Hitachi RAK-18QXB, RAK-35RXB, RAK-25RXB, RAK-50RXB Installation manual

1
EN
FOR SERVICE PERSONNEL ONLY
INDOOR UNIT
RAK-18QXB
MODEL
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION .......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or stronger vibration may occur.
Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause electric shocks.
When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
When installing the unit, be sure to install the refrigerant pipe before starting the compressor. If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
The electric cables should neither be reworked nor added. Make sure to use an exclusive circuit breaker. Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
Otherwise, over heating at terminal contact, fire or electric shock might occur. Make sure that there is no dust on any connected points of electric cables and fix firmly.
Otherwise, fire or electric shock might occur.
RAK-25RXB RAK-35RXB RAK-50RXB
WARNING
CAUTION
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other
installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas.
The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.
An IEC approved power cord should be used. Power cord type:
NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation.)
WARNING
The unit should be mounted at stable, non-vibratory location which can
full support to the unit.
provide
CAUTION
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure
The location must be convenient for water drainage and pipe connection
with the Outdoor unit.
To avoid interference from noise, please place the unit and its remote controller at least 1m from the radio and television. To avoid any error in signal transmission from the remote controller,
put the controller far away from high-frequency machines and high-power
wireless systems.
size Battery
AAA
from the floor.
The installation height should be at least 2300 mm or more
Be sure to completely seal any gap with putty.
about 450mm
dneb ton tsum
mm003 tuoba
9
4
Figure showing the Installation
above
above
50mm
50mm
1
Th e i nd oo r p ip ing sh oul d be i ns ula te d wi th th e e ncl os ed insulation pipe. (If the
insulator is insufficient,
please use commercial
products.)
Plug
7
8
above
50mm
2300 mm or more
2
Names of Indoor Components
No. Item Qty
Hanger
1
Screw for Hanger
2
3
Remote Controller
4
Wasabi-Nano Titanium Air Cleaning Mesh
5
Direction of Piping
3
Backward piping from left
Connection
There are 6 directions allowed,namely,backward piping, backward piping from left,horizontally piping from right,horizontally piping from left,vertically down from right,vertically down from left.
C-case
6
Remote Controller Holder
7
Screw for Remote
Controller Holder
8
Insulation sheet
9
below.
please
1
5
2
1
2
2
1
2
1
1 Installation of Hanger , Wall Penetration and Installation of Protection Pipe
CAUTION
The draining of the water container inside the Indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Installation Of Remote Controller
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Visible outline of the outdoor unit
100
42.5
180
Line
Level
Weight
668
550
2
Wall hole
100
160
115
Screw for Hanger
Hanger
1
37
39
193
Drain Hose
Screw the hanger at the positions possibly near the upper and lower hooks where the indoor unit is hung. Use 4 or more screws to fix the hanger.
Wall Penetration and Installation of Protection Pipe
Procedures of Installation and Precautions
Procedures to fix the hanger.
1.Drill holes on wall.
(As shown below)
Wall
32mm
ø mm8.4
Procedures to fix the holder of remote control. Drill holes on wall.
1.
Wall
ø mm4.4
2.Push plug into the holes. (As shown below)
Hanger
1
Screw
2
Wall
(As shown below)
20mm
3.Fix the hanger on with 4.1 x 32 screw.
Plug (Procure locally)
Push plug into the holes.
2.
Remote
7
Control Holder
(As shown in figure below)
Plug (Procure locally)
Ceiling
(As shown below)
Screw
8
wall
The remote controller can be placed in its holder which is fixed on wall or beam. To operate the remote controller at its holder, please ensure that the
unit can receive signal transmitted from the controller at the place where the holder is to be fixed.The unit will beep when signal is received from the remote controller . The signal transmission is weaken by the fluorescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting of
the holder
Drill a ø65mm hole on wall which is
.
Screw (2 pieces)
Remote Controller
Remote Controller Holder
The remote controller must be slide in the remote controller holder, in the direction as shown in the figure, until it hooks at the lower end of the remote controller holder.
