Thank you for purchase of “SJ2-CO (CANopen Interface Option)”.
This manual explains about treatment of “SJ2-CO”. By reading this
manual and an instruction manual of inverter use practically for
installation, maintenance, and inspection. After reading this manual,
keep it handy for future reference.
Make sure to deliver this manual to the end user.
Table of Contents
Chapter1 Introduction 1
Chapter2 Mounting method of option 4
Chapter3 Wiring, Connecting 7
Chapter4 Setting 9
Chapter5 CANopen communication function 11
Chapter6 Countermeasure for abnormality 21
Chapter7 Communication Objects Lists 23
Chapter8
Chapter9 Contact information 31
After reading this manual, keep it at handy for future reference.
Specifications 30
NB 654 X
- Request -
Thank you for purchase of “SJ2-CO (CANopen Interface Option)”.
This instruction manual explains about treatment and maintenance of “SJ2-CO”. Before using the product,
carefully read this manual with the instruction manual of inverter, and keeps it handy for quick reference of
operator and maintenance inspector. Before installing, operating, maintenance and inspection read this
manual carefully and follow the instructions exactly.
Always keep various kinds of specifications mentioned in this manual and use exactly. And make sure to
prevent trouble by correct inspection and maintenance. Make sure to reach this manual to the end user.
- About treatment of this manual -
(1)Please consent that mentioned items of this manual may be change without permission.
(2)Keep this manual carefully not to lose because it can not be reissued
(3)All right reserved.
(4)Please contact the Hitachi inverter dealer from whom you purchased the unit, if you have some
doubts about spelling mistakes, omitted word etc.
(5)Please agree that there is no responsibility for effects resulted, in spite of contents above
mentioned.
Revision History Table
No.
1.Initial release of Manual NB654XJune. 2006NB654X
Except this table, revised only spelling mistakes omitted words, and error writings without notice.
Revision contentsThe date of issuedManual No.
SAFETY PRECAUTIONS
CAUTION
SAFTY PRECAUTIONS
Carefully read this manual and all of the warning labels attached to the inverter before installing,
operating, maintaining, inspecting, it. Safety precautions are classified into “Warning” and “Caution” in this
manual.
!
WARNING
!
The situation described in may, if not avoided, lead to serious results. Important safety
measures are described in CAUTION (as well as WARNING) so be sure observe them.
Notes are described in this manual in “(Note)”. Carefully read the contents and follow them exactly.
In all the illustrations in this manual, covers and safely device are occasionally removed to describe the
details. When the product is operated, make sure that the covers and safety devices are placed as they
were specified originally and operate it according to the instruction manual.
:Indicates a potentially hazardous situation which, if not avoided, can result in serious
injury or death.
:Indicates a potentially hazardous situation which, if not avoided, can result in minor to
CAUTIO
moderate injury, or serous damage to the product
!
CAUTION
!
SAFETY PRECAUTIONS
WARNING
!
Wiring:
Wiring work shall be carried out by electrical experts.
Otherwise, there is a danger of electric shock, fire and/or damage of product.
Implement wiring after checking that the power supply is off.
Otherwise, there is a danger of electric shock and/or fire.
Operating:
Be sure not to touch the surface or the terminal of option board while energizing.
Otherwise, there is a danger of electric shock and/or fire.
Be sure not to remove the Canopen option printed board while operating.
Otherwise, there is a danger of electric shock and/or fire.
Maintenance, Inspection and Part Replacement:
Wait at least 5 minutes after turning off the input power supply before performing maintenance and
inspection.
(Make sure the “POW” LED display on the inverter is off and DC voltage between P-N terminals is less
than 45V)
Otherwise, there is a danger of electric shock.
Make sure that only qualified persons will perform maintenance, inspection, and part replacement
(Before starting the work, remove metallic objects from your person (wristwatch, bracelet, etc.).
Be sure to use tools protected with insulation.)
Otherwise, there is a danger of electric shock and/or injury.
Note:
Never modify the unit.
Otherwise, there is a danger of electric shock and/or injury.
CAUTION
!
