PARTS LIST AND DIAGRAM ------------------------------------------------- 113
SPECIFICATIONS
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
COOLING
HEATING
DIMENSIONS
(mm)
NET WEIGHT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
DC INVERTER (CEILING CASSETTE TYPE)
INDOOR UNIT
RAI-50NH5
1 PHASE, 50 Hz, 220-240V
1,990 (155~2,200)
9.10 ~ 8.37
5.00 (0.90 ~ 5.20)
17,070
2,160 (155 ~ 2,200)
9.87 ~ 9.05
6.50 (0.90 ~ 8.10)
22,190
580
285
580
20
OUTDOOR UNIT
RAC-50NH5
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
850
650
298
60
DECEMBER 2005
0274E cover(RAI-50NH5)19/10/05, 2:41 PM1
ROOM AIR CONDITIONER
INDOOR UNIT + OUTDOOR UNIT
Refrigeration & Air-Conditioning Division
Page 2
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair
the unit in question, be sure to
disconnect the power cord plug
from the power outlet before starting
the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and
the replacement must be effected in correct manner according to the instructions in the Service Manual of
the unit.
If the contacts of electrical parts
are defective, replace the
electrical parts without trying to
repair them.
First, I must disconnect
the power cord plug
from the power outlet.
3. After completion of repairs, the initial state
should be restored.
4. Lead wires should be connected and laid as
in the initial state.
5. Modification of the unit by user himself should
absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as
electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and
grounding terminal of the unit. The insulation resistance should be 1M
DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe
enough to support the repaired unit again.
If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new
location.
10. Any inflammable thing should never
be placed about the location of
installation.
or more as measured by a 500V
DANGER
11. Check the grounding to see whether
it is proper or not, and if it is found
improper, connect the grounding
terminal to the earth.
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM1
– i –
Page 3
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope
The standards provide for items to be generally observed in carrying and handling semiconductors in relative
manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods
such as rejected goods being returned).
2. Object parts
(1) Micro computer
(2) Integrated circuits (IC)
(3) Field-effect transistors (FET)
(4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
A conductive polyvinyl bag
IC
Conductive sponge
IC
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through
a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM2
Body earth
(Elimik conductive band)
1M
Fig. 2. Body Earth
Clip for connection with a
grounding wire
– 1 –
Page 4
(6) Use a three wire type soldering iron including a grounding wire.
Metal plate (of aluminium, stainless steel, etc.)
Working
table
Bare copper wire (for body earth)
Staple
Fig. 3. Grounding of the working table
Soldering iron
2
Resistor of 1 M
Earth wire
Grounding
wire
(1/2W)
Screw stop at the screwed
part using a rag plate
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M
or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
– 2 –
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM3
Page 5
CAUTION
!
1.In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is
heard occasionally, but this noise is not abnormal for the operation.
2.When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3.The room air conditioner does not start automatically after recovery of the electric power failure for
preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4.If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal
and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no
danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5.This room air conditioner should not be used at the cooling operation when the outside temperature is
below –10°C (14°F).
6.This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–15°C (5°F).
If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7.When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM4
– 3 –
Page 6
SPECIFICATIONS
MODEL
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
RAI-50NH5
25W
NO
NO
–
NO
NO
NO
NO
NO
NO
RAC-50NH5
40 W
NO
NO
JU1013D
NO
YES
YES
3.0A
G4A
NO
TEMPORARY SWITCH
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
REFRIGERANT CHARGING
UNIT
VOLUME
(Refrigerant 410A)
PIPES (MAX. 20m)
YES
NO
NO
NO
NO
YES(IC)
YES
----------
NO
YES
NO
450NR
YES
YES(IC)
NO
1400g
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM5
– 4 –
Page 7
Figure showing the Installation of Indoor and Outdoor unit.
!
CAUTION
The installation height of indoor unit must be 2.3m or more.
Be sure to
completely
seal any
gap with
putty.
Maximum pipe length 20m
Minimum pipe length 5m
above 200mm
above 50mm when
installed on the
(
ceiling of balcony
)
above 100mm
give clearance as
wide as possible
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products)
● The difference in height
between the indoor and
outdoor unit should be
kept below 5m.
● The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then wrapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
Drain Pipe
Must be installed separately.
Insulate indoor part of pipe
to prevent condensation.
above 100mm
above 700mm
0274E Pg 1-5(RAI-50NH5)19/10/05, 2:44 PM6
above 200mm
– 5 –
Page 8
SAFETY PRECAUTION
●
Please read the “Safety Precaution” carefully before operating the unit to ensure correct usage of the unit.
●
Pay special attention to signs of “ Warning” and “ Caution”. The “Warning” section contains matters which,
if not observed strictly, may cause death or serious injury. The “Caution” section contains matters which may
result in serious consequences if not observed properly. Please observe all instructions strictly to ensure safety.
●
The sign indicate the following meanings.
!
!
Make sure to connect earth line.
Indicates the instructions that must be followed.
●
Please keep this manual after reading.
PRECAUTIONS DURING INSTALLATION
●
Do not reconstruct the unit.
Water leakage, fault, short circuit or fire may occur if you reconstruct the
unit by yourself.
●
!
WARNING
!
CAUTION
Please ask your sales agent or qualified technician for the installation of
your unit. Water leakage, short circuit or fire may occur if you install the unit
by yourself.
●
Please use earth line.
Do not place the earth line near water or gas pipes, lightning-conductor, or
the earth line of telephone. Improper installation of earth line may cause
electric shock.
●
A circuit breaker should be installed depending on the mounting site of the
unit. Without a circuit breaker, the danger of electric shock exists.
●
Do not install near location where there is flammable gas. The outdoor unit
may catch fire if flammable gas leaks around it.
●
Please ensure smooth flow of water when installing the drain hose.
The sign in the figure indicates prohibition.
W
A
R
N
N
G
!
W
A
R
N
N
G
PRECAUTIONS DURING SHIFTING OR MAINTENANCE
●
Should abnormal situation arises (like burning smell), please stop operating the unit
!
I
and turn off the circuit breaker. Contact your agent. Fault, short circuit or fire may
occur if you continue to operate the unit under abnormal situation.
●
Please contact your agent for maintenance. Improper self maintenance may cause
electric shock and fire.
●
Please contact your agent if you need to remove and reinstall the unit. Electric
shock or fire may occur if you remove and reinstall the unit yourself improperly.
PRECAUTIONS DURING OPERATION
●
Avoid an extended period of direct air flow for your health.
●
Do not insert a finger, a rod or other objects into the air outlet or inlet. As the
fan is rotating at a high speed, it will cause injury. Before cleaning, be sure
to stop the operation and turn the breaker OFF.
●
I
Do not use any conductor as fuse wire, this could cause fatal accident.
●
During thunder storm, disconnect and turn off the circuit breaker.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM6
– 6 –
Page 9
PRECAUTIONS DURING OPERATION
●
The product shall be operated under the manufacturer specification and
not for any other intended use.
●
Do not attempt to operate the unit with wet hands, this could cause fatal
accident.
●
When operating the unit with burning equipments, regularly ventilate the
room to avoid oxygen insufficiency.
●
Do not direct the cool air coming out from the air-conditioner panel to face
household heating apparatus as this may affect the working of apparatus
such as the electric kettle, oven etc.
●
Please ensure that outdoor mounting frame is always stable, firm and
without defect. If not, the outdoor unit may collapse and cause danger.
●
Do not splash or direct water to the body of the unit when cleaning it as this
!
may cause short circuit.
C
A
U
T
I
●
Do not use any aerosol or hair sprays near the indoor unit. This chemical
can adhere on heat exchanger fin and blocked the evaporation water flow
to drain pan. The water will drop on tangential fan and cause water splashing
out from indoor unit.
O
N
●
Please switch off the unit and turn off the circuit breaker during cleaning, the
high-speed fan inside the unit may cause danger.
●
Turn off the circuit breaker if the unit is not to be operated for a long period.
●
Do not climb on the outdoor unit or put objects on it.
●
When operating the unit with the door and windows opened, (the room humidity is always above
80%) and with the air deflector facing down or moving automatically for a long period of time,
water will condense on the air deflector and drips down occasionally. This will wet your furniture.
Therefore, do not operate under such condition for a long time.
●
If the amount of heat in the room is above the cooling or heating capability of the unit (for
example: more people entering the room, using heating equipments and etc.), the preset room
temperature cannot be achieved.
●
This appliance is not intended for use by young children or infirm persons unless they have been
adequately supervised by a responsible person to ensure that they can use the appliance safely.
●
Young children should be supervised to ensure that they do not play with the appliance.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM7
– 7 –
Page 10
NAMES AND FUNCTIONS OF EACH PART
INDOOR UNIT
AIR FILTER
To prevent dust from coming into the indoor unit.
(Refer page 19)
INDOOR UNIT INDICATORS
Light indicator showing the operating condition.
(Refer page 5)
SUCTION GRILL (AIR INLET)
HORIZONTAL DEFLECTOR (AIR OUTLET)
(Refer page 15)
REMOTE CONTROL
Send out operation signal to the indoor unit. So as to
operate the whole unit.
(Refer page 6)
MODEL NAME AND DIMENSIONS
MODEL
RAI-50NH5
WIDTH (mm)
580
HEIGHT (mm)
285
DEPTH (mm)
580
MULTI-AIR CONDITIONER
With this multi-air conditioner, several indoor units can be connected to one outdoor unit to be driven. You can operate
the required number of indoor units.
Combination of Operations:
When operation mode is selected:
● You cannot operate the indoor units in the
following combinations.
One unit
Heating
During automatic operation:
● When heating operation is automatically selected for the first indoor unit, the next indoor unit will then start to heat.
Also, if cooling or dehumidifying is automatically selected for the first indoor unit, the next indoor unit will also start
to cool or dehumidify.
Other unit
Cooling
Dehumidifying
Circulating (fan)
● The indoor unit which is switched on first continues to
operate, but other indoor units which is switched on later
does not operate while the lamp lights.
● To re-start an indoor unit which was operated later, stop
the indoor unit which was operated first or later and reset
the type of operation, then perform operation again.
Adjusting the Number of Indoor Units:
Decrease the number of indoor
units to be operated especially
when it is very hot or cold or
when you want to reach the
present temperature quickly.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM8
Stopped Indoor Units:
When an indoor unit is operated in the cooling,
heating or dehumidifying mode in the room, the
sound of refrigerant flow may be heard from a
stopped indoor unit or a stopped indoor unit may
become warm. This is because the indoor unit
returns refrigerant to the outdoor unit to be ready
for operation.
– 8 –
Page 11
OPERATION INDICATOR
TEMPORARY SWITCH
TEMPORARY
SWITCH
Use this switch to start and stop when the remote controller does not work.
[Use non-conductor stick (example toothpick)]
● By pressing the temporary switch, the operation is done in previously set
operation mode.
● When the operation is done using the temporary switch after the power
source is turned off and turn on again, the operation will be done in automatic
mode.
INDOOR UNIT INDICATORS
OPERATION LAMP
This lamp lights during operation.
The OPERATION LAMP flashes in the following
cases during heating.
(1) During preheating
For about 2–3 minutes after starting up.
(2) During defrosting
Defrosting will be performed about once an
hour when frost forms on the heat exchanger
of the outdoor unit, for 5–10 minutes each
time.
Press
Nonconducted
stick
Temporary Switch
about 5.5mm
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM9
TIMER LAMP
This lamp lights when the timer is working.
FILTER LAMP
When the device is operated for a total of about
200 hours, the FILTER lamp lights to indicate
that it is time to clean the filter. The lamp goes
out when the “ (AUTO SWING)” button is
pressed while the device is on “STANDBY
MODE”.
– 9 –
Page 12
NAMES AND FUNCTIONS OF REMOTE CONTROL UNIT
REMOTE CONTROLLER
● Operate by pointing towards the signal receptor on the indoor unit. The range of control is
about 7 meters. Signal receivable angle range is approximately 70°. However, if there is an
electronic light sensor device (inverter) in the room, signal may not be received or receivable
distance may become shorter.
● Indoor unit must be install 1 meter or more away from lighting.
● Handle the remote controller with care. Dropping it or getting it wet may compromise its
signal transmission capability.
● After new batteries are inserted into the remote controller, the unit will initially require
approximately 10 seconds to respond to commands and operate.
● Signal emitting window/transmission sign
Point this window toward the indoor unit when controlling it.
CH
˚
CH
˚
RESET
AUTO
HEAT
DEHUMIDIFY
COOL
FAN
FAN SPEED
LOW
MED
HI
SLEEPING
STOP (CANCEL)
START (RESERVE)
START/STOP
TIME
TIMER SET
TIMER SELECTOR
ON TIMER
OFF TIMER
AUTO SWING
The transmission sign blinks when a signal is sent.
● Display
This indicates the room temperature selected, current time, timer status, function
and intensity of circulation selected.
● START/STOP button
Press this button to start operation. Press it again to stop operation.
● SLEEP button
Use this button to set the sleep timer.
● TEMPERATURE buttons
Use these buttons to raise or lower the temperature setting. (Keep pressed, and
the value will change more quickly.)
