Hitachi RAS-60YHA4, RAC-60YHA4 Installation Manual

Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user’s guide.
HITACHI SPLIT-UNIT AIR CONDITIONER
Indoor Unit Outdoor Unit
RAS-60YHA4 RAC-60YHA4
SAFETY PRECAUTION
!
!
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation).
WARNING
!
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
WARNING
The outdoor unit must be mounted at a location which can support
heavy weight. Otherwise, noise and vibration will increase.
CAUTION
No nearby heat source and no obstruction near the air outlet is
allowed.
The clearance distances from top, right and left are specifi ed in
gure below.
The location must be convenient for water drainage and pipe
connection with the outdoor unit.
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter type uorescent lamp.
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more.
INDOOR UNIT
Figure showing the Installation of Indoor and Outdoor Unit.
OUTDOOR UNIT
FOR SERVICE PERSONNEL ONLY
Direction of Piping
WARNING
!
Please request your sales agent or qualifi ed technician to install your unit. Water leakage, short circuit or fi re may occur if
you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fi re.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not,
the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the specifi ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and re.
Please use the specifi ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and re may occur.
Be sure to use the speci ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only speci ed refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high that may cause rupture to the refrigeration cycle.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fi re, a poisonous
gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas
leaks into the room, coming into contact with fi re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali ed air
conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fi re, etc.
There are 6 directions allowed, namely, horizontally perpendicular to the unit, vertically down from right, horizontally out from right, horizontally out to left, horizontally out to right, vertically down from left. Don’t form the piping downward at the left of the unit.
Carefully read through the procedures of proper
installation before starting installation work.
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
Screw for Mounting Plate
(4.1x32)
Names of Indoor Components
Screw for holder of Remote Controller
(3.1x16)
AAA Size Battery
Holder for Remote Controller
Mounting Plate
QtyNo. Component’s Name
1
6
1
2
2
Remote Controller
Purifying Filter
1
2
3
4
5
6
7
1
2
<
IA1367: A
>
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
1
CAUTION
!
The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be fi xed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overfl ow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the mounting plate.
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on
wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe
according to the wall thickness.
Empty gap in the sleeve
of protection pipe should be completely sealed with putty to avoid dripping of rain water into the room.
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fi t into the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered with
insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical
cover. (Refer to “CONNECTION OF POWER CORD”)
After adjustment, fi t the connecting cord and pipes into
the space available under the indoor unit.
When connection is at left side, refrigerating pipe and
cabinet shall be tied together.
Failing to do so may cause the unit bottom side become
warping.
Excess binder shall be cut to prevent abnormal sound
and water dripping.
!
CAUTION
The rubber strap used for
xing the insulator should not be tied with great force. Otherwise, this will damage heat insulation and causes water condensation.
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
!
CAUTION
Please fi x in the plastic core
after fl aring to avoid copper chips entering the pipes.
CAUTION
!
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth fl ow of condensed water of the Indoor unit during installation. (Carelessness may result in water leakage.)
!
CAUTION
Be sure that the drain hose is not loosely connected or bend.
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse. Unless it seals completely, any air with high humidity flows from outdoor and dew may drop.
!
WARNING
The refrigerating pipes and connecting cord
arrangement are attached.
The end of the refrigerating pipes are at locations
marked with “
” symbol.
Installation of Drain Hose
3
INDOOR UNIT
Heat insulation pipe
Connecting cord
Refrigerating pipe
Pull this to the front during the connection of refrigerating pipes to ease task.
Procedures of Installation and Precautions
Procedures to fi x the mounting plate.
1. Drill holes on wall. 2. Push plug into the holes. 3. Fix the mounting plate on wall (As shown below) (As shown below) with 4.1 x 32 screw (As shown in fi gure below)
Procedures to fi x the holder of remote control.
1. Drill holes on wall. 2. Push plug into the holes. (As shown below) (As shown below)
Installation of the Indoor Unit
2
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the indoor unit is hanged on the mounting plate.
The projection at the lower part of the indoor unit is hooked onto the mounting plate.
Please pull the lower part of the indoor unit outwards to check if the unit is hooked onto the mounting plate. Improper installation may cause vibration and noise.
!
CAUTION
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull
out the drain cap.
(This is an easier way to
remove the drain cap).