Installation:
Be sure not to let the foreign matter enter such as wire clippings, spatter from welding, metal shaving,
dust etc.
Otherwise, there is a danger of fire.
Be sure to fix inverter to option printed board with an attached fixed screw.
Otherwise, there is a danger of connecting error.
Be sure to fasten the screws connecting signal wire in side of option printed board. Check for any
loosening of screw.
Otherwise, there is a danger of connecting error.
Wiring:
Be sure to fasten the screws not to loose.
Otherwise, there is a danger of connecting error.
Operation:
Check rotary direction, abnormal motor noise and vibrations during operating.
Otherwise, there is a danger of injury to personnel and/or machine breakage
CHAPTER 1 INTRODUCTION
1.1 INSPECTION UPON UNPACKING
Make sure to treat the product carefully not to give shock and vibration while unpacking. Check that the
product is the one you ordered, no defect, and that there is no damage during transportation.
(Contents of packing)
(1) SJ2-CO(CANopen Interface option ):1
(2) Instruction manual:1
(3) CANopen connector:1
(4) The screw which fixes a facecover (M3 times 8 mm):1
(5) Bus resister(120Ω):1
If you discover any problems, contact the Hitachi inverter dealer from whom you purchased the unit
immediately.
1.2 INQUIRY OF THE PRODUCT AND WARRANTY FOR THE PRODUCT
1.2.1 Request upon inquiring
If inquiry of breakage, question, damage etc. is needed, please tell the following information to the supplier
you ordered.
(1) Type(SJ2-CO)
(2) Manufacturing number (MFG No. (See 1.5
(3) Date of purchasing
(4) Contents of inquiry
・ Damage parts and its condition etc.
・ Question parts and their contents etc.
In order to shorten impossible working time, standing spare unit is recommended.
SJ2-CO Specifications Label
))
1.2.2 Warranty of the product
This product is guaranteed one year after the purchase. But, the next case is toll repair, even if within
warranty period.
(1) In case caused by operating mistake, and incorrect repair and modification.
(2) Trouble caused by reasons except the shipped product.
(3) In case of using in range over the value of specifications.
(4) In case caused by natural calamity, disaster, and secondary disaster.
Warranty mentioned here means warranty for shipped product itself. Damage caused by trouble of shipped
product is not guaranteed.
[Replacement]
Any inspection and replacement after the expiration of warranty period (one-year) shall be charged to the
purchaser. And also any inspection and replacement which are not covered in warranty mentioned above,
even if it is within warranty period, it shall be charged to the purchaser. If you require the replacement,
please contact the Hitachi inverter dealer from whom you purchased the unit.
1
1.3 Appearance and Names of Parts
CHAPTER 1 INTRODUCTION
LED display
Power supply(POW)
Inverter Status(RUN)
Inverter condition mode(MOD)
CANbus Status(CAN)
Bus ready
(in CANopen this LED always green)
Baud rate & Node ID setting(See 4.1.2)
CAN bus Interface
Figure 1-1 Appearance of SJ2-CO
2
1.4 CANopen Support Version
Production time
SJ2-CO can use following Inverter model of SJ200-2/L200-2.
SJ200-2 -0.2-7.5kW
L200-2 -0.2-7.5kW
How to distinguish SJ200-2(L200-2) from SJ200(L200)
CHAPTER 1 INTRODUCTION
SJ200(L200)
Series
name
Applicable
motor
004HFEF2
Configuration
EMC filter
type
Input
voltage
Restricted
distribution
1.5 Specifications Label
There is the Specifications Label of SJ2-CO on the back side.
model name
Manufacturing No.
A
6 7
year month
MFG No. 67A T25724B6 0001
Hitachi Industrial Equipment Systems Co.,Ltd.
MADE IN JAPAN
other model names :SJ2-MF,SJ2-CCV
SJ2-CO
Version: 2=SJ200-2(L200-2)
space=SJ200 (L200)
NEXXXXX
1.6 LED display
LED FunctionColorState
Power Supply
Inverter Status
Inverter condition mode(MOD)-See 6.4 LED display and Countermeasure
CAN condition/status(CAN)-See 6.4 LED display and Countermeasure
CAN bus power supply(DC+24V)
(Internal power supply)
OrangeInverter Main power supply is ON.
