Hitachi SJ200-2 Instruction Manual

Cover

SJ200
2
Series Inverter
Instruction Manual
•Single-phase Input 200V Class
•Three-phase Input 200V Class
•Three-phase Input 400V Class
Manual Number: NB670X-PC
May 2007
After reading this manual,
keep it handy for future reference.

Safety Messages

For the best results with the SJ2002 Series inverter, carefully read this manual and all of the warning labels attached to the inverter before installing and operating it, and follow the instructions exactly. Keep this manual handy for quick reference.

Definitions and Symbols

A safety instruction (message) includes a “Safety Alert Symbol” and a signal word or phrase such as WARNING or CAUTION. Each signal word has the following meaning:
HIGH VOLTAGE: This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operation this equipment. Read the message and follow the instructions carefully.
WARNING: Indicates a potentially hazardous situation that, if not avoided, can result in serious injury or death.
SJ2002 Inverter
i
CAUTION: Indicates a potentially hazardous situation that, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results. Important safety measures are described in CAUTION (as well as WARNING), so be sure to observe them.
1 Step 1: Indicates a step in a series of action steps required to accomplish a goal. The
number of the step will be contained in the step symbol.
NOTE: Notes indicate an area or subject of special merit, emphasizing either the product’s capabilities or common errors in operation or maintenance.
TIP: Tips give a special instruction that can save time or provide other benefits while installing or using the product. The tip calls attention to an idea that may not be obvious to first-time users of the product.

Hazardous High Voltage

HIGH VOLTAGE: Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking com­ponents. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
ii

General Precautions - Read These First!

WARNING: This equipment should be installed, adjusted, and serviced by qualified electrical maintenance personnel familiar with the construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury.
WARNING: The user is responsible for ensuring that all driven machinery, drive train mechanism not supplied by Hitachi Industrial Equipment Systems Co., Ltd., and process line material are capable of safe operation at an applied frequency of 150% of the maximum selected frequency range to the AC motor. Failure to do so can result in destruction of equipment and injury to personnel should a single-point failure occur.
WARNING: For equipment protection, install a ground leakage type breaker with a fast response circuit capable of handling large currents. The ground fault protection circuit is not designed to protect against personal injury.
WARNING: HAZARD OF ELECTRICAL SHOCK. DISCONNECT INCOMING POWER BEFORE WORKING ON THIS CONTROL.
WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock.
CAUTION: These instructions should be read and clearly understood before working on SJ2002 series equipment.
CAUTION: Proper grounds, disconnecting devices and other safety devices and their location are the responsibility of the user and are not provided by Hitachi Industrial Equipment Systems Co., Ltd.
CAUTION: Be sure to connect a motor thermal disconnect switch or overload device to the SJ200 overload or an overheated motor.
HIGH VOLTAGE: Dangerous voltage exists until power light is OFF. Wait at least five (5) minutes after input power is disconnected before performing maintenance.
WARNING: This equipment has high leakage current and must be permanently (fixed) hard-wired to earth ground via two independent cables.
2 series controller to assure that the inverter will shut down in the event of an
SJ2002 Inverter
WARNING: Rotating shafts and above-ground electrical potentials can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Installation, alignment and maintenance should be performed only by qualified personnel. Factory-recommended test procedures included in the instruction manual should be followed. Always disconnect electrical power before working on the unit.
CAUTION:
a) Class I motor must be connected to earth ground via low resistive path (< 0.1Ω) b) Any motor used must be of a suitable rating. c) Motors may have hazardous moving parts. In this event suitable protection must
be provided.
CAUTION: Alarm connection may contain hazardous live voltage even when inverter is disconnected. When removing the front cover for maintenance or inspection, confirm that incoming power for alarm connection is completely disconnected.
CAUTION: Hazardous (main) terminals for any interconnection (motor, contact breaker, filter, etc.) must be inaccessible in the final installation.
iii
CAUTION: This equipment should be installed in IP54 or equivalent (see EN60529) enclosure. The end application must be in accordance with BS EN60204-1. Refer to the section be suitably amended for your application.
CAUTION: Connection to field wiring terminals must be reliably fixed having two independent means of mechanical support. Use a termination with cable support (figure below), or strain relief, cable clamp, etc.
CAUTION: A double-pole disconnection device must be fitted to the incoming main power supply close to the inverter. Additionally, a protection device meeting IEC947-1/ IEC947-3 must be fitted at this point (protection device data shown in
Wire and Fuse Sizes” on page 2–18).
Choosing a Mounting Location” on page 2–10. The diagram dimensions are to
Terminal (ring lug) Cable support
Cable
Determining
NOTE: The above instructions, together with any other requirements highlighted in this manual, must be followed for continued LVD (European Low Voltage Directive) compliance.
iv

