Hitachi RAS-60YH5, RAC-60YH5 Service Manual

Page 1
NO. 0299E
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
ROOM AIR CONDITIONER
INDOOR UNIT + OUTDOOR UNIT
DECEMBER 2005
Refrigeration & Air-Conditioning Division
SERVICE MANUAL
REFER TO THE FOUNDATION MANUAL
TECHNICAL INFORMATION
FOR SERVICE PERSONNEL ONLY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
RAS-60YH5 RAC-60YH5
DC INVERTER (WALL TYPE)
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
DIMENSIONS (mm)
NET WEIGHT
SPECIFICATIONS
1,030
295
191
12
RAS-60YH5
CONTENTS
SPECIFICATIONS ------------------------------------------------------------------- 4
HOW TO USE ------------------------------------------------------------------------ 6
CONSTRUCTION AND DIMENSIONAL DIAGRAM --------------------- 28
MAIN PARTS COMPONENT --------------------------------------------------- 30
WIRING DIAGRAM ---------------------------------------------------------------- 33
CIRCUIT DIAGRAM --------------------------------------------------------------- 35
PRINTED WIRING BOARD LOCATION DIAGRAM --------------------- 41
BLOCK DIAGRAM ----------------------------------------------------------------- 43
BASIC MODE ----------------------------------------------------------------------- 45
REFRIGERATING CYCLE DIAGRAM --------------------------------------- 59
AUTO SWING FUNCTION ------------------------------------------------------ 60
DESCRIPTION OF MAIN CIRCUIT OPERATION ----------------------- 61
SERVICE CALL Q & A ---------------------------------------------------------- 92
TROUBLE SHOOTING ----------------------------------------------------------- 95
PARTS LIST AND DIAGRAM ------------------------------------------------- 115
RAS-60YH5/RAC-60YH5
RAC-60YH5
COOLING
HEATING
INDOOR UNIT
OUTDOOR UNIT
2,300
10.60 – 9.70
6.05 (0.90 – 6.50)
20,660
2,400
11.0 – 10.10
7.05
24,060
After installation
1 PHASE, 50 Hz, 220 – 240V
850
650
298
45
Page 2
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair the unit in question, be sure to disconnect the power cord plug from the power outlet before starting the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and the replacement must be effected in correct manner according to the instructions in the Service Manual of the unit.
If the contacts of electrical parts are defective, replace the electrical parts without trying to repair them.
3. After completion of repairs, the initial state should be restored.
4. Lead wires should be connected and laid as in the initial state.
5. Modification of the unit by user himself should absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe enough to support the repaired unit again. If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new location.
10. Any inflammable thing should never be placed about the location of installation.
11. Check the grounding to see whether it is proper or not, and if it is found improper, connect the grounding terminal to the earth.
DANGER
First, I must disconnect the power cord plug
from the power outlet.
– i –
Page 3
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope The standards provide for items to be generally observed in carrying and handling semiconductors in relative manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods such as rejected goods being returned).
2. Object parts
(1) Micro computer (2) Integrated circuits (IC) (3) Field-effect transistors (FET) (4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
1M
Fig. 2. Body Earth
Body earth (Elimik conductive band)
Clip for connection with a grounding wire
IC
A conductive polyvinyl bag
IC
Conductive sponge
– 1 –
Page 4
(6) Use a three wire type soldering iron including a grounding wire.
Bare copper wire (for body earth)
Working table
Resistor of 1 M (1/2W)
Earth wire
Fig. 3. Grounding of the working table
2
Screw stop at the screwed part using a rag plate
Soldering iron
Grounding wire
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Metal plate (of aluminium, stainless steel, etc.)
Staple
– 2 –
Page 5
1. In quiet or stopping operation, slight flowing noise of refrigerant in the refrigerating cycle is heard occasionally,
but this noise is not abnormal for the operation.
2. When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3. In the event of power failure, the air conditioner will restart automatically in the previously selected mode
once the power is restored. In the event of power failure during TIMER operation, the timer will be reset and the unit will begin or stop operating under a new timer setting.
4. If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5. This room air conditioner should not be used at the cooling operation when the outside temperature is
below –10°C (14°F).
6. This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–15°C (5°F). If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7. When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
!
CAUTION
– 3 –
Page 6
SPECIFICATIONS
MODEL
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
RAS-60YH5
PWM DC35V
NO
NO
NO
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
YES(IC)
YES
----------
40 W
NO
NO
NO
YES (INTERNAL)
YES
3.0A
G4A
NO
NO
YES
NO
450NR
YES
YES(IC)
NO
1420g
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
UNIT
PIPES (MAX. 30m)
REFRIGERANT CHARGING VOLUME (Refrigerant R410A)
RAC-60YH5
JU1013D5
– 4 –
Chargeless upto 20m, above 20m upto max 30m, charge refrigerant R410A 5 g/m.
Page 7
– 5 –
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2,300mm or more
Maximum pipe length 30m
Minimum pipe length 5m
above 200mm
above 700mm
above 200mm
above 50mm when installed on the ceiling of balcony
(
)
above 100mm
above 100mm
give clearance as wide as possible
Plug
The difference in height
between the indoor and outdoor unit should be kept max 10m.
The connecting pipe, no
matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commersial products).
Be sure to completely seal any gap with putty.
CAUTION
The installation height of indoor unit must be 2.3m or more.
!
Figure showing the installation of Indoor and Outdoor unit
Page 8
– 6 –
!
SAFETY PRECAUTION
Please read the “Safety Precaution” carefully before operating the unit to ensure correct usage of the unit.
Pay special attention to signs of “ Warning” and “ Caution”. The “Warning” section contains matters which, if not observed strictly, may cause death or serious injury. The “Caution” section contains matters which may result in serious consequences if not observed properly. Please observe all instructions strictly to ensure safety.
The sign indicate the following meanings.
Please keep this manual after reading.
WARNING
PRECAUTIONS DURING INSTALLATION
Do not reconstruct the unit. Water leakage, fault, short circuit or fire may occur if you reconstruct the unit by yourself.
Please ask your sales agent or qualified technician for the installation of your unit. Water leakage, short circuit or fire may occur if you install the unit by yourself.
Please use earth line. Do not place the earth line near water or gas pipes, lightning-conductor, or
the earth line of telephone. Improper installation of earth line may cause electric shock.
A circuit breaker should be installed depending on the mounting site of the unit. Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
CAUTION
!
!
PRECAUTIONS DURING SHIFTING OR MAINTENANCE
Should abnormal situation arises (like burning smell), please stop operating the unit and turn off the circuit breaker. Contact your agent. Fault, short circuit or fire may occur if you continue to operate the unit under abnormal situation.
Please contact your agent for maintenance. Improper self maintenance may cause electric shock and fire.
Please contact your agent if you need to remove and reinstall the unit. Electric shock or fire may occur if you remove and reinstall the unit yourself improperly.
!
Make sure to connect earth line.
Indicates the instructions that must be followed.
The sign in the figure indicates prohibition.
W
A R N
I N G
!
PRECAUTIONS DURING OPERATION
Avoid an extended period of direct air flow for your health.
W
A R N
I
N G
Do not insert a finger, a rod or other objects into the air outlet or inlet. As the fan is rotating at a high speed, it will cause injury. Before cleaning, be sure to stop the operation and turn the breaker OFF.
During thunder storm, disconnect and turn off the circuit breaker.
Do not use any conductor as fuse wire, this could cause fatal accident.
Page 9
– 7 –
PRECAUTIONS DURING OPERATION
Do not attempt to operate the unit with wet hands, this could cause fatal accident.
When operating the unit with burning equipments, regularly ventilate the room to avoid oxygen insufficiency.
Do not direct the cool air coming out from the air-conditioner panel to face household heating apparatus as this may affect the working of apparatus such as the electric kettle, oven etc.
Do not use any aerosol or hair sprays near the indoor unit. This chemical can adhere on heat exchanger fin and blocked the evaporation water flow to drain pan. The water will drop on tangential fan and cause water splashing out from indoor unit.
Please ensure that outdoor mounting frame is always stable, firm and without defect. If not, the outdoor unit may collapse and cause danger.
Do not splash or direct water to the body of the unit when cleaning it as this may cause short circuit.
When operating the unit with the door and windows opened, (the room humidity is always above 80%) and with the air deflector facing down or moving automatically for a long period of time, water will condense on the air deflector and drips down occasionally. This will wet your furniture. Therefore, do not operate under such condition for a long time.
If the amount of heat in the room is above the cooling or heating capability of the unit (for example: more people entering the room, using heating equipments and etc.), the preset room temperature cannot be achieved.
This appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely.
Young children should be supervised to ensure that they do not play with the appliance.
Do not climb on the outdoor unit or put objects on it.
Please switch off the unit and turn off the circuit breaker during cleaning, the high-speed fan inside the unit may cause danger.
Turn off the circuit breaker if the unit is not to be operated for a long period.
C A U T
I O N
!
The product shall be operated under the manufacturer specification and not for any other intended use.
Do not put water container (like vase) on the indoor unit to avoid water dripping into the unit. Dripping water will damage the insulator inside the unit and causes short-circuit.
Do not place plants directly under the air flow as it is bad for the plants.
Page 10
– 8 –
INDOOR UNIT
NAMES AND FUNCTIONS OF EACH PART
Air filter
To prevent dust from coming into the indoor unit. (Refer page 25)
Front panel
Indoor unit indicators
Light indicator showing the operating condition. (Refer page 9)
Horizontal deflector
Vertical deflector
(Air Outlet)
(Refer page 20)
Remote controller
Send out operation signal to the indoor unit. So as to operate the whole unit. (Refer page 10)
Drain pipe
Condensed water drain to outside.
Connecting cord and insulation pipe for piping
Air inlet (Back and Left side)
Air outlet
WIDTH (mm)
1030
850
MODEL
RAS-60YH5
RAC-60YH5
HEIGHT (mm)
295
650
DEPTH (mm)
191
298
MODEL NAME AND DIMENSIONS
OUTDOOR UNIT
CAUTION
• When heating operation, drain or defrosted water flows out from outdoor unit. Don’t close drain outlet portion
in chilly area so as not to freeze these.
!
Page 11
– 9 –
INDOOR UNIT INDICATORS
TEMPORARY SWITCH
Use this switch to start and stop when the remote controller does not work.
By pressing the temporary switch, the operation is done in automatic mode.
OPERATION INDICATOR
This figure shows the opening condition of
front panel. Refer to page 20 in relation to how to open or close the front panel.
FILTER LAMP
When the device is operated for a total of about 200 hours, the FILTER lamp lights to indicate that it is time to clean the filter. The lamp goes out when the “ (AUTO SWING)” button is pressed while the device is on “STANDBY MODE”.
OPERATION LAMP
This lamp lights during operation. The OPERATION LAMP flashes in the following cases during heating.
(1) During preheating
For about 2–3 minutes after starting up.
(2) During defrosting
Defrosting will be performed about once an hour when frost forms on the heat exchanger of the outdoor unit, for 5–10 minutes each time.
TIMER LAMP
This lamp lights when the timer is working.
HITACHI
TEMPORARY
SWITCH
TEMPORARY
SWITCH
Page 12
– 10 –
AUTO
HEAT
DEHUMIDIFY
COOL
FAN
FAN SPEED LOW MED HI
SLEEPING
STOP (CANCEL)
START (RESERVE)
START/STOP
TIME
TIMER SET
TIMER SELECTOR ON TIMER OFF TIMER
AUTO SWING
˚
CH
RESET
˚
CH
NAMES AND FUNCTIONS OF REMOTE CONTROL UNIT
REMOTE CONTROLLER
This controls the operation of the indoor unit. The range of control is about 7 meters. If indoor lighting is controlled
electronically, the range of control may be shorter. This unit can be fixed on a wall using the fixture provided. Before fixing it, make sure the indoor unit can be controlled from the remote controller.
Handle the remote controller with care. Dropping it or getting it wet may compromise its signal transmission capability.
After new batteries are inserted into the remote controller, the unit will initially require approximately 10 seconds to
respond to commands and operate.
Signal emitting window/transmission sign
Point this window toward the indoor unit when controlling it. The transmission sign blinks when a signal is sent.
Display
This indicates the room temperature selected, current time, timer status, function and intensity of circulation selected.
START/STOP button
Press this button to start operation. Press it again to stop operation.
SLEEP button
Use this button to set the sleep timer.
TEMPERATURE buttons
Use these buttons to raise or lower the temperature setting. (Keep pressed, and the value will change more quickly.)
TIME button
Use this button to set and check the time and date.
RESET buttons
FUNCTION selector
Use this button to select the operating mode. Every time you press it, the mode will change from (AUTO) to (HEAT) to (DEHUMIDIFY) to
(COOL) and to (FAN) cyclically.
FAN SPEED selector
This determines the fan speed. Every time you press this button, the intensity of circulation will change from (AUTO) to (HI) to (MED) to (LOW) (This button allows selecting the optimal or preferred fan speed for each operation mode).
AUTO SWING button
Controls the angle of the horizontal air deflector.
TIMER control
Use this button to set the timer.
OFF-TIMER button Select the turn OFF time.
ON-TIMER button Select the turn ON time.
RESERVE button Time setting reservation.
CANCEL button Cancel time reservation.
Precautions for Use
Do not put the remote controller in the following places.
Under direct sunlight.
In the vicinity of a heater.
Handle the remote controller carefully. Do not drop it on the floor,
and protect it from water.
Once the outdoor unit stops, it will not restart for about 3 minutes
(unless you turn the power switch off and on or unplug the power cord and plug it in again).
This is to protect the device and does not indicate a failure.
If you press the FUNCTION selector button during operation, the
device may stop for about 3 minutes for protection.
Page 13
11
AUTOMATIC OPERATION
The device will automatically determine the mode of operation, HEAT, COOL or DEHUMIDIFY depending on the current room temperature. The selected mode of operation will change when the room temperature varies.
