Hitachi 0174E Service Manual

Page 1
PM
NO. 0174E
RAK-25NH4/RAC-25NH4 RAK-35NH4/RAC-35NH4
SERVICE MANUAL
TECHNICAL INFORMATION
FOR SERVICE PERSONNEL ONLY
RAK-25NH4 RAK-35NH4 RAK-50NH4
RAC-25NH4 RAC-35NH4 RAC-50NH4
RAK-50NH4/RAC-50NH4
CONTENTS
SPECIFICATIONS ------------------------------------------------------------------- 5 HOW TO USE ------------------------------------------------------------------------ 6 CONSTRUCTION AND DIMENSIONAL DIAGRAM --------------------- 29 MAIN PARTS COMPONENT --------------------------------------------------- 31 WIRING DIAGRAM ---------------------------------------------------------------- 33 CIRCUIT DIAGRAM --------------------------------------------------------------- 35 PRINTED WIRING BOARD LOCATION DIAGRAM --------------------- 41 BLOCK DIAGRAM ----------------------------------------------------------------- 43 BASIC MODE ----------------------------------------------------------------------- 45 REFRIGERATING CYCLE DIAGRAM --------------------------------------- 59 AUTO SWING FUNCTION ------------------------------------------------------ 61 DESCRIPTION OF MAIN CIRCUIT OPERATION ----------------------- 62 SERVICE CALL Q & A ---------------------------------------------------------- 93 TROUBLE SHOOTING ----------------------------------------------------------- 96 PARTS LIST AND DIAGRAM ------------------------------------------------- 116
SPECIFICATIONS
TYPE
MODEL POWER SOURCE
TOTAL INPUT
COOLING
HEATING
DIMENSIONS (mm)
NET WEIGHT
TOTAL AMPERES
CAPACITY
TOTAL INPUT TOTAL AMPERES
CAPACITY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H D
(kg)
INDOOR UNIT
RAK-25NH4 RAC-25NH4
1 PHASE, 50 Hz, 220-230V
695 (155~1,050)
2.50 (0.90 ~ 3.00)
900 (115 ~ 1,400)
3.50 (0.90 ~ 5.00)
860 285 183
9.0
OUTDOOR UNIT
3.20-3.05
8,540
4.15-4.00
11,950
750 570 280
38
DC INVERTER (WALL TYPE)
INDOOR UNIT
RAK-35NH4 RAC-35NH4
1 PHASE, 50 Hz, 220-230V
1,080 (155~1,280)
3.50 (0.90 ~ 4.00)
1,320 (115 ~ 1,920)
4.80 (0.90 ~ 6.60)
860 285 183
9.0
OUTDOOR UNIT
4.94-4.72
11,950
6.04-5.77
16,390
750 570 280
38
INDOOR UNIT
RAK-50NH4 RAC-50NH4
1 PHASE, 50 Hz, 220-230V
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
OUTDOOR UNIT
1,780 (155~2,200)
8.17-7.82
5.00 (0.90 ~ 5.20) 17,070
1,970 (115 ~ 2,100)
9.04-8.65
6.50 (0.90 ~ 8.10) 22,200
860 285 183
9.0
After installation
850 650 298
60
MAY 2003
ROOM AIR CONDITIONER
INDOOR UNIT + OUTDOOR UNIT
Refrigeration & Air-Conditioning Division
Page 2
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair the unit in question, be sure to disconnect the power cord plug from the power outlet before starting the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and the replacement must be effected in correct manner according to the instructions in the Service Manual of the unit.
If the contacts of electrical parts are defective, replace the electrical parts without trying to repair them.
First, I must disconnect the power cord plug
from the power outlet.
3. After completion of repairs, the initial state should be restored.
4. Lead wires should be connected and laid as in the initial state.
5. Modification of the unit by user himself should absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe enough to support the repaired unit again. If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new location.
10. Any inflammable thing should never be placed about the location of installation.
DANGER
11. Check the grounding to see whether it is proper or not, and if it is found improper, connect the grounding terminal to the earth.
– 1 –
Page 3
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope The standards provide for items to be generally observed in carrying and handling semiconductors in relative manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods such as rejected goods being returned).