Index to Warnings and Cautions in This Manual

Cautions and Warnings for Orientation and Mounting Procedures

CAUTION: Hazard of electrical shock. Disconnect incoming power before working on this control. Wait five (5) minutes before removing the front cover.
CAUTION: Be sure to install the unit on flame-resistant material such as a steel plate. Otherwise, there is the danger of fire.
CAUTION: Be sure not to place any flammable materials near the inverter. Otherwise, there is the danger of fire.
CAUTION: Be sure not to let the foreign matter enter vent openings in the inverter housing, such as wire clippings, spatter from welding, metal shavings, dust, etc. Otherwise, there is the danger of fire.
CAUTION: Be sure to install the inverter in a place that can bear the weight according to the specifications in the text (Chapter 1, Specifica­tions Tables). Otherwise, it may fall and cause injury to personnel.
CAUTION: Be sure to install the unit on a perpendicular wall that is not subject to vibration. Otherwise, it may fall and cause injury to personnel.
CAUTION: Be sure not to install or operate an inverter that is damaged or has missing parts. Otherwise, it may cause injury to personnel.
....... 2–4
..... 2–10
..... 2–10
..... 2–10
..... 2–10
..... 2–10
..... 2–10
CAUTION: Be sure to install the inverter in a well-ventilated room that does not have direct exposure to sunlight, a tendency for high tempera­ture, high humidity or dew condensation, high levels of dust, corrosive gas, explosive gas, inflammable gas, grinding-fluid mist, salt damage, etc. Otherwise, there is the danger of fire.
CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.
..... 2–10
..... 2–11

Wiring - Warnings for Electrical Practices and Wire Specifications

WARNING: “Use 60/75°C Cu wire only” or equivalent. ..... 2–17
WARNING: “Open Type Equipment.” ..... 2–17
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 240 V maximum.” For models with suffix N or L.
..... 2–17
SJ2002 Inverter
v
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Otherwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is not mounted according the instructions given in this manual. Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Make sure the input power to the inverter is OFF. If the drive has been powered, leave it OFF for five minutes before continuing.

Wiring - Cautions for Electrical Practices

.... 2–17
.... 2–17
.... 2–17
.... 2–17
.... 2–17
.... 2–23
CAUTION: Fasten the screws with the specified fastening torque in the table below. Check for any loosening of screws. Otherwise, there is the danger of fire.
CAUTION: Be sure that the input voltage matches the inverter specifica­tions: • Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFE(F)/NFU models • Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models • Three phase 380 to 480 V 50/60Hz for HFE(F) models
CAUTION: If you power a 3-phase-only inverter with single phase power, you must derate the output current. Be sure to call your Hitachi distributor for assistence. Otherwise, there is the possibility of damage to the inverter and the danger of fire.
SJ2002 Inverter
Power Input Output to Motor
.... 2–19
.... 2–21
.... 2–21
vi
CAUTION: Be sure not to connect an AC power supply to the output terminals. Otherwise, there is the possibility of damage to the inverter and the danger of injury and/or fire.
CAUTION: Remarks for using ground fault interrupter breakers in the main power supply: Adjustable frequency inverters with CE-filters (RFI­filter) and shielded (screened) motor cables have a higher leakage current toward Earth GND. Especially at the moment of switching ON this can cause an inadvertent trip of ground fault interrupters. Because of the rectifier on the input side of the inverter there is the possibility to stall the switch-off function through small amounts of DC current. Please observe the following: • Use only short time-invariant and pulse current-sensitive ground fault interrupters with higher trigger current. • Other components should be secured with separate ground fault interrupters. • Ground fault interrupters in the power input wiring of an inverter are not an absolute protection against electric shock.
CAUTION: Be sure to install a fuse in each phase of the main power supply to the inverter. Otherwise, there is the danger of fire.
CAUTION: For motor leads, ground fault interrupter breakers and electromagnetic contactors, be sure to size these components properly (each must have the capacity for rated current and voltage). Otherwise, there is the danger of fire.
..... 2–21
..... 2–21
..... 2–21
..... 2–21

Powerup Test Caution Messages

CAUTION: The heat sink fins will have a high temperature. Be careful not to touch them. Otherwise, there is the danger of getting burned.
CAUTION: The operation of the inverter can be easily changed from low speed to high speed. Be sure to check the capability and limitations of the motor and machine before operating the inverter. Otherwise, there is the danger of injury.
CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage and/or injury.
CAUTION: Check the following before and during the powerup test. Otherwise, there is the danger of equipment damage. • Is the shorting bar between the [+1] and [+] terminals installed? DO NOT power or operate the inverter if the jumper is removed. • Is the direction of the motor rotation correct? • Did the inverter trip during acceleration or decelera­tion? • Were the rpm and frequency meter readings as expected? • Were there any abnormal motor vibrations or noise?
..... 2–24
..... 2–24
.... 2–24,
..... 2–30
..... 2–24

Warnings for Configuring Drive Parameters

SJ2002 Inverter
vii
WARNING: When parameter B012, level of electronic thermal setting, is set to motor FLA rating (Full Load Ampere nameplate rating), the inverter provides solid state motor overload protection at 115% of motor FLA or equivalent. If parameter B012 exceeds the motor FLA rating, the motor may overheat and be damaged. Parameter B012, level of electronic thermal setting, is a variable parameter.

Cautions for Configuring Drive Parameters

CAUTION: Be careful to avoid specifying a braking time that is long enough to cause motor overheating. If you use DC braking, we recom­mend using a motor with a built-in thermistor, and wiring it to the inverter’s thermistor input (see “Thermistor Thermal Protection” on page 4–26). Also refer to the motor manufacturer’s specifications for duty-cycle recommendations during DC braking.