BlankBoth power supplies are OFF.
RedAlarm or Inverter main power supply is OFF.
GreenRun
StopStop (Normal)
GreenON
BlankOFF
3
CHAPTER 2 MOUNTING METHOD OF OPTION
the main body of
2.1 Mounting method of option
Please connect the following cables first, and then attach the SJ2-CO to the front cover of SJ/L200-2.
[Installation step]
(1) mounting location
(2) Change the dipswitch position to lower ( OPE
(3) Connecting the cables
The cables are shown as bellow:
Power input cable, Motor output cable, Input terminal cable, Output terminal cable, Analog input cable,
Analog output cable etc
Because the following cables cannot be connected, after the instllation of SJ2-CO.
Figure 2-1 describes how to mount the SJ2-CO to the SJ200-2.
Figure 2-2 describes how to mount the SJ2-CO to the L200-2.
Figure 2-3 describes how to remove the SJ2-CO to the SJ200-2.
Figure 2-4 describes how to mount the SJ2-CO and operator(OPE-SRmini) to the SJ200-2
Note: Optional operator
(SRW-0J/0EX) cannot be used via SJ2-CO
)
.
If the lever is not dropped down,
please lift up the lever, and remount
the unit again.
Note : Please move the OPE/485 dip switch
bottom position labeled “OPE”.
Please mount the
SJ2-CO tightly to
the inverter.
Then lift down the
plastic lever.
Figure 2-1 Installation of SJ2-CO (SJ200-2 + SJ2-CO)
4
CHAPTER 2 MOUNTING METHOD OF OPTION
Note : Please move the OPE/485
dip switch bottom position
labeled “OPE”.
SJ2-MF
*1:The CANopen connector is connected to the bottom side of the SJ2-CO
SJ2-MF Specifications Label: See 1.5 Specifications Label
Figure 2-2 Installation of SJ2-CO (L200-2 + SJ2-CO + SJ2-MF)
*1
Figure 2-3 Remove of SJ2-CO (SJ200-2 + SJ2-CO)
5
SJ2-CCV (Optional)
CHAPTER 2 MOUNTING METHOD OF OPTION
OPE-SRmini
HITAC HI
SJ2-CCV
SJ200-2
SJ2-CO
SJ2-CCV
SJ2-CCV Specifications Label: See 1.5 Specifications Label
Figure 2-4 Installation of option unit (SJ200-2 + SJ2-CO + SJ2-CCV)
6
CHAPTER 3 WIRING, CONNECTING
Dimension in mm
3.1 Connection for CANopen connector
SJ2-CO has a Pluggable open connector (Male contacts), and a Network connector (Female contacts)
attached. The inverter and attach connector have a seal which is color coordinated to correspond to the
network cable. Ensure the cable and contact are wired in the same color cable.
Cable side connector (attached connector)
Maker
Phoenix contact co, Ltd.MSTB 2.5/5ST-5.08 AU
Type
Dimension
18.2
Wiring of CANopen
Communication connector
Figure 3-1 Connector specifications
Blue
Black
White
Red
Color label
No.1
8.3
2.54
5.0
20.3
25.4
No.Signal
mark
1GroundInternal power supply(-)Black
2CAN_LCAN L bus line(dominant low)Blue
3DRAINOptional CAN shieldBare
4CAN_HCAN H bus line(dominant high)White
5NCNo connectRed
Type of signal
No.5
Cable
color
Note:Communication power supply(DC 24V) of SJ2-CO is not required.
Please don’t make a short circuit between PIN 1(Black) and 5(Red).
3.2 Communication cable for CANopen
Use the connector which conforms to CANopen specifications or five conductor cable and also make sure
that cable, connector and Network distance conform to CANopen specifications.