● TIME button
Use this button to set and check the time and date.
● RESET buttons
● FUNCTION selector
Use this button to select the operating mode. Every time you press it,
the mode will change from (AUTO) to (HEAT) to (DEHUMIDIFY) to
(COOL) and to (FAN) cyclically.
● FAN SPEED selector
This determines the fan speed. Every time you press this button, the intensity
of circulation will change from (AUTO) to (HI) to (MED) to (LOW)
(This button allows selecting the optimal or preferred fan speed for each operation
mode).
● AUTO SWING button
Controls the angle of the horizontal air deflector.
● TIMER control
Use this button to set the timer.
● OFF-TIMER button Select the turn OFF time.
● ON-TIMER button Select the turn ON time.
● RESERVE button Time setting reservation.
● CANCEL button Cancel time reservation.
Precautions for Use
● Do not put the remote controller in the following places.
● Under direct sunlight.
● In the vicinity of a heater.
● Handle the remote controller carefully. Do not drop it on the floor,
and protect it from water.
● Once the outdoor unit stops, it will not restart for about 3 minutes
(unless you turn the power switch off and on or unplug the power
cord and plug it in again).
This is to protect the device and does not indicate a failure.
● If you press the FUNCTION selector button during operation, the
device may stop for about 3 minutes for protection.
▲
▲
Approximately 70°
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM10
– 10 –
Page 13
VARIOUS FUNCTIONS
■ Auto Restart Control
● If there is a power failure, operation will be automatically restarted when the power is resumed with previous operation mode
and airflow direction.
(As the operation is not stopped by remote controller.)
● If you intend not to continue the operation when the power is resumed, switch off the power supply.
When you switch on the circuit breaker, the operation will be automatically restarted with previous operation mode and airflow
direction.
Note: 1. If you do not require Auto Restart Control, please consult your sales agent or OFF by remote control.
2. Auto Restart Control is not available when Timer or Sleep Timer mode is set.
AUTOMATIC OPERATION
The device will automatically determine the mode of operation, HEAT, COOL or DEHUMIDIFY depending on the current room
temperature. The selected mode of operation will change when the room temperature varies. However the mode of operation will
not change when indoor unit connected to multi type outdoor unit.
Press the FUNCTION selector so that the display indicates the (AUTO) mode of operation.
●When AUTO has been selected, the device will automatically determine the mode of
operation, HEAT, COOL or DEHUMIDIFY depending on the current room temperature.
1
However the mode of operation will not change when indoor unit connected to multi type
outdoor unit.
●If the mode automatically selected by the unit is not satisfactory, manually change the
mode setting (heat, dehumidify, cool or fan).
RESET
START
STOP
■ As the settings are stored in memory in the remote controller, you only have to press the
Press the (START/STOP) button.
Operation starts with a beep.
Press the button again to stop operation.
(START/STOP) button next time.
You can raise or lower the temperature setting as necessary by maximum of 3°C.
°C
● The preset temperature and the actual room temperature may vary somewhat depending on
conditions.
● The display does not indicate the preset temperature in the AUTO mode. If you change the
setting, the indoor unit will produce a beep.
Press the (FAN SPEED) button, AUTO and LOW is available.
Press the temperature button and the temperature setting will change by
1°C each time.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM11
– 11 –
Page 14
HEATING OPERATION
● Use the device for heating when the outdoor temperature is under 21°C.
When it is too warm (over 21°C), the heating function may not work in order to protect the device.
● In order to keep reliability of the device, please use this device above -15°C of the outdoor temperature.
Press the FUNCTION selector so that the display indicates
(HEAT).
Set the desired FAN SPEED with the (FAN SPEED) button
(the display indicates the setting).
(AUTO): The fan speed is HI at first and varies to MED
or LOW automatically when the preset
temperature has been reached.
(HI): Economical as the room will become warm
quickly.
But you may feel a chill at the beginning.
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
RESET
C
˚
1
2
Set the desired room temperature with the TEMPERATURE
buttons (the display indicates the setting).
3
C
˚
START
STOP
■ As the settings are stored in memory in the remote controller, you only
The temperature setting and the actual room temperature may
vary somewhat depending on conditions.
Press the (START/STOP) button. Heating operation starts
with a beep. Press the button again to stop operation.
have to press the (START/STOP) button next time.
0274E Pg 6-18(RAI-50NH5)15/11/05, 9:30 AM12
– 12 –
Page 15
DEHUMIDIFYING OPERATION
Use the device for dehumidifying when the room temperature is over 16°C.
When it is under 15°C, the dehumidifying function will not work.
Press the FUNCTION selector so that the display indicates
(DEHUMIDIFY).
The FAN SPEED is set at LOW automatically.
The FAN SPEED button does not work.
Set the desired room temperature with the TEMPERATURE
button (the display indicates the setting).
The range of 20-26˚C is recommended as
the room temperature for dehumidifying.
RESET
C
˚
1
2
C
˚
■ Dehumidifying Function
START
STOP
■ As the settings are stored in memory in the remote controller, you
Press the (START/STOP) button. Dehumidifying operation
starts with a beep. Press the button again to stop operation.
only have to press the
(START/STOP) button next time.
When the room temperature is higher than the temperature setting: The device will dehumidify the room,
reducing the room temperature to the preset level.
When the room temperature is lower than the temperature setting: Dehumidifying will be performed at
the temperature setting slightly lower than the current room temperature, regardless of the temperature
setting. The function will stop (the indoor unit will stop emitting air) as soon as the room temperature
becomes lower than the setting temperature.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:46 PM13
– 13 –
Page 16
COOLING OPERATION
Use the device for cooling when the outdoor temperature is 22-42°C.
If in doors humidity is very high (80%), some dew may form on the air outlet grille of the indoor unit.
Press the FUNCTION selector so that the display indicates
C
˚
1
(COOL).
RESET
Set the desired FAN SPEED with the
(the display indicates the setting).
(AUTO): The FAN SPEED is HI at first and varies to
MED or LOW automatically when the preset
2
(HI): Economical as the room will become cool
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
Set the desired room temperature with the TEMPERATURE
button (the display indicates the setting).
3
C
˚
START
STOP
The temperature setting and the actual room temperature may
vary some how depending on conditions.
Press the
with a beep. Press the button again to stop operation. The
cooling function does not start if the temperature setting is
higher than the current room temperature (even though the
(OPERATION) lamp lights). The cooling function will start as
soon as you set the temperature below the current room
temperature.
temperature has been reached.
quickly.
(START/STOP) button. Cooling operation starts
(FAN SPEED) button
■ As the settings are stored in memory in the remote controller, you
only have to press the
(START/STOP) button next time.
0274E Pg 6-18(RAI-50NH5)15/11/05, 9:30 AM14
– 14 –
Page 17
FAN OPERATION
You can use the device simply as an air circulator. Use this function to dry the interior of the indoor
unit at the end of summer.
Press the FUNCTION selector so that the display indicates
1
(FAN).
RESET
FAN SPEED (AUTO)
For the heating operation
2
START
STOP
.....
When the AUTO fan speed mode is set in the cooling/heating operation:
● The fan speed will automatically change according to the temperature
of discharged air.
● When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
● When the room temperature reaches setting temperature, fan speed
changes to LOW automatically.
Press the (FAN SPEED) button.
Press the (START/STOP) button. Fan operation starts with
a beep. Press the button again to stop operation.
For the cooling operation
● When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
● After room temperature reaches the preset temperature, the cooling
operation, which changes the fan speed and room temperature to obtain
optimum conditions for natural healthful cooling will be performed.
– 15 –
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:47 PM15
Page 18
HOW TO SET THE TIMER
RESET
Time, Day, Month
TIME, DAY,
MONTH
After you change the
batteries;
(current time,
day, month)
OFF TIMER
ON TIMER
OFF-Timer
RESERVE
CANCEL
You can set the device to turn off
at the present time.
ON-Timer
● The device will turn on
at the designated times.
Start
MD
STOP
Stop
Start
1
Set the current month and
day with the TIMER control
button.
MD
1
Press the (OFF-TIMER)
button. The (OFF) mark blinks
on the display.
AM
1
Press the (ON-TIMER)
button the (ON) mark blinks
on the display.
AM
3
ON/OFF-Timer
StartStop
● The device will turn on (off) and off
(on) at the designated times.
● The switching occurs first at the
preset time that comes earlier.
● The arrow mark appearing on the
display indicates the sequence of
switching operations.
1
Press the (ON-OFF)
button so that the (OFF)
mark blinks.
PM
2
Set the turn-off time
with the TIMER control
button.
Press the (RESERVE)
button.
PM
Press the (ON-
TIMER) button so that the
(OFF) mark lights and
the (ON) mark blinks.
PM
AM
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL)
button.
The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
NOTE
You can set only one of the OFF-timer,
ON-timer and ON/OFF-timer.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:47 PM16
– 16 –
Page 19
2
Press the
(TIME) button.
AM
PMPM
2
Set the turn-off time with the
TIMER control button.
3
TIMER control button.
PM
Set the current time with the
Example: The current time is 1:30 p.m.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (OFF) mark starts lighting instead of flashing and the sign (RESERVED)
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
4
Press the (TIME) button again.
The time indication starts lighting
instead of flashing.
● The time indication will disappear
PM
● To check the current time setting,
automatically in 10 second.
press the (TIME) button twice.
The setting of the current time is
now complete.
2
Set the turn-on time with the
TIMER control button.
AM
4
Set the turn-on time with the
TIMER control button.
PM
AM
PM
The setting of turn-off time is now complete.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (ON) mark starts lighting instead of flashing and the (RESERVED) sign
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
Example:
AM
5
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (ON) mark starts lighting instead of flashing and the (RESERVED) sign
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
PM
AM
The device will turn on at 7:00 a.m.
The setting of the turn-on time is now complete.
Example:
The device will turn off at 10:30 p.m. and it will be turned on
at 7:00 a.m.
The settings of the turn-on/off times are now complete.
Example: The device will turn off at 11:00p.m.
● The timer may be used in three ways: off-timer, on-timer, and ON/OFF (OFF/ON)-timer. Set
the current time at first because it serves as a reference.
● As the time settings are stored in memory in the remote controller, you only have to press
the (RESERVE) button in order to use the same settings next time.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:47 PM17
– 17 –
Page 20
HOW TO SET THE SLEEP TIMER
Set the current time at first if it is not set before (see the pages for setting
the current time). Press the (SLEEP) button, and the display changes as
shown below.
Mode
4444
H
SLEEP
Sleep timer
Sleep Timer: The device will continue working for the designated
number of hours and then turn off.
Point the signal window of the remote controller toward the indoor
unit, and press the SLEEP button.
The timer information will be displayed on the remote controller.
The TIMER lamp lights with a beep from the indoor unit. When the
sleep timer has been set, the display indicates the turn-off time.
H
Sleep
timer
1
Set the ON-timer.
Start
1 hour 2 hours 3 hours 7 hours
The device will be turned off by the sleep
timer and turned on by on-timer.
Indication
Sleep timer off
Example: If you set 3 hours sleep
time at 11:38 p.m., the turn-off
time is 2:38 a.m.
1
2
Press the (SLEEP) button and set the sleep timer.
AM
H
AM
For heating:
In this case, the device will turn off
in 2 hours (at 1:38 a.m.) and turn
on early so that the preset
temperature will be almost reached
at 6:00 next morning.
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL)
button.
The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
0274E Pg 6-18(RAI-50NH5)19/10/05, 2:47 PM18
– 18 –
Page 21
ADJUSTING THE AIR DEFLECTOR
about 45˚
SWINGING
RANGE
45˚
about 45˚
SWINGING
RANGE
45˚
Adjustment of the conditioned air in the upward and
1
downward directions.
According to “Dehumidifying” or “Cooling” operation, the
horizontal air deflector is automatically set to the proper
angle suitable for each operation. The deflector can be
swung up and down and also set to the desired angle
using the “ (AUTO SWING)” button. (If the angle
of the deflector is changed, it will not return to the autoset position after operations start unless the operation
mode is switched.)
● If the “ (AUTO SWING)” button is pressed
once, the horizontal air deflector swings up and
down. If the button is pressed again, the deflector
stops in its current position. Several seconds (about
6 seconds) may be required before the deflector
starts to move.
● Use the horizontal air deflector within the adjusting
range shown on the right.
RESET
ENGLISH
● When the “ (AUTO SWING)” button is
pressed while the operation is stopped, the horizontal
air deflector moves and stops at the position where
the air outlet closes.
● When the auto swing operation is performed, if the
horizontal air deflector is moved manually, the
swinging range may drift. However, it will return to
the original operation range after a short time.
CAUTION
!
When operating the unit in cooling operation with the air deflector facing down and moving
automatically for a long period of time, water will condensed on the air deflector and drips down
occasionally. This will wet your furniture.
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM19
– 19 –
Page 22
HOW TO EXCHANGE THE BATTERIES IN THE REMOTE CONTROLLER
Remove the cover as shown in the figure and take out the
1
old batteries.
=
Install the new batteries.
2
The direction of the batteries should match the marks in the
case.
!
CAUTION
1. Do not use new and old batteries, or different kinds of batteries
together.