( mark is tool exclusive use for R410A)
+
Screwdriver
Measuring Tape
Knife Saw
Pipe Cutter Hexagonal Wrench Key ( 4mm)
Power Drill (ø 65mm ~ ø 80mm) Vacuum Pump
Pliers or Wrench Torque Wrench Vacuum Pump
Adaptor
Flare Tool Gas Leakage Detector
Manifold Valve
Charge Hose
Dimension of Mounting Stand
of the outdoor unit
(unit : mm)
The difference in height
between the indoor and outdoor unit should be kept max 20m.
The connecting pipe,
no matter big or small, should all be insulated with insulation pipe and then wrapped with plastic tape. (The insulator will deteriorate if it is not wrapped with tape).
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products).
In case the pipe length is more than 20m, add refrigerant R410A at 10 gram per every meter exceeds. However, pipe length shall not exceed 30m.
CAUTION
!
Be sure to completely seal any gap with putty.
HOW TO REMOVE INDOOR UNIT
Push up the (PUSH) sections at the bottom of the indoor unit and
pull the bottom plate towards you. Then the claws are released from the stationary plate.
(The (PUSH) sections are indicated by 2 arrows in the right fi gure)
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary stand at the back of the Indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover.
(Refer to “Connection of Power Cord”)
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the mounting plate.
!
!
!
A circuit breaker must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
The external switch shall be incorporated to completely disconnect from power supply. It should disconnect all poles, and a
contact separation of at least 3mm must be present.
Do not install the unit near a location where there is fl ammable gas. The outdoor unit may catch fi re if
ammable gas leaks around it.
Do not install the indoor unit in a machine shop or kitchen where vapor from oil or its mist fl ows to the indoor unit. The oil will deposit on the heat exchanger, thereby reducing the indoor unit performance and may deform and in the worst case, break the plastic parts of the indoor unit.
Please ensure smooth ow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
CAUTION
CAUTION
!
Selecting the installation location: Suitable location that will reduce the
impact from rain and direct sun that may affect the unit performance. Besides that, ventillation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right, front and back are specifi ed
in gure below. At least 3 of the above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb
the neighbourhood.
Do not install at a location where there is ammable gas, steam, oil and
smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 1m away from the
antenna or signal line of television, radio or telephone. This is to avoid noise interference.
Do not install outdoor unit facing strong wind direction. It may damage
the fan motor.
Do not install the outdoor unit in a place where small animals may build their nests. If small animal goes inside the unit and touches the electrical parts, failure of the unit, smoke or fi re may be caused. Request your customer to keep the surrounding of the unit is clean.
1
Bush
Names of Outdoor Components
QtyNo. Item
1
Drain Pipe
Bush
3
8
9
10
!
CAUTION
Condensed water may leak out if not inserted properly.
Remove the cap for drain hose installation
Drain cap
Drain cap shall be fully tightened by pushing with Hexagonal wrench key when changing location.
INS RAS-RAC-60YHA4 (EN) 1INS RAS-RAC-60YHA4 (EN) 1 8/23/16 3:12 PM8/23/16 3:12 PM
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided for R410A)
<
IA1367: A
>
Preparation of Pipe
1
Use a pipe cutter to cut the copper pipe.
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
Before fl aring,
please put on the fl are nut.
Pipe Connection
2
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
CAUTION
!
CONNECTION OF POWER CORD
Removal Of Air From The Pipe And Gas Leakage Inspection
3
Outer Diameter (mm)
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
Clutch type
A (mm)
1.5 ~ 2.0
1.5 ~ 2.0
1.5 ~ 2.5
1.5 ~ 2.5
Wing nut type
Thickness
(mm)
0.8
0.8
0.8
1.0
0.0
~ 0.5
0.0
~ 0.5
0.0
~ 0.5
0.0
~ 0.5
Flare tool for R410A
Clutch type
Conventional are tool
Outer
diameter
of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
15.88 (5/8")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
15.88 (5/8")
Valve core cap
Torque N.m
(kgf
cm)
13.7 ~ 18.6 (140 ~ 190)
34.3 ~ 44.1 (350 ~ 450)
44.1 ~ 53.9 (450 ~ 550) 49 ~ 58.8 (500 ~ 600)
19.6 ~ 24.5 (200 ~ 250)
19.6 ~ 24.5 (200 ~ 250)
29.4 ~ 34.3 (300 ~ 350)
29.0 ~ 31.0 (296 ~ 316)
12.3 ~ 15.7 (125 ~ 160)
Small dia. side
Large dia. side
Valve
head cap
Small dia. side
Large dia. side
CAUTION
!