Baud rate(kbps)Maximum Bus length(m)
1000
(1M)
80050
500100
250250
125500
501000
202500
105000
25
7
CHAPTER 3 WIRING, CONNECTING
3.3 Wiring note
1.Installing the cable to Network connector must be done after checking the power supply off and “POW”
LED is “OFF”.
2.Wiring should not have bare cables exposed between connector contacts.
3.Network cables should be fixed without tension. Cables fixed under tension have potential of causing a
communication fault by to be removed a connector.
4.A terminating resistor is not built-in the unit. Please use the accessory of Bus resister(120
5.Ensure external emergency stop measures are taken to stop the inverter, in the event of a network fault.
(a) Remove the Power supply of the Inverter when the network master detects a communication fault.
(b) When the master detects a communication fault, turn on the intelligent input terminal which would be
allocated (FRS), (RS) and/or (EXT) function.
(c) Setting command P045 to except “02”.
In this setting, the inverter is tripped, deceleration or free run stop when it detects a communication
fault itself. (Factory initialization of command P045 is trip after deceleration stop (code: 01).)
See “4.2 Setting of the Inverter”.
6.Basic components for construction of CANopen application are shown bellow.
Refer to the master’s description manuals when CANopen Network system comes into operation.
Ω
).
CANopen Master UNIT
Terminating
Resistor (120Ω )
(PLC)
Trunk line
SJ200-2
HITAC HI
Configurater (PC)
Drop
line
Multi port Tap
SJ200-2
HITAC HI
Multiple Node branching drop line.
DC24V
Power
Supply
Other slave units
Trunk line
Terminating
resistor
(120Ω)
Terminating
resistor
(120Ω)
Figure 3-2 Example of components for construction of CANopen application
Note:Communication power supply(DC 24V) of SJ2-CO is not required.
Please don’t make a short circuit between PIN 1(Black) and 5(Red).
8
CHAPTER4 SETTING
4.1 Setting methods of Baud rate and Node ID
Follow the procedure below to set Baud rate in CANopen and Node ID, reset the power supply after
changing the setting (setting will be reflected after resetting power supply.). Initial Baud rate: 125kbps,
Initial Node ID: 2.
4.1.1 Setting method of CANopen Baud rate
The table below is setting method of Baud rate with Dip switch.
Baud rate
(kbps)
Dip switch
Setting
Note
Baud rate
(kbps)
Dip switch
Setting
Note
2
1
3
10250
F
F
O
For bus
2
1
25500
F
O
2
1
length
3
greater than
1km bridge
or repeater
F
device may
be needed
3
.
50
F
F
O
2
1
3
1251000
F
F
O
1=OFF 2=ON 3=ON
4.1.2 Setting method of CANopen Node
800
2
1
3
F
F
O
2
1
3
F
F
O
2
1
3
F
F
O
2
1
3
F
F
O
Figure left describes the direction of Dip Switches. See below
ON: 1 OFF: 0
Bit increases from right to left switches. Figure formula below.
DR
NODE ID
ON
ON
OFF
1-9 = OFF, 10=ON:
OFF
NA64NA16NA32NA08 NA04 NA02 NA01
NODE ID = 1
NODE ID = NA64*26+ NA32*25+ NA16*24+ NA08*23+ NA04*22+ NA02*21+ NA01*2
9
0
CHAPTER4 SETTING
4.2 Parameter setting of the Inverter
Following table describes setting items relate SJ200-2/L200-2 series Inverter with connecting SJ2-CO.
Following parameter will appear with connecting SJ2-CO to SJ200-2/L200-2 Inverter.
ParameterFunctionRange of DATA
Timer setting of
P044
P045
P049*
Communication
timeout W hilst
running
Inverter action
when
communication
error
Motor Poles
setting for
revolution per
minutes
/ 02(ignore) / 03(Free-RUN)
(It is possible to set only even
Setting value ‘0’, monitoring unit is
Setting value except ‘0’, monitoring
0.00~99.990.00**
00(TRIP) / 01(TRIP after
deceleration stop)
/ 04(deceleration stop)
0 to 38
number )
Hz.
-1
unit is min
.