2. Take out the batteries when you do not use the remote controller
for 2 or 3 months.
Push and pull to the
direction of arrow
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM20
– 20 –
Page 23
THE IDEAL WAYS OF OPERATION
Suitable Room TemperatureInstall curtain or blinds
!
Warning
Freezing temperature
is bad for health and a
waste of electric power.
It is possible to
reduce heat
entering the
room through
windows.
VentilationEffective Usage Of Timer
At night, please use the “OFF or ON timer
Caution
!
Do not close the room for a long period of
time. Occasionally open the door and windows
to allow the
entrance of
fresh air.
operation mode”, together with your wake up
time in the morning. This will enable you to
enjoy a comfortable room temperature. Please
use the timer effectively.
ENGLISH
Do Not Forget To Clean The Air Filter
Dusty air filter will reduce the air volume and
the cooling efficiency. To prevent from wasting
electric energy, please clean the filter every 2
weeks.
– 21 –
Please Adjust Suitable Temperature
For Baby And Children
Please pay attention to the room temperature
and air flow direction when operating the unit
for baby, children and old folks who have
difficulty in movement.
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM21
Page 24
FOR USER’S INFORMATION
The Air Conditioner And The Heat Source In The Room
Caution
!
If the amount of heat in the room is above the cooling
capability of the air conditioner (for example: more
people entering the room, using heating equipments
and etc.), the preset room temperature cannot be
achieved.
Not Operating For A Long Time
When the indoor unit is not to be used for a long
period of time, please switch off the power from the
mains. If the power from mains remains “ON”, the
indoor unit still consumes about 8W in the operation
control circuit even if it is in “OFF” mode.
OFF
When Lightning Occurs
!
Warning
To protect the whole unit during lightning, please
stop operating the unit and remove the plug from the
socket.
Interference From Electrical Products
!
Caution
To avoid noise interference, please place the indoor
unit and its remote controller at least 1m away from
electrical products.
To prevent
interference,
place at least
1m away.
Inverter-type
fluorescent
lamp.
TV
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM22
– 22 –
Page 25
MAINTENANCE
!
CAUTION
Cleaning and maintenance must be carried out by qualified service personnel.
Before the cleaning, stop operation and disconnect the power supply.
Clean the filter at least once every one month. This helps save electricity cost.
1. CLEANING OF AIR FILTER
REMOVAL AND ATTACHMENT OF AIR FILTER
ENGLISH
PROCEDURE
1
2
3
Remove the filter from indoor
● Press the mark “PUSH” on the left and
right sides of the suction grille.
● Pull out the filter from the grille.
Remove dust from the filter using a vacuum
cleaner.
If there is too much dust, use neutral
detergent. After using neutral detergent, wash
with clean water and dry in the shade.
Install the filter. (Set it with “UP SIDE” mark
facing front.)
Slot the filter to suction grille and close as
original state.
(Press the mark “PUSH” at the left and right
sides of the suction grille to fix it securely.)
Safety Cable
Air Filter
PUSH
Filter Guide
Grille
Note:
● This model has an air cleaning filter. The cooling capacity is slightly weakened and the cooling
speed becomes slower when the air cleaning filter is used. So, set the fan speed to “HIGH” when
using it in this condition.
● Recommended to replace the air cleaning filter after every 3 months for normal usage. Type number
for this air cleaning filter is <SPX-CFH5>. Please use this number for ordering when you want to
renew it.
!
CAUTION
● Do not wash with hot water at more than 40°C. The filter may shrink.
● When washing it, shake off moisture completely and dry it in the shade; do not expose it directly to
the sun. The filter may shrink.
● Do not operate the air conditioner with the filter removed. Dust may enter the air conditioner and
cause trouble.
– 23 –
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM23
Page 26
2. CLEANING OF FRONT PANEL
● Wipe it with a soft dry cloth.
● When it is excessively dirty, wipe with soft cloth soaked in lukewarm water or neutral detergent. Then
wipe thoroughly with a soft dry cloth.
!
CAUTION
● Do not splash or direct water to the body of the unit when cleaning it as
this may cause short circuit.
● Never use hot water (above 40°C), benzine, gasoline, acid, thinner or a
brush, because they will damage the plastic surface and the coating.
3. MAINTENANCE AT BEGINNING OF LONG OFF PERIOD
● Running the unit setting the operation mode to (FAN) and
the fan speed to HI for about half a day on a fine day, and
dry the whole of the unit.
● Turn off the circuit breaker.
Air
Blow
REGULAR INSPECTION
PLEASE CHECK THE FOLLOWING POINTS EITHER EVERY HALF YEARLY OR YEARLY.
CONTACT YOUR SALES AGENT SHOULD YOU NEED ANY HELP.
Is the earth line disconnected or broken?
WARNING
1
2
!
Coming off or breakage of grounding wire may cause malfunction
or electrical shock.
Is the mounting frame seriously affected by rust and is the outdoor
unit tilted or unstable?
WARNING
!
Outdoor unit may fall or drop if there is extreme rust on mounting
frame or outdoor unit is unstably installed. This may cause injury.
3
Confirm
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM24
Is the plug of power line firmly plugged into the socket?
(Please ensure no loose contact between them).
– 24 –
Page 27
AFTER SALES SERVICE AND WARRANTY
WHEN ASKING FOR SERVICE, CHECK THE FOLLOWING POINTS.
CONDITIONCHECK THE FOLLOWING POINTS
● Is the fuse blown out or the circuit breaker tripped?
When it does not operate
When it does not cool well
When it does not hot well
Notes
● In quiet operation or stopping the running, the following phenomena may
occassionally occur, but they are not abnormal for the operation.
(1)Slight flowing noise of refrigerant in the refrigerating cycle.
(2)Slight rubbing noise from the fan casing which is cooled and then
● The odor will possibly be emitted from the room air conditioner because
the various odor, emitted by smoke, foodstuffs, cosmetics and so on,
sticks to it. So please clean the air filter and the evaporator regularly to
reduce the odor.
● Is the voltage normal?
● Is the circuit breaker “ON”?
● Is the air filter blocked with dust?
● Does sunlight fall directly on the outdoor unit?
● Is the air flow of the outdoor unit obstructed?
● Are the doors or windows opened, or is there any source of
heat in the room?
● Is the set temperature suitable?
gradually warmed as operation stops.
ENGLISH
●
Please contact your sales agent immediately if the air conditioner still fails to operate normally after the above
inspections. Inform your agent of the model of your unit, production number, date of installation. Please also
inform him regarding the fault.
●
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the
specified capacity.
0274E Pg 19-26(RAI-50NH5)19/10/05, 2:51 PM25
– 25 –
Page 28
Please note:
On switching on the equipment, particularly when the room light is dimmed, a slight brightness fluctuation
may occur. This is of no consequence.
The conditions of the local Power Supply Companies are to be observed.
Note
●Avoid to use the room air conditioner for cooling operation when the outside temperature is below
21°C (70°F).
The recommended maximum and minimum operating temperatures of the hot and cold sides
should be as below:
1.Insulated pipes should be used for both the narrow and wide dia. pipes.
2.Piping length is within 20m.
3.Height difference of the piping between the indoor unit and the outdoor unit should be within 10m.
4.An F-cable 1.6mm or 2.0mm dia. X 3 (control side) is used for the connection cable.
0274E Pg 27-30(RAI-50NH5)19/10/05, 2:57 PM27
– 27 –
Page 30
CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR
MODEL RAC-50NH5
Handle
Fixing hole
Air suction
grille
700
100
More than
340
201
2022298
Handle
96
More than
100
169.5
955
10464
26850
Holes for anchor bolt
(2-ø12)
507198
Notch for anchor bolt
(2-ø12 Notchs)
57
12
37
Air outlet
10
1010
320
340
79
More than
100
638
650
More than
Service space
0274E Pg 27-30(RAI-50NH5)19/10/05, 2:57 PM28
– 28 –
Page 31
MAIN PARTS COMPONENT
THERMOSTAT
Thermostat Specifications
THERMOSTAT MODELIC
OPERATION MODECOOLHEAT
MODELRAI-50NH5RAI-50NH5
ON13.0 (55.4)20.0 (68.0)
OFF12.7 (54.9)20.3 (68.5)
ON21.0 (69.8)28.0 (82.4)
OFF20.7 (69.3)28.3 (82.9)
ON29.0 (84.2)36.0 (96.8)
OFF
TEMPERATURE
°C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
FAN MOTOR
Fan Motor Specifications
MODEL
RAI-50NH5
POWER SOURCEDC: 0 ~ 35V
OUTPUT25W
CONNECTION
0~35V
5V
28.7 (83.7)36.3 (97.9)
RAC-50NH5
DC360V
40W
RED
YEL
BLU
M
360V
0V
15V
0~6V
0~15V
RED
BLK
WHT
YEL
BLU
M
(Control circuit built in)
BLU : BLUEYEL : YELLOWBRN : BROWNWHT : WHITE
GRY : GRAYORN : ORANGEGRN : GREENRED : RED
BLK : BLACKPNK : PINKVIO : VIOLET
– 29 –
0274E Pg 27-30(RAI-50NH5)19/10/05, 2:57 PM29
Page 32
COMPRESSOR MOTOR
Compressor Motor Specifications
MODEL
COMPRESSOR MODEL
RAC-50NH5
JU1013D
PHASESINGLE
RATED VOLTAGEAC 220 ~ 240 V
RATED FREQUENCY50 Hz
POLE NUMBER4
(U)
CONNECTION
M
WHITE
M
M
(W)
(V)
YELLOW
RESISTANCE VALUE
20°C
(68°F)
2M = 1.05
RED
75°C
(167°F)
YELLOW
2M = 1.28
WHITE
RED
!
CAUTION
( )
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed
or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the
color has been changed conspicuously, replace the compressor.
Door openAutomatic swingFan speed selectionOperation selectionStart/Stop
P10
Door shut––Automatic swingStart/Stop
Door openDay
• present timeHour downHour upOn timer
P11
Door shutFan speedRoom temperature downRoom temperature up–
Door openCancelReservation–Off timer
P12
Door shut–––Sleep
– 33 –
0274E Pg 33(RAI-50NH5)19/10/05, 3:00 PM1
Page 35
CIRCUIT DIAGRAM
MODEL RAI-50NH5
0274E Pg 35(RAI-50NH5)19/10/05, 3:09 PM1
– 35 –
Page 36
CIRCUIT DIAGRAM
MODELRAC-50NH5
0274E Pg 37(RAI-50NH5)19/10/05, 3:14 PM1
– 37 –
Page 37
PRINTED WIRING BOARD LOCATION DIAGRAM
MODEL RAI-50NH5
MAIN P.W.B.
Marking on P.W.B.
COMPONENT SIDE
SOLDERING SIDE
0274E Pg 39-40(RAI-50NH5)19/10/05, 3:16 PM39
– 39 –
Page 38
MODEL RAC-50NH5
MAIN P.W.B.Marking on P.W.B
COMPONENT SIDE
0274E Pg 39-40(RAI-50NH5)19/10/05, 3:16 PM40
– 40 –
Page 39
Wireless receive
circuit
Filter.
Operation.
Timer.
Auto sweep motor for
Air deflector
Drain Pump Motor
LCD wireless
Heat exchanger
thermistor
Room temperature
thermistor
Reset circuit
Initial setting circuit
Temporary switch
Electric Expansion valve
drive circuit
Electric
Expansion
valve
Outdoor microcomputer / HIC (AX-6V00)
Trip signal
synthesis circuit
L
N
RAI-50NH5 / RAC-50NH5
SPM2
Outdoor
unit
Terminal
board
Indoor microcomputer (AX-7R11)
0274E Pg 41(RAI-50NH5)19/10/05, 3:23 PM1
– 41 –
Page 40
47.
0274E Pg 43(RAI-50NH5)19/10/05, 3:24 PM1
– 43 –
Page 41
Table 1 Mode data file
RAI-50NH5
LABEL NAMEVALUE
WMAX6000 min
WMAX26000 min
WSTD4250 min
WBEMAX3500 min
CMAX4700 min
CMAX24700 min
CSTD4100 min
CKYMAX3500 min
CJKMAX2700 min
CBEMAX2000 min
WMIN1800 min
CMIN1800 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
STARTMC60 Seconds
DWNRATEW80%
DWNRATEC80%
SHIFTW4.00°C
SHIFTC–2.99°C
CLMXTP30.00°C
YNEOF21.00°C
TEION2.00°C
TEIOF6.00°C
SFTDSW2.66°C
DFTIM150 Minutes
DFTIM290 Minutes
DFTIM360 Minutes
0274E pg 45(RAI-50NH5)19/10/05, 3:25 PM45
– 45 –
Page 42
Reversing valve (heating “on” mode)
NOTE (9)
Table 2 ∆TCMAX
TemperatureCalculated
differencecompressor rpm
1.662265 min
22435 min
2.332600 min
2.662765 min
32935 min
3.333100 min
3.663265 min
43435 min
4.333600 min
4.663765 min
53935 min
5.334100 min
5.664265 min
64435 min
6.334600 min
6.664765 min
74935 min
7.335100 min
7.665265 min
85435 min
8.335600 min
8.665765 min
95935 min
9.336100 min
9.666265 min
106435 min
10.336600 min
10.666765 min
116935 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
Notes:
(1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode.