Warnings for Operations and Monitoring

WARNING: Be sure to turn ON the input power supply only after closing the front case. While the inverter is energized, be sure not to open the front case. Otherwise, there is the danger of electric shock.
.... 3–34
.... 3–20
...... 4–3
WARNING: Be sure not to operate electrical equipment with wet hands. Otherwise, there is the danger of electric shock.
WARNING: While the inverter is energized, be sure not to touch the inverter terminals even when the motor is stopped. Otherwise, there is the danger of electric shock.
WARNING: If the Retry Mode is selected, the motor may suddenly restart after a trip stop. Be sure to stop the inverter before approaching the machine (be sure to design the machine so that safety for personnel is secure even if it restarts.) Otherwise, it may cause injury to personnel.
WARNING: If the power supply is cut OFF for a short period of time, the inverter may restart operation after the power supply recovers if the Run command is active. If a restart may pose danger to personnel, so be sure to use a lock-out circuit so that it will not restart after power recovery. Otherwise, it may cause injury to personnel.
WARNING: The Stop Key is effective only when the Stop function is enabled. Be sure to enable the Stop Key separately from the emergency stop. Otherwise, it may cause injury to personnel.
WARNING: During a trip event, if the alarm reset is applied and the Run command is present, the inverter will automatically restart. Be sure to apply the alarm reset only after verifying the Run command is OFF. Otherwise, it may cause injury to personnel.
...... 4–3
...... 4–3
...... 4–3
...... 4–3
...... 4–3
...... 4–3
viii
WARNING: Be sure not to touch the inside of the energized inverter or to put any conductive object into it. Otherwise, there is a danger of electric shock and/or fire.
WARNING: If power is turned ON when the Run command is already active, the motor will automatically start and injury may result. Before turning ON the power, confirm that the RUN command is not present.
WARNING: When the Stop key function is disabled, pressing the Stop key does not stop the inverter, nor will it reset a trip alarm.
WARNING: Be sure to provide a separate, hard-wired emergency stop switch when the application warrants it.
WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.
WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.
....... 4–3
....... 4–3
....... 4–3
....... 4–3
..... 4–12
..... 4–25

Cautions for Operations and Monitoring

CAUTION: The heat sink fins will have a high temperature. Be careful not to touch them. Otherwise, there is the danger of getting burned.
CAUTION: The operation of the inverter can be easily changed from low speed to high speed. Be sure check the capability and limitations of the motor and machine before operating the inverter. Otherwise, it may cause injury to personnel.
CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage.
CAUTION: It is possible to damage the inverter or other devices if your application exceeds the maximum current or voltage characteristics of a connection point.
CAUTION: Be sure to turn OFF power to the inverter before changing the SR/SK switch position. Otherwise, damage to the inverter circuitry may occur.
CAUTION: Be careful not to turn PID Clear ON and reset the integrator sum when the inverter is in Run Mode (output to motor is ON). Other­wise, this could cause the motor to decelerate rapidly, resulting in a trip.
....... 4–2
....... 4–2
....... 4–2
....... 4–4
....... 4–9
..... 4–29
SJ2002 Inverter

Warnings and Cautions for Troubleshooting and Maintenance

ix
WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Other­wise, there is the danger of electric shock.
WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement. Before starting to work, remove any metallic objects from your person (wristwatch, bracelet, etc.). Be sure to use tools with insulated handles. Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Never remove connectors by pulling on its wire leads (wires for cooling fan and logic P.C.board). Otherwise, there is a danger of fire due to wire breakage and/or injury to personnel.
CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter.
CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground.
HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working with the inverters and taking measurements. Be sure to place the measurement circuitry components above in an insulated housing before using them.
...... 6–2
...... 6–2
...... 6–2
.... 6–10
.... 6–10
.... 6–14

