Control mode (A044) PM motor control (06) is added to the selection in A044
PM motor control
parameters (H101~H134)
Automatic return
to the initial display (b164)
Data Read/Write selection
(b166)
Inverter mode monitor
(d060)
Phase loss output
protection (b141,b142)
Improvement
Additional function
Full compatibility with the copy unit WOP(5 line display)
Communication speed
is improved.
Modbus RTU
Initializing method Parameter setting (b180=01) triggers initializationInitialization method of SJ700-2 is also valid.
Selection of initial display is expanded
(all monitoring parameters, frequency command F001 (WOP monitor B)
At occurrence of warning, the inverter does not accept Run command.
Newly added parameter b049 to switch between
Constant torque mode and Variable torque mode.
Parameters related to PM motor control are newly added
(same as WJ200 series)
Without operating for 10 minutes,
the display returns to the initial display automatically.
Selection of enabling or disabling data Read / Write from the
copy unit WOP for parameter setting protection and security
Displays currently selected inverter mode, IM motor
(induction motor) or PM motor mode.(IM mode or PM mode.)
The inverter detects motor output phase loss
Parallel processing of 5 tasks
EzSQ starting trigger terminal: changed from FW terminal to
PRG terminal which can be assigned any of input terminals.
Always running mode is added to
selection of starting method for EzSQ.
Command to store changed data into EEPROM (eepwrt command)
Part of EzSQ program variables (P129 (U29) to P131 (U31))
are automatically stored at power down (only when A017 is
other than 00)
2400/4800/9600/19.2k/38.4k/57.6k/76.8k/115.2k bps
Maximum data length is expanded.
03h (Read holding register) 10h (Write in holding resisters)
Command to write into/read from multiple holding registers
is added (17h: Write/Read multiple holding registers)
In case of driving light load application, you can
choose one power size smaller inverter or one
frame size smaller inverter.
PM motor control is only available in Variable torque
mode.
(note) The model supporting PM motor control is
ordering production.
4 registers (8 byte) to 16 registers (32 byte)
Read and Write 16 registers (32 byte)
2
Series
Line up
S
J
700
S
J
700B
For More Precise ControlFor General Purpose Use
High starting torque,
Powerful drive and easy setting
High starting torque
Improved sensorless vector control and auto tuning
produce high starting torque of 200% or more at 0.3Hz.*
Easy setup of motor constants
Ideal for applications which need high torque, such as
cranes, extruders and lifts.
Motor Torque vs. Speed
200
0.3Hz
100
0
-100
Torque [%]
-200
*1Starting torque
SeriesApplicable motor
SJ700D(CT)
SJ700
SJ700B
30060090012001500 1800
Speed (min-1)
0.4 to 55kW
75 to 132kW
185 to 400kW
11 to 75kW
90 to 160kW
Starting torque
0.3Hz/200%
0.3Hz/180%
0.3Hz/150%
0.5Hz/150%
0.5Hz/120%
1
Trip avoidance function
Over current &
voltage suppress function
Higher internal calculation speed improves current control
performance.
Over-current suppress and Over-voltage suppress functions
avoid inverter trips during acceleration and deceleration.
Frequency
Over-current trip
Motor current
Over-current suppress OFF
Possible with SJ700 series
Hitachi exclusive
0Hz domain sensorless
)
vector control
Develops 150% (SJ700B:120%)
0Hz speed reference
Ideal for cranes and other applications
that require high torque upon starting.
*2 when inverter is one frame size larger than motor.
Position control function
The SJ700D/SJ700/SJ700B, with optional feedback board
installed, together with an encoder-equipped motor can
perform position control.
For many applications, suitable performance can be
achieved at a lower cost than servo systems.
Based on your four motion parameters (position command,
speed command, acceleration time and deceleration time),
the SJ700D/SJ700/SJ700B will move an object from original
position A to target position B.
After the movement,
the inverter keeps
hold motor position.
*
2
torque at
*
Target point B
Starting point A
)
*
Impact load
Suppresses over current and continues running
Over-current suppress ON
DC bus AVR function
during deceleration
The SJ700D/SJ700/SJ700B controls deceleration time so that
the DC bus voltage does not exceed the over-voltage trip
level, providing trip-less operation during deceleration.
Motor current
Voltage of the
main circuit DC
Output frequency
) Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use.
3
*
High performance, powerful functions,
yet user friendly.
Programming [EzSQ: easy sequence] function
Inverter control by built-in
programming functions
Custom operation is realized by downloading to an inverter a
user program created with ProDriveNext, Hitachi inverter
configuration software.
Tailor inverter operation to meet changing process
requirements, and replace separate PLCs in some cases.
By simplifying or eliminating external hardware, signficant cost
savings can be achieved.
Password function is incorporated to provide security for proprietary
program data against loss or unauthorized modification.
Typical example - Replacing external relay circuit
Standard InverterSJ700 Using EzSQ
PB2
PB1
RY1
PB2
RY2
Operation
circuit
RYA
RYB
CM1
RY1
T2
RYA
T1
PB1
RY2
T1
RYB
T2
EzSQ
Programming
Programming Window
Download
PB1
FW
8
1
PB2
2
CM1
ItemDescription
Language type BASIC Like
Supported Device
Memory area
Programming
environment
Language SpecI/O functionReserved word
Executable format
External input
External output
Command
Variable
Windows® is a registered trademark of Microsoft Corporation.U.S.A and other countries.
*
Windows (DOS/V)OS:WindowsVista, Windows7)
1,024 steps or 6k byte
(Smaller of these)Program is stored in internal of inverter.
I/O control (Bit input, Word input, Bit output, Word output)
Timer control <on delay, off delay>
Inverter parameter setting
UserU (00)-U (31)/32 point
TimerUL (00)-UL (07)/8 point
Set frequencySET-Freq
Acceleration time
Deceleration time
Monitor
General-purpose
input contact
General-purpose
output contact
Internal timer
contact
Inverter input
and output
Contact signal/Open collector signal input
(Internal DC24V power supply available)
Program RUN
command
General-purpose
input
XA (0) : 0-10V (O terminal)
XA (1) : 4-20mA (OI terminal)
XA (2) : 0-10V (O2 terminal)
Maximum of 6 point (Y (00)-Y (05))
YA (0) : Setup for FM terminal is possible.
YA (1) : Setup for AM terminal is possible.
YA (2) : Setup for AMI terminal is possible.
ACCEL
DECEL
Output frequency, Output current, Rotation direction,
PID feedback, Converted frequency, Output torque,
Output voltage, Power, Cumulative RUN time,
Cumulative power-on time, trip
X (00)-X (07)/8 point
Y (00)-Y (05)/6 point (1 point is relay output)
UB (00)-UB (07)/8 pointInternal user
TD (0)-TD (7)/8 point
In a remote operator display code.
SJ700D:PRG terminal
SJ700/SJ700B:FW terminal
Maximum of 8 point (X(00)-X (07))
EMC Filter & brake circuit integrated as standard
Built-in EMC filter up to 150kW
*
Cost and space reduction compared with external EMC filter.
Reduces electromagnetic noise.
SJ700: European Version and Japanese Version does not have 150 kW
*
SJ700B: All models(5.5kW is without EMC Filter)
Meets EN61800-3 2nd-Environment
Built-in brake resistor
circuit up to 22kW
Cost and space reduction compared with external braking controller.
SJ700B: Up to 30kW
*
*
Level [db]
Example (SJ700D-110HFEF3)
130
120
110
100
90
80
70
60
50
40
30
20
10
0
150k 200k 500k 1M 2M 5M 7M 10M 20M 30M
EN61800-3 2nd Environment
[C3]QP Limit Level
Frequency [Hz]
QP: Quasi Peak
4
Ease of maintenanceEasy operation
Easy-removable construction
for maintenance
Field replacement of cooling fan (s) and DC bus capacitors
can be accomplished in a fraction of the time.
Using Logic terminal move to SJ700D/SJ700 without wiring
change.
Read SJ300 Parameter by WOP remote operator and write
them in to SJ700D/SJ700
Easy-removable
Cooling Fan
SJ300seriesSJ700series
Easy-removable
DC bus Capacitors
(SJ700D/SJ700: above 15kW
SJ700B: above 18.5kW)
Parameter
read write
User selection of displayed
parameters
Data comparison display mode
Displays only parameters changed from factory default
User-define parameter display mode
Displays only user defined parameters
(up to 12 parameters, U001 to U012)
Basic parameter display mode
Displays only pre-defined basic parameters which are used
commonly
Basic
mode
Indication only
Chose Basic
Parameter
Other functions
Direct digit edit mode for quicker selection of parameter.
Returning to output frequency monitor display (d001) by
holding the FUNC key for 3 seconds regardless of the
current content.
Basic Parameter
Removable Control circuit terminals
(Move to SJ700D/SJ700 without rewiring)
*1 Control circuit terminals comparison table
SeriesInput terminals
SJ700D/SJ700
SJ700B
SJ300
L300P
9 terminals
(Intelligent 8terminals,FW)
6 terminals
(Intelligent 5terminals,FW)
Output terminals
5 terminals
(Open collector outputs)
2 terminals
(Relay outputs)
Long lifetime components &
Lifetime warning function
Long lifetime components
Design lifetime 10 Years or more for DC bus capacitors & Cooling
Fan.Cooling Fan ON/OFF control function for longer fan life.
*Condition for lifetime calculation -
Ambient temperature: 40 deg C (SJ700B: 30 deg C)
Ambient condition: No corrosive gas, oil mist nor dust
10 years is a design lifetime base on calculation, and not guaranteed
Lifetime warning function
Lifetime warning function helps to perform preventive
maintenance before a failure occurrence.
DC bus capacitor, cooling fan, heat sink temperature and
motor temperature can be monitored in order to replace
components prior to failure.
Network compatibility
The Modbus-RTU communication is embedded as standard
along with a dedicated terminal.
Other fieldbus communications such DeviceNet and
PROFIBUS-DP are supported with optional fieldbus modules.
-DeviceNet is a trade mark of Open DeviceNet Vender Association, Inc.
-PROFIBUS-DP is a registered trade mark of PROFIBUS Nutzer
Organization
Simple & Low cost wiring, ease of installation
and replacement using feildbus commuincation
Input voltage 240V for 200V class and 480V
for 400V class as standard.
Environmental friendliness
Micro surge voltage
suppress function
Hitachi original PWM control method limits motor terminal
voltage to less than two times of inverter DC bus voltage.
Lower than Hitachi motor Max. insulation voltage (1,250V)
(During regeneration, the motor terminal voltage may exceed the motor
maximum insulation voltage (1,250V))
Motor terminal voltage
Instantaneous power failure
disregard function
The SJ700D/SJ700/SJ700B overrides instantaneous power
failure when power fluctuation happens frequently, as long as
DC bus voltage remains higher than under-voltage trip level.
Emergency stop
Shuts down the inverter by hardware, bypassing
the CPU, to achieve a reliable, emergency stop function.
Intelligent input terminal and output
terminal ON/OFF delay function
Helps simplify external circuits.
Active frequency matching function
Motor frequency match restart function operates
effectively even without motor residual voltage.
Controlled deceleration and stop
on power loss
Analog input disconnection
detection function
The SJ700D/SJ700/SJ700B outputs a disconnection signal
when frequency command through analog input is lost.
Acceleration/Deceleration curve
functions
The curve shape (five types, such as S-curve, etc.) can be
chosen according to the application requirements.
Analog command holding
function (AHD)
Output frequency can be changed with UP/DOWN Function,
or with an analog signal as reference value. The set
frequency at power shutdown can be saved, too.
1,250V
E=650V, cable=100m
EU RoHS compliant
EU RoHS compliant (except solder in power module)
Improvement of environmental tolerance
Varnish coating of internal PC board & plating of main circuit
copper bus bar are standard.