(3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP.
(6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX.
(7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX.
(8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX.
(9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Note:
1. See the data in Table 1 on
page 45 for each constant in
capital letters in the diagrams.
– 47 –
0274E Pg 47(RAI-50NH5)19/10/05, 3:29 PM1
Page 43
Cooling Sleep Operation
Compressor speed
Horizontal air
deflector
Shut
Horizontal
Facing down
Maximum speed
Indoor fan
Outdoor fan
Timer lamp
Operation lamp
Sleep key
(Cooling/dehumidifying set
temperature = Remote control set
temperature (+) SHIFTC)
Final set temperature
(Cooling/dehumidifying set
temperature (+) sleep shift)
Set to 7 hours
0.5hr
1.5hr
3hr
P1
2.5hr3.5hr6hr7hr
Hi
See basic operation
Med
Lo (sleep)
Lo
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to “sleep Lo”.
(3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached.
(4) The sleep shift upper value of set temperature is 28˚C.
(5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min.
(6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made.
(7) The indoor fan speed does not change even when the fan speed mode is changed.
(8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted.
(9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted.
(10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
0274E Pg 49(RAI-50NH5)19/10/05, 3:30 PM1
– 49 –
Page 44
+
+
Delay
–1.33˚C
–0.66˚C
0274E Pg 51(RAI-50NH5)19/10/05, 3:31 PM1
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2°C).
(2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
– 51 –
Page 45
1.33˚C.
SFTDSW
0.66˚C.
Fan speed set to "auto"
1 min.
Hi
LoHiHiHi
ultra Hi
Basic Heating Operation
Start
StopStartStartStopStop
Thermo
OFF
Thermo
OFF
Heating set temperature
(remote control set temperature
(+))
Start/stop switch
Thermo judgment
Indoor fan
Ultra-Hi
Hi
Med
Lo
Ultra-Lo
Operation lamp
Max.
Rating
3000
0
Compressor speed
Outdoor fan
Reversing valve (heating "on" model)
Thermo OFF
Dash period
TWMAX
Wtd
Defrost signal
Preheating judgment
30sec. 30sec.
10sec.
15sec.15sec.
15sec.15sec.15sec.
10sec.
15sec.
15sec.
150sec. Delay
150sec. Delay150sec. Delay
3min.
Max. 3 min.
Preheating released
Control by
heat exchanger temperature
Control by
heat exchanger temperature
15sec.
Control by
heat exchanger temperature
Control by
heat exchanger temperature
Control by
heat exchanger temperature
18˚C
10sec.
30sec.30sec.
10sec.
30sec.30sec.30sec.30sec.30sec.30sec.
10sec.
Preheat released
WMIN
(WSTD)
(WMAX)
NOTE (11)
WMAX2
Notes:
(1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm (calculated value in Table 3) larger than WMAX.
(2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off.
(3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor temperature
is lower than 18°C and outdoor temperature is lower than 2°C.
(6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”.
(7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C.
(8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX.
(9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode.
(10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2.
(11) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor rpm is actual rpm x DWNRATEW.
Table 3 ∆TWMAX
TemperatureCalculated
differencecompressor rpm
1.661965 min
22135 min
2.332300 min
2.662465 min
32635 min
3.332800 min
3.662965 min
43135 min
4.333300 min
4.663465 min
53635 min
5.333800 min
5.663965 min
64135 min
6.334300 min
6.664465 min
74635 min
7.334800 min
7.664965 min
85135 min
8.335300 min
8.665465 min
95635 min
9.335800 min
9.665965 min
106135 min
10.336300 min
10.666465 min
116635 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
Notes:
1. See the data in Table 1 on
page 45 for each constant in
capital letters in the diagrams.
0274E Pg 53(RAI-50NH5)19/10/05, 3:32 PM1
– 53 –
Page 46
1 min
WMIN
TDF TDF TDF
TDF
TDF
TDF
Setting Defrosting Inhibit Period
D F T I M 3
D F T I M 2
Time
Outdoor temperature
– 1 0– 5˚C0˚C
D F T I M 1
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to “sleep Lo”.
(3) 30 minutes after the sleep key is set, the sleep shift of set temperature starts.
(4) The maximum sleep shift of set temperature is 5°C, and the minimum is 12°C.
(5) If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts.
(6) The indoor fan speed does not change even when the fan speed mode is changed. (Lo)
(7) When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting.
(8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted.
(9) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted.
(10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Notes:
(1) The first inhibit time after operation start is set to DFTIM1.
(2) From the second time onwards, the inhibit time is set according to the time required for
0274E Pg 55(RAI-50NH5)19/10/05, 3:33 PM1
defrosting.
Reverse cycle operation time ≥ [DEFCOL] : DFTIM1 is set.
Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor temperature is set.
– 55 –
Page 47
REFRIGERATING CYCLE DIAGRAM
MODEL RAI-50NH5
RAC-50NH5
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
ELECTRIC
EXPANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING
VALV E
SERVICE VALVE
SERVICE VALVE
SUCTION
TANK
(1/4)
(1/2)
ADAPTOR
INDOOR UNIT
SINGLE-ENDED
UNION (3/8)
SINGLE-ENDED
UNION (1/4)
HEATING
OUTDOOR UNIT
ELECTRIC
EXPANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING
VALV E
SERVICE VALVE
SERVICE VALVE
(1/2)
SUCTION
TANK
(1/4)
ADAPTOR
INDOOR UNIT
SINGLE-ENDED
UNION (3/8)
SINGLE-ENDED
UNION (1/4)
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM57
– 57 –
Page 48
REFERENCE
INITIALIZE AT NEXT
OPERATION.
OPERATING SPECIFICATION
INITIALIZE AT NEXT
OPERATION.
ONE SWING (CLOSING AIR DEFLECTOR)
PRESENT CONDITION
OPERATIONOPERATION MODEAIR DEFLECTOR
STOP AT THE MOMENT.
1 DOWNWARD
2 UPWARD
STOP
DURING ONE SWING
EACH MODE
STOP
START SWINGING
1 DOWNWARD
2 UPWARD
STOP
AUTO COOL
COOL
FAN
STOP AT THE MOMENT.
3 DOWNWARD
DURING SWINGING
AUTO DRY
DRY
DURING
START SWINGING
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP
AUTO HEAT
HEAT
CIRCULATOR
OPERATION
START SWING AGAIN.
STOP AT THE MOMENT.
DURING SWINGING
STOP SWINGING TEMPORARILY.
(SWING MODE IS CLEARED IF SWING COMMAND IS
TEMPORARY STOP
AUTO DRY
DURING SWINGING
DRY
AUTO HAET
HEAT
DURING
OPERATION
INITIALIZE
TRANSMITTED DURING TEMPORARY STOP.)
COOL
CIRCULATOR
1 DOWNWARD
2 UPWARD
INITIALIZE
STOP
DURING ONE SWING
STOP
FAN
DRY
HEAT
STOP
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
DURING ONE SWING
STOP
CIRCULATOR
INITIALIZING CONDITION OF EACH MODE.
1 DOWNWARD
2 UPWARD
DURING SWINGING
DURING
INITIALIZING
EACH MODE
DURING
OPERATION
STOP SWINGING AND MODE BECOMES INITIALIZING
CONDITION.
STOP
DURING SWINGING
EACH MODE
DURING
OPERATION
INPUT SIGNAL
AUTO SWING FUNCTION
MODEL: RAI-50NH5
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM58
KEY INPUT
– 58 –
THERMO. ON
(INTERNAL FAN
ON)
THERMO. ON
(INTERNAL FAN
OFF)
MAIN SWITCH
ON
MAIN SWITCH
OFF
CHANGE OF
OPERATION
Page 49
DESCRIPTION OF MAIN CIRCUIT OPERATION
MODEL RAI-50NH5
1. Reset Circuit
5V
2
R522
1
C521
R521
5
C524
NORMAL : HI
RESET: LO
RES
7
Microcomputer
C522
Voltage
Voltage supply to
2
of IC521
pin
Reset release at 4.4V
3
IC521
0V
Fig. 1-1
5.0V
Reset enter at 4.2V
voltage
Voltage at pin
of microcomputer
7
5.0V
Fig. 1-2
● The reset circuit initializes the microcomputer program when power is ON or OFF.
● Low voltage at pin 7 resets the microcomputer and Hi activates the microcomputer.
● When power “ON” 5V voltage rises and reaches 4.4V, pin 1 of IC521 is set to “Hi”. At this time the
microcomputer starts operation.
● When power “OFF” voltage drops and reaches 4.2V, pin 1 of IC521 is set to “Low”. This will RESET the
microcomputer.
– 59 –
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM59
Page 50
2. Receiver Circuit
R412
5V12V
R411
R413
C413
C412
C411
ZD411
0V
IRR
V
DD
GND
out
V
R611
C414
13
RECEIVER I/P
C611
0V
Microcomputer
Fig. 2-1
● The light receiver unit receives the infrared signal from the wireless remote control. The receiver amplifies
and shapes the signal and outputs it.
3. Buzzer Circuit
12V
R722
BZ
BZ
Microcomputer
Buzzer output
●When the buzzer sounds, an approx.
3.9kHz square signal is output from buzzer
output pin of the microcomputer. After
30
the amplitude of this signal has been set
to 12Vp-p by a transistor, it is applied to
the buzzer. The piezoelectric element in
the buzzer oscillates to generate the
buzzer’s sound.
30
Fig. 3-1 Buzzer Circuit
Metal diaphragm
Sound wave
0V
Q722
Pizoelectric element
V
V
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM60
Fig. 3-2 Buzzer Operation
– 60 –
Page 51
D712
P.W.B. MAIN
12V
CN8
Auto sweep motor for
horizontal air deflector
Rotor
AUTO SWEEP
M
MOTOR
AUTO SWEEP
M
MOTOR
AUTO SWEEP
M
MOTOR
CN7
1
2
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
7
8
9
10
4. Auto Sweep Motor Circuit
22
21
20
Microcomputer
19
18
17
16
15
R711
IC711
7
6
5
4
3
2
1
R712
C712
9
8
Q711
Q712
0V
10
11
12
13
14
15
16
C711
0V
Fig.4-1
● Fig. 4-1 shows the Auto sweep motor drive circuit; the signals shown in Fig.4-2 are output from pins
15 – 22 of microcomputer.
Microcomputer pinsStep width
Horizontal air deflectors
15
16
12345678
Horizontal air
deflectors: 10ms.
17
18
19
20
21
22
Fig.4-2 Microcomputer Output Signals
● As the microcomputer’s outputs change as shown in Fig.4-2, the core of the auto sweep motor is excited
to turn the rotor. Table 4-1 shows the rotation angle of horizontal air deflectors.
Table 4-1 Auto sweep Motor Rotation
● The air deflectors are driven by the stepping motors, which are instructed by the microcomputer.
● The air deflectors on the left and right are each driven by two stepping motors.
● The stepping motors and main unit are connected via relay connectors. The air deflectors will not operate
unless the relay connectors are connected: Securely connect the relay connectors identified by colors
when attaching the panel.
● Before removing the panel for servicing, be sure to disconnect the relay connector to protect the lead
wires.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM61
Rotation angle per step (˚ )Time per step (ms.)
0.088210Horizontal air deflectors
– 61 –
Page 52
5. Room Temperature Thermistor Circuit
● Fig. 5-1 shows the room temperature
● The voltage at depends on the room
thermistor circuit.
5V
Room
temperature
thermistor
A
0V
R301
R305
0V
Fig. 5-1
C302
Microcomputer
Room
62
temp. input
5
4
(V)
A
3
2
Voltage at
1
0
6. Heat exchanger temperature thermistor circuit
A
temperature as shown in Fig. 5-2.
010
Room temperature (˚C)
203040
Fig. 5-2
5V
Heat exchanger
temperature thermistor
R302
A
0V
● The circuit detects the indoor heat
exchanger temperature and controls
the following.
(1)Preheating.
(2)Low-temperature defrosting
during cooling and dehumidifying
operation.
(3)Detection of the reversing valve
non-operation or heat exchanger
temperature thermistor open.
The voltage at depends on the
A
heat exchanger temperature as shown
in Fig. 6-2.
R306
Fig. 6-1
C303
0V
5
4
(V)A
3
2
Voltage at
1
0
Microcomputer
Heat
61
exchanger
temperature
input
-10
010
203040
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM62
Heat exchanger temperature (˚C)
Fig. 6-2
– 62 –
Page 53
7. Initial Setting Circuit (IC401)
● When power is supplied, the microcomputer reads the data in IC401 (E
2
PROM) and sets the preheating
activation value and the rating and maximum speed of the compressor, etc. to their initial values.
● Data of self-diagnosis mode is stored in IC401; data will not be erased even when power is turned off.