2. Object parts (1) Micro computer
(2) Integrated circuits (IC) (3) Field-effect transistors (FET) (4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling (1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
A conductive polyvinyl bag
IC
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken. (4) Be sure to place a part on a metal plate with grounding. (5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
IC
Conductive sponge
Body earth (Elimik conductive band)
1M
Fig. 2. Body Earth
Clip for connection with a grounding wire
– 2 –
Page 4
(6) Use a three wire type soldering iron including a grounding wire.
Metal plate (of aluminium, stainless steel, etc.)
Staple
Bare copper wire (for body earth)
Fig. 3. Grounding of the working table
Working table
Resistor of 1 M (1/2W)
Earth wire
Soldering iron
2
Screw stop at the screwed part using a rag plate
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Grounding wire
– 3 –
Page 5
CAUTION
!
1. In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is heard occasionally, but this noise is not abnormal for the operation.
2. When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug from the power outlet for safety.
3. The room air conditioner does not start automatically after recovery of the electric power failure for preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4. If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment, there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5. This room air conditioner should not be used at the cooling operation when the outside temperature is below 10°C (50°F).
6. This room air conditioner (the reverse cycle) should not be used when the outside temperature is below –10°C (14°F). If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7. When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
– 4 –
Page 6
SPECIFICATIONS
MODEL
RAK-25NH4 RAK-35NH4 RAK-50NH4
RAC-25NH4 RAC-50NH4RAC-35NH4
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
PWM DC35V
NO
NO
NO
NO
NO
NO
NO
NO
YES
40 W
NO
NO
JU1012D JU1013D
NO
YES
YES
3.0A
G4A
NO
NO
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
REFRIGERANT CHARGING VOLUME (Refrigerant 410A)
UNIT
PIPES (MAX. 20m)
NO
NO
NO
NO
YES(IC)
YES
----------
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
450NR
YES(IC)
1150g1150g
YES
NO
YES
NO
1400g
– 5 –
Page 7
SAFETY PRECAUTION
Please read the “Safety Precaution” carefully before operating the unit to ensure correct usage of the unit.
Pay special attention to signs of “ Warning” and “ Caution”. The “Warning” section contains matters which, if not observed strictly, may cause death or serious injury. The “Caution” section contains matters which may result in serious consequences if not observed properly. Please observe all instructions strictly to ensure safety.
The sign indicate the following meanings.
!
!
Make sure to connect earth line.
Indicates the instructions that must be followed.
Please keep this manual after reading.
PRECAUTIONS DURING INSTALLATION
Do not reconstruct the unit. Water leakage, fault, short circuit or fire may occur if you reconstruct the unit by yourself.
!
WARNING
!
CAUTION
Please ask your sales agent or qualified technician for the installation of your unit. Water leakage, short circuit or fire may occur if you install the unit by yourself.
Please use earth line. Do not place the earth line near water or gas pipes, lightning-conductor, or
the earth line of telephone. Improper installation of earth line may cause electric shock.
A circuit breaker should be installed depending on the mounting site of the unit. Without a circuit breaker, the danger of electric shock exists.
Do not install near location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
The sign in the figure indicates prohibition.
W
A R N
N G
!
W
A R N
N
G
PRECAUTIONS DURING SHIFTING OR MAINTENANCE
Should abnormal situation arises (like burning smell), please stop operating the unit
!
I
and turn off the circuit breaker. Contact your agent. Fault, short circuit or fire may occur if you continue to operate the unit under abnormal situation.
Please contact your agent for maintenance. Improper self maintenance may cause electric shock and fire.
Please contact your agent if you need to remove and reinstall the unit. Electric shock or fire may occur if you remove and reinstall the unit yourself improperly.
PRECAUTIONS DURING OPERATION
Avoid an extended period of direct air flow for your health.
Do not put objects like thin rods into the panel of blower and suction side because the high-speed fan inside may cause danger.
I
Do not use any conductor as fuse wire, this could cause fatal accident.
During thunder storm, disconnect and turn off the circuit breaker.
– 6 –
Page 8
PRECAUTIONS DURING OPERATION
The product shall be operated under the manufacturer specification and not for any other intended use.
Do not attempt to operate the unit with wet hands, this could cause fatal accident.
When operating the unit with burning equipments, regularly ventilate the room to avoid oxygen insufficiency.
Do not direct the cool air coming out from the air-conditioner panel to face household heating apparatus as this may affect the working of apparatus such as the electric kettle, oven etc.