General Warnings and Cautions

WARNING: Never modify the unit. Otherwise, there is a danger of electric shock and/ or injury.
CAUTION: Withstand voltage tests and insulation resistance tests (HIPOT) are executed before the units are shipped, so there is no need to conduct these tests before operation.
CAUTION: Do not attach or remove wiring or connectors when power is applied. Also, do not check signals during operation.
CAUTION: Be sure to connect the grounding terminal to earth ground.
CAUTION: When inspecting the unit, be sure to wait five minutes after tuning OFF the
power supply before opening the cover.
CAUTION: Do do not discard the inverter with household waste. Contact an industrial waste management company in your area who can treat industrial waste without polluting the environment.
x
CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary sides of the inverter.
Ground fault
interrupter
Power
Input
L1, L2, L3
Inverter
U, V, W
PCS
FW
Motor
When there has been a sudden power failure while an operation instruction is active, then the unit may restart operation automatically after the power failure has ended. If there is a possibility that such an occurrence may harm humans, then install an electromagnetic contactor (Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the power supply recovers. If the optional remote operator is used and the retry function has been selected, this will also cause automatic restarting when a Run command is active. So, please be careful.
CAUTION: Do not insert leading power factor capacitors or surge absorbers between the output terminals of the inverter and motor.
Power
Input
Ground fault
interrupter
L1, L2, L3
U, V, W
Inverter
GND lug
Surge absorber
Motor
Leading power
factor capacitor
CAUTION: MOTOR TERMINAL SURGE VOLTAGE SUPPRESSION FILTER (For the 400 V CLASS)
In a system using an inverter with the voltage control PWM system, a voltage surge caused by the cable constants such as the cable length (especially when the distance between the motor and inverter is 10 m or more) and cabling method may occur at the motor terminals. A dedicated filter of the 400 V class for suppressing this voltage surge is available. Be sure to install a filter in this situation.
SJ2002 Inverter
CAUTION: EFFECTS OF POWER DISTRIBUTION SYSTEM ON INVERTER
In the cases below involving a general-purpose inverter, a large peak current can flow on the power supply side, sometimes destroying the converter module:
1. The unbalance factor of the power supply is 3% or higher.
2. The power supply capacity is at least 10 times greater than the inverter capacity (or the power supply capacity is 500 kVA or more).
3. Abrupt power supply changes are expected, due to conditions such as: a. Several inverters are interconnected with a short bus. b. A thyristor converter and an inverter are interconnected with a short bus. c. An installed phase advance capacitor opens and closes.
Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightning strike are possible, install a lightning conductor.
CAUTION: SUPPRESSION FOR NOISE INTERFERENCE FROM INVERTER
The inverter uses many semiconductor switching elements such as transistors and IGBTs. Thus, a radio receiver or measuring instrument located near the inverter is susceptible to noise interference. To protect the instruments from erroneous operation due to noise interference, they should be used well away from the inverter. It is also effective to shield the whole inverter structure. The addition of an EMI filter on the input side of the inverter also reduces the effect of noise from the commercial power line on external devices. Note that the external dispersion of noise from the power line can be minimized by connecting an EMI filter on the primary side of inverter.
xi
EMI Filter Inverter
R1
S1
T1
noise
EMI Filter
Completely ground the enclosed panel, metal screen, etc. with as short a wire as possible.
R2
S2
T2
L1
L2
L3
Operator
U
V
W
Inverter
Remote
Motor
Motor
Grounded frame
Conduit or shielded cable—to be grounded
xii
CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values again.
CAUTION: When using normally closed active state settings (C011 to C016) for exter- nally commanded Forward or Reverse terminals [FW] or [RV], the inverter may start automatically when the external system is powered OFF or disconnected from the inverter! So, do not use normally closed active state settings for Forward or Reverse terminals [FW] or [RV] unless your system design protects against unintended motor operation.
CAUTION: In all the illustrations in this manual, covers and safety devices are occasionally removed to describe the details. While operating the product, make sure that the covers and safety devices are placed as they were specified originally and operate it according to the instruction manual.

UL® Cautions, Warnings, and Instructions

Wiring Warnings for Electrical Practices and Wire Sizes

The Warnings and instructions in this section summarize the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories
WARNING: “Use 60/75°C Cu wire only” or equivalent.
WARNING: “Open Type Equipment.”
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000
rms symmetrical amperes, 240 V maximum.” For models with suffix N or L.
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H.
WARNING: “Hot surface—risk of burn.”
WARNING: “Install device in pollution degree 2 environment.”
WARNING: “Maximum Surrounding Air Temperature 50°C.”
®
guidelines.
WARNING: “Risk of electric shock—capacitor discharge time is at least 5 minutes.”
WARNING: “Solid state motor overload protection is provided in each model.”
WARNING: “Tightening torque and wire range for field wiring terminals are marked
adjacent to the terminal or on the wiring diagram.”

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the tables below.
SJ2002 Inverter
xiii
Input
Voltage
200V
400V
Motor Output
Inverter Model
kW HP ft-lbs (N-m)
0.2 1/4 SJ200-002NFE(F)2/NFU2
0.55 3/4 SJ200-005NFE(F)2
0.75 1 SJ200-007NFE(F)2/NFU2
1.1 1 1/2 SJ200-011NFE(F)2
1.5 2 SJ200-015NFE(F)2/NFU2 12
2.2 3 SJ200-022NFE(F)2/NFU2 10
3.7 5 SJ200-037LFU2 10
5.5 7 1/2 SJ200-055LFU2 10
7.5 10 SJ200-075LFU2 8
0.4 1/2 SJ200-004HFE(F)2/HFU2
0.75 1 SJ200-007HFE(F)2/HFU2
1.5 2 SJ200-015HFE(F)2/HFU2
2.2 3 SJ200-022HFE(F)2/HFU2
3.0 4 SJ200-030HFE(F)2
4.0 5 SJ200-040HFE(F)2/HFU2
Power Terminal
Wiring Size
Range (AWG)
16 0.6 0.80.4 1/2 SJ200-004NFE(F)2/NFU2
14
16
14
Torq ue
0.9 1.2
1.5 2.0
0.9 1.2
5.5 7 1/2 SJ200-055HFE(F)2/HFU2
7.5 10 SJ200-075HFE(F)2/HFU2
Terminal Connector
Logic and Analog connectors 30—16 0.16—0.19 0.22—0.25
Relay connector 30—14 0.37—0.44 0.5—0.6

Wire Connectors

WARNING: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the connector manufacturer.
Wiring Size
Range (AWG)
12 1.5 2.0
Torqu e R ang e
ft-lbs (N-m)
Terminal (ring lug)
Cable support
Cable
xiv