Pulse train input function
Pulse train input for Frequency reference or PID
feed back signal, with SJ-FB (speed feed back card option).
Integrated input electric power monitor
Input electric power (kW) and Integrated input electric
power for monitoring energy saving.
Automatic carrier frequency
adjustment function
The SJ700D/SJ700/SJ700B detects motor current and
automatically reduces carrier frequency according to the current.
The resolution of analog outputs
(voltage, current) is improved to 10 bits.
*1: The protection method conforms to JIS C 0920 (IEC60529)
*2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole).To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3: The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4: Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5: Conforms to the test method specified in JIS C 60068-2-6:2010 (IEC 60068-2-6 :2007).
*6: To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*7: Storage temperature refers to the temperature in transportation.
*8: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC, or at 19.8mA for input current 4 to 20mA.
If this characteristic is not satisfactory for your application,contact your Hitachi representative.
Rated capacity
(kVA)
Rated output current (A)
Overload capacity (output current)
Rated output voltage (*3)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
0LQLPXPYDOXHRIUHVLVWRUї
US Version
200V
240V
Asia Version
US Version
400V
480V
185LFUF
150LFUF
110LFUF
18.5(25)
15(20)
11(15)
15.2
18.2
44
20.0
24.1
58
25.2
30.3
73
3-phase (3-wire) 200 to 240V (corresponding to input voltage)
*1 : The protection method conforms to JIS C 0920 (IEC60529)
*2 : The applicable motor refers to Hitachi standard 3-phase motor (4-pole). To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3 : The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4 : Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5 : Conforms to the test method specified in JIS C 60068-2-6:2010 (IEC 60068-2-6:2007).
*6 : To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*7 : Storage temperature refers to the temperature in transportation.
The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC,or at 19.8mA for input current 4 to 20mA.If this characteristic is not satisfactory for your application,contact your Hitachi representative.
*10 : Please be sure to connect DC reactor attached to 1850HF,2200HF,3150HF and 4000HF. (1850HF,2200HF and 3150HF of US/JP Version:The DC reactor is not attached.)
*11 : 1850HF,2200HF,3150HF and 4000HF:The function is not provided.
*12 : SJ700D-3 only.
*13 : The option cannot access new parameters in SJ700D-3.
Speed fluctuation
Acceleration/deceleration time
SLV
Starting
Torque
0Hz-SLV
PM-SLV[ordering production]
Carrier frequency range
DC braking
Frequency
setting
Forward /reverse
Start /stop
Intelligent
input terminals
Intelligent
output terminals
Ambient operating/storage
temperature (*7)/ humidity
LocationAltitude 1,000m or less, indoors (no corrosive gases or dust)
Digital input expansion card
Feedback expansion card
Network interface card
Others
Operator
External signal(*8)
External port
Operator
External signal
External port
Terminals
Functions
Terminals
Functions
Monitor output
terminals
Line to line sine wave pulse-width modulation (PWM) control
SJ700/SJ700D (CT) 200%/0.3Hz, (VT) 150%/0.5Hz, 75kW to 150kW (CT) 180%/0.3Hz, (VT) 120%/0.5Hz, 185kW and over 150% /0.3Hz.
SJ700B : 150%/0.5Hz, 90kW and over : 120%/0.5Hz,
SJ700/SJ700D (CT) (0Hz domain with motor one frame size down) 150% at around 0Hz, 75kW and over: 130% at around 0Hz.
SJ700B : 120% at around 0Hz,SJ700D (VT):Disable.
SJ700D (0.4 to 132kW) : 50% (at 10% of motor constant speed) [ordering production] (only SJ700D (VT))
SJ700/SJ700D (CT) 0.5 to 15kHz, (VT) 0.5 to 12 kHz, 75kW to 150kW (CT) 0.5 to 10kHz, (VT) 0.5 to 8 kHz,185kW and over : 0.5 to 3.0kHz
SJ700B : 0.5 to 12.0kHz (90kW and over : 0.5 to 8.0kHz)
Performs at start: under set frequency at deceleration, via an external input (braking force, time, and operating frequency).
Start/stop commands (forward/reverse switching by parameter setting)
Forward-operation start/stop commands (reverse-operation start/stop possible when relevant commands are assigned to intelligent input terminals)3-wire
input possible (when relevant commands are assigned to control circuit terminals)
Setting via RS485 communication
8 terminals, NO/NC switchable, sink logic/source logic switchable
Reverse operation (RV), Multi-speed 1 setting (CF1), Multi-speed 2 setting (CF2), Multi-speed 3 setting (CF3), Multi-speed 4 setting (CF4), Jogging (JG),
external DC braking (DB), 2nd motor control (SET), 2-stage acceleration/deceleration (2CH), free-run stop (FRS), external trip (EXT), unattended start
protection (USP), commercial power supply switching (CS), software lock (SFT), analog input switching (AT), 3rd motor control (SET3), reset (RS), starting by
3-wire input (STA), stopping by 3-wire input (STP), forward/reverse switching by 3-wire input (F/R), PID disable (PID), PID integration reset (PIDC), control
gain switching (CAS), acceleration by remote control (UP), deceleration by remote control (DWN), data clearance by remote control (UDC), forcible operation
(OPE), Multi-speed bit 1 (SF1), Multi-speed bit 2 (SF2), Multi-speed bit 3 (SF3), Multi-speed bit 4 (SF4), Multi-speed bit 5 (SF5), Multi-speed bit 6 (SF6),
Multi-speed bit 7 (SF7), overload restriction selection (OLR), torque limit selection (enabling/disabling) (TL), torque limit 1 (TRQ1), torque limit 2 (TRQ2), P/PI
Running (RUN), constant-speed reached (FA1), set frequency overreached (FA2), overload notice advance signal (1) (OL), output deviation for PID control
(OD), alarm signal (AL), set frequency reached (FA3), over-torque (OTQ), instantaneous power failure (IP), undervoltage (UV), torque limited (TRQ),
operation time over (RNT), plug-in time over (ONT), thermal alarm signal (THM), brake release (BRK), braking error (BER), 0Hz detection signal (ZS),
speed deviation maximum (DSE), positioning completed (POK), set frequency overreached 2 (FA4), set frequency reached 2 (FA5), overload notice
advance signal (2) (OL2), PID feedback comparison (FBV), communication line disconnection (NDc), logical operation result 1 (LOG1), logical operation
result 2 (LOG2), logical operation result 3 (LOG3), logical operation result 4 (LOG4), logical operation result 5 (LOG5), logical operation result 6 (LOG6),
capacitor life warning (WAC)(*11), cooling-fan speed drop (WAF), starting contact signal (FR), heat sink overheat warning (OHF), low-current indication
signal (LOC), general-purpose output 1 (M01), general-purpose output 2 (M02), general-purpose output 3 (M03), general-purpose output 4 (M04),
general-purpose output 5 (M05), general-purpose output 6 (M06), inverter ready (IRDY), forward rotation (FWR), reverse rotation (RVR), major failure
(MJA), window comparator O (WCO), window comparator OI (WCOI), window comparator O2 (WCO2), alarm code 0 to 3 (AC0 to AC3)
Analog voltage output, analog current output, pulse-string output (e.g., A-F, D-F [n-fold, pulse output only], A, T, V, P)
Output frequency, output current, output torque, frequency conversion data, trip history, input/output terminal status, electric power, and others
Free V/f setting (7 breakpoints), frequency upper/lower limit, jump (center) frequency, acceleration/deceleration according to characteristic curve, manual
torque boost level/breakpoint, energy-saving operation, analog meter adjustment, start frequency setting, carrier frequency adjustment, electronic thermal
function (available also for free setting), external start/end frequency/frequency rate, analog input selection, retry after trip, restart after instantaneous power
failure, output of various signals, starting with reduced voltage, overload restriction, initial-value setting, automatic deceleration at power failure, AVR function,
fuzzy acceleration/deceleration, online/offline auto-tuning, high-torque multi-motor operation (*11) (sensorless vector control of two motors by one inverter)
Overcurrent protection, overvoltage protection, undervoltage protection, electronic thermal protection, temperature error protection, instantaneous power
failure protection, phase loss input protection, braking-resistor overload protection, ground-fault current detection at power-on, USP error, external trip,
emergency stop trip, CT error, communication error, option board error, and others
Attachment DC reactor (DCL-H-185-H-R),(DCL-H-220-H-R)
305W
150
X
H200
230
DCL-H-185-H-R
DCL-H-220-H-R
11x18
245
φ18
HModelWX
350
395
25
50
Downward details drawing
305
31556
Attachment DC reactor (DCL-H-315-H-R)
325365
150
5
460285
285
15x25
335
2-φ14
50
100
Downward details drawing
50
(1.96)
15(0.59)
290(11.41)
680(26.77)
15
(0.59)
50(1.96)290(11.41)
4-M12 Screw Holes For Eyebolts
*1 Vent-Holes A are formed on both right and left side portions.Vent-Holes B are just on right side.
Air Intake
450(17.71)
・SJ700-4000HFE2,HFU2,HF2Attachment DC reactor (DCL-H-400-H-R)
2-M16 Screw Holes
15(0.59)
1670(65.74)
1700 (66.92)
15
(0.59)
75 (2.95)
Exhaust
Air Intake
450(17.71)
4-M16 Screw Holes For Eyebolts
Wall
365365
180
460285
285
15x25
335
2-φ14
50
100
Downward details drawing
Digital Oprator
75 (2.95)
4-
φ15(0.59)
15(0.59)
300 (11.81) 300 (11.81) 300 (11.81)
2-M16 Eyebolts
1050 (41.33)
25
5
25
[Unit : mm (inch)]
Inches for reference only.
2
1850H,2200H and 3150H of US/JP Version:The DC resctor is not attached.
*
12
OPERATION and PROGRAMMING
SJ700/SJ700D and SJ700B Series can be easily operated with the digital operator provided as standard. The digital operator can
also be detached and can be used for remote mounted control. Operator with copy function (WOP) and digital operator with
potentiometer are also available as options.
Parameter DisplayPower LED
Displays frequency, motor current,
rotational speed of the motor, and
an alarm code.
Lights when the power input
to the drive is ON.
Monitor LEDs
Shows drive status.
RUN key enable LED
Lights up when the inverter
is ready to respond to the
RUN key.
RUN Key
Press to run the motor.
STOP/RESET Key
Press to stop the drive or
reset an alarm.
Function Key
Press to set or monitor a
parameter value.
Setting the output frequency
Power on
(1) or the value previously monitored is displayed.
POWER
ALARM
FUNCFUNC
Hz
V
kW
A
%
記憶
STR
RUN
PRG
機能
FUNC
Press key.
(2)Function code appears.
POWER
ALARM
RUN
PRG
機能
FUNC
Hz
V
kW
A
%
記憶
STR
Press
until appears.
(3)appears.
POWER
ALARM
FUNC
Hz
V
kW
A
%
記憶
STR
RUN
PRG
機能
FUNC
Press key.
13
(4)Preset value is displayed.
POWER
ALARM
RUN
PRG
機能
FUNC
Hz
V
kW
A
%
記憶
STR
Press
to set desired value.
(5)Newly set value is displayed.
POWER
ALARM
STR
Hz
V
kW
A
%
記憶
STR
RUN
PRG
機能
FUNC
Press key
to store the value.
(6)Returns to and the setting is complete.
POWER
ALARM
RUN
PRG
機能
FUNC
Hz
V
kW
A
%
記憶
STR
*To run the motor, go back to
monitor mode or basic setting mode.
ALARM LED
Lights to indicate that the
inverter has tripped.
Display Unit LEDs
Indicates the unit associated
with the parameter display.
Store Key
Press to write the new value
to the EEPROM.
Up/Down Keys
Press up or down to sequence
through parameters and functions
shown on the display, and
increment/decrement values.
The contents of a basic mode display.