Please ensure that outdoor mounting frame is always stable, firm and without defect. If not, the outdoor unit may collapse and cause danger.
Do not splash or direct water to the body of the unit when cleaning it as this may cause short circuit.
!
C A
Do not use any aerosol or hair sprays near the indoor unit. This chemical can adhere on heat exchanger fin and blocked the evaporation water flow to drain pan. The water will drop on tangential fan and cause water splashing out from indoor unit.
U T
I
O
Please switch off the unit and turn off the circuit breaker during cleaning, the high-speed fan inside the unit may cause danger.
N
Turn off the circuit breaker if the unit is not to be operated for a long period.
Do not climb on the outdoor unit or put objects on it.
Do not put water container (like vase) on the indoor unit to avoid water dripping into the unit. Dripping water will damage the insulator inside the unit and causes short-circuit.
Do not place plants directly under the air flow as it is bad for the plants.
When operating the unit with the door and windows opened, (the room humidity is always above 80%) and with the air deflector facing down or moving automatically for a long period of time, water will condense on the air deflector and drips down occasionally. This will wet your furniture. Therefore, do not operate under such condition for a long time.
If the amount of heat in the room is above the cooling or heating capability of the unit (for example: more people entering the room, using heating equipments and etc.), the preset room temperature cannot be achieved.
– 7 –
Page 9
NAMES AND FUNCTIONS OF EACH PART
INDOOR UNIT
Air filter
To prevent dust from coming into the indoor unit. (Refer page 25)
Front panel
Indoor unit indicators
Light indicator showing the operating condition. (Refer page 9)
Horizontal deflector (Air Outlet)
(Refer page 20)
Vertical deflector
MODEL NAME AND DIMENSIONS
MODEL
RAK-25NH4, RAK-35NH4, RAK-50NH4
Remote controller
Send out operation signal to the indoor unit. So as to operate the whole unit. (Refer page 10)
WIDTH (mm)
860
HEIGHT (mm)
295
DEPTH (mm)
183
– 8 –
Page 10
INDOOR UNIT INDICATORS
HITACHI
FILTER LAMP
When the device is operated for a total of about 200 hours, the FILTER lamp lights indicates that it is time to clean the filter. The lamp goes out when the POWER SWITCH set to OFF and ON again.
OPERATION LAMP
This lamp lights during operation. The OPERATION LAMP flashes in the following cases during heating.
(1) During preheating
For about 2–3 minutes after starting up.
(2) During defrosting
Defrosting will be performed about once an hour when frost forms on the heat exchanger of the outdoor unit, for 5–10 minutes each time.
TIMER LAMP
This lamp lights when the timer is working.
OPERATION INDICATOR
This figure shows the opening condition of
front panel. Refer to page 24 in relation to how to open or close the front panel.
TEMPORARY SWITCH
TEMPORARY SWITCH
Use this switch to start and stop when the remote controller does not work.
By pressing the temporary switch, the operation is done in automatic mode.
TEMPORARY SWITCH
– 9 –
Page 11
NAMES AND FUNCTIONS OF REMOTE CONTROL UNIT
REMOTE CONTROLLER
This controls the operation of the indoor unit. The range of control is about 7 meters. If indoor lighting is controlled
electronically, the range of control may be shorter. This unit can be fixed on a wall using the fixture provided. Before fixing it, make sure the indoor unit can be controlled from the remote controller.
Handle the remote controller with care. Dropping it or getting it wet may compromise its signal transmission capability.
After new batteries are inserted into the remote controller, the unit will initially require approximately 10 seconds to
respond to commands and operate.
Signal emitting window/transmission sign
Point this window toward the indoor unit when controlling it.
CH
˚
CH
˚
RESET
AUTO HEAT DEHUMIDIFY COOL FAN
FAN SPEED LOW MED HI
SLEEPING STOP (CANCEL) START (RESERVE) START/STOP TIME TIMER SET
TIMER SELECTOR ON TIMER OFF TIMER
AUTO SWING
The transmission sign blinks when a signal is sent.
Display
This indicates the room temperature selected, current time, timer status, function and intensity of circulation selected.
START/STOP button
Press this button to start operation. Press it again to stop operation.
SLEEP button
Use this button to set the sleep timer.
