estart, frequency matching, overload restriction, over current restriction, DC bus voltage AVR Over-current, over-voltage, under-voltage, overload, brake resistor overload, CPU error, memory error, external trip, USP error, ground fault detection at power on, temperature error, internal communication error, driver error, thermistor error, brake error, safe stop, overload at low speed, modbus communication error, option error, encoder disconnection, speed excessive, EzSQ command error, EzSQ nesting error, EzSQ execution error, EzSQ user trip
°
C / Stor age: -2 0 to 65°C *
8
5.9m/s2 (0.6G), 10 to 55 Hz
7
Ii
Loading...