Model-specific tables for 200V and 400V class inverters
The following tables are specific to SJ100 inverters for the 200V and 400V class model
groups. Note that “General Specifications” on page 1–9 apply to both voltage class
groups. Footnotes for all specifications tables follow the table below.
Item200V Class Specifications
SJ100 inverters,
200V models
Applicable motor size *2kW0.20.40.550.751.1
Rated capacity
(kVA) *12
Rated input voltage1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input
current (A)
Rated output voltage *33-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)1.62.63.04.05.0
Efficiency at 100% rated output (%)90.592.893.694.195.4
Watt loss,
approximate (W)
Starting torque *6200% or more
Dynamic braking
approx. %
torque, short
time stop *7
CE version002NFE004NFE005NFE007NFE011NFE
UL version002NFU004NFU—007NFU—
HP1/41/23/411.5
230V0.61.01.11.51.9
240V0.61.01.21.62.0
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, and 075LFU 3phase only)
1-phase3.55.86.79.011.2
3-phase2.03.43.95.26.5
at 70% output1521253138
at 100% output1929324151
without resistor,
from 50 / 60 Hz
with resistor150%
100%: ≤ 50Hz
50%: ≤ 60Hz
70%: ≤ 50Hz
50%: ≤ 60Hz
DC brakingVariable operating frequency, time, and braking force
Weightkg0.70.850.851.31.3
lb1.541.871.872.872.87
SJ100 Inverter Specifications
Footnotes for the preceding table and the tables that follow:
Note 1:The protection method conforms to JEM 1030.
Note 2:The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When
using other motors, care must be taken to prevent the rated motor current (50/
60 Hz) from exceeding the rated output current of the inverter.
Note 3:The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed
the input power supply voltage.
Note 4:To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
Note 5:When SLV is selected, please set the carrier frequency higher than 2.1 kHz.
Note 6:At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor
(when selecting sensorless vector control—SLV).
Note 7:The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not
continuous regenerative braking torque. The average deceleration torque
varies with motor loss. This value decreases when operating beyond 50 Hz. If
a large regenerative torque is required, the optional regenerative braking
resistor should be used.
Note 8:The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic
is not satisfactory for your application, contact your Hitachi sales representative.
Note 9:If operating the inverter at 40 to 50° C, reduce the carrier frequency to 2.1
kHz, derate the output current by 80%, and remove the top housing cover.
Note that removing the top cover will nullify the NEMA rating for the inverter
housing.
Note 10: The storage temperature refers to the short-term temperature during transport.
Note 11: Conforms to the test method specified in JIS C0911 (1984). For the model
types excluded in the standard specifications, contact your Hitachi sales representative.
Note 12: The input voltage of xxLFU is 230V.
SJ100 Inverter Specifications, continued...
Item200V Class Specifications, continued
SJ100 Inverter
SJ100 inverters,
200V models
CE version015NFE022NFE———
UL version015NFU022NFU037LFU055LFU075LFU
Applicable motor size *2kW1.52.23.75.57.5
HP2357.510
Rated capacity
(kVA) *12
230V3.14.36.99.512.7
240V3.04.57.29.913.3
Rated input voltage1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, 075LFU 3-phase only)
Rated input
current (A)
1-phase17.524.0———
3-phase10.014.022.030.040.0
Rated output voltage *33-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)8.011.017.52432
Efficiency at 100% rated output (%)94.795.195.196.196.2
Watt loss,
approximate (W)
at 70% output5778130152204
at 100% output79107181216288
Starting torque *6200% or more180% or more
Dynamic braking
approx. %
torque, short
time stop *7
without resistor,
from 50 / 60 Hz
with resistor150%100%80%
70%: ≤ 50Hz
50%: ≤ 60Hz
20%: ≤ 50Hz
20%: ≤ 60Hz
DC brakingVariable operating frequency, time, and braking force
Weightkg2.22.82.85.55.7
lb4.856.176.1712.1312.57
SJ100 Inverter Specifications
Item400V Class Specifications
SJ100 inverters,
400V models
CE version004HFE007HFE015HFE022HFE
UL version004HFU007HFU015HFU022HFU
Applicable motor size *2kW0.40.751.52.2
HP1/2123
Rated capacity (460V) kVA1.11.92.94.2
Rated input voltage3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A)2.03.35.07.0
Rated output voltage *33-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A)1.52.53.85.5
Efficiency at 100% rated output (%)92.093.795.795.8
Watt loss,
approximate (W)
at 70% output25334868
at 100% output32446592
Starting torque *6200% or more
Dynamic braking
approx. %
torque, short
time stop *7
without resistor,
from 50/60 Hz
with resistor150%100%
100%: ≤ 50Hz
50%: ≤ 60Hz
70%: ≤ 50Hz
20%: ≤ 60Hz
DC brakingVariable operating frequency, time, and braking force
Weightkg1.31.71.71.8
lb2.873.753.753.97