TEMPERATURE buttons
Use these buttons to raise or lower the temperature setting. (Keep pressed, and the value will change more quickly.)
TIME button
Use this button to set and check the time and date.
RESET buttons
FUNCTION selector
Use this button to select the operating mode. Every time you press it, the mode will change from (AUTO) to (HEAT) to (DEHUMIDIFY) to
(COOL) and to (FAN) cyclically.
FAN SPEED selector
This determines the fan speed. Every time you press this button, the intensity of circulation will change from (AUTO) to (HI) to (MED) to (LOW) (This button allows selecting the optimal or preferred fan speed for each operation mode).
AUTO SWING button
Controls the angle of the horizontal air deflector.
TIMER control
Use this button to set the timer.
OFF-TIMER button Select the turn OFF time.
ON-TIMER button Select the turn ON time.
RESERVE button Time setting reservation.
CANCEL button Cancel time reservation.
Precautions for Use
Do not put the remote controller in the following places.
Under direct sunlight.
In the vicinity of a heater.
Handle the remote controller carefully. Do not drop it on the floor,
and protect it from water.
Once the outdoor unit stops, it will not restart for about 3 minutes
(unless you turn the power switch off and on or unplug the power cord and plug it in again).
This is to protect the device and does not indicate a failure.
If you press the FUNCTION selector button during operation, the
device may stop for about 3 minutes for protection.
– 10 –
Page 12
VARIOUS FUNCTIONS
Auto Restart Control
If there is a power failure, operation will be automatically restarted when the power is resumed with previous operation mode
and airflow direction. (As the operation is not stopped by remote controller.)
If you intend not to continue the operation when the power is resumed, switch off the power supply.
When you switch on the circuit breaker, the operation will be automatically restarted with previous operation mode and airflow direction. Note: 1. If you do not require Auto Restart Control, please consult your sales agent.
2. Auto Restart Control is not available when Timer or Sleep Timer mode is set.
AUTOMATIC OPERATION
The device will automatically determine the mode of operation, HEAT, COOL or DEHUMIDIFY depending on the initial room temperature. The selected mode of operation will not change when the room temperature varies.
Press the FUNCTION selector so that the display indicates the (AUTO) mode of operation.
When AUTO has been selected, the device will automatically determine the mode of operation, HEAT, COOL or DEHUMIDIFY depending on the initial room temperature.
1
If the mode automatically selected by the unit is not satisfactory, manually change the mode setting (heat, dehumidify, cool or fan).
RESET
START
STOP
Press the (START/STOP) button. Operation starts with a beep. Press the button again to stop operation.
As the settings are stored in memory in the remote controller, you only have to press the
(START/STOP) button next time.
You can raise or lower the temperature setting as necessary by maximum of 3°C.
°C
The preset temperature and the actual room temperature may vary somewhat depending on conditions.
The display does not indicate the preset temperature in the AUTO mode. If you change the setting, the indoor unit will produce a beep.
Press the (FAN SPEED) button, AUTO and LOW is available.
Press the temperature button and the temperature setting will change by 1°C each time.
Condition of Automatic Operation
Initial room temperature (approx.)
Function
-
Over 27°C COOL
-
23~27°C
DEHUMIDIFY
-
Under 23°C
HEAT
Temperature setting
27°C
Slightly lower than the room temperature
23°C
– 11 –
FAN SPEED
HI at start, MED or LOW after the preset temperature is reached
LOW
HI at start, MED or LOW after the preset temperature is reached
Page 13
HEATING OPERATION
Use the device for heating when the outdoor temperature is under 21°C.
When it is too warm (over 21°C), the heating function may not work in order to protect the device.
Press the FUNCTION selector so that the display indicates (HEAT).
Set the desired FAN SPEED with the (FAN SPEED) button (the display indicates the setting).
(AUTO) : The fan speed is HI at first and varies to MED
automatically when the preset temperature has been reached.
(HI) : Economical as the room will become warm
quickly.
But you may feel a chill at the beginning. (MED) : Fan speed slow. (LOW) : Fan speed slower.
RESET
C
˚
1
2
Set the desired room temperature with the TEMPERATURE buttons (the display indicates the setting).
3
C
˚
START
STOP
As the settings are stored in memory in the remote controller, you only
The temperature setting and the actual room temperature may vary somewhat depending on conditions.