Initial
DATA
It is effective when
01
0
Note
“Object #6007”
setting is ‘-3’.
Note*: As “P049 Command” value is setting ‘0’, unit of “Index 6042,6043,6044,6046,6048-1,6049-1”
is ‘Hz’.
Note**: CANopen Interface Option cannot detect bus-off status with heartbeat. Using P045 command,
set value of P044 instead of detecting bus-off status.
4.3 Power Supply LED check
If the Power Supply LED(See 1.3) is not ON ,please remount(See 2.1) the SJ2-CO unit again.
10
CHAPTER5 CANOPEN COMMUNICATION FUNCTION
5.1 Feature of CANopen communication function
5.1.1 SDO(Service Data Object)
When using the segmented SDO download and upload services, the communication software will be
responsible the SDO as a sequence of segments.
Explicit transfer has to be supported. Segmented transfer has to be supported if objects lager than 4
bytes are supported. Optionally the following SDO services for doing a block transfer with higher bus
utilization and performance for large data set size can be implemented.
The model for the SDO communication is the Client/Sever model.
CANopen Interface Option uploads and downloads inverter parameters using Object Dictionary
1200h.
Sub-IndexTypeMeaningNotes
0UNSIGNED8Number of supported entries in the recorddefault: 2
1UNSIGNED32COB-ID Client -> Server (Receive ID)
2UNSIGNED32COB-ID Server -> Client (Transmit ID)
Abort Code
This protocol is used to implement the abort SDO Transfer Service.
The abort code is standard code of CANopen specifications.
Abort codeDescriptionNotes
0503 0000hToggle bit not alternated.
0504 0000hSDO protocol time out.
0504 0001hClient/server command specifier not valid or unknown.
0504 0005hOut of memory.
0601 0000hUnsupported access to an object.
0601 0001hAttempt to read a write only object.
0601 0002hAttempt to write a read only object.
0602 0000hObject does not exist in the object dictionary.
0604 0041hObject cannot be mapped to the PDO.
0604 0042h
0604 0043hGeneral parameter incompatibility reason.
0606 0000hAccess failed due to an hardware error.
0607 0010h
0607 0012hData type does not match, length of service parameter too high
0607 0013hData type does not match, length of service parameter too low
0609 0011hSub-index does not exist.
0609 0030hValue range of parameter exceeded (only for write access)
0609 0031hValue of parameter written too high.
0609 0032hValue of parameter written too low.
0609 0036hMaximum value is less than minimum value.
0800 0000hgeneral error
0800 0020hData cannot be transferred or stored to the application.
0800 0021h
0800 0022h
0800 0023h
The number and length of the objects to be mapped would exceed
PDO length.
Data type does not match, length of service parameter does not
match
Data cannot be transferred or stored to the application because of
local control.
Data cannot be transferred or stored to the application because of
the present device state.
Object dictionary dynamic generation fails or no object dictionary is
present (e.g. object dictionary is generated from file and generation
fails because of an file error).
11
CHAPTER5 CANOPEN COMMUNICATION FUNCTION
5.1.2 PDO(Process Data Object)
The real-time data transfer is using the PDOs.
There are two kinds of PDO transmission modes. One is a synchronization (SYNC), the other is
Data type “21h” is a record, which defines the PDO mapping parameter and it is of the following
format:
Sub-IndexTypeMeaningNotes
0hUNSIGNED8
1h
or
1h, 2h
UNSIGNED32
Number of supported entries in the
record
Number of supported entries in the
record
Structure consisting of mapped
object index (16 bit), sub-index (8
bits) and object data length in bits.
For example “20010010h” defines
object “2001h”, sub-index “0h”, and
data length of16 bits (=word).
Default: 2
Default: 2
12
CHAPTER5 CANOPEN COMMUNICATION FUNCTION
5.1.3 Device Control
CAN open interface option can use "Velocity Mode" DSP-402 V2.0 drive control profile.
5.1.4 Object Dictionary for Standardized Device Profile Area
CAN open interface option is supported following objects.