If a desired parameter is not displayed,
check the setting of function "b037"
(function code display restriction).
To display all parameters, specify "00" for "b037".
No.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
1
2
3
4
5
6
7
8
9
Display code
d001 to d104
F001
F002
F003
F004
A001
A002
A003
A004
A005
A020
A021
A022
A023
A044
A045
A085
b001
b002
b008
b011
b037
b083
b084
b130
b131
C021
C022
C036
Item
Monitor display
Output frequency setting
Acceleration (1) time setting
Deceleration (1) time setting
Operation direction setting
Frequency source setting
Run command source setting
Base frequency setting
Maximum frequency setting
[AT] selection
Multi-speed frequency setting
Multi-speed 1 setting
Multi-speed 2 setting
Multi-speed 3 setting
1st control method
V/f gain setting
Operation mode selection
Selection of restart mode
Allowable under-voltage power failure time
Retry-after-trip selection
Retry wait time after trip
Function code display restriction
Carrier frequency setting
Initialization mode selection
Selection of overvoltage suppression function
Setting of overvoltage suppression level
Setting of intelligent output terminal 11
Setting of intelligent output terminal 12
Alarm relay active state
FUNCTION LIST
MONITORING FUNCTIONS and MAIN PROFILE PARAMETERS
●
CodeFunction NameMonitored data or setting
Output frequency monitor
d001
Output current monitor
d002
Rotation direction minitoring
d003
Process variable (PV), PID feedback monitor
d004
Intelligent input terminal status
d005
Intelligent output terminal status
d006
Scaled output frequency monitoring
d007
Actual-frequency monitoring
d008
Torque command monitoring
d009
Torque bias monitoring
d010
Torque monitoring
d012
Output voltage monitoring
d013
Power monitoring
d014
Cumulative power monitoring
d015
Cumulative operation RUN time monitoring
d016
Cumulative power-on time monitoring
d017
Heat sink temperature monitoring
d018
Motor temperature monitoring
d019
(*3)-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
(*3)-200. to +200. (%)
(*3)-200. to +200. (%)
Monitor Mode
Life-check monitoring
d022
Program counter
d023
Program number monitoring
d024
User monitor 0
d025
User monitor 1
d026
User monitor 2
d027
Pulse counter
d028
Position setting monitor
d029
Position feedback monitor
d030
Clock monitor
d031
Inverter mode monitor
d060
Trip Counter
d080
d081
-
Trip monitoring 1-6
d086
Programming error monitoring
d090
DC voltage monitoring
d102
BRD load factor monitoring
d103
Electronic thermal overload monitoring
d104
Output frequency setting
F001
Acceleration (1) time setting
F002
Acceleration (1) time setting, 2nd motor
F202
Acceleration (1) time setting, 3rd motor
F302
Deceleration (1) time setting
F003
Setting Mode
Deceleration time setting, 2nd motor
F203
Deceleration time setting, 3rd motor
F303
Keypad Run key routing
F004
A Group: Standard functions
A---
b Group: Fine tuning functions
b---
C Group: Intelligent terminal functions
C---
H Group: Motor constants functions
H---
P Group: Expansion card functions
P---
Expanded Function
U Group: User-selectable menu functions
U---
(*3)-1073741823 to 1073741823 (upper 4 digits including “-“)
(*3)-1073741823 to 1073741823 (upper 4 digits including “-“)
(SJ700D only)* In case you use WOP (option), this monitor is activated.
(SJ700D only)I-C (CT) / I-v (VT)
(*1) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*2) 4000HF: -120. to -100., -99.9 to 0.00 to 99.99,100.0 to 120.0 (Hz)
(*3) SJ700D (VT): Not available (no display)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 999.9, 1000 to 9999 (A)
F (forward rotation), o (stopped), r (reverse rotation)
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999. 1000 to 9999 (10000 to 99990),
100 to 「999 (10000 to 999000)
「
FW
54872361
AL
12131115 14
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
-200. to +200. (%)
0.0 to 600.0 (V)
0.0 to 999.9 (kW)
0.0 to 999.9, 1000. to 9999.,1000 to 9999 (10000 to 99990), 「100 to 「999 (100000 to 999000)
0. to 9999., 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000) (hr)
0. to 9999., 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000) (hr)
-020. to 200.0 (℃)
-020. to 200.0 (℃)
21
0 to 1024
0000 to 9999
-2147483647 to 2147483647 (upper 4 digits including “-“)
-2147483647 to 2147483647 (upper 4 digits including “-“)
-2147483647 to 2147483647 (upper 4 digits including “-“)
0 to 2147483647 (upper 4 digits)
0. to 9999., 1000 to 6553 (10000 to 65530) (times)
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
Warning code
0.0 to 999.9 (V)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
0.0, "start frequency" to "maximum frequency" (or maximum frequency,
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1), 03
(switching between OI terminal and keypad potentiometer) (*1), 04 (switching
between O2 and keypad potentiometer) (*1)
00 (single), 01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible), 03 (disabling
O2 terminal)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms fi lter ±0.1 Hz with hysteresis)
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable with 7 terminals)
0.00 or “start frequency” to “maximum frequency” (Hz)
0.00 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00 or “start frequency” to “n-th maximum frequency” (Hz)
"Start frequency" to 9.99 (Hz)
00 (free-running after jogging stops [disabled during operation]), 01 (deceleration
and stop after jogging stops [disabled during operation]), 02 (DC braking after
jogging stops [disabled during operation]), 03 (free-running after jogging stops
[enabled during operation]), 04 (deceleration and stop after jogging stops [enabled
during operation]), 05 (DC braking after jogging stops [enabled during operation])
00 (disabling), 01 (enabling), 02 (set frequency only)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.0 to 5.0 (s)
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0.0 to 60.0 (s)
00 (edge operation), 01 (level operation)
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0.0 to 60.0 (s)
SJ700/SJ700D (CT): 0.5 to 15.0(kHz) <75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0>
SJ700D (VT): 0.5 to
SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0>
12.0 (kHz)
<75 to 132kW:0.5 to 8.0>
SJ700/SJ700D(CTmode)
-FE-FU-F-F-FU
0101020102
0101020102
50.60.60.50.60.
50.60.60.50.60.
50.60.60.50.60.
50.60.60.50.60.
50.60.60.50.60.
50.60.60.50.60.
0000000000
0303030303
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.0.0.0.0.
100. 100. 100. 100. 100.
0101010101
31.31.31.31.31.
0000000000
0000000000
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1.00 1.00 1.00 1.00 1.00
0000000000
0000000000
0000000000
1.01.01.01.01.0
1.01.01.01.01.0
1.01.01.01.01.0
5.05.05.05.05.0
5.05.05.05.05.0
5.05.05.05.05.0
0000000000
0000000000
0000000000
100. 100. 100. 100. 100.
100. 100. 100. 100. 100.
100. 100. 100. 100. 100.
100. 100. 100. 100. 100.
100. 100. 100. 100. 100.
0000000000
0.50 0.50 0.50 0.50 0.50
0.00.00.00.00.0
000020.0
0.00.00.00.00.5
0101010101
0.0.0.0.0.
0.00.00.00.00.0
5.0
<75 to 132kW:3.0>
(*1) This setting is valid only when the OPE-SR is connected. (*2) 4000HF:30. to 120. (Hz)
(*3) Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use. (*4) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz)
(*5) SJ700D (VTmode):00 (VC), 01 (VP), 02 (free V/F), 03 (sensorless vector control)
15
= Allowed
[◯
SJ700B
3.03.0
= Not permitted
×
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
××
××
××
××
××
××
××
××
××
××
×○
×○
×○
×○
×○
×○
××
××
○○
○○
○○
○○
○○
×○
××
××
○○
○○
○○
○○
○○
○○
××
××
××
○○
○○
○○
○○
○○
×○
×○
×○
×○
×○
×○
×○
×○
××
]
CodeFunction NameMonitored data or setting
Frequency upper limit setting
A061
Frequency upper limit setting, 2nd motor
A261
Frequency lower limit setting
A062
Frequency lower limit setting, 2nd motor
A262
Jump (center) frequency setting 1
A063
Jump (hysteresis) frequency width setting 1
A064
Jump (center) frequency setting 2
A065
Jump (hysteresis) frequency width setting 2
A066
Jump (center) frequency setting 3
A067
Jump (hysteresis) frequency width setting 3
A068
Acceleration stop time frequency setting
A069
Acceleration stop time frequency setting
A070
Frequency Upper/Lower Limit and Jump Frequency
PID function enable
A071
PID proportional gain
A072
PID integral time constant
A073
PID derivative gain
A074
PV scale conversion
A075
PV source setting
A076
PID Control
Output of inverted PID deviation
A077
PID variation range
A078
PID feed forward selection
A079
AVR function select
A081
AVR
AVR voltage select
A082
Operation mode selection
A085
Energy saving mode tuning
A086
Acceleration (2) time setting
A092
Acceleration (2) time setting, 2nd motor
A292
Acceleration (2) time setting, 3rd motor
A392
Deceleration (2) time setting
A093
deceleration function
Deceleration (2) time setting, 2nd motor
A293
Deceleration (2) time setting, 3rd motor
A393
Operation Mode and acceleration/
Select method to switch to Acc2/Dec2 profi le
A094
Select method to switch to Acc2/Dec2,
A294
2nd motor
Acc1 to Acc2 frequency transition point
A095
Acc1 to Acc2 frequency transition point,
A295
2nd motor
Dec1 to Dec2 frequency transition point
A096
Dec1 to Dec2 frequency transition point,
A296
2nd motor
Acceleration curve selection
A097
Deceleration curve selection
A098
OI-L input active range start frequency
A101
OI-L input active range end frequency
A102
OI-L input active range start current
A103
External frequency adjustment
OI-L input active range end current
A104
OI-L input start frequency enable
A105
O2-L input active range start frequency
A111
O2-L input active range end frequency
A112
O2-L input active range start voltage
A113
O2-L input active range end voltage
A114
Acceleration curve constants setting
A131
and
Deceleration curve constants setting
A132
deceleration
Acceleration
Operation-target frequency selection 1
A141
Operation-target frequency selection 2
A142
Operator selection
A143
Frequency to be added
A145
Sign of the frequency to be added
A146
Operation-target frequency
EL-S-curve acceleration ratio 1
A150
EL-S-curve acceleration ratio 2
A151
EL-S-curve deceleration ratio 1
A152
Acceleration
EL-S-curve deceleration ratio 2
A153
and deceleration
(*1) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*2) -120. to -100., -99.9 to 0.00 to 99.99 ,100.0 to 120.0 (Hz)
(*3) SJ700D (VT mode):00 (Normal operation), 01 (Energy saving operation)
0.00 or "1st minimum frequency limit" to "maximum frequency" (Hz)
0.00 or "2nd minimum frequency limit" to "maximum frequency, 2nd motor" (Hz)
0.00 or "start frequency" to "maximum frequency limit" (Hz)
0.00 or "start frequency" to "maximum frequency, 2nd motor limit" (Hz)
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
Selection of restart mode
b001
Allowable under-voltage power failure time
b002
Retry wait time before motor restart
b003
Instantaneous power failure/under-voltage
b004
trip alarm enable
Number of restarts on power
b005
failure/under-voltage trip events
(Input) Phase loss detection enable
b006
Restart frequency threshold
b007
Selection of retry after tripping
b008
Selection of retry after undervoltage
b009
Selection of retry count after overvoltage
b010
or overcurrent
Restart after instantaneous power failure or tripping
Retry wait time after tripping
b011
Electronic thermal setting (calculated within
b012
the inverter from current output)
Electronic thermal setting (calculated within
b212
the inverter from current output), 2nd motor
Electronic thermal setting (calculated within
b312
the inverter from current output), 3rd motor
Electronic thermal characteristic
b013
Electronic thermal characteristic, 2nd motor
b213
Electronic thermal characteristic, 3rd motor
b313
Free-setting electronic thermal frequency (1)
b015
Free-setting electronic thermal current (1)
b016
Free-setting electronic thermal frequency (2)
Electronic thermal function
b017
Free-setting electronic thermal current (2)
b018
Free-setting electronic thermal frequency (3)
b019
Free-setting electronic thermal current (3)
b020
Overload restriction operation mode
b021
Overload restriction setting
b022
Deceleration rate at overload restriction
b023
Overload restriction operation mode (2)
b024
Overload restriction setting (2)
b025
Deceleration rate at overload restriction (2)
b026
Overcurrent suppression enable
b027
Active frequency matching,
b028
scan start frequency
Active frequency matching, scan-time constant
b029
Overload restriction and overcurrent restraint
Active frequency matching,
b030
restart frequency select
Software lock mode selection
b031
lock
software
RUN/ power-on warning time
b034
Rotational direction restriction
b035
Reduced voltage start selection
b036
Function code display restriction
b037
Others
Initial-screen selection
b038
Automatic user-parameter setting function enable
b039
(tripping after deceleration and stopping with matching frequency), 04 (restarting
with active matching frequency)
0.3 to 25.0 (s)
0.3 to 100.0 (s)
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating to
stop)
00 (16 times), 01 (unlimited)
00 (disabling), 01 (enabling)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04 (restarting
with active matching frequency)
00 (16 times), 01 (unlimited)
1 to 3 (times)
0.3 to 100.0 (s)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling
during constant speed), 03 (enabling during acceleration and deceleration
(increasing the speed during regeneration))
SJ700/SJ700D (CT): 0.20 x "rated current" to 2.00 x "rated current" (A)
< 75kW and over:0.20 x 1.80 >
SJ700D (VT)/SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling
during constant speed), 03 (enabling during acceleration and deceleration
(increasing the speed during regeneration))
SJ700/SJ700D (CT): 0.20 x "rated current" to 2.00 x "rated current" (A)
< 75kW and over:0.20 x 1.80 >
SJ700D (VT)/SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling)
SJ700/SJ700D (CT): 0.20 x "rated current" to 2.00 x "rated current" (A)
< 75kW and over:0.20 x 1.80 >
SJ700D (VT)/SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (frequency at the last shutoff ), 01 (maximum frequency), 02 (set frequency)
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling
change of data other than "b031" and frequency settings when SFT is on),
02 (disabling change of data other than "b031"), 03 (disabling change of data
other than "b031" and frequency settings), 10 (enabling data changes during
operation)
0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr)
00 (enabling both forward and reverse rotations), 01 (enabling only forward
rotation), 02 (enabling only reverse rotation)
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start
time)
SJ700D: 000 (Func code that STR key pressed last displayed), 001 to 060 (d001
to d060), 201 (F001)
SJ700/SJ700B: 00 (screen displayed when the STR key was pressed last), 01
(d001), 02 (d002), 03 (d003), 04 (d007), 05 (F001)
00 (disabling), 01 (enabling)
(*3)
SJ700/SJ700D(CTmode)
-FE-FU-F-F-FU
0000000000
1.01.01.01.01.0
1.0 (*1) 1.0 (*1) 1.0 (*1)
0000000000
0000000000
0000000000
0.00 0.00 0.00 0.00 0.00
0000000000
0000000000
33333
1.0 (*1) 1.0 (*1) 1.0 (*1)
Rated current of
inverter x 1.00
0101000101
0101000101
0101000101
0.0.0.0.0.
