FOR SERVICE PERSONNEL ONLY
INVERTER SYSTEM MULTI TYPE
INDOOR UNIT
INSTALLATION MANUAL
MODEL
RAD-18QPB
RAD-25QPB
RAD-35QPB
RAD-50QPB
(Mark is exclusive use tool for R410A)
l + – Screwdriver l Measuring Tape l Knife
l Saw l ø 65mm Power Drill l Hexagonal Wrench
Key (
4mm) l Wrench (14, 17, 22, 26mm) Gas
Leakage Detector
l Pipe Cutter l Putty l Vinyl Tape
l Pliers l Flare Tool Vacuum Pump Adapter
Manifold Valve Charge Hose Vacuum Pump
l
Carefully read through the procedure before starting installation work.
l
The sales agent should inform customers regarding
the correct operation of installation.
l
Explanation for outdoor unit is in “How To Use”
(Instruction Manual) that is packed with outdoor unit.
Tools Needed For Installation Work
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Make sure to connect earth wire.
This sign in the fi gures indicates prohibition.
SAFETY PRECAUTION
l Read the safety precautions carefully before operating the unit.
l The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user’s guide.
WARNING
l Please request your sales agent or qualifi ed technician to install your unit. Water leakage, short circuit or fi re may occur if
you do the installation work yourself.
l Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualifi ed air
conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fi re, etc.
l Be sure to connect the earth wire from the power supply wire to the outdoor unit and between the outdoor and indoor
unit. Improper earthing may cause electric shock.
l Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fi re.
l Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not,
the units may collapse and impose danger.
l Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use wire which is approved offi cial in your country. A short circuit and fi re may occur due
to the use of low quality wire or improper work.
l Be sure to use the specifi ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and fi re.
l Please use the specifi ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fi re may occur.
l When installing or transferring an air conditioner to another location, make sure that air other than the specifi ed refrigerant
(R410A) does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may
increase abnormally high leading to possibility of unit rupture.
l Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fi re, a poisonous
gas may occur.
l After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas
leaks into the room, coming into contact with fi re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
l Be sure to use the specifi ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
l When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise,
pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.
CAUTION
l A circuit breaker must be installed in the house distribution box for the direct connected power supply wire to the outdoor
unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit
breaker, the danger of electric shock exists.
l Do not install the unit near a location where there is fl ammable gas. The outdoor unit may catch fi re if fl ammable
gas leaks around it. Piping shall be suitable supported with a maximum spacing of 1m between the supports.
l Please ensure smooth fl ow of water when installing the drain hose.
l An IEC approved power cord should be used. Power cord type: NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from
customer before installation.)
WARNING
l The unit should be mounted at stable, non-vibratory
location which can provide full support to the unit.
WARNING
l No nearby heat source and no obstruction near the air
outlet is allowed.
l The clearance distances from top, right and left are
specifi ed in fi gure below.
l The location must be convenient for water drainage and
pipe connection with the outdoor unit.
l To avoid interference from noise, please place the unit
and its remote controller at least 1m from the radio and
television.
l To avoid any error in signal transmission from the remote
controller, please put the controller far away from highfrequency machines and high-power wireless systems.
Accessories to indoor Unit:
No. QuantityItem
1
2
3
4
5
6
7
8
Flare Insulator
Binder
4.0 x 10 Screw
Insulation Pipe
Aluminium Tape (large)
Band
Suspension Clamp (right, left) each
4.0 x 10 Screw
1
2
2
1
1
1
2
8
[Indoor unit installation]
CAUTION
Always install the indoor unit at level. If the
indoor unit is inclined, water may leak.
Be sure to completely
seal any gap with putty.
l The connecting pipe,
irrespective of the size,
should all be insulated
with insulation pipe and
then wrapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
Drain pipe
Must be installed separately.
Insulate indoor part of pipe to
prevent condensation.
The indoor piping should
be insulated with the
enclosed insulation pipe. (If
the insulator is insuffi cient,
please use commercial
products.)
l “Height difference” and “Piping length” of Indoor and Outdoor unit are different by Outdoor unit.
Please refer to the installation manual in Outdoor unit.
<
IA1171: A
>
1. RECOMMENDATION FOR INSTALLATION
l The fi gures below are the recommended installation type for this duct model.
l All the optional parts mentioned for each installation type and screws should be purchased locally prior to the installation.