As the settings are stored in memory in the remote controller, you only have to
press the (START/STOP) button next time.
Press the FUNCTION selector so that the display indicates the (AUTO) mode of operation.
When AUTO has been selected, the device will automatically determine the
mode of operation, HEAT, COOL or DEHUMIDIFY depending on the current room temperature.
If the mode automatically selected by the unit is not satisfactory, manually
change the mode setting (heat, dehumidify, cool or fan).
Press the (START/STOP) button. Operation starts with a beep. Press the button again to stop operation.
You can raise or lower the temperature setting as necessary by maximum of 3°C.
Press the temperature button and the temperature setting will change by 1°C each time.
The preset temperature and the actual room temperature may vary somewhat
depending on conditions.
The display does not indicate the preset temperature in the AUTO mode. If you
change the setting, the indoor unit will produce a beep.
1
°C
RESET
Press the (FAN SPEED) button, AUTO and LOW is available.
VARIOUS FUNCTIONS
Auto Restart Control
If there is a power failure, operation will be automatically restarted when the power is resumed with previous
operation mode and airflow direction. (As the operation is not stopped by remote controller.)
If you intend not to continue the operation when the power is resumed, switch off the power supply.
When you switch on the circuit breaker, the operation will be automatically restarted with previous operation mode and airflow direction. Note: 1. If you do not require Auto Restart Control, please consult your sales agent or OFF by remote
control.
2. Auto Restart Control is not available when Timer or Sleep Timer mode is set.
START
STOP
Page 14
12
HEATING OPERATION
Use the device for heating when the outdoor temperature is under 21°C.
When it is too warm (over 21°C), the heating function may not work in order to protect the device.
In order to keep reliability of the device, please use this device above –15°C of the outdoor temperature.
Press the FUNCTION selector so that the display indicates (HEAT).
Set the desired FAN SPEED with the (FAN SPEED) button (the display indicates the setting).
(AUTO): The fan speed is HI at first and varies to
MED or LOW automatically when the preset temperature has been reached.
(HI) : Economical as the room will become warm
quickly. But you may feel a chill at the beginning.
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
Set the desired room temperature with the TEMPERATURE buttons (the display indicates the setting).
The temperature setting and the actual room temperature may vary somewhat depending on conditions.
Press the (START/STOP) button. Heating operation starts with a beep. Press the button again to stop operation.
As the settings are stored in memory in the remote controller, you only have to press the (START/STOP) button next time.
1
2
3
START
STOP
˚
C
RESET
˚
C
Page 15
13
DEHUMIDIFYING OPERATION
Use the device for dehumidifying when the room temperature is over 16°C. When it is under 15°C, the dehumidifying function will not work.
Dehumidifying Function
When the room temperature is higher than the temperature setting: The device will dehumidify the room, reducing the room temperature to the preset level. When the room temperature is lower than the temperature setting: Dehumidifying will be performed at the temperature setting slightly lower than the current room temperature, regardless of the temperature setting. The function will stop (the indoor unit will stop emitting air) as soon as the room temperature becomes lower than the setting temperature.
Set the desired room temperature with the TEMPERATURE button (the display indicates the setting).
The range of 20-26˚C is recommended as the room temperature for dehumidifying.
Press the (START/STOP) button. Dehumidifying operation starts with a beep. Press the button again to stop operation.
2
As the settings are stored in memory in the remote controller, you
only have to press the
(START/STOP) button next time.
START
STOP
Press the FUNCTION selector so that the display indicates
(DEHUMIDIFY). The FAN SPEED is set at LOW automatically. The FAN SPEED button does not work.
1
RESET
˚
C
˚
C
Page 16
14
˚
C
RESET
˚
C
COOLING OPERATION
Use the device for cooling when the outdoor temperature is –10~43°C. If in doors humidity is very high (80%), some dew may form on the air outlet grille of the indoor unit.
Press the FUNCTION selector so that the display indicates (COOL).
Set the desired FAN SPEED with the
(FAN SPEED) button
(the display indicates the setting).
(AUTO): The FAN SPEED is HI at first and varies to
MED or LOW automatically when the preset temperature has been reached.
(HI) : Economical as the room will become cool
quickly.
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
Set the desired room temperature with the TEMPERATURE button (the display indicates the setting).
The temperature setting and the actual room temperature may vary some how depending on conditions.
Press the
(START/STOP) button. Cooling operation starts with a beep. Press the button again to stop operation. The cooling function does not start if the temperature setting is
higher than the current room temperature (even though the (OPERATION) lamp lights). The cooling function will start as soon as you set the temperature below the current room temperature.
As the settings are stored in memory in the remote controller, you
only have to press the
(START/STOP) button next time.
1
2
START
STOP
3
Page 17
15
FAN SPEED (AUTO)
.....
When the AUTO fan speed mode is set in the cooling/heating operation:
For the heating operation
The fan speed will automatically change according to the temperature
of discharged air.
When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
When the room temperature reaches setting temperature, fan speed
changes to LOW automatically.
When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
After room temperature reaches the preset temperature, the cooling
operation, which changes the fan speed and room temperature to obtain optimum conditions for natural healthful cooling will be performed.
For the cooling operation
FAN OPERATION
You can use the device simply as an air circulator. Use this function to dry the interior of the indoor unit at the end of summer.
Press the FUNCTION selector so that the display indicates (FAN).
Press the (FAN SPEED) button.
Press the (START/STOP) button. Fan operation starts with a beep. Press the button again to stop operation.
1 2
START
STOP
RESET
Page 18
16
HOW TO SET THE TIMER
ON/OFF-Timer
The device will turn on (off) and off (on) at the designated times.
The switching occurs first at the preset time that comes earlier.
The arrow mark appearing on the display indicates the sequence of switching operations.
1
Press the (ON-OFF)
button so that the (OFF) mark blinks.
OFF-Timer
You can set the device to turn off at the present time.
After you change the batteries;
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL) button. The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
1
Set the current month and
day with the TIMER control button.
1
Press the (OFF-TIMER)
button. The (OFF) mark blinks on the display.
1
Press the (ON-TIMER)
button the (ON) mark blinks on the display.
2
Set the turn-off time
with the TIMER control button. Press the (RESERVE) button.
3
Press the (ON-
TIMER) button so that the (OFF) mark lights and the (ON) mark blinks.
NOTE
You can set only one of the OFF-timer, ON-timer and ON/OFF-timer.
ON-Timer
Time, Day, Month
The device will turn on
at the designated times.
TIME, DAY, MONTH (current time, day, month)
OFF TIMER
ON TIMER
RESERVE
CANCEL
M D
M D
AM
STOP
Start
AM
Start
Stop
PM
Start Stop
PM
AM
PM
RESET
Page 19
17
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (OFF) mark starts lighting instead of flashing and the sign (RESERVED) lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
The time indication will disappear
automatically in 10 second.
To check the current time setting,
press the (TIME) button twice.
The setting of the current time is now complete.
The timer may be used in three ways: off-timer, on-timer, and ON/OFF (OFF/ON)-timer. Set
the current time at first because it serves as a reference.
As the time settings are stored in memory in the remote controller, you only have to press
the (RESERVE) button in order to use the same settings next time.
2
Press the
(TIME) button.
3
Set the current time with the
TIMER control button.
Example: The current time is 1:30 p.m.
2
Set the turn-off time with the
TIMER control button.
The setting of turn-off time is now complete.
Example: The device will turn off at 11:00p.m.
Example: The device will turn on at 7:00 a.m. The setting of the turn-on time is now complete.
4
Set the turn-on time with the
TIMER control button.
5
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (ON) mark starts lighting instead of flashing and the (RESERVED) sign lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (ON) mark starts lighting instead of flashing and the (RESERVED) sign lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
2
Set the turn-on time with the
TIMER control button.
Example: The device will turn off at 10:30 p.m. and it will be turn on at 7:00 a.m. The settings of the turn-on/off times are now complete.
4
Press the (TIME) button again.
The time indication starts lighting instead of flashing.
PM PM
AM
PM
PM
PM
AM
AM
AM
AM
PM
PM
Page 20
18
HOW TO SET THE SLEEP TIMER
1
Set the ON-timer.
Set the current time at first if it is not set before (see the pages for setting the current time). Press the (SLEEP) button, and the display changes as shown below.
Mode
Sleep timer
Indication
1 hour 2 hours 3 hours 7 hours
Sleep timer off
44 44
1
Sleep Timer: The device will continue working for the designated number of hours and then turn off. Point the signal window of the remote controller toward the indoor unit, and press the SLEEP button. The timer information will be displayed on the remote controller. The TIMER lamp lights with a beep from the indoor unit. When the sleep timer has been set, the display indicates the turn-off time.
Example: If you set 3 hours sleep time at 11:38 p.m., the turn-off time is 2:38 a.m.
2
Press the (SLEEP) button and set the sleep timer.
The device will be turned off by the sleep timer and turned on by on-timer.
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL) button. The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
For heating:
In this case, the device will turn off in 2 hours (at 1:38 a.m.) and turn on early so that the preset temperature will be almost reached at 6:00 next morning.
SLEEP
H
H
AM
AM
Sleep
timer
Start
H
If date or current time is not set, sleep timer can not be set.
If you set the sleep timer after the off-, on/off- or off/on-timer has been set, the sleep timer becomes
effective instead of the off-, on/off- or off/on-timer set earlier.
You can not set other timer during sleep timer operation.
After sleep timer time is up and when press sleep button again, the sleep timer will be set as last setting.
Sleep timer effective only once.
NOTE
Page 21
– 19 –
ADJUSTING THE AIR DEFLECTOR
1
2
Adjustment of the conditioned air to the left and right.
Hold the vertical air deflector as shown in the figure and adjust the conditioned air to the left and right.
If the “ (AUTO SWING)” button is pressed once,
the horizontal air deflector swings up and down. If the button is pressed again, the deflector stops in its current position. Several seconds (about 6 seconds) may be required before the deflector starts to move.
Use the horizontal air deflector within the adjusting range
shown on the right.
When the operation is stopped, the horizontal air deflector
moves and stops at the position where the air outlet closes.
When cooling dehumidifying
When heating
!
CAUTION
In Cooling operation, do not keep the horizontal air
deflector swinging for a long time. Some dew may form on the horizontal air deflector and dew may drop.
RESET
Adjustment of the conditioned air in the upward and downward directions.
The horizontal air deflector is automatically set to the proper angle suitable for each operation. The deflector can be swung up and down continuously and also set to the desired angle using the (AUTO SWING) button.
Page 22
20
HOW TO EXCHANGE THE BATTERIES IN THE REMOTE CONTROLLER
1
Remove the cover as shown in the figure and take out the old batteries.
=
2
Install the new batteries. The direction of the batteries should match the marks in the case.
1. Do not use new and old batteries, or different kinds of batteries together.
2. Take out the batteries when you do not use the remote controller for 2 or 3 months.
CAUTION
!
Push and pull to the direction of arrow
Page 23
21
Suitable Room Temperature Install curtain or blinds
Ventilation Effective Usage Of Timer
Do Not Forget To Clean The Air Filter
Please Adjust Suitable Temperature
For Baby And Children
Warning
Freezing temperature is bad for health and a waste of electric power.
!
It is possible to reduce heat entering the room through windows.
At night, please use the OFF or ON timer operation mode, together with your wake up time in the morning. This will enable you to enjoy a comfortable room temperature. Please use the timer effectively.
Dusty air filter will reduce the air volume and the cooling efficiency. To prevent from wasting electric energy, please clean the filter every 2 weeks.
Please pay attention to the room temperature and air flow direction when operating the unit for baby, children and old folks who have difficulty in movement.
Caution
Do not close the room for a long period of time. Occasionally open the door and windows to allow the entrance of fresh air.
!
THE IDEAL WAYS OF OPERATION
Page 24
22
FOR USER’S INFORMATION
The Air Conditioner And The Heat Source In The Room
Not Operating For A Long Time
When Lightning Occurs
Caution
If the amount of heat in the room is above the cooling capability of the air conditioner (for example: more people entering the room, using heating equipments and etc.), the preset room temperature cannot be achieved.
!
When the indoor unit is not to be used for a long period of time, please switch off the power from the mains. If the power from mains remains “ON”, the indoor unit still consumes about 8W in the operation control circuit even if it is in “OFF” mode.
Warning
To protect the whole unit during lightning, please stop operating the unit and remove the plug from the socket.
!
OFF
Interference From Electrical Products
Caution
To avoid noise interference, please place the indoor unit and its remote controller at least 1m away from electrical products.
!
Inverter-type fluorescent lamp.
To prevent interference, place at least 1m away.
TV
Page 25
23
ATTACHING THE AIR CLEANSING AND DEODORIZING FILTERS
1
Open the front panel.
Pull up the front panel by holding it at both sides
with both hands.
2
Remove the filter.
Push upward to release the claws and pull out the
filter.
3
4
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
CAUTION
!
!
CAUTION
NOTE
Claws
(4 places)
Attaching the air cleansing and deodorizing filters to the filter.
Attach the air cleansing and deodorizing filters to
the frame by gently compress its both sides and release after insertion into filter frame.
Attach the filters.
Attach the filters by ensuring that the surface written
FRONT is facing front.
After attaching the filters, push the front panel at
three arrow portion as shown in figure and close it.
Do not bend the air cleansing and deodorizing filter as it may cause damage to the structure.
In case of removing the air cleansing and deodorizing filters, please follow the above procedures.
The cooling capacity is slightly weakened and the cooling speed becomes slower when the air cleansing
and deodorizing filters are used. So, set the fan speed to "HIGH" when using it in this condition.
Air cleansing and deodorizing filters are washable and reusable up to 20 times by using vacuum
cleaner or water rinse under running tap water. Type number for this air cleansing filter is <SPX-CFH5>. Please use this number for ordering when you want to renew it.
Do not operate the air conditioner without filter. Dust may enter the air conditioner and fault may occur.