Press the (START/STOP) button. Heating operation starts with a beep. Press the button again to stop operation.
have to press the (START/STOP) button next time.
– 12 –
Page 14
DEHUMIDIFYING OPERATION
Use the device for dehumidifying when the room temperature is over 16°C. When it is under 15°C, the dehumidifying function will not work.
Press the FUNCTION selector so that the display indicates
(DEHUMIDIFY). The FAN SPEED is set at LOW automatically. The FAN SPEED button does not work.
Set the desired room temperature with the TEMPERATURE button (the display indicates the setting).
The range of 20-26˚C is recommended as the room temperature for dehumidifying.
RESET
C
˚
1
2
C
˚
Dehumidifying Function
START
STOP
As the settings are stored in memory in the remote controller, you
Press the (START/STOP) button. Dehumidifying operation starts with a beep. Press the button again to stop operation.
only have to press the
(START/STOP) button next time.
When the room temperature is higher than the temperature setting: The device will dehumidify the room, reducing the room temperature to the preset level. When the room temperature is lower than the temperature setting: Dehumidifying will be performed at the temperature setting slightly lower than the current room temperature, regardless of the temperature setting. The function will stop (the indoor unit will stop emitting air) as soon as the room temperature becomes lower than the setting temperature.
– 13 –
Page 15
COOLING OPERATION
Use the device for cooling when the outdoor temperature is 22-42°C. If in doors humidity is very high (80%), some dew may form on the air outlet grille of the indoor unit.
Press the FUNCTION selector so that the display indicates
C
˚
1
(COOL).
RESET
Set the desired FAN SPEED with the (the display indicates the setting).
(AUTO): The FAN SPEED is HI at first and varies to
MED automatically when the preset temperature
2
(HI) : Economical as the room will become cool
(MED) : Fan speed slow. (LOW) : Fan speed slower.
Set the desired room temperature with the TEMPERATURE button (the display indicates the setting).
3
C
˚
START
STOP
The temperature setting and the actual room temperature may vary some how depending on conditions.
Press the with a beep. Press the button again to stop operation. The cooling function does not start if the temperature setting is
higher than the current room temperature (even though the (OPERATION) lamp lights). The cooling function will start as soon as you set the temperature below the current room temperature.
has been reached.
quickly.
(START/STOP) button. Cooling operation starts
(FAN SPEED) button
As the settings are stored in memory in the remote controller, you
only have to press the
(START/STOP) button next time.
– 14 –
Page 16
FAN OPERATION
You can use the device simply as an air circulator. Use this function to dry the interior of the indoor unit at the end of summer.
Press the FUNCTION selector so that the display indicates
1
(FAN).
RESET
FAN SPEED (AUTO)
For the heating operation
2
START
STOP
.....
When the AUTO fan speed mode is set in the cooling/heating operation:
The fan speed will automatically change according to the temperature
of discharged air.
When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
When the room temperature reaches setting temperature, fan speed
changes to LOW automatically.
Press the (FAN SPEED) button.
Press the (START/STOP) button. Fan operation starts with a beep. Press the button again to stop operation.
For the cooling operation
When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
After room temperature reaches the preset temperature, the cooling
operation, which changes the fan speed and room temperature to obtain optimum conditions for natural healthful cooling will be performed.
– 15 –
Page 17
HOW TO SET THE TIMER
RESET
Time, Day, Month
TIME, DAY, MONTH
After you change the batteries;
(current time, day, month)
OFF TIMER
ON TIMER
OFF-Timer
RESERVE CANCEL
You can set the device to turn off at the present time.
ON-Timer
The device will turn on
at the designated times.
Start
M D
STOP
Stop
Start
1
Set the current month and
day with the TIMER control button.
M D
1
Press the (OFF-TIMER)
button. The (OFF) mark blinks on the display.
AM
1
Press the (ON-TIMER)
button the (ON) mark blinks on the display.
AM
3
ON/OFF-Timer
Start Stop
The device will turn on (off) and off (on) at the designated times.
The switching occurs first at the preset time that comes earlier.
The arrow mark appearing on the display indicates the sequence of switching operations.
1
Press the (ON-OFF)
button so that the (OFF) mark blinks.
PM
2
Set the turn-off time
with the TIMER control button. Press the (RESERVE) button.
