TEST RUNNING
29
15.1. TEST RUN PROCEDURE BY REMOTE CONTROL SWITCH
x
Turn ON the power source of the Units
y
Procedure for TEST RUN mode of remote control switch.
Depress the MODE and the CHECK switches together for more than 3
seconds.
a If TEST RUN and the counting number of the connected units to the
remote control switch (for example ) are indicated on the remote
control switch, the connection of remote control cable is correct. → Go
to {
b. If no indication appears or the number of the units indicated is smaller
than the actual number of the units, some abnormalities exist. → Go to
z
Remote Control
Switch Indication
Wrong Portions
Inspection Points after
the Power Source OFF
The power source of Outdoor Unit is not turned ON.
The connection of the remote control cable is
incorrect.
1. Connecting Points of Remote Control Cable
Terminal Board of Remote Control Switch and
Indoor Unit
2. Contact of Terminals of Remote Control Cable
No indication
The connecting wires of power supply line are
incorrect or loosened
3. Connection Order of each Terminal Board
4. Screw Fastening of each Terminal Boards.
Counting number of
connected units is
incorrect
The power source of outdoor unit is not turned ON
The operating line wiring between indoor unit and
outdoor unit is not connected.
The connection of control cables between each
indoor units are incorrect. (When one remote control
switch controls multiple units)
5. Dip Switch Setting on Printed Circuit Board
6. Connection on the PCB
7. This is the same as item z 1, 2, and 3
z
Back to x after checking
{
Select TEST RUNNING MODE by depressing MODE Switch (COOL OR HEAT)
|
Depress RUN/STOP switch.
a The TEST RUN operation will be started. (The 2 hours OFF-TIMER will be set and the TEST RUN operation will be finished after
2 hours unit operation or by depressing the RUN/STOP switch again).
NOTE:
TEST RUN operation ignores the temperature limitation and ambient temperature during heating operation to have a
continuous operation, but the protections are alive. Therefore, the protection may activate when the heating TEST RUN
operation is performed in high ambient temperature.
TEST RUN operation time can be modifyed / increased depressing the time switch in the Remote Control.
b If the unit do not start or the operation lamp on the remote control switch is flickered, some abnormalities exist. →Go to }
Remote Control
Switch Indication
Unit Condition
Wrong Portions
Inspection Points after
Power Source OFF
The operation lamp
flickers. (1 time/1
sec.) And the Unit
No. and Alarm Code
03 flicker
The unit does not
start.
The power source of Outdoor Unit
in not turned ON.
The connecting wires of operating
line are incorrect or loosened.
1. Connecting Order of each Terminal Boards.
2. Screw fastening of each Terminal Boards.
NOTE:
Recovering method of FUSE for operating
circuit. There is a fuse (FUSE4 on Indoor
Unit PCB1, EF1 on Outdoor Unit PCB1) to
protect operating circuit on the PCB, when
the power lines are connected to operating
lines. If fuse is melted, operating circuit can
be recovered once by setting the dip switch
on the PCB as shown in ~
The operation lamp
flickers. (1 time/2 s)
The unit does not
start.
Remote control cable is broken.
Contact of connectors is not good.
The connection of remote control
cable is incorrect
This is the same as item z 1, 2
Indication of Flicker
except above
The unit does not
start, or start once
and then stops
The connection of thermistor or
other connectors are incorrect.
Tripping of protector exists, or else.
Check by the abnormality mode table in the
Technical Catalogue (Do it by service people).
The operation lamp
Flickers. (1 Time/1s)
Unit No. , Alarm
Code )) and Unit
Code flicker
The unit does not
start.
The connection of the remote
control cable between Indoor Units
is incorrect.
Check by the abnormality mode table in the
Technical Catalog (Do it by service people).
}
Back to x after checking
Except RPK
Only RPK-FSNM
~
Instructions fot the recovery when the fuse of the transmission circuit is blown out:
1. Correct the wiring to the terminal board.
2. Set the 1
st
pin of DSW7 on the indoor unit PCB to ON
Set the 2
nd
pin of DSW7 on the indoor unit PCB to ON. (Only RPK-FSNM)
ON
1 2
ON
1 2
Operation Lamp
)
(
Counting
Number of
Connected
Units