Page 26
24
MAINTENANCE
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
1. AIR FILTER
Clean the air filter, as it removes dust inside the room. In case the air filter is full of dust, the air flow will decrease and the cooling capacity will be reduced. Further, noise may occur. Be sure to clean the filter following the procedure below.
!
CAUTION
1
2
3
!
CAUTION
PROCEDURE
Open the front panel and remove the filter
Gently lift and remove the air cleansing and
deodorizing filter from the air filter frame.
Vacuum dust from the air filter and air cleansing and deodorizing filter using vacuum cleaner. If there is too much dust, rinse under running tap water and gently brush it with soft bristle brush. Allow filters to dry in shade.
Re-insert the air cleansing and deodorizing
filter to the filter frame. Set the filter with FRONT mark facing front, and slot them into the original state.
After attaching the filters, push the front panel
at three arrow portions as shown in figure and close it.
Do not wash with hot water at more than 40°C. The filter may shrink.
When washing it, shake off moisture completely and dry it in the shade; do not expose it directly to
the sun. The filter may shrink.
Do not use detergent on the air cleansing and deodorizing filter as some detergent may deteriorate
the filter electrostatic performance.
NOTE:
Air cleansing and deodorizing filter should be cleaned every month or sooner if noticeable loading
occurs. When used overtime, it may loose its deodorizing function. For maximum performance, it is recommended to replace it every 3-6 months depending on application requirements.
Page 27
25
2. Washable Front Panel
Remove the front panel and wash with clean
water. Wash it with a soft sponge. After using neutral detergent, wash thoroughly with clean water.
When front panel is not removed, wipe it with
a soft dry cloth. Wipe the remote controller thoroughly with a soft dry cloth.
Wipe the water thoroughly.
If water remains at indicators or signal receiver of indoor unit, it causes trouble.
Method of removing the front panel. Be sure to hold the front panel with both hands to detach and attach it.
!
CAUTION
Do not splash or direct water to the body of the unit when cleaning
it as this may cause short circuit.
Never use hot water (above 40°C), benzine, gasoline, acid, thinner or
a brush, because they will damage the plastic surface and the coating.
Removing the Front Panel
Arm
When the front panel is fully opened with
both hands, push the right arm to the inside to release it, and while closing the front panel slightly, put it out forward.
Attaching the Front Panel
Move the projections of the left and right
arms into the Flanges in the unit and securely insert them into the holes.
Projection
Hole
Flange
Page 28
26
3. MAINTENANCE AT BEGINNING OF LONG OFF PERIOD
Run the unit by setting the operation mode to
(COOL), the temperature to 32°C and the fan speed to HI for about half a day on a fine day, and dry the whole of the unit.
Switch off the power plug.
1
2
3
REGULAR INSPECTION
PLEASE CHECK THE FOLLOWING POINTS BY QUALIFIED SERVICE PERSONAL EITHER EVERY HALF YEARLY OR YEARLY. CONTACT YOUR SALES AGENT OR SERVICE SHOP.
Is the earth line disconnected or broken?
Is the mounting frame seriously affected by rust and is the outdoor unit tilted or unstable?
Is the plug of power line firmly plugged into the socket? (Please ensure no loose contact between them).
Air
Blow
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
!
CAUTION
Confirm
Page 29
27
AFTER SALE SERVICE AND WARRANTY
WHEN ASKING FOR SERVICE, CHECK THE FOLLOWING POINTS.
When it does not operate
Is the fuse all right?
Is the voltage extremely high or low?
Is the circuit breaker ON?
Was the air filter cleaned?
Does sunlight fall directly on the outdoor unit?
Is the air flow of the outdoor unit obstructed?
Are the doors or windows opened, or is there any source of
heat in the room?
Is the set temperature suitable?
CONDITION CHECK THE FOLLOWING POINTS
Notes
In quiet operation or stopping the operation, the following phenomena
may occassionally occur, but they are not abnormal for the operation. (1) Slight flowing noise of refrigerant in the refrigerating cycle. (2) Slight rubbing noise from the fan casing which is cooled and then
gradually warmed as operation stops.
The odor will possibly be emitted from the room air conditioner because
the various odor, emitted by smoke, foodstuffs, cosmetics and so on, sticks to it. So the air filter and the evaporator regularly must be cleaned to reduce the odor.
Please contact your sales agent immediately if the air conditioner still fails to operate normally after the above inspections. Inform your agent of the model of your unit, production number, date of installation. Please also inform him regarding the fault.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
When it does not cool well When it does not hot well
Please note: On switching on the equipment, particularly when the room light is dimmed, a slight brightness fluctuation
may occur. This is of no consequence.
The conditions of the local Power Supply Companies are to be observed.
Minimum Maximum Minimum Maximum
Indoor
Dry bulb °C21 32 20 27
Wet bulb °C15 23 12 19
Outdoor
Dry bulb °C21 43 2 21
Wet bulb °C15 26 1 15
Note
Avoid to use the room air conditioner for cooling operation when the outside temperature is below
21°C (70°F). The recommended maximum and minimum operating temperatures of the hot and cold sides should be as below:
Cooling Heating
Page 30
– 28 –
CONSTRUCTION AND DIMENSIONAL DIAGRAM
1019
1030
Top air suction grille
47
47
28
147
380
About
About
350
31 120.5
56 17.5
60 60
7070158
263 317450
Drain outlet
Connecting cable
Power cord
Hole on the wall for ¿ 65mm pipe
Drain cap connection port
Narrow pipe
Wide pipe
Drain
Drain hose
View from back
(Pipe lead-out)
When piping is drawn horizontally, exchange the drain hose for the drain cap
191
6.5
60
47
6.5
60
Front cover
47
295
Vertical deflector
P
Horizontal deflector
Discharge grille
Page 31
29
CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR
Handle
Air suction
grille
10464
26 850
955
79
650
96
169.5
638
1010
10
320
340
Air outlet
340
2022 298
201
Handle
Holes for anchor bolt
(2-ø12)
Fixing hole
507 198
57
12 37
Notch for anchor bolt
(2-ø12 Notchs)
More than
More than
More than
100
More than
700
100
100
Service space
Page 32
30
MAIN PARTS COMPONENT
THERMOSTAT
Thermostat Specifications
FAN MOTOR
Fan Motor Specifications
CONNECTION
TEMPERATURE °C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
MODEL RAS-60YH5/RAC-60YH5
THERMOSTAT MODEL IC
OPERATION MODE COOL HEAT
ON 15.6 (60.1) 20.0 (68.0)
OFF 15.3 (59.5) 20.7 (69.3)
ON 23.6 (74.5) 28.0 (82.4)
OFF 23.3 (73.9) 28.7 83.7)
ON 31.6 (88.9) 36.0 (96.8)
OFF 31.3 (88.3) 36.7 (98.1)
M
RED
BLK
WHT
YEL
BLU
35V
5V
0V
0 ~ 5V
FG
MODEL
RAS-60YH5
POWER SOURCE DC: 0 ~ 35V
DC360V
OUTPUT 23W
40W
(Control circuit built in)
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE
GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED
BLK : BLACK PNK : PINK VIO : VIOLET
RED
360V
BLK
0V
WHT
15V
M
YEL
0~6V
BLU
0~15V
RAC-60YH5
Page 33
– 31 –
WHITE (U)
RED (W)
YELLOW (V)
MODEL
COMPRESSOR MODEL
PHASE SINGLE
RATED VOLTAGE AC 220 ~ 240 V
RATED FREQUENCY 50 Hz
POLE NUMBER 4
COMPRESSOR MOTOR
Compressor Motor Specifications
CONNECTION
20°C
(68°F)
75°C
(167°F)
( )
RESISTANCE VALUE
!
CAUTION
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the color has been changed conspicuously, replace the compressor.
2M = 1.05
2M = 1.28
(U)
(V)
(W)
M
M
M
WHITE
YELLOW
RED
RAC-60YH5
JU1013D5
Page 34
MODEL RAS-60YH5 / RAC-60YH5
WIRING DIAGRAM
– 33 –
INDOOR UNIT
OUTDOOR UNIT
BLU
POWER RELAY
COIL
NF COIL 1
C003
C001
C002
VARISTOR1
L001
CT1
VARISTOR3
SURGE
ABSORBER
DIODE STACK
R010
L002
R011
C011
C010
FAN MOTOR
VARISTOR2
CN6 WHT
C008 C013 C015
M
WHT YEL
RED
WHT YEL
YEL
YEL
YEL
DIODE STACK
RED
UVW
REACTOR
SYSTEM POWER
MODULE 2
L2
L1
CN14
CN13
CN11
C503
C502C501
10
CN14
CN10 RED
CN9 BLU
CN8 WHT
CN15 WHT
CN13
CN11
5
5
CN12
CN12
RED
GRY
2A FUSE
ICP RELAY
R008R007
3A FUSE
25A FUSE
C006
R001
BLK GRN WHT
(WHT) (BRN) (RED)(BLK)
CONNECTING
CORD
BRN RED
BLK
BLK
GRN
RED
BLK WHT YEL BLU
POWER CIRCUIT
TERMINAL BOARD
(GRN+YEL)
LNCD
SINGLE PHASE
AC220~240V
50Hz
(GRN+YEL)
THERE ARE SOME LEAD WIRES WHICH HAVE SPIRAL STRIPES WITH WHITE IN ADDITION TO THE ORIGINAL COLOR
CN2 RED
MAIN P.W.B.
REVERSING VALV E
R002
C007 C012 C014
ELECTRIC EXPANSION VALV E
OH THERMISTOR
DEFROST THERMISTOR
OUTDOOR TEMPERATURE THERMISTOR
GRY
GRY
GRY
GRY
RED
RED
COMPRESSOR
Page 35
Remote Control
CIRCUIT DIAGRAM
– 35 –
1 2 3 4 5 6 7 8
10 11
13 14 15 16 17
19 20
9
12
18
SEG19 SEG18 SEG17 SEG16 SEG21 SEG24 SEG25 SEG26 SEG27 SEG28
NC NC NC NC NC NC NC NC NC
SEG20
SEG5 SEG0 SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 COM3 COM2 COM1 COM0 SEG14 SEG13 SEG12 SEG11 SEG13 SEG9 SEG8
40 39 38 37 36 35 34 33
31 30
28 27 26 25 24
22 21
32
29
23
40 39 38 37 36 35 34 33
31 30
28 27 26 25
32
29
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48 47
46
45
44
43
41
42
65
66 67 68 69 70 71 72
74 75
77 78 79 80
73
76
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17 18
19
20
21
22
24
23
SEG20 SEG21 SEG22 SEG23 SEG24 SEG25 SEG26 SEG27 SEG28 SEG29 SEG30 SEG31 SEG32 SEG33 SEG34 SEG35
SEG19
SEG18
SEG17
SEG16
SEG15
SEG14
SEG13
SEG12
SEG11
SEG10
SEG9
SEG8
SEG7
SEG6
SEG5
SEG4
SEG3
SEG2
SEG1
SEG0
SEG43
SEG42
SEG41
SEG40
P40
P41
P42
P43
P00
P01
P02
P03
P10
P11
P12
P13
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
BEEP
P20
P30 P31
NCVL C1
VL C2 VL C3 XC IN
XC OUT
VDD
X OUT
X IN
RESET
CARR
P23 P22
P21
VSS
IC 1 M3455OM6A-504FP
LCD 1
C8
50v/1u
K 1 D3 RB425D(1/2)
K2K3
K4
K5
P10
P11
P12
K6
K7 K8
K9 K10
K11K12
K18
K17
K15 K16
K13 K14
D0
D1
D2
D3
R1
100k
SW1
R2
P
100k
R3
100k
R4
100k
R5
Q1
2SC3443
or 2SC2982
R6
R7
R9
D2D1
D1 D2
EL-1L7
D3
(1/2)
RB425D
R10 12M
K19
X1
C9
R11
R15
R16
R13
R14
910kHz
105
104
104
150k
X2
kHz
C4
C5
C6
C7
18p
22p
R12 220k
220K
220k
100k
100k
32.768
C1
C2
C3
220p
220p
334
R6 R9
24(1/8W)
R8
330
SW-187-2P
Key matrix table
Input
D3D2D1
D0
Output
Door open Automatic swingFan speed selectionOperation selectionStart/Stop
Door shut Automatic swingStart/Stop
Door open Day
present timeHour downHour upOn timer
Door shut Fan speedRoom temperature downRoom temperature up
Door open CancelReservationOff timer
Door shut Sleep
P10
P11
P12
Page 36
CIRCUIT DIAGRAM
– 37 –
Page 37
CIRCUIT DIAGRAM
MODEL RAC-60YH5
– 39 –
Page 38
– 41 –
PRINTED WIRING BOARD LOCATION DIAGRAM
MAIN P.W.B.
Marking on P.W.B.
RECEIVING P.W.B.
Marking on P.W.B.
COMPONENT SIDE
SOLDERING SIDE
R621
LIGHT
RECEIVING UNIT
2RZK81395A
7
CN11
1
+
C621
C622
SW2
SW1
TEMPORARY OPERATION
TEMPORARY
SWITCH
NORMAL
FILTER
RESET
SWITCH
11
Page 39
– 43 –
Wireless receive
circuit
Filter. Operation. Timer.
Auto sweep motor for Air deflector
LCD wireless
Heat exchanger thermistor
Room temperature thermistor
Reset circuit
Initial setting circuit
Temporary switch
Electric Expansion valve drive circuit
Electric
Expansion
valve
Outdoor microcomputer / HIC (AX-8T)
Trip signal synthesis circuit
L
N
SPM2
Power source 1¿, 50Hz, 220~240V
Outdoor unit Terminal board
Indoor microcomputer (AX-7R11)
Page 40
– 45 –
Notes:
1. The speed set of rotation for the fan motor in each operation mode are as shown in Table 1.
2. The set room temperatures in the diagram include the shift values in Table 2.
3. See Damper control theory for damper control and upper/lower fan operations.
Same as at left.