Fuse and Circuit Breaker Sizes

The inverter’s input power wiring must include UL Listed, dual-element, 600V fuses, or
UL Listed, inverse-time circuit breakers of appropriate voltage rating for the supply.
Input
Voltage
200V
Motor Output
Inverter Model
kW HP
0.2 1/4 SJ200-002NFE(F)2/NFU2 10
0.4 1/2 SJ200-004NFE(F)2/NFU2 10
0.55 3/4 SJ200-005NFE(F)2 10
0.75 1 SJ200-007NFE(F)2/NFU2 15
1.1 1 1/2 SJ200-011NFE(F)2 15
1.5 2 SJ200-015NFE(F)2/NFU2 20 (single ph.)
2.2 3 SJ200-022NFE(F)2/NFU2 30 (single ph.)
3.7 5 SJ200-037LFU2 30
5.5 7 1/2 SJ200-055LFU2 40
7.5 10 SJ200-075LFU2 50
0.4 1/2 SJ200-004HFE(F)2/HFU2 3
0.75 1 SJ200-007HFE(F)2/HFU2 6
1.5 2 SJ200-015HFE(F)2/HFU2 10
Ampere Rating for
Fuse or Breaker
15 (three ph.)
20 (three ph.)
400V
2.2 3 SJ200-022HFE(F)2/HFU2 10
3.0 4 SJ200-030HFE(F)2 15
4.0 5 SJ200-040HFE(F)2/HFU2 15
5.5 7 1/2 SJ200-055HFE(F)2/HFU2 20
7.5 10 SJ200-075HFE(F)2/HFU2 25

Motor Overload Protection

Hitachi SJ2002 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters:
• B012 “electronic overload protection”
• B212 “electronic overload protection, 2nd motor”
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.2 * rated current to 1.2 * rated current.
WARNING: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload protection. Install an external thermal relay on each motor.
SJ2002 Inverter

Table of Contents

Safety Messages
Hazardous High Voltage i General Precautions - Read These First! ii Index to Warnings and Cautions in This Manual iv General Warnings and Cautions ix UL® Cautions, Warnings, and Instructions xii
Table of Contents
Revisions xvii Contact Information xviii
xv
Chapter 1: Getting Started
Introduction 1–2 Inverter Specifications 1–5 Introduction to Variable-Frequency Drives 1–18 Frequently Asked Questions 1–23
Chapter 2: Inverter Mounting and Installation
Orientation to Inverter Features 2–2 Basic System Description 2–8 Step-by-Step Basic Installation 2–9 Powerup Test 2–23 Using the Front Panel Keypad 2–25
Chapter 3: Configuring Drive Parameters
Choosing a Programming Device 3–2 Using Keypad Devices 3–3 “D” Group: Monitoring Functions 3–6 “F” Group: Main Profile Parameters 3–8 “A” Group: Standard Functions 3–9 “B” Group: Fine Tuning Functions 3–32 “C” Group: Intelligent Terminal Functions 3–45 “H” Group: Motor Constants Functions 3–61 “P” Group: Expansion Card Functions 3–62
xvi
Chapter 4: Operations and Monitoring
Introduction 4–2 Connecting to PLCs and Other Devices 4–4 Control Logic Signal Specifications 4–6 Intelligent Terminal Listing 4–7 Using Intelligent Input Terminals 4–9 Using Intelligent Output Terminals 4–36 Analog Input Operation 4–54 Analog Output Operation 4–56 PID Loop Operation 4–57 Configuring the Inverter for Multiple Motors 4–59
Chapter 5: Inverter System Accessories
Introduction 5–2 Component Descriptions 5–3 Dynamic Braking 5–5
Chapter 6: Troubleshooting and Maintenance
Troubleshooting 6–2 Monitoring Trip Events, History, & Conditions 6–5 Restoring Factory Default Settings 6–8 Maintenance and Inspection 6–9 Warranty 6–16
Appendix A: Glossary and Bibliography
Glossary A–2 Bibliography A–8
Appendix B: ModBus Network Communications
Introduction B–2 Connecting the Inverter to ModBus B–3 Network Protocol Reference B–6 ModBus Data Listing B–19
Appendix C: Drive Parameter Settings Tables
Introduction C–2 Parameter Settings for Keypad Entry C–2
Appendix D: CE–EMC Installation Guidelines
CE–EMC Installation Guidelines D–2 Hitachi EMC Recommendations D–6
Index

Revisions

Revision History Table
SJ2002 Inverter
xvii
No. Revision Comments Date of Issue
Initial release of manual NB670X Sept. 2006 NB670X
Operation
Manual No.
xviii

Contact Information

Hitachi America, Ltd. Power and Industrial Division 50 Prospect Avenue Tarrytown, NY 10591 U.S.A. Phone: +1-914-631-0600 Fax: +1-914-631-3672
Hitachi Europe GmbH Am Seestern 18 D-40547 Düsseldorf Germany Phone: +49-211-5283-0 Fax: +49-211-5283-649
Hitachi Asia Ltd. 16 Collyer Quay #20-00 Hitachi Tower, Singapore 049318 Singapore Phone: +65-538-6511 Fax: +65-538-9011
Hitachi Asia (Hong Kong) Ltd. 7th Floor, North Tower World Finance Centre, Harbour City Canton Road, Tsimshatsui, Kowloon Hong Kong Phone: +852-2735-9218 Fax: +852-2735-6793
Hitachi Australia Ltd. Level 3, 82 Waterloo Road North Ryde, N.S.W. 2113 Australia Phone: +61-2-9888-4100 Fax: +61-2-9888-4188
Hitachi Industrial Equipment Systems Co., Ltd. AKS Building, 3, Kanda Neribei-cho Chiyoda-ku, Tokyo, 101-0022 Japan Phone: +81-3-4345-6910 Fax: +81-3-4345-6067
Hitachi Industrial Equipment Systems Co, Ltd. Narashino Division 1-1, Higashi-Narashino 7-chome Narashino-shi, Chiba 275-8611 Japan Phone: +81-47-474-9921 Fax: +81-47-476-9517
NOTE: To receive technical support for the Hitachi inverter you purchased, contact the Hitachi inverter dealer from whom you purchased the unit, or the sales office or factory contact listed above. Please be prepared to provide the following inverter nameplate information:
1. Model
2. Date of purchase
3. Manufacturing number (MFG No.)
4. Symptoms of any inverter problem If any inverter nameplate information is illegible, please provide your Hitachi contact with any other legible nameplate items. To reduce unpredictable downtime, we recom­mend that you stock a spare inverter.