0.00.00.00.00.0
0.0.0.0.0.
0.00.00.00.00.0
0.0.0.0.0.
0.00.00.00.00.0
0101010101
Rated current x 1.50
1.00 1.00 1.00 1.00 1.00
0101010101
Rated current x 1.50
1.00 1.00 1.00 1.00 1.00
0101010101
Rated current of inverter x 1.00
0.50 0.50 0.50 0.50 0.50
0000000000
0101010101
0.0.0.0.0.
0000000000
0606060606
00
(*4)00(*4)00(*4)
001
001
(*5)
001
(*5)
(*5)
0000000000
(*1) 4000HF:5.0 (*2) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*3) 4000HF:0. to 120. (Hz) (*4) SJ700-2:04. (basic display) (*5) SJ700-2:01
= Allowed
[◯
SJ700B
1.01.0
1.01.0
Rated current
x 1.20
Rated current
x 1.20
0404
0101
= Not permitted
×
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
××
×○
×○
×○
×○
]
17
= Allowed
[◯
Default Setting
CodeFunction NameMonitored data or setting
Torque limit selection
b040
Torque limit (1)
b041
(Forward-driving in 4-quadrant mode)
Torque limit (2)
b042
(Reverse-regenerating in 4-quadrant mode)
Torque limit (3)
b043
(Reverse-driving in 4-quadrant mode)
Torque limitation
Torque limit (4)
b044
(Forward-regenerating in 4-quadrant mode)
Torque limit LADSTOP enable
b045
Reverse RUN protection enable
b046
CT/VT selection (SJ700D only)
b049
Controlled deceleration and stop on power loss
b050
DC bus voltage trigger level during power loss
b051
Over-voltage threshold during power loss
b052
Deceleration time setting during power loss
b053
Initial output frequency decrease during power loss
b054
Non-stop operation at
momentary power failure
Proportional gain setting for nonstop operation at power loss
b055
Integral time setting for nonstop operation at power loss
b056
Maximum-limit level of window comparators O
b060
Minimum-limit level of window comparators O
b061
Hysteresis width of window comparators O
b062
Maximum-limit level of window comparators OI
b063
Minimum-limit level of window comparators OI
b064
Hysteresis width of window comparators OI
b065
Maximum-limit level of window comparators OI
b066
Minimum-limit level of window comparators O/OI/O2
b067
Hysteresis width of window comparators O/OI/O2
b068
Window comparator
Operation level at O disconnection
b070
Operation level at OI disconnection
b071
Operation level at O2 disconnection
b072
Cumulative input power data clearance
b078
Cumulative input power display gain setting
b079
Start frequency adjustment
b082
Carrier frequency setting
b083
Initialization mode (parameters or trip history)
b084
Country code for initialization
b085
Frequency scaling conversion factor
b086
STOP key enable
b087
Restart mode after FRS
b088
Others
Automatic carrier frequency reduction
b089
Dynamic braking usage ratio
b090
Stop mode selection
b091
Cooling fan control
b092
Dynamic braking control
b095
Dynamic braking activation level
b096
Thermistor for thermal protection control
b098
Thermal protection level setting
b099
Free-setting V/f frequency (1)
b100
Free-setting V/f voltage (1)
b101
Free-setting V/f frequency (2)
b102
Free-setting V/f voltage (2)
b103
Free-setting V/f frequency (3)
b104
Free-setting V/f voltage (3)
characteristic
b105
Free setting of V/f
(
*1) “Over current protection” , ” Overload restriction” , “Over current limiting” and “Electronic thermal protection” might operate from the set value when “Carrier frequency
Free-setting V/f frequency (4)
b106
Free-setting V/f voltage (4)
b107
00 (quadrant-specifi c setting), 01 (switching by terminal), 02 (analog input),
03 (option 1),04 (option 2)
SJ700/SJ700D (CT): 0. to 200. (%), no (disabling torque limitation)
< 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%), no (disabling torque limitation)
SJ700/SJ700D (CT): 0. to 200. (%), no (disabling torque limitation)
< 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%), no (disabling torque limitation)
SJ700/SJ700D (CT): 0. to 200. (%), no (disabling torque limitation)
< 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%), no (disabling torque limitation)
SJ700/SJ700D (CT): 0. to 200. (%), no (disabling torque limitation)
< 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%), no (disabling torque limitation)
00 (disabling), 01 (enabling)
00 (disabling), 01 (enabling)
00 (CT : Constant torque), 01 (VT : Variable torque)
00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage constant
control, with resume), 03 (DC voltage constant control, without resure)
0.0 to 999.9, 1000. (V)
0.0 to 999.9, 1000. (V)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.00 to 10.00 (Hz)
0.00 to 2.55
0.0 to 9.999 /10.00 to 65.55
0. to 100. (lower limit : b061 + b062*2) (%)
0. to 100. (lower limit : b060 - b062*2) (%)
0. to 10. (lower limit : b061 - b062 / 2) (%)
0. to 100. (lower limit : b064 + b066*2) (%)
0. to 100. (lower limit : b063 - b066*2) (%)
0. to 10. (lower limit : b063 - b064 / 2) (%)
-100. to 100. (lower limit : b067 + b068*2) (%)
-100. to 100. (lower limit : b066 - b068*2) (%)
0. to 10. (lower limit : b066 - b067 / 2) (%)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
Clearance by setting "01" and pressing the STR key
1. to 1000.
0.10 to 9.99 (Hz)
SJ700/SJ700D (CT): 0.5 to 15.0 (kHz)
<75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0>
SJ700D (VT): 0.5 to 12.0 (kHz) <75 to 132kW:0.5 to 8.0.>
SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0>
SJ700D: 00 (disabling), 01 (cleaning the trip history), 02 (initializing the data), 03
(cleaning the trip history and initializing the data), 04 (cleaning the trip history
and initializing the data and EzSQ program)
SJ700/SJ700B: 00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)
00 (Japan), 01 (EU), 02 (U.S.A.)
0.1 to 99.9
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (starting with active matching frequency)
00: invalid, 01: valid
0.0 to 100.0 (%)
00 (deceleration until stop), 01 (free-run stop)
00 (always operating the fan), 01 (operating the fan only during inverter operation
[including 5 minutes after power-on and power-off ])
00 (disabling), 01 (enabling [disabling while the motor is topped]),
02 (enabling [enabling also while the motor is topped])
330 to 380, 660 to 760 (V)
00 (disabling the thermistor), 01 (enabling the thermistor with PTC),
02 (enabling the thermistor with NTC)
setting” is used with less than 2kHz by a low value. Please set to 2kHz or more and use the setting of “Carrier frequency setting” for such a situation.