Performs the sleep operation of each operation mode.
Operating mode is judged by room temperature and outdoor temperature.
(1) Judging by outdoor temperature
Operating mode is judged by outdoor temperature. Only when the mode is not restricted by this judgment, the judgment by room temperature in the next paragraph will be performed. (a) Outdoor temperature 30°C : Restricted to cooling (b) Outdoor temperature 9°C : Restricted to heating
(2) Judging by room temperature
Operating mode at start up is judged (initial judgment) (a) Conditions for judgment (any of the followings)
When auto operation is started after 1 hour has elapsed since the operation was stopped.
When auto operation is started after the previous manual mode operation.
When the operating mode is switched to auto while operating at manual mode.
(b) Judging method
Room temperature 23°C ±3°C : Cooling
Room temperature < 23°C ±3°C : Heating
±3°C is the fine adjustment value from the remote controller.
Judging operating mode change during operation (Continuous judgment)
(a) Conditions for judgment (any of the followings)
The mode is reviewed at every interval time.
When auto operation is started again before 1 hour has elapsed since the operation was stopped.
(b) Judging method
Judge by setting the hysteresis on the final preset temperature. The final preset temperature is the actually targeted preset temperature which is the sum of the basic preset temperature and each type of shift value (e.g. ±3°C by remote controller, preset temperature correction value, powerful shift value, etc.). [Currently cooling]
Room temperature Final preset temperature 3 °C Change to heating
Room temperature > Final preset temperature 3° C Continue cooling
[Currently heating]
Room temperature Final preset temperature +2°C Change to cooling
Room temperature < Final preset temperature +2°C Continue heating
Set to ultra-Lo, Lo, Med, Hi, ultra-Hi or “stop” depending on the room temperature, time and heat exchange temperature. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preheating (cooling is recovered at 18.33˚C).
Set to ultra-Lo, Lo, Med, Hi, ultra-Hi or “stop” depending on the room temperature, and time. Set to stop if the room temperature is 18˚C in the ultra-Lo” mode other than during preheating (cooling is recovered at 18.33˚C). Set to ultra-Hi when the compressor is running at maximum speed during hot dash or when recovered from defrosting.
Set to ultra-Lo, Lo, Med or stop depending on the room temperature and time. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C).
Set to ultra-Lo, Lo, or stop depending on the room temperature and time. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C). The fan speed is controlled by the heat exchanger temperature; the overload control is executed as in the following diagram:
See page 55.
Same as at left
See page 57.
Set to Hi in modes other than when the compressor stops.
Set to Med in modes other than when the compressor stops.
Set to Lo in modes other than when the compressor stops.
See page 53.
Same as at left
See page 53.
Set to ultra-Hi when the compressor runs at maximum speed, and to Hi in other modes.
1. Runs at Hi until first thermo off after operation is started.
2. Runs at Lo when thermo is off.
1. The indoor fan also stops when the compressor is in stop status.
Changes between Lo and Med depending on the room temperature.
Changes from Hi to Med or Lo depending on room temperature.
Division 1
Division 2
Division 3
Division 4
Lo
Fan speedTemperature division
Lo
Med
Med
Same as at left.
Same as at left.
See page 49.
Same as at left
See page 51.
Operates at Hi regardless of the room temperature.
Operates at Med regardless of the room temperature.
Operates at Lo regardless of the room temperature.
Performs only fan operation at the set speed regardless of the room temperature.
Enters sleep operation after set as on the left.
Action during sleep operation Lo (sleep) operation
Hi
Fan speed mode (indoor fan)
Med
Lo
Basic operation of temperature controller
Sleep operation (with sleep button ON)
When the compressor is running at maximum speed during hot dash or when recovered from defrosting.
In modes other than left
42. 66
˚C
37. 66
32. 66
29. 66
Lo
Med
Med with overload
Lo
KAFON
Heat exchanger temperature
KAFOF
Hi or ultra-HI (fan speed set to auto”)
Heat exchanger temperature
(Compressor stopped forcibly for 3 minutes)
Thermo iudgment
Temperature set for cooling
Compressor
Hi Med Lo
AutoHeatingCooling
Dehumidifying
(dehumidifying operation by the function select button only, not including that engaged by the dehumidify button)
Fan
Operation mode
BASIC MODE
Basic operation of start/stop switch
Off-timer
On-timer
Timer functions
Off -> On On -> Off timer
Auto
Start Stop
(Off-timer during stop)
(On-timer during operation)
ON ONONOFF OFF OFF ONOFF
(Change in reserved time)
(Change in reserved time)
(Off->On timer) (On->Off timer) (On->Off timer)
during operation)
(Off->On timer)
during stop)
Start Start/stop switch Operation tamp
Start/stop switch Operation tamp Cancel switch
Cancel switch
Reserve switch
Srart/stop switch
Operation temp
Operation temp
Timer tamp
Timer tamp
Timer memory
Timer memory
Timer memory
Timer lamp
Operation lamp
Cancel switch
Reserve switch
Start/stop switch
Stop
Start/stop switch Operation lamp
Hi
Hi Med Lo
Fan
Speed
Med Lo
Cooling
Heating
Room
-temperature
22°C
9°C30°C
Outdoor temperature
Cooling
Heating
final preset temperature
Page 41
– 47 –
Table 1 Mode data file
RAS-60YH5
LABEL NAME VALUE
WMAX 6300 min
–1
WMAX2 6300 min
–1
WSTD 5900 min
–1
WBEMAX 3600 min
–1
CMAX 6300 min
–1
CMAX2 6300 min
–1
CSTD 5850 min
–1
CKYMAX 4550 min
–1
CJKMAX 3700 min
–1
CBEMAX 3000 min
–1
WMIN 1200 min
–1
CMIN 1500 min
–1
STARTMC 60 Seconds
DWNRATEW 80%
DWNRATEC 80%
SHIFTW 3.33°C
SHIFTC 0.33°C
CLMXTP 30.00°C
YNEOF 28.00°C
TEION 2.00°C
TEIOF 9.00°C
SFTDSW 1.00°C
DFTIM1 45 Minutes
DFTIM2 60 Minutes
Page 42
– 49 –
Reversing valve (heating on mode)
NOTE (9)
Notes: (1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 2) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode. (3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP. (6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX. (7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX. (8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX. (9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Temperature Calculated
difference compressor rpm
1.66 2265 min
–1
2 2435 min
–1
2.33 2600 min
–1
2.66 2765 min
–1
3 2935 min
–1
3.33 3100 min
–1
3.66 3265 min
–1
4 3435 min
–1
4.33 3600 min
–1
4.66 3765 min
–1
5 3935 min
–1
5.33 4100 min
–1
5.66 4265 min
–1
6 4435 min
–1
6.33 4600 min
–1
6.66 4765 min
–1
7 4935 min
–1
7.33 5100 min
–1
7.66 5265 min
–1
8 5435 min
–1
8.33 5600 min
–1
8.66 5765 min
–1
9 5935 min
–1
9.33 6100 min
–1
9.66 6265 min
–1
10 6435 min
–1
10.33 6600 min
–1
10.66 6765 min
–1
11 6935 min
–1
Table 2 ∆TCMAX
Note:
1. See the data in Table 1 on page 47 for each constant in capital letters in the diagrams.
Page 43
– 51 –
Notes:
(1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to “sleep Lo”. (3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached. (4) The sleep shift upper value of set temperature is 28˚C. (5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min. (6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point
when switching is made. (7) The indoor fan speed does not change even when the fan speed mode is changed. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted. (9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Cooling Sleep Operation
Compressor speed
Horizontal air deflector
Shut
Horizontal
Facing down
Maximum speed
Indoor fan
Outdoor fan
Timer lamp
Operation lamp
Sleep key
(Cooling/dehumidifying set temperature = Remote control set temperature (+) SHIFTC)
Final set temperature (Cooling/dehumidifying set temperature (+) sleep shift)
Set to 7 hours
0.5hr
1.5hr
3hr
P1
2.5hr 3.5hr 6hr 7hr
Hi
See basic operation
Med
Lo (sleep)
Lo
10 mins
Page 44
+
+
Delay
–1.33˚C
–0.66˚C
53
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2°C). (2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute. (3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation. (4) The compressor is operated forcedly for 3 minutes after operation is started. (5) The minimum ON time and OFF time of the compressor are 3 minutes.
Page 45
– 55 –
1.33˚C.
SFTDSW
0.66˚C.
Fan speed set to "auto"
1 min.
Hi
Lo Hi Hi Hi
ultra Hi
Basic Heating Operation
Start
Stop Star t Start StopStop
Thermo
OFF
Thermo
OFF
Heating set temperature (remote control set temperature (+))
Start/stop switch
Thermo judgment
Indoor fan
Ultra-Hi
Hi
Med
Lo
Ultra-Lo
Operation lamp
Max.
Rating
3000
0
Compressor speed
Outdoor fan
Reversing valve (heating "on" model)
Thermo OFF
Dash period
TWMAX
Wtd
Defrost signal
Preheating judgment
30sec. 30sec.
10sec.
15sec. 15sec.
15sec. 15sec. 15sec.
10sec.
15sec.
15sec.
150sec. Delay
150sec. Delay150sec. Delay
3min.
Max. 3 min.
Preheating released
Control by heat exchanger temperature
Control by heat exchanger temperature
15sec.
Control by heat exchanger temperature
Control by heat exchanger temperature
Control by heat exchanger temperature
18˚C
10sec.
30sec. 30sec.
10sec.
30sec. 30sec.30sec. 30sec. 30sec. 30sec.
10sec.
Preheat released
WMIN
(WSTD)
(WMAX)
NOTE (11)
WMAX2
Notes: (1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm (calculated value in Table 3) larger than WMAX. (2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off. (3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor temperature
is lower than 18°C and outdoor temperature is lower than 2°C. (6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”. (7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C. (8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX. (9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode. (10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2. (11) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor rpm is actual rpm x DWNRATEW.
Temperature Calculated
difference compressor rpm
1.66 1965 min
–1
2 2135 min
–1
2.33 2300 min
–1
2.66 2465 min
–1
3 2635 min
–1
3.33 2800 min
–1
3.66 2965 min
–1
4 3135 min
–1
4.33 3300 min
–1
4.66 3465 min
–1
5 3635 min
–1
5.33 3800 min
–1
5.66 3965 min
–1
6 4135 min
–1
6.33 4300 min
–1
6.66 4465 min
–1
7 4635 min
–1
7.33 4800 min
–1
7.66 4965 min
–1
8 5135 min
–1
8.33 5300 min
–1
8.66 5465 min
–1
9 5635 min
–1
9.33 5800 min
–1
9.66 5965 min
–1
10 6135 min
–1
10.33 6300 min
–1
10.66 6465 min
–1
11 6635 min
–1
Table 3 ∆TWMAX
Notes:
1. See the data in Table 1 on page 47 for each constant in capital letters in the diagrams.
Page 46
– 57 –
1 min
WMIN
Notes: (1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to sleep Lo. (3) 30 minutes after the sleep key is set, the sleep shift of set temperature starts. (4) The maximum sleep shift of set temperature is 5°C, and the minimum is 12°C. (5) If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts. (6) The indoor fan speed does not change even when the fan speed mode is changed. (Lo) (7) When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted. (9) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Page 47
– 59 –
REFRIGERATING CYCLE DIAGRAM
MODEL RAS-60YH5 / RAC-60YH5
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TANK
SERVICE VALVE
(1/2)
INDOOR UNIT
SINGLE-ENDED UNION (1/2)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
HEATING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TANK
SERVICE VALVE
(1/2)
INDOOR UNIT
SINGLE-ENDED UNION (1/2)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
Page 48
– 60 –
OPERATING SPECIFICATION
REFERENCE
OPERATION OPERATION MODE AIR DEFLECTOR
PRESENT CONDITION
KEY INPUT
THERMO. ON
(INTERNAL FAN
ON)
THERMO. ON
(INTERNAL FAN
OFF)
MAIN SWITCH
ON
MAIN SWITCH
OFF
CHANGE OF
OPERATION
STOP
DURING
OPERATION
DURING
OPERATION
STOP
DURING
OPERATION
DURING
OPERATION
EACH MODE
AUTO COOL
COOL
FAN
AUTO DRY
DRY
AUTO HEAT
HEAT
CIRCULATOR
AUTO DRY
DRY
AUTO HAET
HEAT
CIRCULATOR
COOL
FAN
DRY
HEAT
CIRCULATOR
EACH MODE
EACH MODE
STOP SWINGING AND MODE BECOMES INITIALIZING
CONDITION.
INITIALIZING CONDITION OF EACH MODE.
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
INITIALIZE
1 DOWNWARD
INITIALIZE
1 DOWNWARD
2 UPWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
INITIALIZE AT NEXT
OPERATION.
INITIALIZE AT NEXT
OPERATION.
STOP
DURING ONE SWING
STOP
DURING SWINGING
STOP
DURING SWINGING
TEMPORARY STOP
DURING SWINGING
STOP
DURING ONE SWING
STOP
DURING ONE SWING
STOP
DURING SWINGING
DURING
INITIALIZING
STOP
DURING SWINGING
AUTO SWING FUNCTION
STOP SWINGING TEMPORARILY.
(SWING MODE IS CLEARED IF SWING COMMAND IS
TRANSMITTED DURING TEMPORARY STOP.)
START SWING AGAIN.
INPUT SIGNAL
Page 49
61
The reset circuit initializes the microcomputer program when power is ON or OFF.
Low voltage at pin 7 resets the microcomputer and Hi activates the microcomputer.
When power ON 5V voltage rises and reaches 4.4V, pin 1 of IC521 is set to Hi. At this time the
microcomputer starts operation.
When power “OFF voltage drops and reaches 4.2V, pin 1 of IC521 is set to “Low. This will RESET the
microcomputer.