5V
5V5V
1
2
3
4
IC401 (E
0V
2
PROM)
8
7
6
5
0V
C401
0V
R404
R403
27
26
SCL
SDA
Microcomputer
External ROM
}
Fig. 7-1
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM63
– 63 –
Page 54
Model RAI-50NH5
1. Power Circuit
TERMINAL
BOARD
25A FUSE
L
SURGEABSORBER
N
VARISTOR3
L001
C001
VARISTOR1
C002
CT1
C009
0V
0V
NF COIL1
C003
R001
C004C005
COIL
C006
POWER RELAY
R007
R008
ICP RELAY
DIODE
STACK 1
(D25VB60)
SPM2
TB8
TB2
REACTOR
L1L2
TB7TB6
TB10
U
Vdba
N1
P1
TB11
TB12
V
W
3A FUSE
VARISTOR2
STACK 2 (RC2)
C010
C011
POWER CIRCUIT
R010R011
DIODE
L002
C014
C015
C012
C013
C007
C008
JW6
R002
Fig. 1-1
● This circuit full-wave rectifies 220-240V AC applied between terminals L and N, and boosts it to a required
voltage with the active module, to create a DC voltage.
The voltage becomes 260-360V when the compressor is operated
(1) Active module
The active filter, consisting of a reactor and
switching element, eliminates higher
harmonic components contained in the
current generated when the compressor is
operated, and improves the power-factor.
< Reference >
● In case of malfunction or defective connection:
Immediately after the compressor starts, it may stop
due to “abnormally low speed” active error, etc.
The compressor may continue to operate normally,
but the power-factor will decrease, the operation
current will increase, and the overcurrent breaker
(2) Diode stacks
These rectify the 220-240V AC from
terminals L and N to a DC power supply.
of the household power board will probably activate.
● In case of active module faulty or defective
connection:
Although the compressor continues to operate
normally, the power-factor will decrease, the
operation current will increase, and the overcurrent
breaker of the household power board will probably
activate.
< Reference >
● If diode stack 1 is faulty, the compressor may stop
due to “lp”, “anbormally low speed”, etc. immediately
after it starts, or it may not operate at all because
no DC voltage is generated between the positive e
and negative d terminals.
If diode stack 1 is faulty, be aware that the 25A
fuse might also have blown.
● If diode stack 2 is faulty, DC voltage may not be
generated and the compressor may not operate at
all. Also, be aware that the 3A fuse might have
blown.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM64
– 64 –
Page 55
(3) Smoothing capacitor (C501, C502, C503)
This smoothes (averages) the voltage rectified by the diode stacks.
<Notes> Smoothing capacitor C501 is not available for model RAC-50NH5.
Smoothing Capacitors
SPM2
Fig. 1-2
a
b
DC voltage
Vd
(approx. 260-360V during operation)
OV
OV
OV
Fig. 1-3
(4) Smoothing capacitor (C010, C011)
This smoothes (averages) the voltage rectified by the diode
stack2. A DC voltage is generated in the same way as in
Fig. 1-3.
Voltage between + side of C010 and – side of C011 is about
330V.
(5) C001 to C003, C012 to C015, C007, C008, NF COIL1, COIL,
absorb electrical noise generated during operation of
compressor, and also absorb external noise entering from
power line to protect electronic parts.
(6) Surge absorber, Varistor 1, 2, 3,
absorbs external power surge.
(7) Inrush protective resistor (R007, R008)
This works to protect from overcurrent when power is turned
on.
● Be careful to avoid an electric shock as a
high voltage is generated. Also take care
not to cause a short-circuit through incorrect
connection of test equipment terminals. The
circuit board could be damaged.
< Reference >
● When inrush protective resistor is
defective, diode stack may
malfunction. As a result, DC voltage
is not generated and no operation can
be done.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM65
– 65 –
Page 56
2. Indoor/Outdoor Interface Circuit
● The interface circuit superimposes an interface signal on the DC 35V line supplied from the outdoor unit
to perform communications between indoor and outdoor units. This circuit consists of a transmiting circuit
which superimposes an interface signal transmit from the microcomputer on the DC 35V line and a
transmiting circuit which detects the interface signal on the DC 35V line and outputs it to the microcomputer.
● Communications are performed by mutually transmiting and receiving the 4-frame outdoor request signal
one frame of which consists of a leader of approx. 100 ms., start bit, 8-bit data and stop bit and the
command signal with the same format transmit from the indoor unit.
● Communication signal from outdoor microcomputer to indoor microcomputer. At first outdoor microcomputer
will send a request signal (SDO) to indoor microcomputer. A high-frequency IF signal approx. 38 KHz is
generated and modulated by the request signal (SDO) inside the outdoor microcomputer then output to
11
of microcomputer. This modulated IF signal is output to pin 30 of HIC and amplified by amp. This
pin
signal is superimposed to DC 35V line via C801 and L801.
To prevent erroneous reception, the outdoor microcomputer is designed so that it cannot receive a signal
while it is outputting a request signal.
The receiving circuit in the indoor unit consists of a comparator and transistor. The interface signal from
the outdoor unit on the DC 35V line is supplied to C821, where DC components are eliminated, and is
then shaped by the comparator. The shaped signal is detected by diode, amplified by amp, and output
49
to pin
Fig. 2-2 shows the voltages at each component when data is transferred from the outdoor microcomputer
to the indoor microcomputer.
● Communication signal from indoor microcomputer to outdoor microcomputer. The request signal (SDO)
generates by indoor microcomputer is output to pin
is generated by comparator, then modulate by the request signal from pin
This modulated IF signal is then amplified and superimposed to DC 35V line via L801 and C802 of indoor
interface circuit.
Fig. 2-3 shows the voltages at each component when data is transferred from outdoor microcomputer to
indoor microcomputer.
The circuit operation of the outdoor receiving circuit is same as indoor receiving circuit.
of the indoor microcomputer.
50
, and amplifies by C801. IF signal approx. 38 kHz
50
of indoor microprocessor.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM66
– 66 –
Page 57
● Fig. 2-1 shows the interface circuit used for the indoor and outdoor microcomputers to communicate with
each other.
C802
I/F 0V
D101
L801
C803
5V
C804
0V
C821R821
Terminal board
CD
CD
Terminal board
R813
R812
Q803
C822
R810
Q802
R811
0V
5V5V5V
R822
R823
0V0V0V
Indoor P.W.B.
Outdoor P.W.B.
35V
R825
R824
3
2
IC801
5V5V
R807
1
R805
IC801
7
R806
C823
R826
D821
5V
R828
5V
0V
0V
R803
R804
Q821
5V
0V
R829
R830
Q801
0V
HIC
C824
IF transmit
50
output (SDO)
MICROCOMPUTER
IF receive
49
input (SDI)
5
6
C801
0V
R827
0V
Interface
relay
0V
L802
12V
C811
C812
C807
C808
0V
L801
C801
0V
C806
NF COIL2
5V
C809
C810
I/F 0V
R801
R802 Q801
29
C802
IF transmit
11
output (SDO)
0V
30
R803
0V0V
5V
5V5V
0V
0V
0V
0V
0V
5V
0V
MICROCOMPUTER
68
0V
IF receive
input (SDI)
(Communications from outdoor microcomputer to indoor
microcomputer)
(Communications from indoor microcomputer to outdoor
microcomputer)
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM67
Fig. 2-1 Indoor/outdoor interface Circuit
– 67 –
Page 58
Outdoor HIC
Pin
Pin
30
29
0.7V
0V
5V
0V
Indoor microcomputer
DC 35V line
Pin
Pin
50
49
100ms.
Leader
33ms.
1 frame
5V
0V
5V
0V
35V
Fig. 2-2 Voltages Waveforms of indoor / Outdoor Microcomputers (Outdoor to Indoor Communications)
Outdoor HIC
Pin
30
0V
29
Indoor microcomputer
DC 35V line
Pin
Pin
Pin
50
49
4.95ms.
Transmit / receive
switching time
33ms.
1 frame
5V
0V
5V
0V
5V
0V
35V
Fig. 2-3 Voltages Waveforms of indoor / Outdoor Microcomputers (Indoor to Outdoor Communications)
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM68
– 68 –
Page 59
[Serial Communications Format during Normal Communications]
(1) Outdoor microcomputer (HIC) to indoor microcomputer
(2) Indoor microcomputer to outdoor microcomputer (HIC)
Fig. 3-1 shows the system power module and its peripheral circuit.
The three transistors on the positive e side are called the upper arm, and the three transistors on the negative d side, the lower arm.
●
– 71 –
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:34 PM71
Page 62
● DC 260-360V is input to system power module and system power module switches power supply current
according to rotation position of magnet rotor. The switching order is as shown in Fig. 3-2.
At point E: U+ is ON, V– is ON (circuit in Fig. 3-1)
At point F: U+ is chopped (OFF), V– is ON (circuit in Fig. 3-4)
[]
E
F
+
Upper arm
transistor
++T+
UVVW
Lower arm
transistor
–
U
–
V
–
W
Time
Fig. 3-2 Switching order of power module
● Upper arm transistor is controlled to ON/OFF by 3.3kHz chopper signal. Rotation speed of the compress
is proportional to duty ratio (ON time/ ON time + OFF time) of this chopper signal.
● Time T in Fig. 3-2 shows the switching period, and relation with rotation speed (N) of the compressor is
shown by formula below;
N = 60/2 X 1/T
● Fig. 3-3 shows voltage waveform at each point shown in Figs. 3-1 and 3-4. First half of upper arm is
chopper, second half is ON, and first half of lower arm is chopper, second half is ON.
Voltage at
260V-360V
+
U transistor chopped
A
-
U transistor ON
Upper arm transistor
Current at
B
Chopping period
ON
T
Fig. 3-3 Voltage waveform at each point
● When power is supplied U
+
[ U–, because of that U+ is chopped, current flows as shown below;
(1) When U+ transistor is ON: U+ transistor [ U coil [ V coil [ V– transistor [ DC current detection
resistor [ Point (Fig. 3-1)
B
(2) When U+ transistor is OFF: (by inductance of motor coil) U coil [ V coil [ V– transistor [ Return
diode [ Point (Fig. 3-4)
A
B
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM72
– 72 –
Page 63
260V-360V
+
System Power Module 2
+
U
—
B
R24
U
_
+
V
—
V
+
W
—
W
A
U
V
W
U coil
V coil
DC compressor
motor
W coil
DC current (Id)
detection resistor
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
● Since current flows at point only when U+ transistor is ON, the current waveform at point becomes
intermittent waveform as shown in Fig. 3-3. Since current at point is approximately proportional to the
BB
B
input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
Table 3-1
Self-diagnosis lamp
and mode
LD301
LD301
LD301
Blinks 2
times
Blinks 3
times
Blinks 4
times
P.W.B (Main)
Self diagnosis lamps
(LD303, 302, 301)
Self-diagnosis
lp (peak current cut)
Abnormal low speed
rotation
Switching incomplete
Fig. 3-5
● Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
❈ Refer to other item (troubleshooting on page 94) for independent checking of power module.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM73
– 73 –
Page 64
4. Power Circuit for P.W.B.
● Fig. 4-1 shows the power circuit for P.W.B. and waveform at each point.
Diode stack 2
R002
(RC2)
+
C010
+
C011
R010
R011
C905
D902
IC901
34
25
L901
R907
R906
R903
1
C906
R911
R904
+
R901
D911
3
C903
D906
Switching transformer (T1)
R902
C901
D905
D904
R909
R910
R908
C907
D903
PQ1
4
C908
C
4
3
1
9
12
11
C918
PQ2
C924
R922
C909
20
D907
D909
C913
D910
R921
2
3
+
+
1
REG2
+
C910
+
C911
FM–15V
C912
C914
R916
R925
L903
JW8
1
2
21
22
D908
R915
18
19
R917
16
17
15
14
13
R920
1
VR1
2
L902
R918
FM–0V
JW8
PQ1
R923
R914
35V
0V
R919
I/F0V
17V
12V
+
R924 ZD904
C919
C920
D912
12
43
REG1
5V
+
C921
0V
Fig. 4-1 Power circuit for P.W.B.
● In the power circuit for P.W.B., power supply for microcomputer, peripheral circuits, and system power
Q706
0V
module driver circuit and, as well as DC 35V, are produced by switching power circuit.
● Switching power circuit performs voltage conversion effectively by switching transistor IC901 to convert
DC 330V voltage to high frequency of about 20kHz to 200kHz.
● Transistor IC901 operates as follows:
(1) Shifting from OFF to ON
● DC about 330V is applied from smoothing capacitors C010 Œ and C011 œ in the control power circuit.
With this power, current flows to pin of IC901 via R903 and R904 and IC901 starts to tum ON. Since
voltage in the direction of arrow generates at point at the same time, current passing through R910 and
4
C
D903 is positive-fed back to IC901.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM74
– 74 –
Page 65
(2) During ON
● The drain current at IC901 increases linearly. During this period, the gate voltage and current become
constant because of the saturation characteristics of the transformer.
(3) Shifting from ON to OFF
● This circuit applies a negative feedback signal from the 12V output. When the voltage across C919
reaches the specified value, REG2 turns on and current flows to PQ2 1-2. This turns the secondary
circuits on, sets IC901 pin 1 to “Hi”, and turns IC901 off.