(*2) 750HF to 1320HF: 3.0 1850HF, 2200HF and 3150HF:2.1, 4000HF:1.9 (*3) 4000HF: 0.0 to 120.0 (Hz
)
]
18
CodeFunction NameMonitored data or setting
Free-setting V/f frequency (5)
b108
Free-setting V/f voltage (5)
b109
Free-setting V/f frequency (6)
b110
Free-setting V/f voltage (6)
b111
Free-setting V/f frequency (7)
characteristic
b11
2
Free setting of V/f
Free-setting V/f voltage (7)
b11
3
Brake control enable (*3)
b120
Brake wait time for release (*3)
b121
Brake wait time for acceleration (*3)
b122
Brake wait time for stopping (*3)
b123
Brake wait time for confi rmation (*3)
b124
Brake release frequency setting (*3)
b125
Brake release current setting (*3)
b126
Braking frequency (*3)
b127
Overvoltage suppression enable
b130
Others
Overvoltage suppression level
b131
Acceleration and deceleration rate
b132
at overvoltage suppression
Overvoltage suppression propotional gain
b133
Overvoltage suppression Integral time
b134
Output loss detection enable (SJ700D only)
b141
Output loss detection sensibility (SJ700D only)
b142
Automatic return to initial display (SJ700D only)
b164
Data Read/Write select (SJ700D only)
b166
Initialization trigger (SJ700D only)
b180
0. to "free-setting V/f frequency (6)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (7)" (Hz)
0.0 to 800.0 (V)
0.0 to 400.0 (Hz) (*4)
0.0 to 800.0 (V)
00 (disabling), 01 (enabling)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
SJ700/SJ700D: 0.0 to 2.00 x "rated current" (A)
< 75kW and over:0.0 to 1.80 x "rated current" (A)>
SJ700B: 0.0 to 1.50 x "rated current" (A)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
00 (disabling the restraint), 01 (decelerating and stagnating),
02 (enabling acceleration with deceleration),
03 (enabling acceleration) (SJ700D only)
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
setting), 04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG:
Jogging), 07 (DB: external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH:
2-stage acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external
trip), 13 (USP: unattended start protection), 14: (CS: commercial power source
enable), 15 (SFT: software lock), 16 (AT: analog input voltage/current select), 17
(SET3: 3rd motor control), 18 (RS: reset), 20 (STA: starting by 3-wire input), 21
(STP: stopping by 3-wire input), 22 (F/R: forward/reverse switching by 3-wire
input), 23 (PID: PID disable), 24 (PIDC: PID reset), 26 (CAS: control gain setting),
27 (UP: remote control UP function), 28 (DWN: remote control DOWN function),
29 (DWN: remote control data clearing), 31 (OPE: forcible operation), 32 (SF1:
multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3: multispeed bit 3), 35 (SF4:
multispeed bit 4), 36 (SF5: multispeed bit 5), 37 (SF6: multispeed bit 6), 38 (SF7:
multispeed bit 7), 39 (OLR: overload restriction selection), 40 (TL: torque limit
enable), 41 (TRQ1: torque limit selection bit 1), 42 (TRQ2: torque limit selection
bit 2), 43 (PPI: P/PI mode selection), 44 (BOK: braking confi rmation), 45 (ORT:
orientation), 46 (LAC: LAD cancellation), 47 (PCLR: clearance of position
deviation), 48 (STAT: pulse train position command input enable), 50 (ADD:
trigger for frequency addition [A145]), 51 (F-TM: forcible-terminal operation),
52 (ATR: permission of torque command input), 53 (KHC: cumulative power
clearance), 54 (SON: servo-on), 55 (FOC: pre-excitation), 56 (MI1: generalpurpose input 1), 57 (MI2: general-purpose input 2), 58 (MI3: general-purpose
input 3), 59 (MI4: general-purpose input 4), 60 (MI5: general-purpose input 5),
61 (MI6: general-purpose input 6), 62 (MI7: general-purpose input 7), 63 (MI8:
general-purpose input 8), 64 (EMR: Emergency stop) (*1), 65 (AHD: analog
command holding), 66 (CP1: multistage position settings selection 1 ), 67 (CP2:
multistage position settings selection 2), 68 (CP3: multistage position settings
selection 3), 69 (ORL: Zero-return limit function), 70 (ORG: Zero-return trigger
function), 71 (FOT: forward drive stop), 72 (ROT: reverse drive stop), 73 (SPD:
speed / position switching), 74 (PCNT: pulse counter), 75 (PCC: pulse counter
clear), 82 (PRG: EzSQ program) (SJ700D only), no (NO: no assignment)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
= Allowed
[◯
Default Setting
SJ700/SJ700D(CTmode)
-FE-FU-F-F-FU
18
(RS)18(RS)18(RS)18(RS)18(RS)
16
(AT)16(AT)16(AT)16(AT)16(AT)
06
(JG)06(JG)06(JG)06(JG)03(CF2)
11
(FRS)11(FRS)11(FRS)11(FRS)02(CF1)
09
(2CH)09(2CH)09(2CH)09(2CH)01(RV)
03
(CF2)13(USP)03(CF2)03(CF2)06(JG)
02
(CF1)02(CF1)02(CF1)02(CF1)11(FRS)
01
(RV)01(RV)01(RV)01(RV)13(USP)
0000000000
0000000000
0000000000
0000000000
0000000000
0001000000
0000000000
0000000000
0000000000
SJ700B
= Not permitted
×
Setting
during
operation
(allowed or not)
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
×○
(*1) When the emergency stop function is enabled (SW1 = ON), "18" (RS) and "64" (EMR) are forcibly written to parameters "C001" and "C003",
respectively. (You cannot arbitrarily write "64" to "C001".) If the SW1 signal is turned off and then turned on, "no" (no assignment) is set in parameter "C003".
(*2) 1850HF,2200HF,3150HF and 4000HF:The function is not provided.
]
Change
during
operation
(allowed or not)
19
CodeFunction NameMonitored data or setting
00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set frequency
Terminal (11) function
C021
Terminal (12) function
C022
Terminal (13) function
C023
Terminal (14) function
C024
Intelligent output terminals
Terminal (15) function
C025
Alarm relay terminal function
C026
FM signal selection
C027
AM signal selection
C028
AMI signal selection
C029
Analog monitoring
Digital current monitor reference value
C030
Terminal (11) active state
C031
Terminal (12) active state
C032
Terminal (13) active state
C033
Terminal (14) active state
C034
Intelligent
Terminal (15) active state
C035
output terminals
Alarm relay terminal active state
C036
Low-current indication signal output mode
C038
selection
Low-current indication signal detection level
C039
Overload signal output mode
C040
Overload level setting
C041
Frequency arrival setting for accel.
C042
Frequency arrival setting for decel.
C043
PID deviation level setting
C044
Frequency arrival setting for acceleration (2)
C045
Frequency arrival setting for deceleration (2)
C046
Maximum PID feedback data
C052
Minimum PID feedback data
C053
Over-torque (Forward-driving) level setting
C055
Over-torque (Reverse-regenerating)
C056
level setting
Levels and output terminal status
Over-torque (Reverse-driving) level setting
C057
Over-torque (Forward-regenerating)
C058
level setting
Electronic thermal warning level setting
C061
Alarm code input
C062
Zero speed detection level
C063
Heat sink overheat warning level
C064
Communication speed selection (*2)
C071
Node allocation
C072
Communication data length selection
C073
Communication parity selection
C074
Communication function
Communication stop bit selection
C075
(*1) 4000HF:0.00 to 99.99, 100.0 to 120.0 (Hz)
overreached), 03 (OL: overload notice advance signal (1)), 04 (OD: output
deviation for PID control), 05 (AL: alarm signal), 06 (FA3: set frequency
reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power failure), 09 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT: operation time over), 12 (ONT:
plug-in time over), 13 (THM: thermal alarm signal), 19 (BRK: brake release), 20
(BER: braking error), 21 (ZS: 0 Hz detection signal), 22 (DSE: speed deviation
maximum), 23 (POK: positioning completed),24 (FA4: set frequency overreached
2), 25 (FA5: set frequency reached 2), 26 (OL2: overload notice advance
signal (2)), 27 (Odc: Analog O disconnection detection), 28 (OIDc: Analog OI
disconnection detection), 29 (O2Dc: Analog O2 disconnection detection), 31
(FBV: PID feedback comparison), 32 (NDc: communication line disconnection),
33 (LOG1: logical operation result 1), 34 (LOG2: logical operation result 2),
35 (LOG3: logical operation result 3), 36 (LOG4: logical operation result 4), 37
(LOG5: logical operation result 5), 38 (LOG6: logical operation result 6), 39 (WAC:
capacitor life warning) (*2), 40 (WAF: cooling-fan speed drop), 41 (FR: starting
contact signal), 42 (OHF: heat sink overheat warning), 43 (LOC: low-current
indication signal), 44 (M01: general-purpose output 1), 45 (M02: general-purpose
output 2), 46 (M03: general-purpose output 3), 47 (M04: general-purpose output
4), 48 (M05: general-purpose output 5), 49 (M06: general-purpose output 6),
50 (IRDY: inverter ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation),
53 (MJA: major failure), 54 (WCO: window comparator O), 55 (WCOI: window
comparator OI), 56 (WCO2: window comparator O2) (When alarm code output
is selected for "C062", functions "AC0" to "AC2" or "AC0" to "AC3" [ACn: alarm
code output] are forcibly assigned to intelligent output terminals 11 to 13 or 11
to 14, respectively.)
SJ700/SJ700D:0.20 x "rated current" to 2.00 x "rated current" (A) / SJ700B:0.20
x "rated current" to 1.50 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
< 75kW and over:0.0 to 1.80 x "rated current" (A)>
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
< 75kW and over:0.0 to 1.80 x "rated current" (A)>
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 100.0 (%)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring
errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping
the motor)
0.00 to 99.99 (s)
0. to 1000. (ms)
00 (ASCII), 01 (Modbus-RTU)
0. to 9999., 1000 to 6553 (10000 to 65530)
0. to 9999., 1000 to 6553 (10000〜65530)
0. to 9999., 1000 to 6553 (10000〜65530)
0.0 to 999.9, 1000.
(Do not change this parameter, which is intended for factory adjustment.)
00 (not storing the frequency data), 01 (storing the frequency data)
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off ),
02 (enabling resetting only upon tripping [resetting when RS is on]),
03 (resetting only trip)
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
50. to 200. (%)
50. to 200. (%)
50. to 200. (%)
0. to 100. (%)
0. to 100. (%)
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
<75kW and over:0.0 to 1.80 x "rated current">
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
0. to 9999., 1000 to 6553 (10000 to 65530)
0. to 9999., 1000 to 6553 (10000 to 65530)
0. to 9999., 1000 to 6553 (10000 to 65530)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Zero LV starting boozst current for 2nd motor (*4)
H261
Control constants
Terminal selection PI proportional gain setting
H070
Terminal selection PI integral gain setting
H071
Terminal selection P proportional gain setting
H072
Gain switching time
H073
(*1) 1850HF,2200HF,3150HF and 4000HF:0.1 to 999.9,1000. to 6553. (mΩ).
(*2) 1850HF,2200HF,3150HF and 4000HF:0.001 to 9.999,10.00. to 65.53 (mH).
(*3) 1850HF,2200HF,3150HF and 4000HF:0.01 to 0.35 “ rated current ” (A).
(*4) SJ700D (VT): Not available (no display)
00 (disabling auto-tuning), 01 (auto-tuning without rotation),
02 (auto-tuning with rotation)
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
SJ700/SJ700D:0.20 to 160 (kW), 185kW and over :11.0 to 400 (kW)
SJ700B:0.20 to 160(kW)
SJ700/SJ700D:0.20 to 160 (kW), 185kW and over :11.0 to 400 (kW)
SJ700B:0.20 to 160 (kW)
2, 4, 6, 8, 10 (poles)
2, 4, 6, 8, 10 (poles)
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
0. to 255.
0. to 255.
0. to 255.
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
SJ700/SJ700D: 0. to 200. (%) < 75kW and over:0. to 180. (%) >
SJ700B: 0. to 180. (%)
00 (as indicated by the sign), 01 (depending on the operation direction)
00 (disabling the mode), 01 (digital operator), 02 (input via O2 terminal)
SJ700/SJ700D: -200. to +200. (%) < 75kW and over:-180. to +180. (%) >
SJ700B: -180. to +180. (%)
00 (as indicated by the sign), 01 (depending on the operation direction)
0.00 to "maximum frequency" (Hz)
0.00 to "maximum frequency" (Hz)
0.00 to 99.99 (s)
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors),
03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
20, 21, 100
70, 71, 101
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors),
03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
The inverter output was short-circuited, or the motor shaft is locked or has a
heavy load. These conditions cause excessive current for the inverter, so the
inverter output is turned off.
When a motor overload is detected by the electronic thermal function, the inverter trips and turns off its output.
When the regenerative braking resistor exceeds the usage time allowance or an over-voltage caused by the
stop of the BRD function is detected, the inverter trips and turns off its output.
When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor, the inverter trips
and turns off its output.
When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips
and turns off its output.
A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can
also generate excessive motor heat or cause low torque. The inverter trips and turns off its output.
If a strong source of electrical interference is close to the inverter or abnormal operations occur in the
built-in CT, the inverter trips and turns off its output.
When a malfunction in the built-in CPU has occurred, the inverter trips and turns off its output.
When a signal to an intelligent input terminal configured as EXT has occurred, the inverter trips and turns off its output.