In case of removing fl are nut of an Indoor unit, fi rst remove a nut of small diameter side, or a seal cap of big diameter side will fl y out. Prevent water from entering into the piping when working.
Recommend to use
R410A fl aring tool
FINAL STAGE OF INSTALLATION
Insulation And Maintenance Of Pipe Connection
1
The connected terminals should be completed sealed with heat insulator
and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in
the gure showing the installation of indoor and outdoor units. Then fi x their position with holders.
To enhance the heat insulation and to prevent water condensation, please
cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Installation Of Remote Controller
2
The remote controller can be placed in its holder which is xed on wall or beam.
To operate the remote controller at its holder, please ensure that the unit can
receive signal transmitted from the controller at the place where the holder is to be xed. The unit will beep when signal is received from the remote controller. The signal transmission is weaken by the fl orescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting location of the holder.
Power Source And Operation Test
3
Power Source
CAUTION
!
Please use a new socket. Accident may occur due to the use of old socket because
of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the
plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the plug under external
force as this may cause poor contact.
Do not fi x the power cord with U-shape nail.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user’s manual.
The controller should be insert from top into bottom side of the holder as shown in fi gure below.
AIR REMOVAL
When the meter reaches - 101KPa (-76cmHg) during pumping, fully tighten the shuttle.
Lo Hi
Meter showing pressure
Closed
R410A Manifold valve
Vacuum pump
Valve
Charge hose
Valve
Vacuum pump adapter
When pumping starts, slightly loosen the are nut to check of air sucked in. Then tighten the fl are nut.
Procedures of using Vacuum Pump for Air Removal
As shown in right fi gure, remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump and connect the charge hose to the adapter.
Fully tighten the “Hi” knob of the manifold valve and completely unscrew the “Lo” knob. Run the vacuum pump for about 10~15 minutes, then completely tighten the “Lo” knob and switch off the vacuum pump.
2
Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise direction to allow the fl ow of refrigerant (using Hexagonal Wrench key).
Re-cap the service valve and tighten using wrench. Check the cap’s periphery if there is any gas leakage. The task is then completed.
Remove the charge hose and tighten the cap of valve core. Check the cap’s periphery if there is any gas leakage.
4
5
1
3
OUTDOOR UNIT
Please mount the Outdoor unit on stable ground to prevent
vibration and increase of noise level.
Decide the location for piping after sorting out the different
types of pipe available.
When removing side cover, please pull the handle after undoing
the hook by pulling it downward.
Please face this side (suction side) of the unit to the wall.
Please remove side cover when connecting the piping and connecting cord.
Pull downward
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed
water to exhaust.
In order to fl ow condensed water to the drain, the unit is installed
on a stand or a block so that the unit is 100mm above the ground as shown fi gure. Join the drain pipe to one hole.
At fi rst insert one portion of the hook to the base (Portion A),
then pull the drain pipe in the direction shown by the arrow while inserting the hook into the base. After installation, check whether the drain pipe cling to the base fi rmly.
When Using and Installing In Cold Areas
When the air conditioner is used in low temperature and in snowy
conditions, water from the heat exchanger may freeze on the base surface to cause poor drainage. When using the air conditioner in such areas, do not install the bushings. Keep a minimum of 250mm between the drain hole and the ground. When using the drain pipe, consult your sales agent.
For more details, refer to the installation Manual for Cold Areas.
BASE
DRAIN PIPE
How to check pipe bending. – Compare bended pipe with the picture below. – If bended pipe is not good enough, cut bended area and bend it again.
a all areas are smooth, no notching area
b no scratch or mark inside f there are scratches around bending area c all have the same length g crack
d phase of bending is too long h different length
e slanting i sample of bending pipe cannot be used
INS RAS-RAC-60YHA4 (EN) 2INS RAS-RAC-60YHA4 (EN) 2 8/23/16 3:12 PM8/23/16 3:12 PM