Getting Started

1
In This Chapter... page
Introduction ..................................................... 2
Inverter Specifications..................................... 5
Introduction to Variable-Frequency Drives.... 18
Frequently Asked Questions......................... 23
1–2
Getting Started

Introduction

Introduction

Main Features

Congratulations on your purchase of an SJ200 inverter! This inverter drive features state-of-the-art circuitry and components to provide high performance. The housing footprint is exceptionally small, given the size of the corresponding motor. The Hitachi SJ200 includes more than a dozen inverter models to cover motor sizes from 1/ 4 horsepower to 10 horsepower, in either 240 VAC or 480 VAC power input versions. The main features are:
2 Series Hitachi
2 product line
SJ200-004LFU2
SJ200-037LFU2
• 200V and 400V Class inverters
• US or EU versions available (country-specific input voltage range and default values)
• New intelligent sensorless vector control (iSLV)—auto-tuning no longer necessary
• Dynamic braking with external resistor
• Convenient, removable keypad for parameter settings, can be mounted on panel door
• Built-in RS-485 MODBUS RTU as standard
• New current limit function
• Sixteen programmable speed levels
• PID control adjusts motor speed automatically to maintain a process variable value
The design in Hitachi inverters overcomes many of the traditional trade-offs between speed, torque and efficiency. The performance characteristics are:
• High starting torque of 200% at 1Hz
• Continuous operation at 100% torque within a 1:10 speed range (6/60 Hz / 5/50 Hz)
without motor derating
• Fan has ON/OFF selection to provide longer life for cooling fan (on models with fan)
A full line of accessories from Hitachi is available to complete your motor application:
• Digital remote operator keypad
• Panel-mount keypad bezel kit and DIN rail mounting adapter (35mm rail size)
• Dynamic braking unit with resistors
• Radio noise filters
• CE compliance filters

Operator Interface Options

The SJ2002 inverter has a removable keypad, as shown to the right (part no. OPE–SRmini). This allows the keypad to operate the inverter remotely, as shown (below, left). A cable (part no. ICS–1 or ICS–3, 1m or 3m) connects the modular connectors of the keypad and inverter.
Hitachi provides a panel mount keypad kit (below, right). It includes the mounting flange, gasket, keypad, and other hardware. You can mount the keypad with the potentiometer for a NEMA1 rated installation. The kit also provides for removing the potentiometer knob to meet NEMA 4X requirements, as shown (part no. 4X–KITmini).
Cable
ICS–1 or
ICS–3
SJ2002 Inverter
1–3
Getting Started
OPE–SRmini
Digital Operator Copy Unit - The optional digital operator / copy unit (part no. SRW-0EX) is shown to the right. It has a 2-line display that shows parameters by function code and by name. It has the additional capability of reading (uploading) the parameter settings in the inverter into its memory. Then you can connect the copy unit on another inverter and write (download) the parameter settings into that inverter. OEMs will find this unit particularly useful, as one can use a single copy unit to transfer parameter settings from one inverter to many.
Other digital operator interfaces may be available from your Hitachi distributor for particular indus­tries or international markets. Contact your Hitachi distributor for further details.
4X–KITmini
SRW–0EX
1–4
Getting Started
Introduction

Inverter Specifications Label

The Hitachi SJ2002 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, motor, and application safety requirements.
Specifications label
Regulatory agency approval labels (opposite side)
Inverter model number
Motor capacity for this model
Power Input Rating: frequency, voltage, phase, current
Output Rating: Frequency, voltage, current
Manufacturing codes: Lot number, date, etc.

Model Number Convention

The model number for a specific inverter contains useful information about its operating characteristics. Refer to the model number legend below:
SJ200 037 H F E
Series name
F
2
EMC filter
Restricted distribution: E=Europe, U=USA, R=Japan
Configuration type F = with digital operator (keypad)
Input voltage: N = single or three-phase 200V class H = three-phase 400V class L = three phase only, 200V class
Versi on
Applicable motor capacity in kW
002 = 0.2 kW 004 = 0.4 kW 005 = 0.55 kW 007 = 0.75 kW 011 = 1.1 kW 015 = 1.5 kW
022 = 2.2 kW 030 = 3.0 kW 037 = 3.7 kW 040 = 4.0 kW 055 = 5.5 kW 075 = 7.5 kW
SJ2002 Inverter
1–5