An error occurs when power is cycled while the inverter is in RUN mode if the Unattended Start Protection
(USP) is enabled. The inverter trips and does not go into RUN mode until the error is cleared.
The inverter is protected by the detection of ground faults between the inverter output and the motor during
power-up tests. This feature protects the inverter only.
When the input voltage is higher than the specified value, it is detected 60 seconds after power-up and the
inverter trips and turns of its output.
When power is cut for more than 15ms, the inverter trips and turns off its output. If power failure continues,
the error will be cleared. The inverter restarts if it is in RUN mode when power is cycled.
The inverter will display the error code shown on the right if the lowering of cooling-fan speed is detected at
the occurrence of the temperature error described below.
When the inverter internal temperature is higher than the specified value, the thermal sensor in the inverter
module detects the higher temperature of the power devices and trips, turning off the inverter output.
Communication error has occurred between CPU and gate array.
One of three lines of 3-phase power supply is missing.
The inverter will trip if the gate array cannot confirm the on/off state of IGBT because of a malfunction due
to noise or damage to the main circuit element.
If the rotation speed of the internal cooling fan decreases so that the cooling effect decreases,inverter
output turns OFF for protection. (available only for SJ700 1850-4000)
When an instantaneous over-current has occurred, the inverter trips and turns off its output to protect main
circuit element.
When the phase loss output protection has been enabled (b141=01), the inverter will trip to avoid damage if
a phase loss output is detected.
When the thermistor inside the motor detects temperature higher than the specified value, the inverter trips
and turns off its output.
The inverter turns off its output when it can not detect whether the braking is ON or OFF within waiting time
set at b024 after it has released the brake. (When braking is enabled at b120)
If the EMR signal (on three terminals) is turned on when the slide switch (SW1) on the logic board is set to
ON, the inverter hardware will shut off the inverter output and display the error code shown on the right.
If overload occurs during the motor operation at a very low speed at 0.2 Hz or less, the electronic thermal protection
circuit in the inverter will detect the overload and shut off the inverter output. (2nd electronic thermal control)
(Note that a high frequency may be recorded as the error history data.)
If timeout occurs because of line disconnection during the communication in Modbus-RTU mode, the inverter
will display the error code shown on the right. (The inverter will trip according to the setting of "C076".)
Due to insufficient voltage, the inverter has turned off its output and been trying to
restart. If it fails to restart, it goes into the under-voltage error.
While at constant speed
During deceleration
During acceleration
Others
Display
on digital
operator
Display on remote
operator/copy unit
ERR1****
OC.Drive
OC.Decel
OC.Accel
Over.C
Over.L
OL.BRD
Over.V
EEPROM
Under.V
CT
CPU
EXTERNAL
USP
GND.Flt.
OV.SRC
Inst.P-F
OH.stFAN
OH FIN
GA.COM
PH.Fail
Main.Cir
Fan. Slow
IGBT
O.PH.Fail
TH
BRAKE
EMR
OL-LowSP
NET.ERR
UV.WAIT
PRG.CMD
Easy sequence function Error
Error indications by protective functions with the easy sequence function used.
PRG.NST
PRG.ERR1
Expansion card 1 connection error
Expansion card 2 connection error
(*1): Reset operation is acceptable 10 seconds after the trip. (185kW and over :90 seconds)(*2): Check the parameters when EEPROM error occurs. (*3): The inverter will not accept reset commands input via the RS terminal
or entered by the STOP/RESET key. Therefore, turn off the inverter power. (*4): The inverter will not accept the reset command entered from the digital operator. Therefore, reset the inverter by turning on the RS terminal.
An error has been detected in an expansion card or at its connecting terminals.
Common Terminal for
Intelligent Input Terminals,
Common Terminal for
External Power Supply for
PLCs, etc.
Intelligent Output Terminals
Common Terminal for
Intelligent Output Terminals
Thermistor Input Terminals
Alarm Output Terminals
Common terminal for H, O, O2, OI, AM, and AMI. Do not ground.
Power supply for frequency command input
Maximum frequency is attained at DC 10V in DC 0-10V range. Set the voltage at
A014 to command maximum frequency below DC 10V.
O2 signal is added to the frequency command of O or OI in DC 0-±10V range. By
changing configuration, frequency command can be input also at O2 terminal.
Maximum frequency is attained at DC 20mA in DC 4-20mA range.
When the intelligent terminal configured as AT is on, OI signal is enabled.
Selection of one function from:
Output frequency, output current, torque, output voltage, input power, electronic
thermal load ratio, and LAD frequency.
[DC0-10V output (PWM output)]
Selection of one function from: Output frequency, output current, torque, output
voltage, input power, electronic thermal load ratio, and LAD frequency.
[Digital pulse output (Pulse voltage DC 0/10V)]
Outputs the value of output frequency as digital pulse (duty 50%)
Internal power supply for input terminals. In the case of source type logic,
common terminal for contact input terminals.
Common terminal for P24, TH, and FM. In the case of sink type logic, common
terminal for contact input terminals. Do not ground.
The motor runs forward when FW terminal is ON,
and stops when FW is OFF.
Assign 8 functions to terminals.
(Refer to the standard specifications for the functions.)
Select sink or source logic with the short-circuit bar on the control terminals.
Sink logic: Short P24 to PLC / Source logic: Short CM1 to PLC.
When applying external power source, remove the short-circuit bar and connect
PLC terminal to the external device.
Assign 5 functions to open collector outputs.
When the alarm code is selected at C062, terminal 11-13 or 11-14 are reserved
for error codes of inverter trip.
(Refer to the standard specifications for the functions.)
Both sink and source logic are always applicable between each terminal and CM1.
Common terminal for intelligent output terminal 11-15.
The inverter trips when the external thermistor detects abnormal temperature.
Common terminal is CM1.
[Recommended thermistor characteristics]
Allowable rated power: 100mW or over.
The alarm relay contacts ALO and AL2
when it is in Trip Mode or when input
Power is OFF,by factory default setting.
RS-485
Serial communication port
AL1
RB
AL2
P
RB
AL1
P
AL2
SJ700: For up to 22kW (30HP)
SJ700B: For up to 30kW (40HP)
P
P
RB
RB
(Inverter)
N
Braking resistor (RB
Option
Customer wiring
(Outside the inverter)
AL
AL2
)
(To operating circuit)
28
CONNECTING TO PLC
Connection with Input Terminals
1.Using Internal Power Supply of The Inverter
(1)
Sink type logic
S
P24
PLC
FW
(2)
Source type logic
+
-DC24V
COM
FW
P24
PLC
+
DC24V
Hitachi EH-150 series PLC
Output Module
EH-YT16
2.Using External Power Supply
(1)
Sink type logic
COMCM1
DC24V
S
FW
8
1
SCM1
Inverter
+
-
P24
PLC
+
-
DC24V
8
1
(2)
Source type logic
Hitachi EH-150 series PLC
Output Module
EH-YTP16
8
1
(Note: Place short-circuit bar
between PLC and CM1 instead
of P24 and PLC)
COM
DC24V
+
-
FW
P24
PLC
8
1
Inverter
+
DC24V
Hitachi EH-150 series PLC
Output Module
EH-YT16
(Note: Be sure to turn on the inverter after turning on the PLC and its external power source to prevent the parameters in the inverter from being modified.)
Connection with Output Terminals
(1)
Sink type logic
Inverter
29
COMCM1
11
12
CM2
Inverter
(Note: Remove short-circuit bar
between P24 and PLC)
COM
DC24V
Hitachi EH-150 series PLC
Input Module
EH-XD16
(2)
Source type logic
SCM1
Hitachi EH-150 series PLC
Output Module
EH-YTP16
CM2
DC24V
11
12
Inverter
Inverter
(Note: Remove short-circuit
bar between P24 and PLC)
COM
Hitachi EH-150 series PLC
Input Module
EH-XD16
WIRING and ACCESSORIES
Power Supply
Fuse
R
(L1)(L2)(L3)
PD
ST
(+1)
Inverter
R0
T0
(T1)(T2)(T3)
(
RB
-
UVW
Motor
IM
Input
Voltage
Motor Output
(kW (HP))
Model
AWG
SJ700/SJ700DSJ700/SJ700D
0.4 (1/2)
0.75 (1)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
200V
400V
Note 1:
Connector must be fixed using the crimping tool specified by the connector manufacture.
Note 2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft).
This is useful in suppressing harmonics induced on the power supply
)
N
Input side AC reactor
EMI filter
Radio noise filter
Radio noise filter
(Capacitor filter)
DC link choke
Braking resistor
Braking unit
Output side noise filter
Radio noise filter
AC reactor
LCR filter
lines, or when the main power voltage imbalance exceeds 3% (and power
source capacity is more than 500kVA), or to smooth out line fluctuations. It
also improves the power factor.
Reduces the conducted noise on the power supply wiring generated by
the inverter. Connect to the inverter input side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise (can
also be used on output).
This capacitor filter reduces radiated noise from the main power wires in
the inverter input side.
Suppresses harmonics generated by the inverter.
This is useful for increasing the inverter's control torque for high duty-cycle
(on-off) applications, and improving the decelerating capability.
Reduces radiated noise from wiring in the inverter output side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise (can
also be used on input).
This reactor reduces the vibration in the motor caused by the inver-ter's
switching waveforms, by smoothing the waveforms to approxi-mate
commercial power quality. It is also useful when wiring from the inverter to
the motor is more than 10m in length, to reduce harmonics.
Sine wave shaping filter for the output side.
Note: An EMI filter is required for European EMC directive and C-Tick, but the others are not for this purpose.
30
OPERATOR
■Operator, Cable
●
Operator
Model
OPE-SR mini
Potentiometer
○
OPE-SBK
OPE-SR
WOP
SRW-0EX
○
*1
*1) Production has been stopped.
●
Cable
Cable <ICS-1,3>
L
■Operator
Remote Control
○
○
○
○
○
Model
ICS-1
ICS-3
Copy function
○
○
Cable Length
1m (3.3ft)
3m (9.8ft)
<OPE-SBK (SR)><OPE-SR mini>
Applied Cable
・ICS-1 (1m)
・ICS-3 (3m)
Applied Model for Built-in
SJ200
Standard for SJ700/SJ700D,SJ700B
SJ700/SJ700D,SJ700B
SJ700/SJ700D,SJ700B,SJ300,L300P
SJ300,L300P
<SRW-0J, SRW-0EX>
4X-KITmini (For installation with OPE-SR mini)
Screw
External
Gasket
Front
Cover
Internal
Gasket 1
Seal
Internal
Gasket 2
Rear Cover
<WOP>
You can mount the keypad
with the potentiometer for a
NEMA1 rated installation.
Panel
The kit also provides for
removing the potentiometer
knob to meet NEMA 4X
requirements,as shown
(part no.4X-KITmini).
Additional operation using optional operator WOP
Main Features for WOP (SJ700D only)
-Large 5-line LCD screen
-Real time clock
-Copy function: Storing 4 sets of parameter settings
-Selectable display mode
●
Dimentions (Unit:mm (inch) Inches for reference only)
Output frequency, acceleration time, deceleration time, torque limit, and orientation position*1 can be set by a digital output device
such as PLC, etc. (Binary or BCD)
●
Standard Specifications
Input
Output
Sequence error signal (Data input error signal)
Power supply
Item
Data setting signal
Strobe signal
Power supply for interface
●
Connecting Diagram
Commonterminal
Specification
Input
Output
Power supply
*1 Orientation position setting is enabled when the feedback PCB (SJ-FB) is used together.
NO contact input
(sink/ source compatible)
Open collector output
(sink/ source compatible)
DC+24V 90mA max., between P24B and CM1
D0,D1, … between D15 and PLCB
Between STRB and PLCB
DC+27V 50mA max.,
between SEQ and CMB
Datainputterminals
Commonterminal
Feedback Expansion Card SJ-FB
Detects motor speed with an encoder and receives the
feedback speed fluctuation to realize high-precision
operation. Positioning control and orientation with
pulse-train input are also possible.