PM
Press the (ON-
TIMER) button so that the (OFF) mark lights and the (ON) mark blinks.
PM
AM
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL) button. The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
NOTE
You can set only one of the OFF-timer, ON-timer and ON/OFF-timer.
– 16 –
Page 18
2
Press the
(TIME) button.
AM PM PM
2
Set the turn-off time with the
TIMER control button.
3
TIMER control button.
PM
Set the current time with the
Example: The current time is 1:30 p.m.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (OFF) mark starts lighting instead of flashing and the sign (RESERVED) lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
4
Press the (TIME) button again.
The time indication starts lighting
instead of flashing.
The time indication will disappear
PM
To check the current time setting,
automatically in 10 second.
press the (TIME) button twice. The setting of the current time is
now complete.
2
Set the turn-on time with the
TIMER control button.
AM
4
Set the turn-on time with the
TIMER control button.
PM
AM
PM
The setting of turn-off time is now complete.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (ON) mark starts lighting instead of flashing and the (RESERVED) sign lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
Example:
AM
5
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button. The (ON) mark starts lighting instead of flashing and the (RESERVED) sign lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
PM
AM
The device will automatically turn on earlier so that the preset temperature can be reached at 7:00 a.m. The setting of the turn-on time is now complete.
Example: The device will turn off at 10:30 p.m. and then automatically turn on earlier so that the preset temperature can be reached at 7:00 a.m. The settings of the turn-on/off times are now complete.
Example: The device will turn off at 11:00p.m.
The timer may be used in three ways: off-timer, on-timer, and ON/OFF (OFF/ON)-timer. Set
the current time at first because it serves as a reference.
As the time settings are stored in memory in the remote controller, you only have to press
the (RESERVE) button in order to use the same settings next time.
– 17 –
Page 19
HOW TO SET THE SLEEP TIMER
Set the current time at first if it is not set before (see the pages for setting the current time). Press the (SLEEP) button, and the display changes as shown below.
Mode
44 44
H
SLEEP
Sleep timer
Sleep Timer: The device will continue working for the designated number of hours and then turn off. Point the signal window of the remote controller toward the indoor unit, and press the SLEEP button. The timer information will be displayed on the remote controller. The TIMER lamp lights with a beep from the indoor unit. When the sleep timer has been set, the display indicates the turn-off time.
H
Sleep
timer
1
Set the ON-timer.
Start
1 hour 2 hours 3 hours 7 hours
The device will be turned off by the sleep timer and turned on by on-timer.
Indication
Sleep timer off
Example: If you set 3 hours sleep time at 11:38 p.m., the turn-off time is 2:38 a.m.
1
2
Press the (SLEEP) button and set the sleep timer.
AM
H
AM
For heating: In this case, the device will turn off
in 2 hours (at 1:38 a.m.) and turn on early so that the preset temperature will be almost reached at 6:00 next morning.
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL) button. The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
– 18 –
Page 20
Explanation of the sleep timer
The device will control the FAN SPEED and room temperature automatically so as to be quiet and good for peoples health. You can set the sleep timer to turn off after 1, 2, 3 or 7 hours. The FAN SPEED and room temperature will be controlled as shown below.
Operation with the sleep timer
Function Operation
Heating
Cooling
and
dehumidifying
Fan
The room temperature will be controlled 5°C below the temperature and the FAN SPEED will be set to LOW setting 30 minutes after the setting of the sleep timer.
The room temperature will be
Sleep timer set
30 minutes later
2°C
2 hours later
1 hour later
controlled 2°C above the temperature and the FAN SPEED will be set to LOW setting 30 minutes after the setting of the sleep timer.
Sleep timer set
30 minutes later
2 hours later
6 hours later
3 hours later
The settings of room temperature and circulation are varied.
5°C
7 hours later
3 hours later
7 hours later
NOTE
If date or current time is not set, sleep timer can not be set.
If you set the sleep timer after the off-, on/off- or off/on-timer has been set, the sleep timer
becomes effective instead of the off-, on/off- or off/on-timer set earlier.
You can not set other timer during sleep timer operation.
After sleep timer time is up and when press sleep button again, the sleep timer will be set as
last setting.
Sleep timer effective only once.
19
Page 21
ADJUSTING THE AIR DEFLECTOR
1
Adjustment of the conditioned air in the upward and downward directions.