Inverter Specifications

Model-specific tables for 200V and 400V class inverters

The following tables are specific to SJ2002 inverters for the 200V and 400V class model groups. Note that groups. Footnotes for all specifications tables follow the table below.
Item 200V Class Specifications
2 inverters,
SJ200 200V models
Applicable motor size *2 kW 0.2 0.4 0.55 0.75 1.1
Rated capacity (kVA)
Rated input voltage 1-phase: 200 to 240V ±10%, 50/60 Hz ±5%,
Integrated EMC filter
EU types 002NFEF2
USA type 002NFU2 004NFU2 007NFU2
230V 0.6 1.0 1.1 1.5 1.9
240V 0.6 1.0 1.2 1.6 2.0
NFEF type Single phase filter, Category C3 *5
NFE, NFU types
General Specifications” on page 1–10 apply to both voltage class
004NFEF2
002NFE2
HP 1/4 1/2 3/4 1 1.5
004NFE2
3-phase: 200 to 240V ±10%, 50/60 Hz ±5%,
(037LFU2, 055LFU2, and 075LFU2 3-phase only)
005NFEF2
005NFE2
007NFEF2
007NFE2
011NFEF2
011NFE2
Getting Started
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Rated output current (A) 1.6 2.6 3.0 4.0 5.0
Efficiency at 100% rated output (%) 89.5 93.5 94.2 94.1 95.0
Watt loss, approximate (W)
Starting torque *7 200% or more
Dynamic braking approx. % torque, short time stop *8
DC braking Variable operating frequency, time, and braking force
Weight
1-phase 3.5 5.8 6.7 9.0 11.2
3-phase 2.0 3.4 3.9 5.2 6.5
at 70% output
at 100% output
without resistor, from 50 / 60 Hz
with resistor 150%
NFEF type
NFE type
NFU type
kg 0.8 0.95 0.95 1.4 1.4
lb 1.75 2.09 2.09 3.09 3.09
kg 0.7 0.85 0.85 1.8 1.8
lb 1.54 1.87 1.87 3.97 3.97
kg 0.7 0.85 1.8
16 20 21 30 40
21 26 29 41 55
100%: 50Hz
50%: 60Hz
lb 1.54 1.87 3.97
1–6
Getting Started
Inverter Specifications
Footnotes for the preceding table and the tables that follow:
Note 1: The protection method conforms to JEM 1030. Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When
using other motors, care must be taken to prevent the rated motor current (50/ 60 Hz) from exceeding the rated output current of the inverter.
Note 3: The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
Note 5: When using the inverter with 3-phase power input, remove the single phase
filter and install a 3-phase filter with the appropriate ratings.
Note 6: For achieving approved input voltage rating categories:
• 460 to 480 VAC – Over-voltage Category 2
• 380 to 460 VAC– Over-voltage Category 3 To meet the Over-voltage Category 3, insert an EN or IEC standard compliant isolation transformer that is earth grounded and star connected (for Low Voltage Directive).
Note 7: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor
(when selecting intelligent sensorless vector control—iSLV).
Note 8: The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average deceleration torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used.
Note 9: The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not satisfactory for your application, contact your Hitachi sales representa­tive.
Note 10: If the inverter is operated outside the region shown in the graph below, the
inverter may be damaged or its service life may be shortened. Set B083 Carrier Frequency Adjustment in accordance with the expected output current level.
Derating Curve
Rated
current
Note 11: The storage temperature refers to the short-term temperature during transport. Note 12: Conforms to the test method specified in JIS C0040 (1999). For the model
types excluded in the standard specifications, contact your Hitachi sales representative.
100%
70%
0
Operating region
5.0
Carrier frequency
14.0
Curve at 40°C
kHz
SJ2002 Inverter Specifications, continued...
Item 200V Class Specifications, continued
SJ2002 Inverter
1–7
Getting Started
2 inverters,
SJ200 200V models
Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5
Rated capacity (kVA)
Rated input voltage 1-phase: 200 to 240V ±10%, 50/60 Hz ±5%,
Integrated EMC filter
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Rated output current (A) 8.0 11.0 17.5 24 32
Efficiency at 100% rated output (%) 94.0 95.2 94.7 95.6 96.0
Watt loss, approximate (W)
EU types 015NFEF2
015NFE2
USA type 015NFU2 022NFU2 037LFU2 055LFU2 075LFU2
HP 2 3 5 7.5 10
230V 3.1 4.3 6.9 9.5 12.7
240V 3.3 4.5 7.2 9.9 13.3
NFEF type Single phase filter,
Category C3 *5
NFE, NFU types
1-phase 17.5 24.0
3-phase 10.0 14.0 22.0 30.0 40.0
at 70% output
at 100% output
60 70 150 175 210
90 105 195 244 300
022NFEF2
022NFE2
3-phase: 200 to 240V ±10%, 50/60 Hz ±5%,
(037LFU, 055LFU, 075LFU 3-phase only)
———
Starting torque *7 200% or more 180% or more
Dynamic braking approx. % torque, short time stop *8
DC braking Variable operating frequency, time, and braking force
Weight
without resistor, from 50 / 60 Hz
with resistor 150% 100% 80%
NFEF type
NFE type
NFU type
70%: 50Hz 50%: 60Hz
kg 1.9 1.9
lb 4.2 4.2
kg 1.8 1.8
lb 3.97 3.97
kg 1.8 1.8 1.9 5.5 5.7
lb 3.97 3.97 4.2 12.13 12.57
20%: 50Hz 20%: 60Hz
1–8
Inverter Specifications
Item 400V Class Specifications
Getting Started
2 inverters,
SJ200 400V models
Applicable motor size *2 kW 0.4 0.75 1.5 2.2
Rated capacity (460V) kVA 1.1 1.9 2.9 4.2
Rated input voltage *6 3-phase: 380 to 480V ±10%, 50/60 Hz ±5%
Integrated EMC filter
Rated input current (A) 2.0 3.3 5.0 7.0
Rated output voltage *3 3-phase: 380 to 480V (proportional to input voltage)
Rated output current (A) 1.5 2.5 3.8 5.5
Efficiency at 100% rated output (%) 93.5 94.0 95.3 95.7
Watt loss, approximate (W)
Starting torque *7 200% or more
Dynamic braking approx. % torque, short time stop *8
EU types 004HFEF2
004HFE2
USA type 004HFU2 007HFU2 015HFU2 022HFU2
HP 1/2 1 2 3
HFEF type Three phase filter, Category C3 *5
HFE, HFU types
at 70% output
at 100% output
without resistor, from 50/60 Hz
with resistor 150% 100%
20 30 45 65
26 42 70 95
007HFEF2
007HFE2
100%: 50Hz
50%: 60Hz
015HFEF2
015HFE2
022HFEF2
022HFE2
70%: 50Hz 20%: 60Hz
DC braking Variable operating frequency, time, and braking force
Weight
HFEF type
HFE type
HFU type
kg 1.4 1.8 1.9 1.9
lb 3.09 3.97 4.19 4.19
kg 1.3 1.7 1.8 1.8
lb 2.87 3.75 3.97 3.97
kg 1.3 1.7 1.8 1.8
lb 2.87 3.75 3.97 3.97
SJ2002 Inverter
1–9
Item 400V Class Specifications, continued
2 inverters,
SJ200 400V models
Applicable motor size *2 kW 3.0 4.0 5.5 7.5
Rated capacity (460V) kVA 6.2 6.6 10.3 12.7
Rated input voltage *6 3-phase: 380 to 480V ±10%, 50/60 Hz ±5%
Integrated EMC filter
Rated input current (A) 10.0 11.0 16.5 20.0
Efficiency at 100% rated output (%) 95.7 95.9 96.6 97.0
Watt loss, approximate (W)
Rated output voltage *3 3-phase: 380 to 480V (proportional to input voltage)
Rated output current (A) 7.8 8.6 13 16
Starting torque *7 180% or more
EU types 030HFEF2
030HFE2
USA type 040HFU2 055HFU2 075HFU2
HP 4 5 7.5 10
HFEF type Three phase filter, Category C3
HFE, HFU types
at 70% output
at 100% output
90 95 135 165
130 150 187 227
040HFEF2
040HFE2
055HFEF2
055HFE2
075HFEF2
075HFE2
Getting Started
Dynamic braking approx. % torque, short time stop *8
DC braking Variable operating frequency, time, and braking force
Weight
without resistor, from 50/60 Hz
with resistor 100% 80%
HFEF type
HFE type
HFU type
kg 1.9 1.9 5.5 5.7
lb 4.19 4.19 12.13 12.57
kg 1.8 1.8 5.4 5.6
lb 3.97 3.97 11.91 12.35
kg 1.8 5.4 5.6
lb 3.97 11.91 12.35
20%: 50Hz 20%: 60Hz
1–10
Inverter Specifications