(4) During OFF
● While IC901 is on, the following energy charges the primary windings of the transformer:
2
Energy=LI
/2. Here, L : Primary inductance
I : Current when IC1 is off
This energy discharges to the secondary windings during power off. That is, C910, C911, C912, C914 is
charged according to the turn ratio of each winding.
● At the start, an overcurrent flows to IC901 because of the charged current at C910, C911, C912, C914.
● The drain current at IC901 generates a voltage across R906. If it exceeds the IC901 base voltage, it sets
the IC901 gate voltage to “HI”.
● R906 limits the gate voltage to prevent excessive collector current from flowing to IC901.
<Reference>
If the power circuit for P.W.B. seems to be faulty:
(1) Make sure that 5V and 12V on the control P.W.B., upper arm U, V and W, and the lower arm power
voltage are the specified values.
(2) When only the 5V output is low:
REG 1 (regulator) faulty, 5V-0V shorted, output is too high, or REG 1 is abnormal.
(3) When 12V and 5V are abnormal:
The following defects can be considered:
1 Fan, operation, power, rush prevention relay (shorting in relay, etc.)
2 Microcomputer is abnormal.
3 REG 1 (regulator is abnormal), etc.
Shorting on primary circuits.
When shorting occurs in the secondary circuits, there is no abnormality in the primary circuits because
of overcurrent protection.
The voltage rises when an opening occurs in the primary circuits, or the feedback system is abnormal.
(4) When 15V and 17V are abnormal:
D908, D909 or drive circuit is abnormal.
(5) When all voltage are abnormal:
IC901, R906, etc. are possibly abnormal.
* If IC901 is abnormal, be aware that other components, such as the power module, REG (regulator), etc.
are possibly defective.
[When the switching power supply seems to be abnormal, the voltage between IC901 pin 4 (to be measured
at the leads of R904 and R903) and IC901 pin 5 (to be measured at R906 lead) may be between 11 and
16V. This is because the protection circuit of IC901 is operating.]
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM75
– 75 –
Page 66
5. Reversing valve control circuit
I/F 35V
Reversing
valve
DC voltmeter
or tester
5V
CN2
3
1
V
I/F 0V
FUSE RESISTOR
D702
Q701
R701
R702
4
1
PQ701
23
R703
Q705
16
0V
HIC
R219
24
MICROCOMPUTER
Fig. 5 – 1
● Reversing valve control circuit can switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 5-1.
Voltage at each point in each operation condition is approximately as shown below when measured by
tester. (When collector voltage of Q701 is measured)
Table 5-1
Operation conditionCollector voltage of Q701
Cooling
General operation of Cooling
In normal heating operation
About 35V
About 0.8V
MAX. rotation speed instructed
Heating
by indoor microcomputer after
About 0.8V
defrost is completed
Dehumidifying
Defrosting
Sensor dry
About 35V
About 35V
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM76
– 76 –
Page 67
6. Rotor magnetic pole position detection circuit
0V
0V
0V
R601
C605
C606
C607
18
19
20
Outdoor microcomputer
R602
C501
+5V
R603
C
D
E
C502
C608
0V
C503
+12V
HIC
System power module
B
36
R604
R605
R606
R607
R604
R603
R602
WV U
33
34
R608
R611
DC brushless
motor for compressor
A
0V
47
35
R610
R609
U phase
terminal voltage
Spike voltage
Pole position
detection signal
Drive signal
No power
supplied
6012060120
A
C
D
E
+
W
Upper armONNo power
(B) reference
voltage (1/2Vd)
Detection point
+
U
—
V
W
supplied
Induced voltage
Comparing process
+
V
—
Lower arm
ON
—
U
No power
supplied
60
+
W
Vd 150 ~ 330
+
U
—
V
Fig. 6-1 Rotor magnetic pole position detection circuit and voltage waveform at each point
To detect U phase, voltage at point C is produced by driving motor induced voltage signal (voltage at point A ) and
1/2 voltage of Vd (voltage at point B ), and comparing with comparator.
For V phase and W phase, voltage at point D and voltage at point E are produced in the same way as above. Voltage
C
at point
is taken into indoor unit microcomputer, switching timing to U+ transistor from W+ transistor is produced by
delaying 30° from rise waveform, ignoring spike voltage. In addition, switching timing to U-transistor from W-transistor is
produced by delaying 30° from fall waveform.
For V phase and W phase, in the same way as above, drive signals are produced from voltages at point
E
. Phases are shifted by 120° and 240°, respectively, comparing with U phase.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM77
– 77 –
D
and point
Page 68
7. Drive Circuit
6
5
4
3
2
1
MICROCOMPUTER
A
R512
R521
R511
R510
R509
R508
R507
10
9
4
3
2
1
8
7
6
5
1
13
14
15
16
17
18
1
23
11
8
7
5
4
10
6
3
9
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
19
20
21
2
3
4
5
6
7
8
9
10
12
22
B
B
B
45
44
43
42
41
38
39
40
46
IP CUTTERId CONTROL CIRCUIT
0V
17V
R501
C404
CN14
17V
0V
PWB (MAIN)
SPM2
0V
17V
U
+
V
+
W
+
U
–
V
–
W
–
IP
Id
IC1
VCC
VCU
PGU
U
VCV
PGV
V
VCW
PGW
W
NGU
NGV
NGW
SVT
SWT
SUB
SVB
SWB
F
OC
CB
A
0
A
–
GL1
GL2
SUT
R502
R503
R504
R505
R506
Q506
R536
R535
R525
Q504
R534
Q503
R524
R533
Q502
Q501
R522
R532
R531
R526
Q505
R523
HIC
P2
N1
HIC
–
+
GRY
R24
U
COMPRESSOR MOTOR
V
W
Fig. 7-1 shows the drive circuit.
The circuits for U phase, V phase and W
phase have the same Configuration.
th
ignal
nsistor
drive
Fig.. 7-1
In low speed rotation mode (PWM range), as shown in Fig. 7-2, 0-5V chopper signal is ouput from microcomputer for each phase. S
output from microcomputer is ouput to IC1 and is inverted by active Lo to become 0-15V chopper signal; it is then drive the tra
of each phase.
●
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM78
In high speed rotation mode (PWM range), as shown in Fig. 7-3, 0-5V drive signal is ouput from microcomputer for each phase (wi
no chopper because of full duty). Signal output from microcomputer is input to IC1 and is inverted by active Lo to become 0-15V
signal; it is then drive the transistor of each phase.
●
– 78 –
Page 69
[Low speed rotation mode]
-
V
5V
+
A
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point
15V
+
U
0V
+
B
V
+
W
-
U
-
V
-
W
Drive signal at point
+
U
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
Fig. 7-2
[High speed rotation mode]
5V
+
A
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point
15V
+
U
0V
+
B
V
+
W
-
U
-
V
-
W
Drive signal at point
+
U
-
V
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM79
Fig. 7-3
– 79 –
Page 70
8. HIC and Peripheral Circuits
● Fig. 8-1 shows the micro computer and its peripheral circuits, Table 8-1, the basic operations of each
circuit block, and Fig. 8-2, the system configuration.
Detection Resistor
R24
N1
R41
R43
DC Current
C34
0V0V
SPM2 – HIC
OC
99
F
8
20
IC1
R42
P2
Direct Current
DC260-380V
10
3938
6
+
C217
R286
C2260VR285
0V
R222
–
+
5
R247
0V
IC4
C225
R245
L
Is
N
CT1
D104
R005
0V
C009
0V0V
R006
C107
0V
+
+
C105
58
62
JW10
0V
12V
0V
R221
R284
R292
Fig. 8-1 Microcomputer and Peripheral Circuits
7
0V
2
–
+
3
R288
IC5
0V
CN13CN14
C205
R249
R248
C215
1
+
D205
37
0V
5V
R252
19
521
5V
C218
R289
R500
R253
D204
0V
SPM2
MAIN P.W.B
HIC
59
Vd
C222
0V
17
Ip
60
Id
C224
0V
C204
0V
IC1
MICROCOMPUTER
61
Is
48
RESET
Table 8-1
Circuit block
Peak current
cutoff circuit
Set value circuit
Voltage amplifier
circuit
Reset circuit
Trip signal
synthesis circuit
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM80
Basic operation
Detects DC current flowing power module and during overcurrent (instantaneous
value) flows, stops upper/lower arm drive circuits and also produces lp signal by
which drive signal output is stopped.
Compares voltage detected, amplified and input to HIC with set voltage value in
microcomputer, and controls overload when set value exceeds input voltage.
Voltage-amplifies DC current level detected by the detection resistor and inputs
this to microcomputer. Internal or external overload is judged in microcomputer.
Produces reset voltage.
Modulates chopper signal to drive signal and stops according to presence/absence of lp signal or reset signal.
– 80 –
Page 71
5V
Reset Voltage
Chopper
signal
Chopper
Trip signal
synthesis circuit
signal
DC 260V
Reset circuit
Over-load external
setting circuit
-360V
IP signal
Current amplified
circuit
DC
Current
level
Outdoor microcomputer
Fig. 8-2
● The following describes the operations of each circuit in detail.
(1) Peak current cut off circuit
Fig.8-3 Peak Current Cut off Circuit and Waveforms at Each Section.
Drive
Circuit
Peak current
cut off circuit
Detection
resistor
Drive
signal
DC current
Powe r
module
Compressor
motor
DC current Id
21A (27A, for RAC-50NH4)
Voltage at point
1.05V (1.35V for RAC-50NH4)
Voltage at point
SPM2
–
Negative
Terminal
DC
current
A
R41
A
Detection
resistor
B
0V
99
SPM2 – HIC
R43
0V
IC1
QC
R43
0V
B
R42
20 923917
8
F
Main P.W.B
CN14
Fig.8-3
● The Ip cut off circuit detects an instantaneous excessive current and stops inverter to protect parts such
as SPM2, etc.
● As shown in diagram, if current exceeding 21A (27A for RAC-50NH5) flows, voltage at point recognized
by detecting resistor is input to pin of SPM2 – HIC, and voltage divided by R41 and R43 is input to pin
9
of IC1. Since threshold of IC1 is exceeded in this case, Lo signal is input from pin (Voltage at point
B
. When Lo signal is input to pin of microcomputer, microcomputer stops drive output.
● When drive output from microcomputer is stopped, all drive output goes Hi, and microcomputer is initialized
10
17
A
8
to enter drive signal standby mode. 3 minutes later, microcomputer outputs drive signal again, to start
operation.
HIC
IP
Outdoor
microcomputer
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM81
– 81 –
Page 72
(2) Overload control circuit (OVL control circuit)
● Overload control is to decrease the speed of the compressor and reduce the load when the load on the
air conditioner increases to an overload state, in order to protect the compressor, electronic components
and power breaker.
● Overloads are judged by comparing the DC current level and set value.
● Fig. 8-4 shows the overload control system configuration and Fig. 8-5 is a characteristic diagram of
overload judgement values. There are two judgement methods-external judgement which compares the
externally set value with the DC current value regardless of the rotation speed and internal judgement
which compares the set value that varies according to the rotation speed programmed in the microcomputer
software with the DC current value.
Microcomputer
To power module
negative terminal
(R24)
DC current
Detection
resistor
Voltage amp
circuit
(Internal judgement)
DC voltage
OVL judgement
with respect to
externally set
value
A/D
converter
A/D
converter
Judgement OVL
according to the rotation
speed
Selects data according
to the rotation speed and
DC voltage
Motor control
process
Rotation speed data
OVL start current data
Fig. 8-4 Overload Control System Configuration
DC current
Judgement value according to the rotation speed
(internal judgement value)
Rotation speed
Fig. 8-5
1. Overload external judgement circuit
● Fig. 8-1. The filter consisting of R245 and C217 removes high harmonic components from the voltage
generated by the current flowing to Detection resistor; R245 and C217 average the voltage. This voltage
is then input to IC4 pin is then amplified and supplied to microcomputer pin . The microcomputer
5
compares this input with the internally set value, and if the input exceeds the set value, it enters overload
control status.
● Fig. 8-7 shows the rotation speed control. When the voltage at pin of the microcomputer exceeds the
60
set value, the microcomputer decreases the rotation speed of the compressor and reduces the load
regardless of the rotation speed commanded by the indoor microcomputer.
60
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM82
– 82 –
Page 73
Detection Resistor
R24
N1
L
Is
N
0V
CT1
C009
0V0V
D104
R006
R005
DC Current
58
+
C105
1
5
373938
5V
5V
C218
Direct Current
DC 260-380V
R500
SPM2
MAIN P.W.B.
R253
C222
0V0V
D204
C224
0V
0V0V
59
Vd
60
Id
61
Is
HIC
IC1
Microcomputer
P2
10
1
R245
0V
R221
CN14
+
C217
R247
R222
6
–
+
5
CN13
+
C205
0V
R249
7
R248IC4
D205
Fig. 8-6
Voltage at microcomputer pin
Rotation speed of compressor
60
Commanded rotation speed
Actual rotation speed
DecelerationDecelerationAccelerationAcceleration
Fig. 8-7
2. Voltage amp. circuit
● The voltage amp. circuit amplifies the DC current level detected by the detection resistor after being
converted to a voltage and supplies it to the microcomputer. Receiving this, the microcomputer converts
it to a digital signal and compares it with the internal data to judge whether or not overload control is
required.