DESCRIPTION OF MAIN CIRCUIT OPERATION
1. Reset Circuit
Fig. 1-1
Fig. 1-2
2
1
5
3
7
NORMAL : HI RESET : LO
RES
Microcomputer
C524
R521
C522
C521
R522
5V
0V
IC521
Voltage
5.0V
Reset enter at 4.2V
Reset release at 4.4V
voltage
5.0V
Voltage at pin
7
of microcomputer
Voltage supply to pin
2
of IC521
Page 50
62
2. Receiver Circuit
The light receiver unit receives the infrared signal from the wireless remote control. The receiver amplifies
and shapes the signal and outputs it.
3. Buzzer Circuit
Fig. 3-1 Buzzer Circuit
Sound wave
Metal diaphragm
V
Pizoelectric element
V
Fig. 3-2 Buzzer Operation
Microcomputer
Buzzer output
BZ1
12V
0V
R219
Q722
30
BZ
When the buzzer sounds, an approx.
3.9kHz square signal is output from buzzer output pin of the microcomputer. After the amplitude of this signal has been set to 12Vp-p by a transistor, it is applied to the buzzer. The piezoelectric element in the buzzer oscillates to generate the buzzers sound.
12V
R201
R1
0V
0V
13 RECEIVER I/P
Microcomputer
R2 R611
IR1
GND
V
out
VDD
C1
ZD211
C611
Fig. 2-1
30
Page 51
63
4. Auto Sweep Motor Circuit
Fig. 4-1 shows the Auto sweep motor drive circuit; the signals shown in Fig.4-2 are output from pins
15 – 18 of microcomputer.
As the microcomputers outputs change as shown in Fig.4-2, the core of the auto sweep motor is excited
to turn the rotor. Table 4-1 shows the rotation angle of horizontal air deflectors.
Table 4-1 Auto sweep Motor Rotation
Rotation angle per step (˚ ) Time per step (ms.)
0.0882 10Horizontal air deflectors
Microcomputer pins Step width
Horizontal air
deflectors: 10ms.
Horizontal air deflectors
15
16
17
18
12345678
Fig.4-2 Microcomputer Output Signals
10
11
8
9
12
0V
7 6 5
4
18 17 16
Microcomputer
IC711
C711
12V
Rotor
Auto sweep motor for horizontal air defectors
15
13
Fig.4-1
Page 52
64
5. Room Temperature Thermistor Circuit
Fig. 5-1 shows the room temperature
thermistor circuit.
5
4
3
2
1
0
010
Room temperature (˚C)
Fig. 5-2
20 30 40
0V
Room temperature thermistor
0V
5V
Fig. 5-1
62
A
R305
C302
Microcomputer
Room temp. input
Voltage at
(V)
R301
0V
Heat exchanger temperature thermistor
0V
5V
Fig. 6-1
61
A
R306
C303
Microcomputer
Heat exchanger temperature input
R302
A
5
4
3
2
1
0
010
-10
Heat exchanger temperature (˚C)
Fig. 6-2
20 30 40
Voltage at
(V)A
6. Heat exchanger temperature thermistor circuit
The voltage at depends on the room
temperature as shown in Fig. 5-2.
The circuit detects the indoor heat
exchanger temperature and controls the following.
(1) Preheating.
(2) Low-temperature defrosting during cooling and dehumidifying operation.
(3) Detection of the reversing valve non-operation or heat exchanger temperature thermistor open.
The voltage at depends on the heat exchanger temperature as shown in Fig. 6-2.
A
A
Page 53
65
7. Initial Setting Circuit (IC401)
When power is supplied, the microcomputer reads the data in IC401 or IC402 (E
2
PROM) and sets the preheating activation value and the rating and maximum speed of the compressor, etc. to their initial values.
Data of self-diagnosis mode is stored in IC401 or IC402; data will not be erased even when power is
turned off.
Fig. 7-1
Microcomputer
External ROM
SCL SDA
0V
0V
0V
5V
5V 5V
C401
IC401 or IC402 (E
2
PROM)
R404
R403
27 26
1
2
3
4
8
7
6
5
}
Page 54
66
1. Power Circuit
This circuit full-wave rectifies 220-240V AC applied between terminals L and N, and boosts it to a required
voltage with the active module, to create a DC voltage.
The voltage becomes 260-360V when the compressor is operated
(1) Active module
The active filter, consisting of a reactor and switching element, eliminates higher harmonic components contained in the current generated when the compressor is operated, and improves the power-factor.
(2) Diode stacks
These rectify the 220-240V AC from terminals L and N to a DC power supply.
< Reference >
In case of malfunction or defective connection:
Immediately after the compressor starts, it may stop due to abnormally low speed active error, etc.
The compressor may continue to operate normally, but the power-factor will decrease, the operation current will increase, and the overcurrent breaker of the household power board will probably activate.
In case of active module faulty or defective
connection:
Although the compressor continues to operate normally, the power-factor will decrease, the operation current will increase, and the overcurrent breaker of the household power board will probably activate.
< Reference >
If diode stack 1 is faulty, the compressor may stop
due to lp, anbormally low speed, etc. immediately after it starts, or it may not operate at all because no DC voltage is generated between the positive e and negative d terminals.
If diode stack 1 is faulty, be aware that the 25A fuse might also have blown.
If diode stack 2 is faulty, DC voltage may not be
generated and the compressor may not operate at all. Also, be aware that the 3A fuse might have blown.
L
25A FUSE
SURGE­ABSORBER
VARISTOR1
VARISTOR3
CT1
C009
L001
C001
C004C005
C006
R007
L002
JW6
R008
ICP RELAY
TB2
TB8
TB7 TB6
TB10 TB11 TB12
U V W
N1
L1 L2
3A FUSE
R002
C008
C007
C012
C013
C014
C015
DIODE
STACK 2 (RC2)
DIODE
STACK 1
(D25VB60)
VARISTOR2
C011
POWER CIRCUIT
R010R011
C002
C003
R001
0V
0V
NF COIL1
COIL
POWER RELAY
TERMINAL
BOARD
N
REACTOR
C010
SPM2
P1
Vdba
Fig. 1-1
Page 55
– 67 –
(3) Smoothing capacitor (C501, C502, C503)
This smoothes (averages) the voltage rectified by the diode stacks.
(4) Smoothing capacitor (C010, C011)
This smoothes (averages) the voltage rectified by the diode stack2. A DC voltage is generated in the same way as in Fig. 1-3. Voltage between + side of C010 and – side of C011 is about 330V.
(5) C001 to C003, C012 to C015, C007, C008, NF COIL1, COIL,
absorb electrical noise generated during operation of compressor, and also absorb external noise entering from power line to protect electronic parts.
(6) Surge absorber, Varistor 1, 2, 3,
absorbs external power surge.
(7) Inrush protective resistor (R007, R008)
This works to protect from overcurrent when power is turned on.
< Reference >
When inrush protective resistor is
defective, diode stack may malfunction. As a result, DC voltage is not generated and no operation can be done.
Be careful to avoid an electric shock as a
high voltage is generated. Also take care not to cause a short-circuit through incorrect connection of test equipment terminals. The circuit board could be damaged.
Fig. 1-3
Fig. 1-2
a
b
OV
OV
OV
Vd
DC voltage (approx. 260-360V during operation)
Smoothing Capacitors
SPM2
Page 56
68
2. Indoor/Outdoor Interface Circuit
The interface circuit superimposes an interface signal on the DC 35V line supplied from the outdoor unit
to perform communications between indoor and outdoor units. This circuit consists of a transmiting circuit which superimposes an interface signal transmit from the microcomputer on the DC 35V line and a transmiting circuit which detects the interface signal on the DC 35V line and outputs it to the microcomputer.
Communications are performed by mutually transmiting and receiving the 4-frame outdoor request signal
one frame of which consists of a leader of approx. 100 ms., start bit, 8-bit data and stop bit and the command signal with the same format transmit from the indoor unit.
Communication signal from outdoor microcomputer to indoor microcomputer. At first outdoor microcomputer
will send a request signal (SDO) to indoor microcomputer. A high-frequency IF signal approx. 38 KHz is generated and modulated by the request signal (SDO) inside the outdoor microcomputer then output to pin 11 of microcomputer. This modulated IF signal is output to pin 30 of HIC and amplified by amp. This signal is superimposed to DC 35V line via C801 and L801. To prevent erroneous reception, the outdoor microcomputer is designed so that it cannot receive a signal while it is outputting a request signal. The receiving circuit in the indoor unit consists of a comparator and transistor. The interface signal from the outdoor unit on the DC 35V line is supplied to C821, where DC components are eliminated, and is then shaped by the comparator. The shaped signal is detected by diode, amplified by amp, and output to pin 49 of the indoor microcomputer. Fig. 2-2 shows the voltages at each component when data is transferred from the outdoor microcomputer to the indoor microcomputer.
Communication signal from indoor microcomputer to outdoor microcomputer. The request signal (SDO)
generates by indoor microcomputer is output to pin 50 , and amplifies by C801. IF signal approx. 38 kHz is generated by comparator, then modulate by the request signal from pin 50 of indoor microprocessor. This modulated IF signal is then amplified and superimposed to DC 35V line via L801 and C802 of indoor interface circuit. Fig. 2-3 shows the voltages at each component when data is transferred from outdoor microcomputer to indoor microcomputer. The circuit operation of the outdoor receiving circuit is same as indoor receiving circuit.
Page 57
69
Fig. 2-1 shows the interface circuit used for the indoor and outdoor microcomputers to communicate with
each other.
Indoor P.W.B.
Outdoor P.W.B.
Terminal board
Terminal board
CD
CD
D101
I/F 0V
C821 R821
C822
0V
0V 0V0V
5V 5V 5V
0V
0V
0V
5V
0V
C801
R829
R830
Q821
C824
0V
IC801
C823
R828
R823
R825
D821
R827
R826
0V
0V
0V
I/F 0V
0V
IF transmit output (SDO)
IF receive input (SDI)
MICROCOMPUTER
5V
0V
5V
5V
12V
5V 5V
5V
5V5V
5V
C802
R813
L801
R812
Q803
C803
C804
R811
Q802
Q801
R824
3 2
1
R822
R806
R807
R805
R803
R804
5
7
6
IC801
R810
50
49
IF transmit output (SDO)
HIC
IF receive input (SDI)
MICROCOMPUTER
11
30
68
29
0V
L801
L802
C801
C809
R802 Q801
5V
0V
R801
R803
0V
0V
0V
0V
0V
0V
0V0V
C808
NF COIL2
C810
C802
C806
C807
C812
C811
Interface relay
35V
(Communications from outdoor microcomputer to indoor microcomputer)
(Communications from indoor microcomputer to outdoor microcomputer)
Fig. 2-1 Indoor/outdoor interface Circuit
Page 58
– 70 –
Outdoor HIC
29
Pin
30
Pin
Indoor microcomputer
DC 35V line
49
Pin
50
Pin
100ms. Leader
33ms. 1 frame
0.7V
0V
5V
0V
5V
0V
5V
0V
35V
Indoor microcomputer
4.95ms. Transmit / receive switching time
33ms. 1 frame
Outdoor HIC
30
Pin
0V
29
Pin
5V
0V
50
Pin
5V
0V
49
Pin
5V
0V
DC 35V line
35V
Fig. 2-2 Voltages Waveforms of indoor / Outdoor Microcomputers (Outdoor to Indoor Communications)
Fig. 2-3 Voltages Waveforms of indoor / Outdoor Microcomputers (Indoor to Outdoor Communications)
Page 59
– 71 –
[Serial Communications Format during Normal Communications]
(1) Outdoor microcomputer (HIC) to indoor microcomputer
(2) Indoor microcomputer to outdoor microcomputer (HIC)
(3) Communications waveforms
1 frame = 100ms. + 33.3ms. x 8 + 4.95ms. = 371.35ms.
Outdoor message
Indoor message
[Example] When the outdoor message is all 0s
and indoor message is all 1s:
36 (V)
35 (V)
34 (V)
When reset
(approx. 10ms.)
Transmit/
receive
switching time
(4.95ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Bit No = 0
Bit No = 0
07
0707077
07077
Leader
(100ms.)
When reset
(approx. 10ms.)
Leader
(100ms.)
Fig. 2-4
Page 60
– 72 –
[ Serial Communications Data ]
7
1/0
6
1/0
5
1/0
4
1/0
3
1/0
2
1/0
1
1/0
0
1/0
7
1/0
6
1/0
5
1/0
4
1/0
3
2
1
0
7
6
5
4
3
2
1
0
7
6
5
4
0
3
1/0
2
1/0
1
1/0
0
1/0
Character No.
Bit No.
Data
0 0 0 1/0 1/0 1/0 0 1/0 0 0 1/0 1/0 1/0 1/0 1/0
OVL up
Compressor command speed (0 LSB)
Compressor ON
Reversing valve
2-way valve
Fan (2 MSB)
Fan (1
Fan (0 LSB)
Capacity code (3 MSB)
Capacity code (2)
Capacity code (1)
Capacity code (0 LSB)
Indoor in-operation bit
Operation mode (2 MSB)
Operation mode (0 LSB)
Contents
0
1
2
3
(2) Indoor message
Operation mode (1)
Compressor command speed (1)
Compressor command speed (2)
Compressor command speed (3)
Compressor command speed (4)
Compressor command speed (5)
Compressor command speed (6)
Compressor command speed (7 MSB)
15/20(A)
Compressor minimum rotation speed (4 MSB)
Compressor minimum rotation speed (3)
Compressor minimum rotation speed (2)
Compressor minimum rotation speed (1)
Compressor minimum rotation speed (0 LSB)
7
0
6
0
5
0
4
0
3
0
2
0
1
1
0
0
7
1/0
6
1/0
5
1/0
4
1/0
3
2
1
0
7
6
5
4
3
2
1
0
7
6
5
4
1/0
3
1/0
2
1/0
1
0
0
1/0
Character No.