The horizontal air deflector is automatically set to the proper angle suitable for each operation. The deflector can be swung up and down continuously and also set to the desired angle using the (AUTO SWING) button.
If the “ (AUTO SWING)” button is pressed once,
the horizontal air deflector swings up and down. If the button is pressed again, the deflector stops in its current position. Several seconds (about 6 seconds) may be required before the deflector starts to move.
Use the horizontal air deflector within the adjusting range
shown on the right.
When the operation is stopped, the horizontal air deflector
moves and stops at the position where the air outlet closes.
RESET
2
CAUTION
!
In Cooling operation, do not keep the horizontal air
deflector swinging for a long time. Some dew may form on the horizontal air deflector and dew may drop.
Adjustment of the conditioned air to the left and right. Hold the vertical air deflector as shown in the figure and adjust
the conditioned air to the left and right.
When cooling dehumidifying
When heating
– 20 –
Page 22
HOW TO EXCHANGE THE BATTERIES IN THE REMOTE CONTROLLER
Remove the cover as shown in the figure and take out the
1
old batteries.
=
Install the new batteries.
2
The direction of the batteries should match the marks in the case.
!
CAUTION
1. Do not use new and old batteries, or different kinds of batteries together.
2. Take out the batteries when you do not use the remote controller for 2 or 3 months.
Push and pull to the direction of arrow
– 21 –
Page 23
THE IDEAL WAYS OF OPERATION
Suitable Room Temperature Install curtain or blinds
!
Warning
Freezing temperature is bad for health and a waste of electric power.
Ventilation Effective Usage Of Timer
It is possible to reduce heat entering the room through windows.
!
Caution
Do not close the room for a long period of time. Occasionally open the door and windows to allow the entrance of fresh air.
Do Not Forget To Clean The Air Filter
Dusty air filter will reduce the air volume and the cooling efficiency. To prevent from wasting electric energy, please clean the filter every 2 weeks.
At night, please use the OFF or ON timer operation mode, together with your wake up time in the morning. This will enable you to enjoy a comfortable room temperature. Please use the timer effectively.
Please Adjust Suitable Temperature
For Baby And Children
Please pay attention to the room temperature and air flow direction when operating the unit for baby, children and old folks who have difficulty in movement.
– 22 –
Page 24
FOR USER’S INFORMATION
OFF
The Air Conditioner And The Heat Source In The Room
!
Caution
If the amount of heat in the room is above the cooling capability of the air conditioner (for example: more people entering the room, using heating equipments and etc.), the preset room temperature cannot be achieved.
Not Operating For A Long Time
When the indoor unit is not to be used for a long period of time, please switch off the power from the mains. If the power from mains remains “ON”, the indoor unit still consumes about 8W in the operation control circuit even if it is in “OFF” mode.
When Lightning Occurs
!
Warning
To protect the whole unit during lightning, please stop operating the unit and remove the plug from the socket.
Interference From Electrical Products
!
Caution
To avoid noise interference, please place the indoor unit and its remote controller at least 1m away from electrical products.
To prevent interference, place at least 1m away.
Inverter-type fluorescent lamp.
TV
– 23 –
Page 25
ATTACHING THE AIR CLEANSING AND DEODORIZING FILTERS
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
1
2
3
Open the front panel.
Pull up the front panel by holding it at both sides
with both hands.
Remove the filter.
Push upward to release the claws and pull out the
filter.
Attaching the air cleansing and deodorizing filters to the filter.
Attach the air cleansing and deodorizing filters to
the frame by gently compress its both sides and release after insertion into filter frame.
Claws
(4 places)
!
CAUTION
Do not bend the air cleansing and deodorizing filter as it may cause damage to the structure.
4
Attach the filters.
Attach the filters by ensuring that the surface written
FRONT is facing front.
After attaching the filters, push the front panel at
three arrow portion as shown in figure and close it.
NOTE
In case of removing the air cleansing and deodorizing filters, please follow the above procedures.
The cooling capacity is slightly weakened and the cooling speed becomes slower when the air cleansing
and deodorizing filters are used. So, set the fan speed to "HIGH" when using it in this condition.
Air cleansing and deodorizing filters are washable and reusable up to 20 times by using vacuum cleaner
or water rinse under running tap water. Type number for this air cleansing filter is <SPX-CFH7>. Please use this number for ordering when you want to renew it.