< During overload control >
● The filter consisting of R245 and C217 removes high harmonic components from the voltage generated
from the DC current flowing to the detection resistor, and supplies it to IC4 pin 5 IC4 forms a non-inverting
voltage amp. circuit together with the peripheral elements.
● The microcomputer stores the set values which vary according to the rotation speed. When the DC current
level exceeds the set value, the microcomputer enters the overload control state.
● The set Value is determined by the amplification of the voltage amp. circuit.
{
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM83
● Amplification : high [ DC current : low
● Amplification : low [ DC current: high
– 83 –
Page 74
● R500, R253, detect the DC voltage at the power circuit. The microcomputer receives a DC voltage (260-
380V) via HIC
37 and applies correction to the overload set value so the DC current is low (high) when
the DC voltage is high (low).
(Since the load level is indicated by the DC voltage multiplied by DC current, R247, R248, R249 are
provided to perform the same overload judgement even when the voltage varies.)
Amplification : low
DC voltage : low
DC current : high
Amplification : 8.5 times
DC voltage : 260V
Amplification : high
DC current
0
G
0
Rotation speed
DC voltage : high
DC current : low
Fig. 8-8
< During start current control >
● It is required to maintain the start current (DC current) constant to smooth the start of the DC motor for
the compressor.
● RAC-50NH5 uses software to control the start current.
● The start current varies when the supply voltage varies. This control method copes with variations in the
voltages as follows.
(1) Turns on the power module's U+ and V– transistors so the current flows to the motor windings as
shown in Fig8-9.
(2) Varies the turn-ON time of the W+ transistor according to the DC voltage level and the start is
controlled so the start current is approx. 10A as shown in Fig. 8-10.
DC 260-360V
Detection
resistor
Chopper duty: high
ON-time
W transistor
20
15
10
5
DC current (A)
0
DC current
Power module
+
U
—
U
+
V
—
V
+
W
—
W
Compressor motor
U
V
W
Fig. 8-9
DC voltage: low
DC voltage: 280V
DC voltage: high
DC voltage (start current)
Start
Set value
Time
Fig. 8-10
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM84
– 84 –
Page 75
9. Temperature Detection Circuit
+5V
O.H. thermistor
CN8
Normal 2.7V or less
Over heat 2.7V or more
Reset 2.3V or less
HIC
O.H.
627
Microcomputer
DEF.
636
Outdoor
645
temperature
DEF. thermistor
CN9
Outdoor temperature
thermistor
CN10
+5V
0V
Normal 2.4V or more
Over heat 2.4V or less
Reset 2.9V or more
+5V
0V
Refer to the table 10-1
0V
Fig. 9-1
● The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the
Defrost. thermistor circuit detects the defrosting operation temperature.
● A thermistor is a negative resistor element which has the characteristics that the higher (lower) the
temperature, the lower (higher) the resistance.
● When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage at
62
of microcomputer is increased.
pin
● Microcomputer compares the voltage present at pin
62
with the internal set value, if it is exceeded the
set value microcomputer judges that the compressor is overheated and stops operation.
● When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly.
63
Therefore the resistance of the Defrost. thermistor becomes high and the voltage at pin
of microcomputer
drops.
If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
● During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
● The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
64
), and
transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set
at the EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dry
mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins
when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode is
entered 12 minutes after the compressor starts operation.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM85
Table 9-1
Outdoor temperature (°C)
Microcomputer pin
5
voltage (V)
– 85 –
-10
1.1901.69102.23
20
2.75
30
3.22403.62
62
– 64 are approx. 0V;
Page 76
10. Reset Circuit
Main
HIC
P. W . B
12V
5V
Microcomputer
C107
0V
R284
R286
62
+
JW10
R292
C226
R285
0V
0V
0V
2
3
IC5 (1/2)
C225
R288
8
C215
–
1
+
R289
R252
C204
0V0V
48
RESET
Fig. 10-1
● The reset circuit initializes the microcomputer program when Power is “ON” or “OFF”.
● Low voltage at pin
● Fig. 10-1 shows the reset circuit and Fig. 10-2 shows waveform at each point when power is turned on
48
resets the microcomputer, and HI activates the microcomputer.
and off.
● When power is turned on, 12V line and 5V line voltages rise and 12V line voltage reaches 10.9V and
48
reset voltage input to pin
● Reset voltage will be hold “Hi” until the 12V line voltage drops to 9.90V even though the power shuts down.
of microcomputer is set to Hi.
12
6
Voltage (V)
Power is ON
0
12
6
Voltage (V)
Power is OFF
0
12V line
5V line
Reset voltage
Time
12V line
5V line
Reset voltage
Time
Fig. 10-2
– 86 –
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM86
Page 77
11. Outdoor DC Fan Motor control circuit.
System power module
PQ102
FM-15V
C103
5V
0V
14
23
R114
R106
Main P.W.B
R115
+
C106
ZD101
R105
R104
R103
FM-15V
Q101
D101
R101
FM-0V
Ap 7V
33.3KHz
5V
T/2
R102
5V
t
T
+++
Smoothing Capacitor
1234 5321
CN12
321
2A-FUSE
C101
R107
FM-0V
1
2
3
4
5
6
7
R108
0V
Fig. 11-1
U
V
W
RC Filter
0V
Vcc
PWM control voltage
FG Pulse
CN6
C104
D105
0V
61
60
59
Power supply for DC fan motor from smoothing
capacitor in system power module
ONE CHIP DRIVER IC
BOARD
DC Fan motor with control board
12V
8
–
1
+
Q201
R298
0V
HIC
R283
R242
0V
C219
VSD
C208
0V
IC4
2
3
+
R246
0V
C209
R243
R244
R297
Microcomputer
65
75
FM–60˚ el
15
FG Pulse
input
Motor coil
●This model uses DC Fan Motor which has a controller circuit in the Motor.
●This DC Fan Motor will rotate by control voltage apply to Vsp input. (Voltage range: 1.7 to 7V DC)
Vsp high : Faster ; Vsp low : slower ; Vsp lower than 1.7V : stop
●Motor will output FG pulse by following this motor revolution.
●Outdoor Microprocessor will output PWM control signal from FMCHOP terminal by following the instruction
from indoor Microprocessor.
●This PWM control signal will convert to Vsp voltage by smoothing circuit (Q101 & RC filter)
●Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by rotation
speed.
●FG pulse will feed back to Outdoor Microprocessor through PQ102.
●PQ102 is the isolator between Microprocessor circuit and DC Fan Motor circuit, which has to match the Fan
Motor revolution with instructed revolution. Such as...
●FG pulse is also used for Fan Motor failure detection
●Microprocessor will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected, it
will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on control PWB
will blink 12 times. (Fan Motor lock detected)
●R107 and IC4 are used for Fan Motor over current
– 87 –
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM87
Page 78
< Reference >
● When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
● In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
● DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
● It will makes “Fan Lock Stop”when something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
● It may make “Fan Lock Stop” by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
● In case of “Fan Lock Stop” even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes,
Fan Motor may be broken.
< Caution >
● Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
● You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
0274E Pg 57-88(RAI-50NH5)19/10/05, 3:35 PM88
– 88 –
Page 79
12. Power Factor Control Circuit
Power factor is controlled to almost 100%. (Effective use of power)
With IC in ACT module, control is performed so that input current waveform will be similar to waveform of input
voltage
I (input current)
V (input voltage)
Effective
voltage
area
Invalid power area
(Even if voltage is applied. current does not flow)
input voltage
input current
Effective
voltage area
* Assuming the same current capacity (20A), power can be used about 10% effective, comparing with curent use
(power factor of 90%), and maximum capacity is thereby improved.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM89
– 89 –
Page 80
SERVICE CALL Q & A
ModelRAI-50NH5
COOLING MODE
Q1
The compressor has
stopped suddenly during
cooling operation.
DEHUMIDIFYING MODE
Q2
Q3
Sound of running water is heard from
indoor unit during dehumidifying.
Compressor occasionally does not
operate during dehumidifying.
HEATING MODE
Q4
The circulation stops
occasionally during
Heating mode.
A1
Check if the indoor heat
exchanger is frosted.
Wait for 3-4 minutes
until it is defrosted.
A2
A3
A4
It occurs during defrosting. Wait for 5-10
minutes until the
condenser is defrosted.
If the air conditioner operates
in cooling mode when it is
cold, the evaporator may get
frosted.
Normal sound when refrigerant flows in pipe.
Compressor may not operate when room
temperature is 10°C or less. It also stops
when the humidity is preset humidity or less.
Q5
Q6
When the fan speed is set
at HIGH or MED, the flow
is actually Weak.
Heating operation stops
while the temperature is
preset at "30".
At the beginning of heating,
A5
the fan speed remains
LOW for 30 seconds. If
HIGH is selected, it
switches to LOW and again
to MED after additional 30
seconds.
If temperature is high in
A6
the outdoor, heating
operation may stop to
protect internal devices.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM90
– 90 –
Page 81
AUTO FRESH DEFROSTING
Q7
After the ON/OFF button is pressed
to stop heating, the outdoor unit is
still working with the OPERATION
lamp lighting.
AUTO OPERATION
Q8
Fan speed does not change when
fan speed selector is changed
during auto operation.
NICE TEMPERATURE RESERVATION
Q9
When on-timer has been
programmed, operation starts before
the preset time has been reached.
Auto Fresh Defrosting is carried out : the
A7
system checks the outdoor heat exchanger
and defrosts it as necessary before stopping
operation.
A8
At this point fan speed is automatic.
This is because “Nice temperature reservation”
A9
function is operating. This function starts
operation earlier so the preset temperature is
reached at the preset time. Operation may start
maximum 60 minutes before the preset time.
Q10
Q11
Does “Nice temperature reservation”
function operate during dehumidifying?
Even if the same time is preset,
the operation start time varies.
INFRARED REMOTE CONTROL
Q12
Q13
Q14
Timer cannot be set.
The current time display
disappears soon.
The timer has been programmed,
but the preset time disappears.
A10
It does not work. It works only during cooling
and heating.
This is because “Nice temperature reservation”
A11
function is operating. The start time varies
according to the load of room. Since load varies
greatly during heating, the operation start time is
corrected, so it will vary each day.
A12
Has the clock been set? Timer cannot be set
unless the clock has been set.
The current time disappears
A13
in approx. 10 seconds. The
time set display has priority.
A14
Is the current time past the preset time?
When the preset time reaches the current
time, it disappears.
When the current time is
set the display flashes for
approx 3 minutes.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM91
– 91 –
Page 82
OTHERS
The indoor fan varies among
Q15
high air flow, low air flow and
breeze in the auto fan speed
mode. (Heating operation)
Q16
Q17
Q18
Q19
Loud noise from the outdoor unit is
heard when operation is started.
Noise from the outdoor unit
occasionally changes.
There is a difference between the set
temperature and room temperature.
Air does not flow immediately
after operation is started.
A15
This is because the cool
wind prevention function
is operating, and does
not indicate a fault.
A16
A17
A18
A19
When operation is started, the compressor
rotation speed goes to maximum to increase the
heating or cooling capability, so noise becomes
slightly louder. This does not indicate a fault.
The compressor rotation speed changes according to
the difference between the thermostat set temperature
and room temperature. This does not indicate a fault.
There may be a difference between the set
temperature and room temperature because of
construction of room, air current, etc. Set the
temperature at a comfortable for the space.
Preliminary operation is performed for one
minute when the power switch on and heating
or dehumidifying is set. The operation lamp
blinks during this time for heating. This does
not indicate a fault.
The heat exchanger temperature
is sensed in the auto speed mode.
When the temperature is low, the
fan speed varies among high air
flow, low air flow and breeze.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM92
– 92 –
Page 83
TROUBLE SHOOTING
ModelRAI-50NH5
PRECAUTIONS FOR CHECKING
DANGER
1. Remember that the
0V line is biased to
155-170V in
reference to the
ground level.
2. Also note that it takes
about 10 minutes
until the voltage fall
after the power switch
is turned off.
Power source
L
Indoor unit
electric parts
Control
P. W . B.
System power module 2
a
N
+
~
~
ACT Module
DC35V
C
0V
D
+–+
–
(0V)
b
MAIN P.W.B.
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
+
–
Power module
M
Compressor motor
approx 260-360V
approx 155-170V
approx 155-170V
DANGER
When using an
oscilloscope, never
ground it. Don't forget
that high voltages as
noted above may
apply to the
oscilloscope.
Outdoor unit P.W.B.
Always keep your hands
and metallic things away
from the enclosure of the
oscilloscope.
Oscilloscope
DANGER!
Don’t install
the ground
line.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM93
– 93 –
Page 84
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
Caution
●
Voltage of about 300-330V is charged between both ends of smoothing capacitors
WARNING
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering
iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to
discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before
performing operation chech of each circuit.
