1
EN
FOR SERVICE PERSONNEL ONLY
INDOOR UNIT
RAK-18QXB
MODEL
SAFETY PRECAUTION
• Read the safety precautions carefully before operating the unit.
• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION .......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
• Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
• Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
• Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
• Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
• Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
• Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
• Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
• When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.
• Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.
• After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
• Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
• Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.
• When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
• When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
•
The electric cables should neither be reworked nor added.
Make sure to use an exclusive circuit breaker.
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
•
Otherwise, over heating at terminal contact, fire or electric shock might occur.
Make sure that there is no dust on any connected points of electric cables and fix firmly.
•
Otherwise, fire or electric shock might occur.
RAK-25RXB
RAK-35RXB
RAK-50RXB
WARNING
CAUTION
•
A circuit breaker must be installed in the house distribution box for the direct
connected power supply cables to the outdoor unit. In case of other
installations
a main switch with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas.
•
The outdoor unit may catch fire if flammable gas leaks around it.
•
Please ensure smooth flow of water when installing the drain hose. Improper
installing may wet your funiture.
•
An IEC approved power cord should be used. Power cord type:
NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation.)
WARNING
•
The unit should be mounted at stable, non-vibratory location which can
full support to the unit.
provide
CAUTION
• No nearby heat source and no obstruction near the air outlet is allowed.
•
The clearance distances from top, right and left are specified in figure
The location must be convenient for water drainage and pipe connection
•
with the Outdoor unit.
• To avoid interference from noise, please place the unit and its remote
controller at least 1m from the radio and television.
To avoid any error in signal transmission from the remote controller,
•
put the controller far away from high-frequency machines and high-power
wireless systems.
size Battery
AAA
from the floor.
The installation height should be at least 2300 mm or more
•
Be sure to
completely
seal any
gap with
putty.
about 450mm
dneb ton tsum
mm003 tuoba
9
4
Figure showing the Installation
above
above
50mm
50mm
1
Th e i nd oo r p ip ing
sh oul d be i ns ula te d
wi th th e e ncl os ed
insulation pipe. (If the
insulator is insufficient,
please use commercial
products.)
Plug
7
8
above
50mm
2300 mm or more
2
of Indoor Unit.
Names of Indoor Components
No. Item Qty
Hanger
1
Screw for Hanger
2
3
Remote Controller
4
Wasabi-Nano Titanium
Air Cleaning Mesh
5
Direction of Piping
3
Backward piping
from left
Connection
There are 6 directions
allowed,namely,backward
piping, backward piping
from left,horizontally piping
from right,horizontally piping
from left,vertically down from
right,vertically down from left.
C-case
6
Remote Controller Holder
7
Screw for Remote
Controller Holder
8
Insulation sheet
9
below.
please
1
5
2
1
2
2
1
2
1
1 Installation of Hanger , Wall Penetration and Installation of Protection Pipe
CAUTION
• The draining of the water container inside the Indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Installation Of Remote Controller
Direct Mounting On The Wall
• Please use hidden beams in the wall to hold the hanger.
Visible outline of the
outdoor unit
100
42.5
180
Line
Level
Weight
668
550
2
Wall hole
100
160
115
Screw for Hanger
Hanger
1
37
39
193
Drain Hose
Screw the hanger at the
positions possibly near the
upper and lower hooks where
the indoor unit is hung. Use 4 or
more screws to fix the hanger.
Wall Penetration and Installation of Protection Pipe
Procedures of Installation and Precautions
• Procedures to fix the hanger.
1.Drill holes on wall.
(As shown below)
Wall
32mm
ø mm8.4
• Procedures to fix the holder of remote control.
Drill holes on wall.
1.
Wall
ø mm4.4
2.Push plug into the holes.
(As shown below)
Hanger
1
Screw
2
Wall
(As shown below)
20mm
3.Fix the hanger on
with 4.1 x 32 screw.
Plug
(Procure
locally)
Push plug into the holes.
2.
Remote
7
Control
Holder
(As shown in figure below)
Plug (Procure locally)
Ceiling
(As shown below)
Screw
8
wall
•
The remote controller can be placed in its holder which is fixed on
wall or beam.
To operate the remote controller at its holder, please ensure that the
•
unit can receive signal transmitted from the controller at the place where
the holder is to be fixed.The unit will beep when signal is received from
the remote controller . The signal transmission is weaken by the fluorescent
light. Therefore, during the installation of the remote control holder, please
switch on the light, even during day time, to determine the mounting
of
the holder
• Drill a ø65mm hole on wall which is
.
Screw (2 pieces)
Remote
Controller
Remote
Controller
Holder
The remote controller
must be slide in
the remote controller
holder, in the direction
as shown in the figure,
until it hooks at the
lower end of the remote
controller holder.