Bit No.
Data
1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0
Fan-7-step request
Actual compressor rotation speed (5 MSB)
Actual compressor rotation speed (4)
Actual compressor rotation speed (3)
Actual compressor rotation speed (2)
Actual compressor rotation speed (1)
Actual compressor rotation speed (0 LSB)
Compressor during operation
Compressor during operation
Outside temperature (7 MSB)
Outside temperature (6)
Outside temperature (5)
Outside temperature (4)
Outside temperature (3)
Outside temperature (2)
Outside temperature (1
Outside temperature (0 LSB)
Self-diagnosis (3 MSB)
Self-diagnosis (2)
Self-diagnosis (1)
Self-diagnosis (0 LSB)
Defrost request signal
During forced operation
Multi-bit
Contents
0
1
2
3
(1) Outdoor message
Page 61
73
3. Power Module Circuit
Fig. 3-1 shows the system power module and its peripheral circuit.
The three transistors on the positive e side are called the upper arm, and the three transistors on the negative d side, the lower arm.
+
W
U
V
W
W
+
V
V
+
U
U
A
+
DC
Compressor
motor
U coil
V coil
W coil
System Power module 2
+
C501
+
C502
+
C503
R24
0.35
m
H
Power relay
Coil
R007
R008
Inrush current
protection
relay
C006
R001
Noise filter
coil
L
N
Terminal
board
FUSE (25A)
Fig. 3-1 Power module circuit (U
+
is ON, V
is ON)
Page 62
74
DC 260-360V is input to system power module and system power module switches power supply current
according to rotation position of magnet rotor. The switching order is as shown in Fig. 3-2.
E
F
UVVW
Upper arm transistor
Lower arm transistor
Time
++T+
+
T
U
V
W
U transistor chopped
U transistor ON
ON
Voltage at
Upper arm transistor
Current at
Chopping period
260V-360V
A
+
-
B
At point E: U+ is ON, V– is ON (circuit in Fig. 3-1) At point F: U+ is chopped (OFF), V– is ON (circuit in Fig. 3-4)
[]
Upper arm transistor is controlled to ON/OFF by 3.3kHz chopper signal. Rotation speed of the compress
is proportional to duty ratio (ON time/ ON time + OFF time) of this chopper signal.
Time T in Fig. 3-2 shows the switching period, and relation with rotation speed (N) of the compressor is
shown by formula below;
Fig. 3-2 Switching order of power module
N = 60/2 X 1/T
Fig. 3-3 shows voltage waveform at each point shown in Figs. 3-1 and 3-4. First half of upper arm is
chopper, second half is ON, and first half of lower arm is chopper, second half is ON.
Fig. 3-3 Voltage waveform at each point
When power is supplied U
+
[ U–, because of that U+ is chopped, current flows as shown below;
(1) When U+ transistor is ON: U+ transistor [ U coil [ V coil [ V– transistor [ DC current detection
resistor [ Point (Fig. 3-1)
(2) When U+ transistor is OFF: (by inductance of motor coil) U coil [ V coil [ V– transistor [ Return
diode [ Point (Fig. 3-4)
A
B
B
Page 63
– 75 –
+
U
U
V
W
U
+
V
V
+
W
W
_
+
System Power Module 2
260V-360V
R24
DC current (Id) detection resistor
A
U coil
DC compressor motor
V coil
W coil
B
Fig. 3-5
Since current flows at point only when U+ transistor is ON, the current waveform at point becomes
intermittent waveform as shown in Fig. 3-3. Since current at point is approximately proportional to the input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
Refer to other item (troubleshooting on page 94) for independent checking of power module.
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
Self-diagnosis
Self-diagnosis lamp and mode
lp (peak current cut)
LD301
Abnormal low speed
rotation
LD301
Switching incomplete
LD301
Blinks 2 times
Blinks 3 times
Blinks 4 times
Table 3-1
B B
B
Self diagnosis lamps (LD303, 302, 301)
P.W.B (Main)
Page 64
76
4. Power Circuit for P.W.B.
Fig. 4-1 shows the power circuit for P.W.B. and waveform at each point.
22
18
19
+
D908
R917
R915
D909
R918
L903
REG1
C911
20
21
+
D907
C910
R914
C912
16
17
+
C903
C907
+
+
C914
14
13
R916
L902
35V
17V
5V
FM–15V
I/F0V
0V
0V
0V
FM–0V
C913
D910
REG2
Q706
C924
R920
R921
R922
PQ2
1
1
2
4
3
4
3
1
2
2
3
PQ1
VR1
R923
C906
C918
R911
D906
C908
PQ1
12
C
11
D904
R908
R909
D903
D905
D911
R910
R901
C901
R902
R903
R002
Diode stack 2
(RC2)
R904
2 5
3 4
1
+
+
IC901
C011
C010
R011
R010
C905
D902
R906
L901
R907
Switching transformer (T1)
Fig. 4-1 Power circuit for P.W.B.
1
9
+
C919
+
C921
C920
12V
D912
R919
R925
R924 ZD904
C909
15
1 2
JW8
JW8
4 3
In the power circuit for P.W.B., power supply for microcomputer, peripheral circuits, and system power
module driver circuit and, as well as DC 35V, are produced by switching power circuit.
Switching power circuit performs voltage conversion effectively by switching transistor IC901 to convert
DC 330V voltage to high frequency of about 20kHz to 200kHz.
Transistor IC901 operates as follows:
(1) Shifting from OFF to ON
DC about 330V is applied from smoothing capacitors C010 Œ and C011 œ in the control power circuit.
With this power, current flows to pin of IC901 via R903 and R904 and IC901 starts to tum ON. Since voltage in the direction of arrow generates at point at the same time, current passing through R910 and D903 is positive-fed back to IC901.
4
C
Page 65
– 77 –
(2) During ON
The drain current at IC901 increases linearly. During this period, the gate voltage and current become
constant because of the saturation characteristics of the transformer.
(3) Shifting from ON to OFF
This circuit applies a negative feedback signal from the 12V output. When the voltage across C919
reaches the specified value, REG2 turns on and current flows to PQ2 1-2. This turns the secondary circuits on, sets IC901 pin 1 to “Hi”, and turns IC901 off.
(4) During OFF
While IC901 is on, the following energy charges the primary windings of the transformer:
Energy=LI2/2. Here, L : Primary inductance
I : Current when IC1 is off
This energy discharges to the secondary windings during power off. That is, C910, C911, C912, C914 is charged according to the turn ratio of each winding.
At the start, an overcurrent flows to IC901 because of the charged current at C910, C911, C912, C914.
The drain current at IC901 generates a voltage across R906. If it exceeds the IC901 base voltage, it sets
the IC901 gate voltage to “HI”.
R906 limits the gate voltage to prevent excessive collector current from flowing to IC901.
<Reference>
If the power circuit for P.W.B. seems to be faulty:
(1) Make sure that 5V and 12V on the control P.W.B., upper arm U, V and W, and the lower arm power
voltage are the specified values.
(2) When only the 5V output is low:
REG 1 (regulator) faulty, 5V-0V shorted, output is too high, or REG 1 is abnormal.
(3) When 12V and 5V are abnormal:
The following defects can be considered:
1 Fan, operation, power, rush prevention relay (shorting in relay, etc.) 2 Microcomputer is abnormal. 3 REG 1 (regulator is abnormal), etc.
Shorting on primary circuits. When shorting occurs in the secondary circuits, there is no abnormality in the primary circuits because of overcurrent protection. The voltage rises when an opening occurs in the primary circuits, or the feedback system is abnormal.
(4) When 15V and 17V are abnormal:
D908, D909 or drive circuit is abnormal.
(5) When all voltage are abnormal:
IC901, R906, etc. are possibly abnormal.
* If IC901 is abnormal, be aware that other components, such as the power module, REG (regulator), etc.
are possibly defective.
[When the switching power supply seems to be abnormal, the voltage between IC901 pin 4 (to be measured at the leads of R904 and R903) and IC901 pin 5 (to be measured at R906 lead) may be between 11 and 16V. This is because the protection circuit of IC901 is operating.]
Page 66
78
5. Reversing valve control circuit
Reversing valve control circuit can switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 5-1.
Voltage at each point in each operation condition is approximately as shown below when measured by tester. (When collector voltage of Q701 is measured)
3
1
16
24
I/F 0V
0V
Fig. 5 – 1
D702
CN2
Q701
DC voltmeter or tester
Reversing valve
R701
R703
R219
Q705
FUSE RESISTOR
MICROCOMPUTER
PQ701
1
23
4
5V
HIC
I/F 35V
R702
V
Operation condition Collector voltage of Q701
Cooling
Heating
Dehumidifying
General operation of Cooling
In normal heating operation
MAX. rotation speed instructed by indoor microcomputer after defrost is completed
Defrosting
Sensor dry
About 35V
About 0.8V
About 0.8V
About 35V
About 35V
Table 5-1
Page 67
79
6. Rotor magnetic pole position detection circuit
A
B
C
D
E
18
19
20
Outdoor microcomputer
C605
+5V
0V
HIC
0V
+12V
WV U
C608
System power module
DC brushless motor for compressor
R604
R605
R606
R607
R601
R602
R603
R604
R603
R602
R608
C503
C502
C501
R611
R610
R609
0V
C606
0V
C607
0V
36
33
34
35
47
Fig. 6-1 Rotor magnetic pole position detection circuit and voltage waveform at each point
E
D
C
A
No power supplied
Upper armONNo power
supplied
No power supplied
Lower arm
ON
60 120 60 120
Induced voltage
Comparing process
60
Vd 150 ~330
Spike voltage
U phase terminal voltage
Drive signal
Pole position detection signal
(B) reference voltage (1/2Vd)
Detection point
W
+
W
+
U
+
U
+
U
V
V
W
V
+
To detect U phase, voltage at point C is produced by driving motor induced voltage signal (voltage at point A ) and
1/2 voltage of Vd (voltage at point B ), and comparing with comparator.
For V phase and W phase, voltage at point
D
and voltage at point E are produced in the same way as above. Voltage at point C is taken into indoor unit microcomputer, switching timing to U+ transistor from W+ transistor is produced by delaying 30° from rise waveform, ignoring spike voltage. In addition, switching timing to U-transistor from W-transistor is produced by delaying 30° from fall waveform.
For V phase and W phase, in the same way as above, drive signals are produced from voltages at point
D
and point
E
. Phases are shifted by 120° and 240°, respectively, comparing with U phase.
Page 68
80
7. Drive Circuit
Fig. 7-1 shows the drive circuit. The circuits for U phase, V phase and W phase have the same Configuration.
In low speed rotation mode (PWM range), as shown in Fig. 7-2, 0-5V chopper signal is ouput from microcomputer for each phase. S
ignal
output from microcomputer is ouput to IC1 and is inverted by active Lo to become 0-15V chopper signal; it is then drive the tra
nsistor
of each phase.
In high speed rotation mode (PWM range), as shown in Fig. 7-3, 0-5V drive signal is ouput from microcomputer for each phase (wi
th
no chopper because of full duty). Signal output from microcomputer is input to IC1 and is inverted by active Lo to become 0-15V
drive
signal; it is then drive the transistor of each phase.
Fig.. 7-1
6
5
4
3
2
1
MICROCOMPUTER
A
R512
R521
R511
R510
R509
R508
R507
10
9
4
3
2
1
8
7
6
5
1
13
14
15
16
17
18
1
23
11
8
7
5
4
10
6
3
9
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
19
20
21
2
3
4
5
6
7
8
9
10
12
22
B
B
B
45
44
43
42
41
38
39
40
46
IP CUTTER Id CONTROL CIRCUIT
0V
17V
R501
C404
CN14
17V
0V
PWB (MAIN)
SPM2
0V
17V
U
+
V
+
W
+
U
V
W
IP
Id
IC1
VCC
VCU
PGU
U
VCV
PGV
V
VCW
PGW
W
NGU
NGV
NGW
SVT
SWT
SUB
SVB
SWB
F
OC
CB
A
0
A
GL1
GL2
SUT
R502
R503
R504
R505
R506
Q506
R536
R535
R525
Q504
R534
Q503
R524
R533
Q502
Q501
R522
R532
R531
R526
Q505
R523
HIC
P2
N1
HIC
+
GRY
R24
U
COMPRESSOR MOTOR
V
W
Page 69
– 81 –
U
+
V
+
5V 0V
W
+
V
-
W
-
U
-
U
+
V
+
15V
0V
W
+
V
-
W
-
U
-
Drive signal at point B Drive signal at point A
V
+
U
+
W
+
V
+
U
+
V
-
W
-
U
-
V
-
W
-
[Low speed rotation mode]
[High speed rotation mode]
V
+
U
+
W
+
V
+
U
+
U
+
V
+
5V 0V
W
+
V
-
V
-
W
-
U
-
U
+
V
+
15V
0V
W
+
V
-
W
-
U
-
W
-
U
-
V
-
W
-
Drive signal at point
B
Drive signal at point
A
Fig. 7-2
Fig. 7-3
Page 70
82
8. HIC and Peripheral Circuits
Fig. 8-1 shows the micro computer and its peripheral circuits, Table 8-1, the basic operations of each
circuit block, and Fig. 8-2, the system configuration.
Table 8-1
Circuit block
Basic operation
Peak current cutoff circuit
Set value circuit
Voltage amplifier circuit
Reset circuit
Trip signal synthesis circuit
Detects DC current flowing power module and during overcurrent (instantaneous value) flows, stops upper/lower arm drive circuits and also produces lp signal by which drive signal output is stopped.
Compares voltage detected, amplified and input to HIC with set voltage value in microcomputer, and controls overload when set value exceeds input voltage.
Voltage-amplifies DC current level detected by the detection resistor and inputs this to microcomputer. Internal or external overload is judged in microcomputer.