General Specifications

The following table applies to all SJ2002 inverters.
Item General Specifications
Protective housing *1 IP20
Control method Sinusoidal Pulse Width Modulation (PWM) control
Getting Started
Carrier frequency 2kHz to 14kHz (default setting: 5kHz)
Output frequency range *4 0.5 to 400 Hz
Frequency accuracy Digital command: 0.01% of the maximum frequency
Analog command: 0.1% of the maximum frequency (25°C ± 10°C)
Frequency setting resolution Digital: 0.1 Hz; Analog: max. frequency/1000
Volt./Freq. characteristic V/f optionally variable, V/f control (constant torque, reduced
torque), intelligent sensorless vector control (iSLV)
Overload capacity 150% of rated current for 1 minute
Acceleration/deceleration time 0.01 to 3000 seconds, linear and S-curve accel/decel, second
accel/decel setting available
Input signal
Freq. setting
FWD/ REV Run
Intelligent input terminal
Operator panel Up and Down keys / Value settings
Potentiometer Analog setting
External signal *90 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input
Operator panel Run/Stop (Forward/Reverse run change by command)
External signal Forward run/stop, Reverse run/stop
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
FW (forward run command), RV (reverse run command), CF1~CF4 (multi-stage speed setting), JG (jog command), DB (external braking), SET (set second motor), 2CH (2-stage accel./decel. command), FRS (free run stop command), EXT (external trip), USP (startup function), SFT (soft lock), AT (analog current input select signal), RS (reset), TH (thermistor thermal protection), STA (start), STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID reset), UP (remote control up function), DWN (remote control down function), UDC (remote control data clearing), OPE (operator control), ADD (ADD frequency enable), F-TM (force terminal mode), RDY (quick start enable)
Output signal
Alarm output contact ON for inverter alarm (1C contacts, both normally open or closed
Intelligent output terminal
Frequency monitor PWM output; Select analog output frequency monitor, analog output
RUN (run status signal), FA1,2 (frequency arrival signal), OL (overload advance notice signal), OD (PID error deviation signal), AL (alarm signal), Dc (analog input disconnect detect), FBV (PID two-stage control output), NDc (network detection signal), LOG (logic output), OPDc (option card detection signal)
current monitor or digital output frequency monitor
avail.)