●
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray
lead wire connected from diode stack to system power module (SPM2) to prevent secondary
trouble. (Be sure to discharge smoothing capacitor)
System power module
RAC-50NH5
SPM2
P1
N1
Smoothing capacitors
Soldering
iron
Do not use a soldering iron with
transformer: If one is used, thermal fuse
inside transformer will be blown
As shown above, apply soldering iron to metal
parts (receptable) inside the sleeve
corresponding to P1 and N1 terminals of
system power module: Do this with smoothing
capacitors kept connected. By removing red/
gray lead wire from diode stack, power supply
can be shut off. (corresponding to + and –
terminals of system power module)
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM94
– 94 –
Page 85
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAI-50NH5
Timer
lamp
Does the timer lamp on the indoor unit blink?
No
See Troubleshooting when the timer lamp
blinks .
Remove the terminal cover and check the voltage
between terminal (C) and terminal (D)
Is approx. DC 33 to 37V being generated? Is the
polarity correct?
Does the operation lamp on the indoor unit
start to light or blink?
Yes
Is the compressor in the outdoor unit operating?
YesNo
Remove the outdoor unit cover and
electrical parts cover, and check
self-diagnosis lamp LD301
CN17
022527
IC3
P. W. B
Service switch
Self diagnosis lamps
(LD303, 302, 301)
Does LD301 blink one time ?
* Repeats 0.25-second on and
2-second off.
No
No
Check to see whether the Fcable is connected incorrectly
or disconnected
Normal
Yes
See Out door unit self-diagnosis lamp
lighting mode .
Check the refrigerating cycle.
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM95
Blinking other than
One-time blinking
one time
Press the service switch for 1 sec.
Does the compressor operate?
(After checking, be sure to press
the service switch to stop the
operation).
Check the outdoor electrical parts.
Yes
No
Check the indoor electrical parts.
– 95 –
Page 86
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Model RAI-50NH5
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
SELF-DIAGNOSIS LIGHTING MODE
Model: RAI-50NH5
No.Timer indicator flashing modeReason for displaySection of estimated fault
Four-way valve faulty
The room heat exchange
1
5 sec.
– ––––––– Once
temperature is low during heating,
or it is high during cooling.
(1) Four-way valve faulty.
(2) Disconnection in heat exchange
thermistor (only during heating)
Outdoor unit forced operation
2
3
4
5
6
7
5 sec.
– –––––– Twice
5 sec.
– ––––– 3 times
5 sec.
5 sec.
5 sec.
5 sec.
–– 4 times
–– 6 times
–– 7 times
–– 9 times
The outdoor unit is in forced
operation or undergoing balancing
after forced operation.
Indoor/outdoor interface faulty
The interface signal from the
outdoor unit has been interrupted.
Outdoor electrical assembly
defective.
Abnormal water level detection
All stop when the float switch has
been activated.
Drain pump forced operation.
When the knob of drain pump test
switch at Indoor P.W.B main slide to
‘test’ position.
Room thermistor or heat
exchanger thermistor is faulty
When room thermistor or heat
exchanger thermistor is opened
circuit or short circuit.
Please check at the outdoor
electrical led lamp blinking (LD301)
and refer to self diagnosis lighting
mode for outdoor unit.
(1) Drain stopped up
(2) Drain pump
(3) Float switch
(1) Indoor P.W.B. Main.
(1) Room thermistor
(2) Heat exchanger thermistor
8
9
1
5 sec.
5 sec.
–– 10 times
–– 13 times
DC fan motor overcurrent detection
Overcurrent in indoor DC fan motor
has been detected.
IC401 data reading fault
There was error in the data read
from IC401
(1) Indoor fan locked
(2) Indoor fan motor
(3) Indoor P.W.B. Main
IC401 faulty
( –– Lights for 0.5 sec. at interval of 0.5 sec..)
<Cautions>
(1) If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2) If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected.
(3) To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark
1).
0274E Pg 89-96(RAI-50NH5)19/10/05, 3:36 PM96
– 96 –
Page 87
SELF-DIAGNOSIS LIGHTING MODE
MODEL: RAI-50NH5
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM97
– 97 –
Page 88
CHECKING INDOOR UNIT ELECTRICAL PARTS
1. Power does not come on (no operation)
NoNo
Is DC 35V being generated between
terminals C and D on the terminal
board?
Is AC 220-240V AC being generated
between terminals L and N on the
outdoor unit terminal board?
Yes
Is DC 35V being generated between
terminals C and D on the outdoor
unit terminal board?
Check AC outlet and breaker, and
repair any defective part.
Yes
Check the indoor/outdoor unit
connection cable, and correct any
defective section (wrong connection,
incomplete insertion reversed).
Are control voltages (12V, 5V)
being generated normally?
Yes
Do the air deflectors perform initial
operation when the power supply is
turned on and off?
No
Is the microcomputer reset input
(pin 7 ) Hi ?
Yes
Is the microcomputer clock signal
10MHz at pin
generated normally?
10 11
being
Yes
No
Yes
No
No
No
Check the outdoor unit power circuit,
and repair the defective section.
Check according to the proper method
for checking the power circuit.
Check the indication P.W.B.
connection cord and light receiving
unit.
Check the reset circuit, and repair
any defective section.
Replace the microcomputer and
oscillator.
Replace the P.W.B Main
Perform final operation check.
– 98 –
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM98
Page 89
2. Outdoor unit does not operate (but receives remote infrared signal)
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM99
– 99 –
Page 90
3. Only indoor fan does not operate (other is normal)
Is approx 20 V DC generated
between pins 2 (blue) and 4 (red)
of CN 10 when operated at high fan
speed during cooling?
No
Are pulses of approx. 33 Vp-p
generated at the collectors of Q901
in the fan operation mode? Are
collectors of Q903 approx.
O V?
Yes
Are microcomputer fan PWM
outputs (micro computer pins 24)“Hi”
or are pulses output
in the fan operation mode?
No
Yes
Is 5 V DC generated between pins
2 (blue) and 1 (yellow) of CN10?
No
No
Is there 1 or less between L901
and L902?
No
Yes
Perform final operation check.
4. Indoor fan speed does not change (other is normal)
Has the fan been stopped by
YesYes
remote control?
No
Are microcomputer fan PWM
outputs micro computer pins
No
Are the collectors of Q903 approx
OV?
No
54
“Hi”?
Yes
Replace indoor fan motor.
Check disconnection, etc of lead
wires.
Yes
Replace Q901.
Replace L901.
Replace Q903.
Replace micro computer.
Replace micro computer.
Yes
Replace Q903.
Replace Q901.
Perform final operation check.
5. Air deflector does not move (other is normal)
Is pulse signal output to micro
computer pins %~™ with air
deflector set to auto during cooling?
Yes
Is there a voltage higher than 15V
across C114 (12 V line)?
No
No
Yes
Perform final operation check.
Replace micro computer.
Replace micro computer.
Replace the air deflector motor.Replace IC111.
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM100
– 100 –
Page 91
6. All systems stop from several seconds to several minutes after operation is started
(all indicators are also off)
Set to the "Hi" fan mode.
The operation lamp lights once and goes out in
5-10 seconds.
Yes
Disconnect, CN10 and set to the fan mode again.
The operation lamp lights once and goes out in
5-10 seconds.
No
Can the indoor fan be lightly turned by hand?
(Set the power switch to "off" to check.)
Yes
Replace the indoor fan motor.
Yes
No
Check to see if shorting, etc.
has occurred in the P.W.B.
pattern.
Check to see if the indoor fan is
touching the chassis, etc.
If it does, repair.
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM101
– 101 –
Page 92
CHECKING THE REMOTE CONTROLLER
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM102
– 102 –
Page 93
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
MODEL RAI-50NH5
Check to see whether the
connected C and D cable
Replace any defective parts.
If the 25A fuse has blown, be aware
that other parts may also be
defective (mainly, varistor 2, diode
stack, smoothing capacitors, system
power module, etc.).
No
correctly? If reversed, correct the
If the 3A fuse has blown, the
switching transformer (T1),
R906, etc. may also be
cable connection.
Replace any defective parts.
Yes
No
Is the switching power circuit OK?
Has the 3A fuse blown?
No
defective.
()
See the self-diagnosis lamp
lighting mode.
Ye s
Is AC220-240V being
supplied to terminal L and N?
[No operation or abnormal operation]
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM103
Is the 25A fuse normal?
Yes
See the description on
power circuit for details.
Is the power circuit normal?
Is 5V being generated
between Pin 4 (0V) and pin
3 (5V) at CN 18 (test pin)?
– 103 –
Yes
”.
Operate the outdoor unit
according to the instruction
“How to operate the outdoor
unit independently
How did the self-diagnosis
lamp (LD301) light?
Page 94
There is a defective section between the
12V output of switching power supply on
the main P.W.B. and interface relay (also,
D907 and C910 may be defective.
check for contact with solder, etc.).
Repalce the interface relay.
No
Yes
Is DC 35V being output at
terminals C and D? (Normally,
DC 33-38.5V is output.)
No
Yes
Is DC 12V being supplied across
Is DC 35V being output across R914?
the control side (coil terminal) of
Yes
interface relay?
Coil terminal
Interface relay
Yes
No
Is a voltage (at least 10V) being
generated between the contact
terminals of interface relay?
Check the interface curcuit.
Contact terminal
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM104
LD301 blinks 9 time.
Communication error.
– 104 –
Page 95
Ye sN o
No
Ye s
Ye s
Ye s
No
No
No
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Replace the power module.
Replace any defective parts.
Connect the thermistor.
”.
“forgetting
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Replace parts in the
Replace the thermistor.
thermistor circuit.
to connect after servicing
Is the power module normal?
Is the drive circuit normal?
❈ The problem may be
Is the thermistor connector
disconnected?
Is the continuity of thermistor normal?
Is the thermistor circuit normal?
Thermistor abnormal.
LD301 blinks 8 time.
Acceleration defect.
LD301 blinks 7 time.
– 105 –
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM105
Page 96
Replace parts in the
thermistor circuit.
Check continuity of new parts.
Replace system power
module or defective parts.
Check continuity of pattern and
lead wires according to the
Replace the system power
module.
Replace any defective
P.W.B. and schematic diagrams.
parts.
No
Is the thermistor circuit normal?
No
Are R503, R541, R542, R549
and peripheral circuits of
system power module normal?
No
normal?
Ye s
Is the drive circuit normal?
Ye s
Replace the main P.W.B.
Is the system power module
LD301 blinks 6 time.
The temperature at the
OH thermistor rises.
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM106
LD301 blinks 5 time.
Overload lower limit cut.
– 106 –
LD301 blinks 4 time.
Failure of switching.
LD301 blinks 3 time.
Abnormal low speed.
Page 97
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM107
– 107 –
Page 98
POWER CIRCUIT
Phenomenon 1 <Rotation speed does not increase>
Is the DC voltage at least 350V?
Ye s
Is the OVL lamp lit?
If the lamp is lit, it does not
indicate fault, but the unit
is overload status.
Overvoltage defect: system power
module faulty (15-times blinking)
No
Recheck cord, etc. of the
system power module. If
they are disconnected,
connect them securely.
If abnormality continues,
replace the system
power module.
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM108
– 108 –
Page 99
CHECKING THE REFRIGERATING CYCLE
(JUDGING BETWEEN GAS LEAKAGE AND
COMPRESSOR DEFECTIVE)
1. Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the
power module again and operate the
air conditioner.
Is the self-diagnosis lamp mode as
shown on the right?
YES
Stop to operate and check the gas
pressure in balancing mode.
Normal
(0.39-0.98 MPaG)
(4-10 kg/cm
2
G)
Lighting mode
Selfdiagnosis lamp
LD301
Time until the
lamp lights
Possible
malfunctioning
part
Blinks
Blinks
Blinks
Blinks
2 times
3 times
4 times
Approx. 10 seconds
Compressor
Blinkingoff
5 times
Approx.
10
seconds
Blinks
6 times
Within
Approx.
30
seconds
Gas
leakage
Checking the system power module
Blinks
8times
Approx.
10
seconds
Compressor
Gas leaking
(less than 4kg/cm
(less than 0.39 MPaG)
Gas leaks.
Repair and seal refrigerant.
2
G)
The compressor is defective. Replace it
and seal refrigerant.
Perform a final check of operation.
When the
self-diagnosis lamp
lights in the same
condition as above.
If the compressor checker for an
inverter type air conditioner is
( )
available, re-check using it.
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM109
– 109 –
Page 100
HOW TO CHECK SYSTEM POWER MODULE
Checking system power module using tester
Set tester to resistance range (X 100)
If indicator does not swing in the following conductivity check, the system power module is normal.
(In case of digital tester, since built-in battery is set in reverse direction, + and – terminals are reversed.)
CAUTION
If inner circuit of system power module is disconnected (open), the indicator of tester will not swing and this may
assumed as normal. In this case, if indicator swings when + and – terminals are connected in reverse of diagram
below, it is normal. Furthermore, compare how indicator swings at U, V and W phases. If indicator swings the same way
at each point, it is normal.
– +
+–
P1P2U
L2 L1
N1
+
–
+
WV
+
– +
+
P1P2U
L2 L1
N1
+
–
–
–
WV
–
0274E Pg 97-118(RAI-50NH5)19/10/05, 3:37 PM110
– 110 –
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.