When communications between CANopen interface option and HOST cannot be active, inverter
actions will decide following this object setting.
valueActionNotes
0No actionSame as"P045 setting value 02”
1No actionSame as"P045 setting value 02”
2Disable voltage-(FRS)Same as"P045 setting value 03”
3Quick stop (Deceleration with 2nd setting)
-3
-4No Action
-5No Action
In new CANopen Interface Option, the trigger of this function is timer out in P044 instead of bus-off
condition.
manufacturer specific:
Enable switch for “P045 setting”.
See 5.1.5 Parameter setting of
SJ200
Enable P045 setting.
13
CHAPTER5 CANOPEN COMMUNICATION FUNCTION
5.1.6 Control word (Index: 6040h)
The control word is used to send control commands to the inverter. (HOST-> Inverter)
BitDescriptionNote
0
1
2
3
4RFG EnableMode Specific
5RFG UnlockMode Specific
6RFG Usr refMode Specific
7Reset Fault (raising edge)Mandatory
8HaltMode Specific
9(Undefined)Reserved
10(Undefined)Reserved
11RDY Function EnableManufacturer Specific
12NetRefManufacturer Specific
13NetCtrlManufacturer Specific
14Move forwardManufacturer Specific
15Move reverseManufacturer Specific
Switch On-Stop
Disable Voltage-Free Run Stop
Quick stop-Stop using 2CH setting
Enable Operation-Run
Mandatory
Mandatory
Mandatory
Mandatory
To use setting frequency from CANopen, please set bit NetRef(bit 12). An inverter parameter A001
is set 10(Calculate function output) with setting NetRef bit is 1, Calculate function output will not
work.
To handle RUN/STOP command form CANopen, you have to set a bit NetCtrl.
14
CHAPTER5 CANOPEN COMMUNICATION FUNCTION
5.1.7 Status word (Index: 6041h)
The status word indicates the current state of the inverter.
BitDescriptionNote
0Ready to switch onMandatory
1Switched onMandatory
2Operation enabledMandatory
3FaultMandatory
4Voltage enabled(~V1.04) Voltage disable -> enabledMandatory
5Quick stopMandatory
6Switch on disabledMandatory
7WarningUnsupported
8Manufacturer SpecificUnsupported
9RemoteMandatory
10Target reachedMandatory
11Internal Limit Active“Index 6046” influences this bit.Mandatory
12(reserved)(reserved)Mode Specific
13(reserved)(reserved)Mode Specific
14Moving forwards
15Moving backwards
Bitmapping of Status word
Bit 6Bit 5Bit 3Bit 2Bit 1Bit 0
Inverter
Not Ready to
Switch On
Switch On
Disabled
Ready to
Switch On
Switched On010011
Operation Enabled010111
Fault0X1111
Fault Reaction
Active
Quick Stop000111
The actual mode is reflected in the modes of operation display (index 6061h), and not in the mode
of operation(index 6060h). But CANopen Interface Option supported only Velocity Mode. These
objects are always stored “2(Velocity mode)”.
5.2 Keypad display(OPTIONAL OPERATOR:OPE-SRMINI)
In status of initializing CANopen option, the keypad shows following display.
Note: This display appears during initializing which is follow conditions;
Initializing with b084
Trip reset
CANopen option initializing when power is lunched.
“RS” terminal is lunched up.
Occurring un-expected matter.
Black:Segment is “ON”
20
CHAPTER6 COUNTERMEASURE FOR ABNORMALITY
Trip
6.1 Trip display
When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history
monitor (d081 to d086) also displays the same error code as the inverter.
6.2 Protection function list
The table below describes an error code for protecting the inverter and the motor.
No.FunctionError
Display
1Network option’s
communication error
2External tripE12This error is displayed, when Halt is set to 1 toward control
With regard to the other errors except table above, refer to Inverter instruction manual chapter 4
Explanation of function.
E70This error is displayed, disconnection occurs when timeout is
Action
occurred, while the inverter is operating with CANopen. (Trip
is caused by P045 setting)
word(Index:6040h) in BIT8(Halt).