Produces reset voltage.
Modulates chopper signal to drive signal and stops according to presence/ab­sence of lp signal or reset signal.
59
17
61
48
58
62
+
+
60
Is
D104
L
CT1
N
R005
0V0V
0V
0V
R221
C218
12V
R292
R247
C107
0V
0V
R006
C105
+
+
C217
C009
JW10
R252
R222
R248
IC4
C205
R288
IC5
+
2
3
1
+
6
5
7
Fig. 8-1 Microcomputer and Peripheral Circuits
RESET
Is
Id
Ip
Vd
CN13CN14
R41
R24
N1
IC1
SPM2 – HIC
DC260-380V
P2
SPM2
MAIN P.W.B
Direct Current
DC Current
Detection Resistor
OC
F
0V0V
HIC
IC1
C2260VR285
R286
D205
D204
R249
R284
0V
C225
C224
0V
0V
C222
0V
0V
C204
0V
C215
R289
0V
0V
5V
5V
R253
R500
R42
R43
C34
37
521
19
20
8
99
10
3938
MICROCOMPUTER
0V
R245
Page 71
– 83 –
Drive
signal
Chopper
signal
Chopper
signal
DC Current level
DC current
Detection
resistor
5V
DC 260V
-360V
Reset circuit
Over-load external
setting circuit
Current amplified
circuit
Drive
Circuit
IP signal
Reset Voltage
Peak current cut off circuit
Outdoor microcomputer
Trip signal
synthesis circuit
Compressor
motor
Powe r module
Fig. 8-2
The following describes the operations of each circuit in detail.
(1) Peak current cut off circuit Fig.8-3 Peak Current Cut off Circuit and Waveforms at Each Section.
DC current Id
Voltage at point
(1.35V)
(27A)
Voltage at point
A
B
A
Fig.8-3
Detection
resistor
Negative Terminal
DC current
0V
0V
R43
0V
R41
QC
R42
SPM2
SPM2 – HIC
Main P.W.B
HIC
IC1
CN14
IP Outdoor microcomputer
F
R43
9 9
8
20 9 2 39 17
B
The Ip cut off circuit detects an instantaneous excessive current and stops inverter to protect parts such
as SPM2, etc.
As shown in diagram, if current exceeding 27A flows, voltage at point recognized by detecting resistor
is input to pin of SPM2 – HIC, and voltage divided by R41 and R43 is input to pin of IC1. Since threshold of IC1 is exceeded in this case, Lo signal is input from pin (Voltage at point . When Lo signal is input to pin of microcomputer, microcomputer stops drive output.
When drive output from microcomputer is stopped, all drive output goes Hi, and microcomputer is initialized
to enter drive signal standby mode. 3 minutes later, microcomputer outputs drive signal again, to start operation.
10
8
9
B
A
17
Page 72
– 84 –
(2) Overload control circuit (OVL control circuit)
Overload control is to decrease the speed of the compressor and reduce the load when the load on the
air conditioner increases to an overload state, in order to protect the compressor, electronic components and power breaker.
Overloads are judged by comparing the DC current level and set value.
Fig. 8-4 shows the overload control system configuration and Fig. 8-5 is a characteristic diagram of
overload judgement values. There are two judgement methods-external judgement which compares the externally set value with the DC current value regardless of the rotation speed and internal judgement which compares the set value that varies according to the rotation speed programmed in the microcomputer software with the DC current value.
To power module negative terminal
(R24)
DC current
Voltage amp
circuit
(Internal judgement)
DC voltage
Judgement value according to the rotation speed
(internal judgement value)
OVL judgement with respect to externally set value
A/D
converter
A/D
converter
Judgement OVL according to the rotation speed
Selects data according to the rotation speed and DC voltage
OVL start current data
Rotation speed data
Motor control process
Microcomputer
Detection
resistor
Fig. 8-4 Overload Control System Configuration
Fig. 8-5
DC current
Rotation speed
1. Overload external judgement circuit
Fig. 8-1. The filter consisting of R245 and C217 removes high harmonic components from the voltage
generated by the current flowing to Detection resistor; R245 and C217 average the voltage. This voltage is then input to IC4 pin is then amplified and supplied to microcomputer pin . The microcomputer compares this input with the internally set value, and if the input exceeds the set value, it enters overload control status.
Fig. 8-7 shows the rotation speed control. When the voltage at pin of the microcomputer exceeds the
set value, the microcomputer decreases the rotation speed of the compressor and reduces the load regardless of the rotation speed commanded by the indoor microcomputer.
5
60
60
Page 73
– 85 –
60
Fig. 8-6
Fig. 8-7
Voltage at microcomputer pin
Rotation speed of compressor
Deceleration DecelerationAcceleration Acceleration
Commanded rotation speed
Actual rotation speed
59
61
58
+
60
Is
D104
L
CT1
N
R005
0V0V
0V
0V
0V0V
R247
R006
C105
+
C217
C009
R222
C218
R221
R248IC4
+
6
5
7
Is
Id
Vd
CN13
CN14
R24
N1
DC 260-380V
SPM2
MAIN P.W.B.
P2
Direct Current
DC Current
Detection Resistor
HIC
IC1
Microcomputer
D205
D204
C224
0V
C222
0V0V
5V
5V
R253
R249
R500
+
C205
0V
5
1
373938
R245
10
1
2. Voltage amp. circuit
The voltage amp. circuit amplifies the DC current level detected by the detection resistor after being
converted to a voltage and supplies it to the microcomputer. Receiving this, the microcomputer converts it to a digital signal and compares it with the internal data to judge whether or not overload control is required.
< During overload control >
The filter consisting of R245 and C217 removes high harmonic components from the voltage generated
from the DC current flowing to the detection resistor, and supplies it to IC4 pin 5 IC4 forms a non-inverting voltage amp. circuit together with the peripheral elements.
The microcomputer stores the set values which vary according to the rotation speed. When the DC current
level exceeds the set value, the microcomputer enters the overload control state.
The set Value is determined by the amplification of the voltage amp. circuit.
Amplification : high [ DC current : low
Amplification : low [ DC current: high
{
Page 74
86
R500, R253, detect the DC voltage at the power circuit. The microcomputer receives a DC voltage (260-
380V) via HIC U and applies correction to the overload set value so the DC current is low (high) when the DC voltage is high (low).
(Since the load level is indicated by the DC voltage multiplied by DC current, R247, R248, R249 are provided to perform the same overload judgement even when the voltage varies.)
< During start current control >
It is required to maintain the start current (DC current) constant to smooth the start of the DC motor for
the compressor.
It is software to control the start current.
The start current varies when the supply voltage varies. This control method copes with variations in the
voltages as follows.
(1) Turns on the power module's U+ and V– transistors so the current flows to the motor windings as shown in Fig8-9.
(2) Varies the turn-ON time of the W+ transistor according to the DC voltage level and the start is controlled so the start current is approx. 10A as shown in Fig. 8-10.
Fig. 8-8
DC current
G
0
0
Rotation speed
Amplification : low DC voltage : low DC current : high
Amplification : high DC voltage : high DC current : low
Amplification : 8.5 times DC voltage : 260V
U
+
U
V
+
V
W
+
W
U V
W
Compressor motor
DC current
Power module
DC 260-360V
Detection
resistor
Fig. 8-9
Fig. 8-10
20
15
10
5
0
DC current (A)
W transistor
ON-time
Start
DC voltage (start current)
Set value
Time
Chopper duty: high
DC voltage: low DC voltage: 280V DC voltage: high
Page 75
87
9. Temperature Detection Circuit
The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the
Defrost. thermistor circuit detects the defrosting operation temperature.
A thermistor is a negative resistor element which has the characteristics that the higher (lower) the
temperature, the lower (higher) the resistance.
When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage at
pin 62 of microcomputer is increased.
Microcomputer compares the voltage present at pin
62
with the internal set value, if it is exceeded the
set value microcomputer judges that the compressor is overheated and stops operation.
When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly.
Therefore the resistance of the Defrost. thermistor becomes high and the voltage at pin
63
of microcomputer drops. If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
64
), and transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set at the EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dry mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins 62 – 64 are approx. 0V; when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode is entered 12 minutes after the compressor starts operation.
Table 9-1
Outdoor temperature (°C)
Microcomputer pin 5 voltage (V)
-10
1.1901.69102.23
20
3.22403.62
627
0V
+5V
O.H. thermistor
O.H.
Normal 2.7V or less Over heat 2.7V or more Reset 2.3V or less
CN8
636
0V
+5V
DEF. thermistor
DEF.
Normal 2.4V or more Over heat 2.4V or less Reset 2.9V or more
CN9
645
0V
+5V
Outdoor temperature thermistor
Outdoor temperature
Refer to the table 10-1
CN10
Microcomputer
HIC
Fig. 9-1
2.75
30
Page 76
88
10. Reset Circuit
The reset circuit initializes the microcomputer program when Power is ON or OFF”.
Low voltage at pin
48
resets the microcomputer, and HI activates the microcomputer.
Fig. 10-1 shows the reset circuit and Fig. 10-2 shows waveform at each point when power is turned on
and off.
When power is turned on, 12V line and 5V line voltages rise and 12V line voltage reaches 10.9V and
reset voltage input to pin 48 of microcomputer is set to Hi.
Reset voltage will be hold “Hi until the 12V line voltage drops to 9.90V even though the power shuts down.
Microcomputer
R252
R289
0V0V
R288
0V
5V
12V
HIC
R284
JW10
IC5 (1/2)
C204
48
RESET
Main
P. W . B
Fig. 10-1
C215
R286
C225
C107
C226
R285
0V
1
3
2
62
8
+
+
0V
0V
R292
12V line
12V line
5V line
5V line
Fig. 10-2
Reset voltage
Reset voltage
12
6
0
Power is ON
Voltage (V)
12
6
0
Power is OFF
Voltage (V)
Time
Time
Page 77
– 89 –
R297
R298
C208
R108
R107
C101
VSD
RC Filter
Motor coil
System power module
Power supply for DC fan motor from smoothing capacitor in system power module
Smoothing Capacitor
U
V
W
BOARD
DC Fan motor with control board
ONE CHIP DRIVER IC
R242
HIC
0V
0V
0V
0V
R283
R246
Q201
5V
PQ102
5V
5V
t
33.3KHz
Ap 7V
T/2
14
23
T
0V
0V
Vcc
PWM control voltage
FG Pulse
CN6
FM-0V
FM-15V
D101
Q101
R101
R102
Main P.W.B
CN12
FM-15V
FM-0V
12V
0V
0V
IC4
R244
Microcomputer
R243
D105
R104
R105
R103
R106
C104
C219
R114
C209
FM–60˚ el FG Pulse input
Fig. 11-1
1
3
60
61
59
2
8
15
75
65
+
+
C106
C103
ZD101
+
R115
7
6
5
4
3
2
1
321
123 4 5321
+++
2A-FUSE
11. Outdoor DC Fan Motor control circuit.
This model uses DC Fan Motor which has a controller circuit in the Motor.
This DC Fan Motor will rotate by control voltage apply to Vsp input. (Voltage range: 1.7 to 7V DC)
Vsp high : Faster ; Vsp low : slower ; Vsp lower than 1.7V : stop
Motor will output FG pulse by following this motor revolution.
Outdoor Microprocessor will output PWM control signal from FMCHOP terminal by following the instruction
from indoor Microprocessor.
This PWM control signal will convert to Vsp voltage by smoothing circuit (Q101 & RC filter)
Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by rotation
speed.
FG pulse will feed back to Outdoor Microprocessor through PQ102.
PQ102 is the isolator between Microprocessor circuit and DC Fan Motor circuit, which has to match the Fan
Motor revolution with instructed revolution. Such as...
FG feedback: Faster – Instruction: Slower ... Decrease pulse width FG feedback: Slower – Instruction: Faster ... Increase pulse width
FG pulse is also used for Fan Motor failure detection
Microprocessor will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected, it
will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on control PWB will blink 12 times. (Fan Motor lock detected)
R107 and IC4 are used for Fan Motor over current
Page 78
– 90 –
< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
It will makes Fan Lock Stopwhen something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make Fan Lock Stop by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
In case of Fan Lock Stop even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes, Fan Motor may be broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
Page 79
– 91 –
Power factor is controlled to almost 100%. (Effective use of power)
With IC in ACT module, control is performed so that input current waveform will be similar to waveform of input voltage
12. Power Factor Control Circuit
* Assuming the same current capacity (20A), power can be used about 10% effective, comparing with curent use (power factor of 90%), and maximum capacity is thereby improved.
I (input current)
V (input voltage)
Invalid power area
(Even if voltage is applied. current does not flow)
Effective
voltage
area
input voltage
input current
Effective
voltage area
Page 80
– 92 –
SERVICE CALL Q & A
COOLING MODE
The compressor has stopped suddenly during cooling operation.
Sound of running water is heard from indoor unit during dehumidifying.
Compressor occasionally does not operate during dehumidifying.
The circulation stops occasionally during Heating mode.
When the fan speed is set at HIGH or MED, the flow is actually Weak.
Heating operation stops while the temperature is preset at "30".
Check if the indoor heat exchanger is frosted. Wait for 3-4 minutes until it is defrosted.
If the air conditioner operates in cooling mode when it is cold, the evaporator may get frosted.
Normal sound when refrigerant flows in pipe.
Compressor may not operate when room temperature is 10°C or less. It also stops when the humidity is preset humidity or less.
It occurs during defrost­ing. Wait for 5-10 minutes until the condenser is defrosted.
At the beginning of heating, the fan speed remains LOW for 30 seconds. If HIGH is selected, it switches to LOW and again to MED after additional 30 seconds.
If temperature is high in the outdoor, heating operation may stop to protect internal devices.