Full duct type
Semi duct type
Need optional parts
when installing full duct type (Local purchase)
Discharge grille
Chamber of discharge grille ø150mm
Chamber of discharge of unit side ø150mm
Chamber of suction of unit side ø150mm
Chamber of suction grille ø150mm
Suction grille with fi lter
Flexible duct ø150mm 1m
Flexible duct ø150mm 2m
2
1
Need optional parts
when installing semi duct type (Local purchase)
Discharge grille
Chamber of discharge grille ø150mm
Chamber of discharge of unit side ø150mm
Suction grille
Flexible duct ø150mm 1m
Flexible duct ø150mm 2m
Non duct type
2. Installation procedure and notice
Select the installation location carefully for the split type
air conditioner. It is very diffi cult to move a split type air
conditioner after the fi rst installation.
2.1 Make a hole on the wall as shown in Fig. 2-1.
l The hole on the wall
should be made
with some inclination
like Fig. 2-1 to keep
the smooth fl ow of
condensed water.
2.2 Connecting pipe installation
l Seal the end of the pipes to prevent damage from
moisture and water.
2.3 Drain pipe installation
l Use PVC pipe VP20 (O.D. 25mm) for drain pipe.
l You must roll an insulation (thickness 10mm or more) over the indoor section of the drain pipe.
l Position the drain pipe in the downward direction to enable free-fl ow of water. Fix it with a hanger and avoid twisting the pipe as
shown in Fig. 2-3.
2.4 Installation method of unit type
INSTALLATION OF FULL DUCT TYPE
l Select the indoor unit position, fi xing direction of air outlet so
that cool/hot air reaches all the room. Standard position of
the indoor unit is with the wall side on the ceiling.
l Remove the factory fi tted fi lter and fi lter holders before installing
of full duct type.
l Secure the space for installation, inspection or servicing.
l Apply water-proof treatment to back surface of ceiling under the indoor unit, to prevent water drop.
l Do not allow any obstacle to block air fl ow within 1m of suction grille.
l Permissible length and bending of duct.
Discharging side duct
Suction side duct
Permissible length
4m or less added to suction side
1m or less
Bending
90° or less, 1 section
45° or less, 1 section
Other optional parts for display panel wired remote controller
& wireless remote controller SPX-RCDA & SPX-RCKA1
Display panel 1
Panel installation plate 1
Panel cover 1
Remote controller (wireless) 1
Remote Controller Holder 1
3.1 x 16 screw 2
Wired Remote Controller with 2 screws 1
Item QuantityNo.
1
2
3
4
5
6
7
3
4
5
6
7
1
2
3
4
5
Need optional parts
when installing non duct type (Local purchase)
Discharge grille
Discharge duct
Suction grille
1
2
3
Electrical
box
Air outlet
Filter
Wired
remote
controller
Air inlet
2 ~ 5mm
65mm
Outdoor
side
Large diameter pipe
Small diameter pipe
Insulation pipe
Stagnant water
No trap
No insulation
Do not do the installation as shown as above
Seal
Downward 1/25 ~ 1/100
Insulation
(Thickness 10mm or more)
Tape
(Unit : mm)
Fig. 2-1
Fig. 2-2
Fig. 2-3
Indoor
side
GAS
!
!
!
!
!
!
!
INS RAD-18-25-35-50QPB (EN) 1INS RAD-18-25-35-50QPB (EN) 1 12/19/14 9:42 AM12/19/14 9:42 AM
(5) Installation of indoor unit
• Set nut and washer on suspension bolt and hook it
to suspend clamp by lifting the indoor unit.
• Make sure that the indoor unit is leveled using a
level or vinyl hose with water.
• Fix the indoor unit so that the space between
bottom surfaces of ceiling and indoor unit is 58mm.
[Installation of chamber of suction grille]
[Installation of chamber of discharge grille]
[Installation of suction grille]
[Installation of discharge grille]
[Installation of flexible duct]
Refer to installation manual of optional part.
• Select the indoor unit position, fi xing direction of air
outlet so that cool/hot air reaches the entire room.
Standard position or the indoor unit is on wall side.
• Permissible length and bending of duct.
Permissible length Bending
Discharging
side duct
4m or less
90° or less,
1 section
• Secure the space for installation, inspection or servicing.
• Apply waterproof treatment under the indoor unit to prevent water leak.
• Make sure that no obstacle is blocking the air fl ow within 1m of suction grille.
(1) Installation fi gure
(2) Opening on ceiling and suspension bolt position
• Indoor unit
(1) Installation fi gure
(2) Opening on ceiling and suspension bolt position
• Indoor unit
• Chamber of suction grille
• Chamber of discharge grille
• Arrange drain pipe, refrigerant pipe, and connecting cord in their installation position.
• For fi nishing of opening on ceiling, arrange with builder in detail.