●
Application Examples
High-precision operation for the main motor of coil winding machine,
wire drawing machine, truck, extruder, etc.
●
General Specifications
Speed control
Position control
Orientation
Item
Encoder feedback
Speed control method
Positioning command
Electronic gear
Stop position
Protective functions
A-, B-phase, 90-degree phase difference input (By A-, B-, and Z-phase encoder), Maximum input pulse: 100k-pulse/s
Pulse ratio A/B (A, B: Setting range of 1-9999) 1/50≦A/B≦20
4096 splitting per motor's single revolution (When using standard encoder)
*Data input mode is selected by the dip switch on the expansion card.
Mode1Mode2
Data classification code
Data can be set by
either 16-bit binary
or 4-digit BCD.
Input data is divided
Setting
into upper 8-bit
data
and lower 8-bit.
EP5
EG5
EAP
EAN
EBP
EBN
EZP
EZN
SAP
SAN
SBP
SBN
AP
AN
BP
BN
90-degree phase
difference pulse
train input
Encoder signal output
Setting data
Data can be
set by either
16-bit binary
or 4-digit BCD.
M
EC
Motor
with encoder
DeviceNet™ EXPANSION CARD SJ-DN2
With fieldbus option module SJ-DN2, the inverter provides network compatibility with DeviceNet communication as a slave, allowing
inverter operation and monitoring from a master device via fieldbus. Expensive hard-wiring can be eliminated for space saving and
cost reduction, and installation/replacement within the system can be easily done.
DeviceNet is a trademark of Open DeviceNet Vendor Association.
●
Cable connection
NoSignalCable color
1
2
3
4
5
V-
CAN_L
Drain
CAN_H
V+
Black
Blue
White
Red
Note: Communication power
ー
Nameplate
RedWhiteBlueBlack
5.08
20.32
25.4
supply (24VDC)is required
in system configuration.
32
TORQUE CHARACTORISTIC
SJ700D (CT) Series / Maximum Torque with Short - Time Rating
Sensorless vector controlV/f control (maximum torque boosting)
200
180
150
130
Output torque (%)
60
55
45
0.4〜55kW
75〜132kW
30〜45kW
55〜132kW
(65Hz max.)
0.4〜3.7kW
5.5〜22kW
150
130
100
Output torque (%)
55〜132kW
30〜45kW
60
55
45
0.4〜3.7kW
5.5〜22kW
Base frequency = 60Hz
Output frequency (Hz)
1001206560460.3
Sensorless vector control
200
180
150
109
Output torque (%)
60
45
35
Base frequency = 50Hz
0.4〜55kW
75〜132kW
55〜132kW
30〜45kW
Output frequency (Hz)
0.4〜3.7kW
5.5〜22kW
1001205065380.3
SJ700B Series / Maximum Torque with Short - Time Rating
Sensorless vector control
150
120
110
100
Output torque (%)
50
45
40
11〜75kW
90〜160kW
30〜45kW
55〜160kW
(65Hz max.)
11〜22kW
6
200.3
Output frequency (Hz)
6560
V/f control (maximum torque boosting)
150
130
109
100
60
Output torque (%)
45
35
5
55〜132kW
30〜45kW
Output frequency (Hz)
V/f control (maximum torque boosting)
130
110
85
50
Output torque (%)
45
40
55〜160kW
30〜45kW
100120
0.4〜3.7kW
5.5〜22kW
100120506516.70.3
11〜22kW
Base frequency = 60HzBase frequency = 50Hz
150
120
109
Output torque (%)
33
Output frequency (Hz)
Sensorless vector control
11〜75kW
90〜160kW
50
45
40
Output frequency (Hz)
55〜132kW
30〜45kW
1001206560460.5
1001205065380.5
11〜22kW
200.5
6
Output frequency (Hz)
6560
V/f control (maximum torque boosting)
130
110
92
85
50
Output torque (%)
40
30
5
55〜132kW
30〜45kW
Output frequency (Hz)
100120
11〜22kW
100120506516.70.5
TORQUE CHARACTORISTIC
SJ700D (CT)/SJ700B Series / Torque Under Continous Operation
Sensorless vector control
0.4〜3.7kW
100
95
92
80
70
55
45
Output torque (%)
35
30
0.4〜11kW
15〜22kW
30〜55kW
55〜132kW
V/f control
100
30〜45kW
0.4〜3.7kW
5.5〜22kW
Output torque (%)
95
90
85
75
70
65
55
45
36
30
0.4〜3.7kW
30〜55kW
5.5〜22kW
0.4〜3.7kW
55〜132kW
Sensorless vector control
V/f control
30〜45kW
0.4〜3.7kW
5.5〜22kW
Base frequency = 60Hz
6
Output frequency (Hz)
1001206560200.3
DERATING DATA
SJ700D (CT)
100
95
90
85
80
75
70
65
60
Output current (Ratio to the rating:%)
55
0.5 2 4 6 8 10 12 14 15
200V class
45,55kW
Carrierfrequency(kHz)
15kW
18.5kW
30kW
37kW
22kW
Base frequency = 50Hz
5
SJ700D (CT)
100
95
90
85
80
75
70
65
60
Output current (Ratio to the rating:%)
55
75kW
0.5 2 4 6 8 10 12 14 15
Output frequency (Hz)
400V class
90kW11kW0.4〜7.5kW0.75〜11kW
110kW
132kW
Carrierfrequency(kHz)
100 120655016.70.3
30kW45kW37kW
15kW
18.5kW
22kW
55kW
SJ700B
100
95
90
85
80
75
70
65
60
Output current (Ratio to the rating:%)
55
200V class
30kW
0.5 2 4 6 8 10 12
22kW15kW
75kW
Carrierfrequency(kHz)
18.5kW 55kW
11kW
37kW
45kW
SJ700B
400V class
90kW30kW
100
95
90
85
80
75
70
65
60
Output current (Ratio to the rating:%)
55
0.5 2 4 6 8 10 12
132kW
110kW
Carrierfrequency(kHz)
55kW
160kW
45kW
5.5〜18.5kW
22kW
37kW
75kW
34
DIFFERENCE and COMPATIBILITY
of SJ300 series and SJ700/SJ700D series
Items
You can copy the parameter settings from the SJ300 series into the SJ700 series.
Copying the parameter settings
Parameter display mode.
Retry or trip parameter
d001:
Output frequency monitoring
d007:
Scaled output frequency monitoring
Change function
Control
Circuit
Terminal
Main
Circuit
Easy-removable Dc bus Capacitor
Dynamic Brake circuit
Minimum value of
UHVLVWRU
Dimensions
Digital operator position
Option boards
Note1: As analog response follows the V/F curve, selection of SLV may require this setting to be reduced.
Note2: 370, 450L/H and 550H:Metal fittings differ.
A016:External frequency filter
time const.
A038:Jog frequency setting
A105:[OI]-[L] input start
frequency enable
b012, b212, b312:
Electronic thermal function
C025:Terminal [15] function
Removable
Position
110L/H
Screw diameter
Position
Arrangement
Others
055L
075L
110L
055H
075H
Installation
External radiating fin
SJ-DG
SJ-FB
SJ-DN / SJ-DN2
SJ-PB/PBT, SJ-PB2/PBT2
SJ-LW
Option position
300L
450L
370H
(You cannot copy the parameter settings from the SJ700 series to the SJ300 series because the SJ700
series has many new functions and additional parameters.)
No display mode selection.
(full display)
Instantaneous power failure/under-voltage/
overvoltage/overcurrent:It sets up by b001.
You can not change the output frequency
setting by using the △ and/or ▽ key.
Default:08 (instantaneous power failure)Default:40 (cooling-fan speed drop)
Removable
Other model:same position. 055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
M6 (Ground Screw)M5 (Ground Screw)
M8 (Ground Screw)
M10M8
M6M8
055 to 110L/H:10mm upper part from SJ300. 300L:77mm upper part from SJ300.
300H:72mm upper part from SJ300. 150 to 185L /220H:29mm upper part from SJ300.
220L:18mm upper part from SJ300. 550L:25mm upper part from SJ300.
Other model:same position.
055 to 110L/H:Two steps, 150 to 550L/H:One step
150 to 220L/H:RB there is not a terminal.
All the models are possible.
up to 11kW
055L/H: SJ700/SJ700D is in next larger enclosure vs. SJ300. All other models are the same enclosure size.
055L/H:Those with no compatibility.075 to 550L/H:Those with compatibility. Note 2
055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
Other model:same position.
Those with compatibility.
Those with compatibility.
Note:Since the SJ700 series has many new functions and additional parameters,
some functions of the SJ-DN, SJ-LW, and SJ-PB/PBT (option boards conforming to the open network
specifications) cannot be implemented on the SJ700 series. SJ-DN2, SJ-PB2/PBT2 has compatibility to SJ700-2.
SJ-DN2, SJ-PB2/PBT2 cannot access new paramaters is SJ700D-3.
availablenot available
Other model:same position. 055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
SJ300seriesSJ700/SJ700Dseries
17
17
17
50
50
Basic display mode/Data comparison function addition.
Note:basic display mode.
To display all parameters, specify "00" for "b037".
Instantaneous power failure/under-voltage:It sets
up by b001.
overvoltage/overcurrent:It sets up by b008.
You can not change the output frequency
setting by using the △ and/or ▽ key.
Setting range:
0.01 to 999Hz (0Hz setup is impossible)
Removable (You can mount the SJ300 series into
the SJ700/SJ700D series.)
M6 (Ground Screw)
055 to 550L/H:One step
150 to 220L/H:RB there is a terminal.
15kW or more is possible.
up to 22kW
16
10
10
35
35
35
DIFFERENCE and COMPATIBILITY
of L300P series and SJ700B series
Items
You can copy the parameter settings from the L300P series into the SJ700B series.
Copying the parameter settings
Parameter display mode.
Retry or trip parameter
d001:Output frequency monitoring
d007:Scaled output frequency monitoring
A001:
Frequency source setting
A016:
External frequency filter time const.
Change function
Control
circuit
Terminal
Main
circuit
Easy-removable Dc bus Capacitor
Dynamic Brake circuit
Minimum value of
UHVLVWRUї
Dimensions
Digital operator position
Keypad potentiometer on digital operator
Option boards
Note1: Since a response falls the V/F characteristic curve selection SLV should make this setup small.
Note2: 450, 550L/H and 750H:Metal fittings differ.
(You cannot copy the parameter settings from the SJ700B series to the L300P series because the SJ700B
series has many new functions and additional parameters.)
No display mode selection.
(full display)
Instantaneous power failure/under-voltage/
overvoltage/overcurrent:It sets up by b001.
You can not change the output frequency setting
by using the up and or down key.
Default:00
(Keypad potentiometer on digital operator)
110,150LF/HF:10mm upper part from L300P. 185 to 220L/ 300H:29mm upper part from L300P.
300L:18mm upper part from L300P. 370L:77mm upper part from L300P.
370H:72mm upper part from L300P. 750L:25mm upper part from L300P.
Other model:same position.
185 to 300L/H:RB there is not a terminal.
All the models are possible.
Up to 15kW
All models are the same enclosure size.
Those with compatibility. Note 2
300L/H:97mm upper part from L300P.
Other model:same position.
Those with compatibility.
Those with compatibility.
Note:Since the SJ700B series has many new functions and additional parameters,some functions of the
SJ-DN, and SJ-PB/PBT (option boards conforming to the open network specifications)cannot be
implemented on the SJ700B series.
availablenot available
370L/H:97mm upper part from L300P.
Other model:same position.
L300PseriesSJ700B series
Basic display mode/Data comparison function addition.
Note:basic display mode [factory setting] To display all
parameters,
specify "00" for "b037".