DEHUMIDIFYING MODE
HEATING MODE
Q1
A1
Q2
A2
Q3
A3
Q4
A4
Q5
A5
Q6
A6
Page 81
– 93 –
AUTO FRESH DEFROSTING
AUTO OPERATION
NICE TEMPERATURE RESERVATION
INFRARED REMOTE CONTROL
After the ON/OFF button is pressed to stop heating, the outdoor unit is still working with the OPERATION lamp lighting.
Fan speed does not change when fan speed selector is changed during auto operation.
When on-timer has been programmed, operation starts before the preset time has been reached.
Does “Nice temperature reservation” function operate during dehumidifying?
Even if the same time is preset, the operation start time varies.
Timer cannot be set.
The current time display disappears soon.
The timer has been programmed, but the preset time disappears.
Auto Fresh Defrosting is carried out : the system checks the outdoor heat exchanger and defrosts it as necessary before stopping operation.
At this point fan speed is automatic.
This is because “Nice temperature reservation” function is operating. This function starts operation earlier so the preset temperature is reached at the preset time. Operation may start maximum 60 minutes before the preset time.
It does not work. It works only during cooling and heating.
This is because “Nice temperature reservation” function is operating. The start time varies according to the load of room. Since load varies greatly during heating, the operation start time is corrected, so it will vary each day.
Has the clock been set? Timer cannot be set unless the clock has been set.
The current time disappears in approx. 10 seconds. The time set display has priority.
Is the current time past the preset time? When the preset time reaches the current time, it disappears.
When the current time is set the display flashes for approx 3 minutes.
Q7
A7
Q8
A8
Q9
A9
Q10
A10
A11
Q12
A12
Q13
A13
Q14
A14
Q11
Page 82
– 94 –
OTHERS
Q15
A15
Q16
A16
Q17
A17
Q18
A18
Q19
A19
The indoor fan varies among high air flow, low air flow and breeze in the auto fan speed mode. (Heating operation)
This is because the cool wind prevention function is operating, and does not indicate a fault.
The heat exchanger temperature is sensed in the auto speed mode. When the temperature is low, the fan speed varies among high air flow, low air flow and breeze.
Loud noise from the outdoor unit is heard when operation is started.
When operation is started, the compressor rotation speed goes to maximum to increase the heating or cooling capability, so noise becomes slightly louder. This does not indicate a fault.
Noise from the outdoor unit occasionally changes.
The compressor rotation speed changes according to the difference between the thermostat set temperature and room temperature. This does not indicate a fault.
There is a difference between the set temperature and room temperature.
There may be a difference between the set temperature and room temperature because of construction of room, air current, etc. Set the temperature at a comfortable for the space.
Air does not flow immediately after operation is started.
Preliminary operation is performed for one minute when the power switch on and heating or dehumidifying is set. The operation lamp blinks during this time for heating. This does not indicate a fault.
Page 83
– 95 –
TROUBLE SHOOTING
PRECAUTIONS FOR CHECKING
Power source
+
~
+
~
ACT Module
+–+
N
C
D
L
Compressor motor
System power module 2
Indoor unit electric parts
Control P. W . B .
DC35V
0V
(0V)
MAIN P.W.B.
Power module
a
b
M
1. Remember that the 0V line is biased to 155-170V in reference to the ground level.
2. Also note that it takes about 10 minutes until the voltage fall after the power switch is turned off.
DANGER
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
approx 260-360V
approx 155-170V
approx 155-170V
When using an oscilloscope, never ground it. Don't forget that high voltages as noted above may apply to the oscilloscope.
DANGER
Always keep your hands and metallic things away from the enclosure of the oscilloscope.
DANGER!
Dont install
the ground
line.
Oscilloscope
Outdoor unit P.W.B.
Page 84
– 96 –
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before performing operation chech of each circuit.
Caution
Voltage of about 300-330V is charged between both ends of smoothing capacitors
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray lead wire connected from diode stack to system power module (SPM2) to prevent secondary trouble. (Be sure to discharge smoothing capacitor)
Do not use a soldering iron with transformer: If one is used, thermal fuse inside transformer will be blown
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
WARNING
As shown above, apply soldering iron to metal parts (receptable) inside the sleeve corresponding to P1 and N1 terminals of system power module: Do this with smoothing capacitors kept connected. By removing red/ gray lead wire from diode stack, power supply can be shut off. (corresponding to + and – terminals of system power module)
N1
P1
Soldering iron
System power module
SPM2
Smoothing capacitors
Page 85
97
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Does the timer lamp on the indoor unit blink?
Is the compressor in the outdoor unit operating?
Does the operation lamp on the indoor unit start to light or blink?
Remove the outdoor unit cover and electrical parts cover, and check self-diagnosis lamp LD301
Does LD301 blink one time ? * Repeats 0.25-second on and 2-second off.
Blinking other than one time
One-time blinking
Ye s
Ye s
Ye s
Ye s N o
No
No
Normal
No
No
Timer lamp
Press the service switch for 1 sec. Does the compressor operate? (After checking, be sure to press the service switch to stop the operation).
Check the refrigerating cycle.
Check the outdoor electrical parts.
Check the indoor electrical parts.
Check to see whether the F­cable is connected incorrectly or disconnected
See Out door unit self-diagnosis lamp lighting mode.
See Troubleshooting when the timer lamp blinks.
Is approx. DC 33 to 37V being generated? Is the polarity correct?
Remove the terminal cover and check the voltage between terminal (C) and terminal (D)
Service switch
P. W . B Self diagnosis lamps (LD303, 302, 301)
CN17
IC3
022527
Terminal C (+35V)
Terminal D
(0V)
Page 86
– 98 –
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
SELF-DIAGNOSIS LIGHTING MODE
No. Blinking of Timer lamp Reason for indication Possible cause
Reversing valve defective When the indoor heat exchanger temperature is too low in the heating mode or it is too high in the cooling mode.
Outdoor unit forced operation When the outdoor unit is in forced operation or balancing operation after forced operation
Indoor/outdoor interface defective When the interface signal from the outdoor unit is interrupted.
Outdoor electrical assembly defective.
Room thermistor or heat exchanger thermistor is faulty When room thermistor or heat exchanger thermistor is opened circuit or short circuit.
Over-current detection at the DC fan motor when over-current is detected at the DC fan motor of the indoor unit.
IC401 or IC402 data reading error When data read from IC401 or IC402 is incorrect.
(1) Reversing valve defective (2) Heat exchanger thermistor dis-
connected
(only in the heating mode) (Note) The malfunction mode is entered the 3rd time this abnormal indication appears (read every 3 minutes).
Electrical parts in the outdoor unit
(1) Indoor interface circuit (2) Outdoor interface circuit
Please check at the outdoor electrical led lamp blinking (LD301) and refer to self diagnosis lighting mode for outdoor unit.
(1) Room thermistor (2) Heat exchanger thermistor
(1) Indoor fan locked (2) Indoor fan motor (3) Indoor control P.W.B.
IC401 or IC402 abnormal
<Cautions>
(1) If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2) If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected.
(3) To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
1
2
3
4
5
6
7
( –– Lights for 0.5 sec. at interval of 0.5 sec..)
–– 10 times
– ––––– 3 times
– ––––––– 1 time
– –––––– 2 times
–– 13 times1
–– 9 times
–– 4 times
5 sec.
5 sec.
5 sec.
5 sec.
5 sec.
5 sec.
5 sec.
Page 87
– 99 –
SELF-DIAGNOSIS LIGHTING MODE
Page 88
– 100 –
1. Power does not come on (no operation)
Is AC 220-240V AC being generated between terminals L and N on the outdoor unit terminal board?
Is DC 35V being generated between terminals C and D on the outdoor unit terminal board?
Check the indoor/outdoor unit connection cable, and correct any defective section (wrong connection, incomplete insertion reversed).
Check AC outlet and breaker, and repair any defective part.
Check the outdoor unit power circuit, and repair the defective section.
Is DC 35V being generated between terminals C and D on the terminal board?
Are control voltages (12V, 5V) being generated normally?
Check according to the proper method for checking the power circuit.
No No
No
No
Ye s
Ye s
Do the air deflectors perform initial operation when the power supply is turned on and off?
Check the indication P.W.B. connection cord and light receiving unit.
No
No
Is the microcomputer reset input (pin 7 )Hi?
Replace the control P.W.B
Perform final operation check.
Check the reset circuit, and repair any defective section.
Ye s
No
Is the microcomputer clock signal 10MHz at pin
10 11
being
generated normally?
Replace the microcomputer and oscillator.
Ye s
Ye s
Ye s
CHECKING INDOOR UNIT ELECTRICAL PARTS
Page 89
101
2. Outdoor unit does not operate (but receives remote infrared signal)
Page 90
102
3. Only indoor fan does not operate (other is normal)
4. Air deflector does not move (others are normal)
5. All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
Page 91
103
6. Check the main P.W.B (power circuit)
Page 92
104
CHECKING THE REMOTE CONTROLLER
Page 93
– 105 –
[No operation or abnormal operation]
Is AC220-240V being
supplied to terminal L and N?
Is the 25A fuse normal?
If the 25A fuse has blown, be aware
that other parts may also be
defective (mainly, varistor 2, diode
stack, smoothing capacitors, system
power module, etc.).
No
Ye s
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
Replace any defective parts.
Is the power circuit normal?
See the description on
power circuit for details.
Is 5V being generated
between Pin 4 (0V) and pin
3 (5V) at CN 18 (test pin)?
Operate the outdoor unit
according to the instruction
How to operate the outdoor
unit independently
.
How did the self-diagnosis
lamp (LD301) light?
Is the switching power circuit OK?
Has the 3A fuse blown?
See the self-diagnosis lamp
lighting mode.
Check to see whether the
connected C and D cable
correctly? If reversed, correct the
cable connection.
Replace any defective parts.
If the 3A fuse has blown, the
switching transformer (T1),
R906, etc. may also be
defective.
()
No
Ye s
Ye s
No
Ye s
Page 94
– 106 –
LD301 blinks 9 time.
Communication error.
Is DC 35V being output at
terminals C and D? (Normally,
DC 33-38.5V is output.)
Ye s
Interface relay
Coil terminal
Contact terminal
Is DC 35V being output across R914?
Is DC 12V being supplied across
the control side (coil terminal) of
interface relay?
Is a voltage (at least 10V) being
generated between the contact
terminals of interface relay?
Check the interface curcuit.
Ye s
Ye s
No
No
Ye s
D907 and C910 may be defective.
There is a defective section between the
12V output of switching power supply on
the main P.W.B. and interface relay (also,
check for contact with solder, etc.).
Repalce the interface relay.
No
Page 95
– 107 –
Ye s N o
No
Ye s
Ye s
Ye s
No
No
No
LD301 blinks 8 time.
Acceleration defect.
LD301 blinks 7 time.
Thermistor abnormal.
Is the power module normal?
Is the drive circuit normal?
Is the thermistor connector
disconnected?
The problem may be
forgetting
to connect after servicing
.
Is the continuity of thermistor normal?
Is the thermistor circuit normal?
Replace the power module.
Replace any defective parts.
Connect the thermistor.
Replace the thermistor.
Replace parts in the
thermistor circuit.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Page 96
– 108 –
LD301 blinks 6 time.
The temperature at the
OH thermistor rises.
LD301 blinks 5 time.
Overload lower limit cut.
LD301 blinks 4 time.
Failure of switching.
LD301 blinks 3 time.
Abnormal low speed.
Replace parts in the
thermistor circuit.
No
No
No
Check continuity of new parts.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Ye s
Ye s
Replace system power
module or defective parts.
Replace the system power
module.
Replace any defective
parts.
Is the thermistor circuit normal?
Are R503 and peripheral
circuits of system power module
normal?
Replace the main P.W.B.
Is the system power module
normal?
Is the drive circuit normal?
Page 97
109
Page 98
110
POWER CIRCUIT
Phenomenon 1 <Rotation speed does not increase>
Is the DC voltage at least 350V?
Is the OVL lamp lit? If the lamp is lit, it does not indicate fault, but the unit is overload status.
Recheck cord, etc. of the system power module. If they are disconnected, connect them securely.
If abnormality continues, replace the system power module.
Overvoltage defect: system power module faulty (15-times blinking)
Ye s
No
Page 99
– 111 –
CHECKING THE REFRIGERATING CYCLE
1. Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the power module again and operate the air conditioner.
Gas leaks. Repair and seal refrigerant.
Is the self-diagnosis lamp mode as shown on the right?
YES
Gas leaking (less than 4kg/cm
2
G)
(less than 0.39 MPaG)
Normal (0.39-0.98 MPaG) (4-10 kg/cm
2
G)
Perform a final check of operation.
When the self-diagnosis lamp lights in the same condition as above.
The compressor is defective. Replace it and seal refrigerant.
If the compressor checker for an inverter type air conditioner is available, re-check using it.
( )
(JUDGING BETWEEN GAS LEAKAGE AND COMPRESSOR DEFECTIVE)
Blinking off
Time until the
lamp lights
Approx. 10 seconds
Approx. 10 seconds
Approx. 10 seconds
Within Approx. 30 seconds
Compressor
Compressor
Gas leakage
Possible
malfunctioning
part
LD301
Self­diagnosis lamp
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8times
Stop to operate and check the gas pressure in balancing mode.
Checking the system power module
Page 100
112
HOW TO CHECK SYSTEM POWER MODULE
+
+
+
– +
+
P1 P2 U
WV
N1
L2 L1
+
+
+
P1 P2 U
WV
N1
L2 L1
Checking system power module using tester
Set tester to resistance range (X 100) If indicator does not swing in the following conductivity check, the system power module is normal. (In case of digital tester, since built-in battery is set in reverse direction, + and – terminals are reversed.)
CAUTION
If inner circuit of system power module is disconnected (open), the indicator of tester will not swing and this may assumed as normal. In this case, if indicator swings when + and – terminals are connected in reverse of diagram below, it is normal. Furthermore, compare how indicator swings at U, V and W phases. If indicator swings the same way at each point, it is normal.
Loading...