Indoor
slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness. Empty gap in the sleeve of protection
Seal with putty
location
Outdoor
2-5mm
Seal with putty
pipe should be completely sealed with putty to avoid dripping of rain water into the room. Please ensure smooth flow of water
when installing the drain hose. Improper installing may wet your funiture.
An IEC approved power cord should be
Protection pipe
WALL
Sleeve of protection pipe
used. Power cord type: NYM.
WARNING
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse. Unless it seals completely,any air with high humidity flows from outdoor and any dew may drop.
2 Installation Of The Indoor Unit
Cutting Low Cover bush
While installing the pipe from the right, left or bottom
side, use a knife to cut openings as shown in figure.
Then smoothen the edges of openings with a file.
Openings
Openings
1
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Connecting cords, pipe and drain hose must be laid
Installation
Insert the pipe through the wall hole.
1
The upper part of the Indoor unit is hanged on the hanger.
2
The projection at the lower part
of the Indoor unit is hooked onto the hanger.
Hanger
1
Refrigerating Pipe
Protection Pipe
Drain Hose
Connecting Cord
together with Vinyl tape.
Cable
Drain layout of backward piping
Lift the body of the unit upwards and then force it downwards.
Wall hole
1
2
Pipe
Drain hose
1
Hanger
Projection
RAK-15QPB/RAK-18_25RPB_IM_English
1
A
2
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
CAUTION
Insufficient insert may result in water leakage.
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
1 Preparation of Pipe
Use a pipe cutter to cut the copper pipe and remove burr.
Trimming tool
Copper pipe
Please be careful when bending the copper pipe.
Screw in manually while adjusting the center.
After that, use a torque wrench to tighten the connection.
Flare nut
Drain cap
Drain cap
Drain Hose
Remove low cover
Insert drain cap up to the location securely till the cap stops.
Push the pipe deeply until the insulating section of the drain hose end gets over the rib at the indoor unit side.
CAUTION
The rubber strap used for fixing the insulator should not
t eb ied with great force. Otherwise,this will damage heat
insulation and causes water condensation.
Pipe
Rubber strap tied with great force
Please pull the lower part of the Indoor unit outwards to check if the unit is hooked onto the hanger. Improper
installation may cause vibration and noise.
Transform the piping while holding down the
of pipe-support by hand.
lower portion
Pipe support
Transform after bending downward.
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
The refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord after removing low
cover. (Refer to "CONNECTION OF POWER CORD")
After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to hold them tight.
Holder can be attached at the either of 2 places.
Please select the easier position.
Pipe
Insulation pipe (must be wrapped with vinyl tape at every 120 mm)
Drain hose
Connecting cord
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigeratin g p ipes and connecti ng cor d
transform and are attached.
Installation
Hang the indoor unit onto the hanger. Use the temporar at the back of the Indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
Wall hole
Pipe
Cable
Drain layout of backward piping from left
Drain hose
Connecting
cord
3 Heat Insulation and Finish of the Piping
The connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
Do not tie the terminals with the tape too tight.
If a ny cleara nc e or over-tightening may cau se condensation.
Please tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of Indoor and Outdoor units.
To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
4 Installation of Drain Hose
Please bend at a small radius to form an arc
Refrigerating pipe
Heat insulation pipe
Pull this to the front during the connection of refrigerating pipe to ease task.
The end of the refrigerating pipes are at locations marked with “
” symbol.
y stand
Projection
about 15cm
Protection
pipe
Drain hose
Connecting cord
Insulation material for pipe connection
Sleeve of protection pipe
Putty
below
5mm
Hook
Connected section
Putty
CAUTION
Bending upwards
CAUTION
Ditch
Condensed water
pond
Condensed water
pond
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth flow of condensed water of the Indoor unit during installation. (Careless may result in water leakage.)
Be sure that the drain hose is not loosely connected bend or proper condition like left figure.
HOW TO REMOVE INDOOR UNIT
Push up the [PUSH] sections at the bottom of the indoor unit and pull the bottom plate towards you. Then the claws are released from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)
[PUSH] mark positions
CAUTION
Wrench
Remove burr and jagged edge will cause leakage.
Point the side to be trimmed downwards during
trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
Die
Die
Please use exclusive tool for
Copper pipe
refrigerant R410A.