(3) Installation of suspension bolt
• Make sure to reinforce furring of ceiling (frame: ceiling joint and supporter) to maintain level of ceiling and
prevent vibration of ceiling plate.
• Suspension bolts should be purchased in the fi eld.
• Refer to diagrams shown below for length of suspension bolts.
(4) Preparation for installing indoor unit
• Remove the screw of the electric box and then
remove electric box.
• Relocate the electric box with lead wires kept
connected. Ensure the lead wire is positioned at the
upper side, and hook the claw of electric box to the
bottom of the indoor unit using 4 screws.
• Install 4 suspension clamps at both sides of indoor unit,
2 clamps at each side, using 8 tapping screws
.
(Since size of left and right clamps are different for
certain parts, refer to diagram on the right.)
• Install chamber of discharge of unit side on the indoor
unit using 10 tapping screws.
• Remove the fi lter at the bottom side of indoor unit by
unscrew 8 screws at the fi lter holders. (4 portions)
• Remove 6 screws at back plate of indoor unit. Then
install the back plate at the bottom of indoor unit using
6 screws.
• Remove 2 screws at top plate of indoor unit and install
chamber of suction of unit side using 7 screws.
CAUTION
• Be sure to install the indoor unit level. If the
indoor unit is inclined, water may leak.
• If space between bottom surfaces of indoor
unit and ceiling is not correct, there may be a
gap between grille and ceiling surface, with
consequent leakage of condensed water.
• In case of wooden frame • In case of steel frame
INSTALLATION OF SEMI DUCT TYPE
Opening on ceiling 96
Flexible duct
Flexible duct
Chamber of discharge grille
Cross section
Front view
Front view
Front view
Front view
Plan view
Plan view
Side view
Side view
Side view
Top view
Cross section
Plan view
Side view
Top view
Chamber of suction of unit side
Chamber of
suction grille
Chamber of discharge
of unit side
Opening on ceiling 864
Indoor unit
Suspension bolt 790
Suspension bolt 793
Opening on ceiling 960
Suspension bolt 740
Discharge opening size
(846 x 96)
Suction opening size
(960 x 233)
(Unit : mm)
(Unit : mm)
Suction grilleDischarge grille
Suspension bolt
(M10: Local purchase)
Suspension bolt
(M10: Local purchase)
Suspension bolt
(M10: Local purchase)
Reinforcement
Ceiling
Suspension bolt
(M10: Local purchase)
Above 300
Above 300
Above 300 Above 300
Opening on ceiling
60~90mm square piece of lumber
Nut
Reinforcing bar
C type metal
H beam
Nut
Ceiling
Ceiling
Suspension bolt
(M10)
Suspension bolt
(M10)
Suspension bolt (M10)
Suspension bolt (M10)
Suspension bolt (M10)
Indoor unit
Chamber of discharge
of unit side
Screw
Bend slip-preventive metal
Opening on ceiling 846
Opening on ceiling 960
Suspension bolt 790
Indoor unit
Suspension bolt 740
Angle
Angle
Angle
Hanger bolt
Concrete
Long nut
Insert
(100~150kg)
150~160mm
About 130
About 130
Above 200
Above 300
Opening on ceiling 960
Suspension bolt 793
Grille 980
Grille
253
Above 300
Reinforcement
Above 330
Above 330
Above 330
Opening on ceiling 233
Opening on ceiling 233
Indoor unit
Back plate
Back plate
Indoor unit
(1) Bottom side suction opening
(2) Back side suction opening
A level
Suspension bolt (M10)
(Local purchase)
Hexagon nut (M10)
(Local purchase)
Washer
(Local purchase)
58mm
Ceiling
Filter holders
Filter
Top plate
Remove the screw
Screws to fit
electric box
Chamber of suction of unit side
Screw
Suspension bolt 347
Suspension bolt
position 740
Suspension bolt
position 793
Opening on ceiling 96
Flexible duct
Flexible duct
Chamber of discharge of unit side
Suction grille
Suction opening size
(960 x 520)
Chamber of discharge grille
Above 300
Above 300
Above 200
Above 300
Discharge grille
Discharge opening size
(846 x 96)
Suspension bolt 347
Suspension bolt position
790 x 347
Suspension bolt
(M10: Local purchase)
Suspension bolt
(M10: Local purchase)
Opening on ceiling
(Unit : mm)
(Unit : mm)
Left side
suspension clamp (2)
Right side
suspension clamp (2)
Screw
3
Screw
8
Screw
3
Screw
8
!
INS RAD-18-25-35-50QPB (EN) 2INS RAD-18-25-35-50QPB (EN) 2 12/19/14 9:42 AM12/19/14 9:42 AM