Instantaneous power failure/under-voltage:It sets
up by b001.
overvoltage/overcurrent:It sets up by b008.
You can not change the output frequency setting
by using the up and or down key.
Default:02
(Digital operator)
Setting range:
0.01 to 999Hz (0Hz setup is impossible)
Default:01 (operating the fan only during inverter
operation
[including 5 minutes after power-on and power-off])
Default:01 (enabling [disabling while the motor is
topped])
Removable
(You can mount the L300P into the SJ700B .)
8 terminals
185 to 300H:RB there is a terminal.
18.5kW or more is possible.
Up to 30kW
17
1710
5035
5035
Yes.No. (Option)
10
36
FOR CORRECT OPERATION
Application to Motors
Application to general-purpose motors
For operation at higher than 60Hz, it is required to examine the allowable torque of the motor, useful life of bearings, noise, vibration,
Operating frequency
Torque characteristics
Motor loss and
temperature increase
Noise
Vibration
Power transmission
mechanism
Application to special motors
Gear motor
Brake-equipped motor
Pole-change motor
Submersible motor
Explosion-proof motor
Synchronous (MS) motor
High-speed (HFM) motor
Single-phase motor
Application to the 400V-class motor
A system applying a voltage-type PWM inverter with IGBT may have surge voltage at the motor terminals resulting from the cable constants including
the cable length and the cable laying method. Depending on the surge current magnification, the motor coil insulation may be degraded. In particular,
when a 400V-class motor is used, a longer cable is used, and critical loss can occur, take any of the following countermeasures:
(1) install the LCR filter between the inverter and the motor,
(2) install the AC reactor between the inverter and the motor, or
(3) enhance the insulation of the motor coil.
etc. In this case,
be sure to consult the motor manufacturer as the maximum allowable rpm differs depending on the motor capacity, etc.
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power
(starting torque decreases in particular). Carefully check the load torque characteristic of a connected machine and the driving torque
characteristic of the motor.
An inverter-driven general-purpose motor heats up quickly at lower speeds. Consequently, the continuous torque level (output) will
decrease at lower motor speeds. Carefully check the torque characteristics vs speed range requirements.
When run by an inverter, a general-purpose motor audible slightly greater than with commercial power.
When run by an inverter at variable speeds, the motor may generate vibration, especially because of (a) unbalance of the rotor
including a connected machine, or (b) resonance caused by the natural vibration frequency of a mechanical system. Particularly, be
careful of (b) when operating at variable speeds a machine previously fitted with a constant speed motor. Vibration can be minimized
by (1) avoiding resonance points using the frequency jump function of the inverter, (2) using a tireshaped coupling, or (3) placing a
rubber shock absorber beneath the motor base.
Under continued, low-speed operation, oil lubrication can deteriorate in a power transmission mechanism with an oil-type gear box
(gear motor) or reducer. Check with the motor manufacturer for the permissible range of continuous speed. To operate at more than
60Hz, confirm the machine's ability to withstand the centrifugal force generated.
The allowable rotation range of continuous drive varies depending on the lubrication method or motor manufacturer.
(Particularly in case of oil lubrication, pay attention to the low frequency range.)
For use of a brake-equipped motor, be sure to connect the braking power supply from the primary side of the inverter.
There are different kinds of pole-change motors (constant output characteristic type, constant torque characteristic type, etc.), with
different rated current values. In motor selection, check the maximum allowable current for each motor of a different pole count. At
the time of pole changing, be sure to stop the motor. Also see: Application to the 400V-class motor.
The rated current of a submersible motor is significantly larger than that of the general-purpose motor. In inverter selection, be sure
to check the rated current of the motor.
Inverter drive is not suitable for a safety-enhanced explosion-proof type motor. The inverter should be used in combination with a
pressure-proof explosion-proof type of motor.
*Explosion-proof verification is not available for SJ700/SJ700D/SJ700B Series.
In most cases, the synchronous (MS) motor and the high-speed (HFM) motor are designed and manufactured to meet the
specifications suitable for a connected machine. As to proper inverter selection, consult the manufacturer.
A single-phase motor is not suitable for variable-speed operation by an inverter drive. Therefore, use a three-phase motor.
Notes on Use
Drive
Run/Stop
Emergency motor stop
High-frequency run
Run or stop of the inverter must be done with the keys on the operator panel or through the control circuit terminal. Do not operate
by installing a electromagnetic contactor (MC) in the main circuit.
When the protective function is operating or the power supply stops, the motor enters the free run stop state. When an emergency
stop is required or when the motor should be kept stopped, use of a mechanical brake should be considered.
A max. 400Hz can be selected on the SJ700/SJ700D/SJ700B Series. However, a two-pole motor can attain up to approx. 24,000
rpm, which is extremely dangerous. Therefore, carefully make selection and settings by checking the mechanical strength of the
motor and connected machines. Consult the motor manufacturer when it is necessary to drive a standard (general-purpose) motor
above 60Hz. A full line of high-speed motors is available from Hitachi.
Repetitive operation on starting or plugging
About frequent repetition use (crane, elevator, press, washing machine) , a power semiconductor (IGBT, a rectification diode, thyristor) in the inverter may
come to remarkably have a short life by thermal fatigue.
The life can be prolonged by lower a load electric current. Lengthen acceleration / deceleration time. Lower carrier frequency. or increasing capacity of the inverter.
Operation use in highlands beyond 1,000m above sea level
Due to the air density decreasing, whenever standard inverters are used for altitudes above 1000m, the following conditions are additionally required for
proper operation. In application for operation over 2500m, kindly contact your nearest sales office for assistance.
1. Reduction of inverter rated current
Current rating has to be reduced 1% for every 100m that exceeds from an altitude of 1000m.
For example, for inverters placed at an altitude of 2000m, the rated current has to be reduced 10% (Rated current x0.9) from its original amount.
{(2000m-1000m)/100m*-1%=-10%}
2. Reduction of breakdown voltage
Whenever an inverter is used at altitudes beyond 1000m, the breakdown voltage decreases as follows:
1000m or less: 1.00 / 1500m: 0.92 / 2000m: 0.90 / 2500m: 0.85. As mentioned in the instruction manual, please avoid any pressure test.
37
Installation location and operating environment
$PELHQWWHPSHUDWXUHÝ&
&DSDFLWRUOLIHWLPH\HDUV
6-6-'&7
SJ700B
6-'97
50
40
30
2.5 510
Avoid installation in areas of high temperature, excessive humidity, or where moisture can easily collect, as well as areas that are dusty, subject to
corrosive gasses, mist of liquid for grinding, or salt. Install the inverter away from direct sunlight in a well-ventilated room that is free of vibration. The
inverter can be operated in the ambient temperature range from SJ700/SJ700D (CT): -10 to 50˚C, SJ700D (VT): -10 to 40˚C, SJ700B: -10 to 45˚C.
(Carrier frequency and output current must be reduced in the range of 40 to 50˚C.)
Main power supply
In the following examples involving a general-purpose inverter, a large peak current flows on the main power supply side, and is
able to destroy the converter module. Where such situations are foreseen or the connected equipment must be highly reliable,
install an AC reactor between the power supply and the inverter. Also, where influence of indirect lightning strike is possible,
install a lightning conductor.
(A) The unbalance factor of the power supply is 3% or higher. (Note)
(B) The power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more).
(C) Abrupt power supply changes are expected.
Installation of an
AC reactor on the
input side
Using a private power
generator
Examples:
(1) Several inverters are interconnected with a short bus.
(2) A thyristor converter and an inverter are interconnected with a short bus.
(3) An installed phase advance capacitor opens and closes.
In cases (A), (B) and (C), it is recommended to install an AC reactor on the main power supply side.
Note: Example calculation with V
RS
V
: R-S line voltage, VST : S-T line voltage, VTR : T-R line voltage
Unbalance factor of voltage =
An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform of the
generator. Generally, the generator capacity should be five times that of the inverter (kVA) in a PWM control system, or six times
greater in a PAM control system.
RS
= 205V, VST = 201V, VTR = 200V
Max. line voltage (min.) - Mean line voltage
RS
V
=
Mean line voltage
-(VRS+VST+VTR)/3
RS+VST+VTR
(V
)/3
x
100 =
205-202
202
x
100
x
100 =1.5(%)
Notes on Peripheral Equipment Selection
(1) Be sure to connect main power wires with R (L1), S (L2), and T (L3) terminals (input) and motor wires to U (T1), V (T2), and W
Wiring connections
Electromagnetic
contactor
Wiring
between
inverter and
motor
Thermal relay
Installing a circuit breaker
Wiring distance
Earth leakage relay
Phase advance capacitor
(T3) terminals (output). (Incorrect connection will cause an immediate failure.)
(2) Be sure to provide a grounding connection with the ground terminal ( ).
When an electromagnetic contactor is installed between the inverter and the motor, do not perform on-off switching during running
operation.
When used with standard applicable output motors (standard three-phase squirrel-cage four-pole motors), the SJ700/SJ700D/
SJ700B Series does not need a thermal relay for motor protection due to the internal electronic protective circuit. A thermal relay,
however, should be used:
• during continuous running outside a range of 30 to 60 Hz.
• for motors exceeding the range of electronic thermal adjustment (rated current).
• when several motors are driven by the same inverter; install a thermal relay for each motor.
• The RC value of the thermal relay should be more than 1.1 times the rated current of the motor. If the wiring length is 10 m or
more, the thermal relay tends to turn off readily. In this case, provide an AC reactor on the output side or use a current sensor.
Install a circuit breaker on the main power input side to protect inverter wiring and ensure personal safety. Choose an invertercompatible circuit breaker. The conventional type may malfunction due to harmonics from the inverter. For more information, consult
the circuit breaker manufacturer.
The wiring distance between the inverter and the remote operator panel should be 20 meters or less. Shielded cable should be used
on thewiring. Beware of voltage drops on main circuit wires. (A large voltage drop reduces torque.)
If the earth leakage relay (or earth leakage breaker) is used, it should have a sensitivity level of 15 mA or more (per inverter).
Do not use a capacitor for power factor improvement between the inverter and the motor because the high-frequency components
of the inverter output may overheat or damage the capacitor.
High-frequency Noise and Leakage Current
(1) High-frequency components are included in the input/output of the inverter main circuit, and they may cause interference in a transmitter,
radio, or sensor if used near the inverter. The interference can be minimized by attaching noise filters (option) in the inverter circuitry.
(2) The switching action of an inverter causes an increase in leakage current. Be sure to ground the inverter and the motor.
Lifetime of Primary Parts
Because a DC bus capacitor deteriorates as it undergoes internal chemical reaction, it should normally be replaced
every five years. Be aware, however, that its life expectancy is considerably shorter when the inverter is subjected
to such adverse factors as high temperatures or heavy loads exceeding the rated current of the inverter. The
approximate lifetime of the capacitor is as shown in the figure at the right when it is used 12 hours daily (according
to the
cooling fan should be replaced. Maintenance inspection and parts replacement must beperformed by only specified
trained personnel. Please plan to replace new inverter depends on the load, ambient condition in advance.
Precaution for Correct Usage
• Before use, be sure to read through the Instruction Manual to insure proper use of the inverter.
• Note that the inverter requires electrical wiring; a trained specialist should carry out the wiring.
• The inverter in this catalog is designed for general industrial applications. For special applications in fields such as aircraft, outer space,
nuclear power, electrical power, transport vehicles, clinics, and underwater equipment, please consult with us in advance.
For application in a facility where human life is involved or serious injury may occur, make sure to provide safety devices to avoid any accident.
•
•
The inverter is intended for use with a three-phase AC motor. For use with a load other than this, please consult with us.
Information in this brochure is subject to change without notice.
"
Instructions for Periodic Inspection of General-Purpose Inverter " (JEMA).) Also, such moving parts as a
38
Printed in Japan (T) SM-E268R 0814
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.