Outer A (mm) Rigid Flaring Tool
Small diameter side
Large diameter side
Valve head cap
Small diameter side
Large diameter side
Valve core cap
Outer diameter
of pipe (ø)
6.35 (1/4”) 13.7 – 18.6 (140 – 190)
Diameter (Ø) For R410A tool For R22 tool
6.35 (1/4") 0 - 0.5 1.0
9.52 (3/8") 0 - 0.5 1.0
0 - 0.5 1.012.7 (1/2")
2 Pipe Connection
CAUTION
Gas leakage inspection
Please use gas leakage detector to check if
leakage
occurs at
as shown in below.
further tighten the connection
connection of Flare nut
If gas leakage occurs,
In case of removing flare nut of a indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Free from water into the piping when working.
Be sure to tighten the flare nut to the specified torque with a torque wrench. If the flare nut is overtightened, the nut may be split after a long period has passed, and may cause a refrigerant leak.
DROC REWOP FO NOITCENNOC
2
in
2
ler
CN21
CN6
WARNING
THIS APPLIANCE MUST BE EARTHED.
Detail of Cutting the Connecting Cord
Indoor Unit
70mm
10mm
Strip wires
10mm
45mm
1
2
3
WARNING
Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the cord band.
Secure the connecting cord along the coated part of the wire using
the cord band. Do not exert pressure on the wire as this may cause overheating or fire.
Wiring of The Indoor Unit
For wire connection of the Indoor unit, you need to remove the front cover, the
Remove the cover from the terminal base and screw the cable.
low cover under the body of the unit and terminal cover.
3
2
1
Earth
After remove the screw and terminal cover, and put the connecting cords and fix the terminal cover with screw.
Green + Yellow (ground)
Connecting cord
Connecting cord
Cord band
Method to remove the low cover
Pull at the 1 and the directions as shown by arrows to remove the cover.
How to connect the optional parts
(H-LINK RAC Adapter, Dry contact, Wired Remote Controller)
For cable connection to control P.W.B., you need to remove front cover and electrical box cover.
Each connecting location is as below.
1
Dry contact: CN6
2
H-LINK RAC AdapterCN7
3
Wired Remote Control : CN20
Please check and confirm manuals attached to each optional parts for more connection details.
You can refer to this installation manual how to remove and re-attach the front cover.
Please be careful not to damage lead wires by edge of plate when connecting the optional parts.
CN20
CN7
FINAL STAGE OF INSTALLATION
How to remove the front cover How to Attach the Front Cover
1
Remove the front panel
Please remove and attach the front panel by
Shaft
Hole
both hands.
After opening the front panel by both hands.
1
Undo the right arm while pushing it inside.
2
Slide the front panel to right as shown in figure. Then remove while pulling it to front.
2
Remove the filters.
3
After removing three screws, pull the center of the front cover
4
Pull the side faces (lower sections) of the front
and release the claws.
cover towards you as shown in the figure and remove the cover.
Screw
Screw
ECO Sensor
1
Check that the drain pan is securely attached. After installing the front cover onto the unit, hook three claws
2
at upper side of the cover securely. Then, push the center of the front cover to lock the claws.
Tighten three screws.
3
Install the filter.
4 5
Slide the shafts of the right and left arms on the front panel along the steps to insert the shafts into the holes till they stop. After checking that the shafts are securely inserted, close the panel.
Shaft Hole
CAUTION
Remove and attach the front cover to the direction as shown in the figure to ensure no damage occurs to the ECO sensor.
Torque wrench
44.1 – 53.9 (450 – 550)
)”2/1( 7.21
12.3 – 15.7 (125 – 160)
to stop leakage.
CN7
CN6
X
Torque N·m
(kgf·cm)
1
O
)054 – 053( 1.44 – 3.43 )”8/3( 25.9
)052 – 002( 5.42 – 6.91 )”4/1( 53.6 )052 – 002( 5.42 – 6.91 )”8/3( 25.9 )053 – 003( 3.43 – 4.92 )”2/1( 7.21
RAK-15QPB/RAK-18_25RPB_IM_English
2