Indoor
slightly tilted towards the outdoor side.
Drill the wall at a small angle.
•
Cut the protection pipe according to the
wall thickness.
Empty gap in the sleeve of protection
•
Seal with
putty
location
Outdoor
2-5mm
Seal with
putty
pipe should be completely sealed with
putty to avoid dripping of rain water into
the room.
Please ensure smooth flow of water
•
when installing the drain hose. Improper
installing may wet your funiture.
•
An IEC approved power cord should be
Protection
pipe
WALL
Sleeve of
protection
pipe
used. Power cord type: NYM.
WARNING
Be sure that the wire is not in contact with any metal in the wall.
Please use the protection pipe as wire passing through the
hollow part of the wall so as to prevent the possibility of
damaged by mouse. Unless it seals completely,any air with high
humidity flows from outdoor and any dew may drop.
2 Installation Of The Indoor Unit
Cutting Low Cover bush
•
While installing the pipe from the right, left or bottom
side, use a knife to cut openings as shown in figure.
Then smoothen the edges of openings with a file.
Openings
Openings
1
PIPING FROM THE RIGHT SIDE
(BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
•
Connect connecting cord.
•
Pull out the pipe, connecting
cord and drain hose.
Connecting cords, pipe and
drain hose must be laid
Installation
•
Insert the pipe through the wall hole.
1
The upper part of the Indoor unit
is hanged on the hanger.
2
The projection at the lower part
of the Indoor unit is hooked onto
the hanger.
Hanger
1
Refrigerating
Pipe
Protection
Pipe
Drain Hose
Connecting Cord
together with Vinyl tape.
Cable
Drain layout of
backward piping
Lift the body
of the unit
upwards and
then force it
downwards.
Wall hole
1
2
Pipe
Drain hose
1
Hanger
Projection
RAK-15QPB/RAK-18_25RPB_IM_English
1
2
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
•
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
• Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain
cap).
CAUTION
Insufficient insert may
result in water leakage.
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
1 Preparation of Pipe
• Use a pipe cutter to cut the copper pipe and remove burr.
Trimming tool
Copper pipe
• Please be careful when bending the copper pipe.
• Screw in manually while adjusting the center.
After that, use a torque wrench to tighten the
connection.
Flare nut
Drain cap
Drain cap
Drain Hose
Remove low cover
•
•
Insert drain cap up to the
location securely till the
cap stops.
•
Push the pipe deeply until the insulating
section of the drain hose end gets over the
rib at the indoor unit side.
CAUTION
•
The rubber strap used for fixing the insulator should not
t eb ied with great force. Otherwise,this will damage heat
insulation and causes water condensation.
Pipe
Rubber strap tied
with great force
• Please pull the lower part of the Indoor unit outwards to
check if the unit is hooked onto the hanger. Improper
installation may cause vibration and noise.
• Transform the piping while holding down the
of pipe-support by hand.
lower portion
Pipe
support
Transform after
bending downward.
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
• The refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further
connection.
• The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
• Connect the connecting cord after removing low
cover.
(Refer to "CONNECTION OF POWER CORD")
• After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to
hold them tight.
• Holder can be attached at the either of 2 places.
Please select the easier position.
Pipe
Insulation pipe (must be wrapped with
vinyl tape at every 120 mm)
Drain hose
Connecting
cord
THE CONNECTION OF REFRIGERATING PIPE DURING
THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
• The refrigeratin g p ipes and connecti ng cor d
transform and are attached.
Installation
Hang the indoor unit onto the hanger. Use the temporar
at the back of the Indoor unit to push its lower part 15cm
forwards.
• Place the drain hose through the hole on the wall.
• Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
• Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
• After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
• The projection of Indoor unit must hook to the hanger.
Wall hole
Pipe
Cable
Drain layout of
backward piping
from left
Drain
hose
Connecting
cord
3 Heat Insulation and Finish of the Piping
• The connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
• Do not tie the terminals with the tape too tight.
If a ny cleara nc e or over-tightening may cau se
condensation.
• Please tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of
Indoor and Outdoor units.
• To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the
drain hose and pipe with insulation pipe.
• Completely seal any gap with putty.
4 Installation of Drain Hose
Please bend at a small
radius to form an arc
Refrigerating
pipe
Heat
insulation pipe
Pull this to the front during
the connection of refrigerating
pipe to ease task.
The end of the refrigerating pipes are at
locations marked with “
” symbol.
y stand
Projection
about 15cm
Protection
pipe
Drain hose
Connecting cord
Insulation material for pipe
connection
Sleeve of
protection pipe
Putty
below
5mm
Hook
Connected
section
Putty
CAUTION
Bending upwards
CAUTION
Ditch
Condensed water
pond
Condensed water
pond
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Careless may result in water leakage.)
Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.
HOW TO REMOVE INDOOR UNIT
•
Push up the [PUSH] sections at the bottom of the indoor unit
and pull the bottom plate towards you. Then the claws are
released from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right
figure)
[PUSH] mark positions
CAUTION
Wrench
• Remove burr and jagged edge will cause leakage.
• Point the side to be trimmed downwards during
trimming to prevent copper chips from entering the pipe.
• Before flaring, please put on the flare nut.
Die
Die
• Please use
exclusive tool for
Copper pipe
refrigerant R410A.
Outer A (mm) Rigid Flaring Tool
Small diameter side
Large diameter side
Valve head
cap
Small diameter side
Large diameter side
Valve core cap
Outer diameter
of pipe (ø)
6.35 (1/4”) 13.7 – 18.6 (140 – 190)
Diameter (Ø) For R410A tool For R22 tool
6.35 (1/4") 0 - 0.5 1.0
9.52 (3/8") 0 - 0.5 1.0
0 - 0.5 1.012.7 (1/2")
2 Pipe Connection
CAUTION
Gas leakage inspection
Please use gas leakage detector to check if
leakage
occurs at
as shown in below.
further tighten the connection
connection of Flare nut
If gas leakage occurs,
• In case of removing flare nut of a indoor unit, first remove
a nut of small diameter side, or a seal cap of big diameter
side will fly out. Free from water into the piping when
working.
• Be sure to tighten the flare nut to the specified torque with
a torque wrench.
If the flare nut is overtightened, the nut may be split after a
long period has passed, and may cause a refrigerant leak.
DROC REWOP FO NOITCENNOC
2
in
2
ler
CN21
CN6
WARNING
• THIS APPLIANCE MUST BE EARTHED.
Detail of Cutting the Connecting Cord
Indoor Unit
70mm
10mm
Strip
wires
10mm
45mm
1
2
3
WARNING
•
Leave some space in the connecting cord for
maintenance purpose and be sure to secure
it with the cord band.
Secure the connecting cord along the coated part of the wire using
•
the cord band. Do not exert pressure on the wire as this may cause
overheating or fire.
Wiring of The Indoor Unit
•
For wire connection of the Indoor unit, you need to remove the front
cover, the
•
Remove the cover from the terminal base and screw the cable.
low cover under the body of the unit and terminal cover.
3
2
1
Earth
After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.
Green + Yellow
(ground)
Connecting cord
Connecting
cord
Cord band
Method to remove the low cover
•
Pull at the 1 and
the directions as shown
by arrows to remove the
cover.
How to connect the optional parts
(H-LINK RAC Adapter, Dry contact, Wired Remote
Controller)
• For cable connection to control P.W.B., you need to
remove front cover and electrical box cover.
Each connecting location is as below.
1
Dry contact: CN6
2
H-LINK RAC Adapter:CN7
3
Wired Remote Control : CN20
• Please check and confirm manuals attached to each
optional parts for more connection details.
• You can refer to this installation manual how to remove
and re-attach the front cover.
• Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
CN20
CN7
FINAL STAGE OF INSTALLATION
How to remove the front cover How to Attach the Front Cover
1
Remove the front panel
• Please remove and attach the front panel by
Shaft
Hole
both hands.
• After opening the front panel by both hands.
1
Undo the right arm while pushing it inside.
2
Slide the front panel to right as shown in figure.
Then remove while pulling it to front.
2
Remove the filters.
3
After removing three screws, pull the center of the
front cover
4
Pull the side faces (lower sections) of the front
and release the claws.
cover towards you as shown in the figure and
remove the cover.
Screw
Screw
ECO Sensor
1
Check that the drain pan is securely attached.
After installing the front cover onto the unit, hook three claws
2
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.
Tighten three screws.
3
Install the filter.
4
5
Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.
Shaft
Hole
CAUTION
Remove and attach the front cover to the
direction as shown in the figure to ensure
no damage occurs to the ECO sensor.
Torque
wrench
44.1 – 53.9 (450 – 550)
)”2/1( 7.21
12.3 – 15.7 (125 – 160)
to stop leakage.
CN7
CN6
X
Torque N·m
(kgf·cm)
1
O
)054 – 053( 1.44 – 3.43 )”8/3( 25.9
)052 – 002( 5.42 – 6.91 )”4/1( 53.6
)052 – 002( 5.42 – 6.91 )”8/3( 25.9
)053 – 003( 3.43 – 4.92 )”2/1( 7.21
RAK-15QPB/RAK-18_25RPB_IM_English
2