6.3 Countermeasure for a trip state
The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to
Inverter instruction manual chapter 4 Explanation of function.
Trip
code
E70CANopen
E12External
Name of tripCauseConformationCountermeasure
Communication
error
Baud rate is
different.
Wiring distance does
not match with Baud
rate
Defective connector
for signal cable
Check Baud
rate
Check the wiring
distance
Check the area of
connection.
Install correct Baud rate and
then reset the power supply.
Adjust the setting to the
matching Baud rate.
Adjust Wiring distance.
Improve the connection and
then reset the power supply.
causes connection
fail.
Terminating resistor
is not connected.
Check the
Connection
Connect the terminating
Resistor and then reset the
power supply
Trip
Control
word(Index:6040h)
Check as mentioned
left.
Set Halt to 0 toward Control
word(Index:6040h)Bit8(Halt).
Bit8:Halt
21
CHAPTER6 COUNTERMEASURE FOR ABNORMALITY
6.4 LED display and Countermeasure
Following states are indicated by Module LED and CANopen status LED.
MOD (Module status) LED: It indicates Inverter condition.
CAN (CANopen status) LED: it indicates CANopen status.
LEDColorStateCountermeasureCategory
Green ON
Green
single flash
Red ON
MOD
Red single
flash
OFFPower off-Mandatory
Green ONOPERATIONAL-Mandatory
Green
single flash
Green
Blinking
CAN
notes
LED ON:
LED OFF:
LED blinking:
LED single flash:
LED double flash:
OFFno error-Mandatory
Red single
flash
Red double
flash
constantly on
constantly off
iso-phase on and off with a frequency of approximately 2.5Hz:
on for approximately 200ms and off for approximately 200ms.
one short flash (approximately 200ms) followed by a long off phase (approximately 1000ms).
a sequence of two short flashes (approximately 200ms),
separated by an off phase (approximately 200ms).
The sequence is finished by a long off phase (approximately 1000ms).
The inverter is in Normal
condition.
The inverter is in Stand-by
condition.
An abnormality occurred
which is impossible to restore.
An abnormality occurred
which is possible to restore.
Mostly this state occurs, when
the inverter is in trip condition.
But except status below.
User initializing with b084 set
to 01 or 02.
STOPPED-Mandatory
PRE-OPERATINAL-Mandatory
Warning limit reachedAny Flaming errorMandatory
Error Control Event
-Mandatory
-Mandatory
Need to fix the inverter.Mandatory
When in trip, remove the trip
causes.
When initializing, the inverter
starts up automatically the
BOOTUP process after the
initializing.
The Guarding Protocol or the
Heartbeat Protocol is
processing.
Mandatory
Mandatory
22
CHAPTER7 COMMUNICATION OBJECTS LISTS
7.Communication Objects
Communication Objects are grouped 3 areas.
IndexProfile Area
1000-1FFFCommunication Profile Area
2000-5FFFManufacturer Specific Profile Area(Inverter's parameter area)
6000-9FFFDevice Profile Area
7.1 Device Profile Area
Supported Communication Object by CANopen interface option ( ) =initial value
Hitachi Australia, Ltd
Level 3,82 Waterloo Road
North Ryde, N.S.W.2113
Australia
Phone:+61-2-9888-4100
Fax: +61-2-9888-4188
Hitachi Industrial Equipment System Co., Ltd
International Sales Department
ASK Bldg., 3,kanda Neribei-cho
Chiyodaku, Tokyo, 101-0022
Japan
Phone:+81-3-4345-6063
Fax: +81-3-4345-6913
Hitachi Industrial Equipment System Co., Ltd
Narashino Division
1-1, Higashi-Narashino 7-chome
Narashino-shi, chiba 275-8611
Japan
Phone:+81-47-474-9921
Fax: +81-47-476-9517
Hitachi Asia(Hong Kong) Ltd
th
7
Floor, North Tower
World Finance Centre, Harbour City
Canton Road, Tsimshatsui, Kowloon
Hong Kong
Phone:+852-2735-9218
Fax: +852-2735-6793
31
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.