Do not operate the air conditioner without filter. Dust may enter the air conditioner and fault may occur.
24
Page 26
MAINTENANCE
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
1. AIR FILTER
Clean the air filter, as it removes dust inside the room. In case the air filter is full of dust, the air flow will decrease and the cooling capacity will be reduced. Further, noise may occur. Be sure to clean the filter following the procedure below.
PROCEDURE
1
2
3
Open the front panel and remove the filter
Gently lift and remove the air cleansing and
deodorizing filter from the air filter frame.
Vacuum dust from the air filter and air cleansing and deodorizing filter using vacuum cleaner. If there is too much dust, rinse under running tap water and gently brush it with soft bristle brush. Allow filters to dry in shade.
Re-insert the air cleansing and deodorizing
filter to the filter frame. Set the filter with FRONT mark facing front, and slot them into the original state.
After attaching the filters, push the front panel
at three arrow portions as shown in figure and close it.
NOTE:
Air cleansing and deodorizing filter should be cleaned every month or sooner if noticeable loading
occurs. When used overtime, it may loose its deodorizing function. For maximum performance, it is recommended to replace it every 3-6 months depending on application requirements.
!
CAUTION
Do not wash with hot water at more than 40°C. The filter may shrink.
When washing it, shake off moisture completely and dry it in the shade; do not expose it directly to
the sun. The filter may shrink.
Do not use detergent on the air cleansing and deodorizing filter as some detergent may deteriorate
the filter electrostatic performance.
– 25 –
Page 27
2. Washable Front Panel
Remove the front panel and wash with clean
water. Wash it with a soft sponge. After using neutral detergent, wash thoroughly with clean water.
When front panel is not removed, wipe it with
a soft dry cloth. Wipe the remote controller thoroughly with a soft dry cloth.
Wipe the water thoroughly.
If water remains at indicators or signal receiver of indoor unit, it causes trouble.
Method of removing the front panel. Be sure to hold the front panel with both hands to detach and attach it.
Removing the Front Panel
Arm
When the front panel is fully opened with
both hands, push the right arm to the inside to release it, and while closing the front panel
Move the projections of the left and right
arms into the Flanges in the unit and securely insert them into the holes.
Attaching the Front Panel
slightly, put it out forward.
!
CAUTION
Do not splash or direct water to the body of the unit when cleaning
it as this may cause short circuit.
Never use hot water (above 40°C), benzine, gasoline, acid, thinner or
a brush, because they will damage the plastic surface and the coating.
Projection
Hole
Flange
– 26 –
Page 28
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning, stop operation and switch off the power supply.
3. MAINTENANCE AT BEGINNING OF LONG OFF PERIOD
Run the unit by setting the operation mode to
(COOL), the temperature to 32°C and the fan speed to HI for about half a day on a fine day, and dry the whole of the unit.
Air
Switch off the power plug.
Blow
REGULAR INSPECTION
PLEASE CHECK THE FOLLOWING POINTS BY QUALIFIED SERVICE PERSONAL EITHER EVERY HALF YEARLY OR YEARLY. CONTACT YOUR SALES AGENT OR SERVICE SHOP.
1
2
3
Confirm
Is the earth line disconnected or broken?
Is the mounting frame seriously affected by rust and is the outdoor unit tilted or unstable?
Is the plug of power line firmly plugged into the socket? (Please ensure no loose contact between them).
– 27 –
Page 29
AFTER SALE SERVICE AND WARRANTY
WHEN ASKING FOR SERVICE, CHECK THE FOLLOWING POINTS.
CONDITION CHECK THE FOLLOWING POINTS
Is the fuse all right?
When it does not operate
When it does not cool well When it does not hot well
Notes
In quiet operation or stopping the operation, the following phenomena
may occassionally occur, but they are not abnormal for the operation. (1) Slight flowing noise of refrigerant in the refrigerating cycle. (2) Slight rubbing noise from the fan casing which is cooled and then
The odor will possibly be emitted from the room air conditioner because
the various odor, emitted by smoke, foodstuffs, cosmetics and so on, sticks to it. So the air filter and the evaporator regularly must be cleaned to reduce the odor.
Is the voltage extremely high or low?
Is the circuit breaker ON?
Was the air filter cleaned?
Does sunlight fall directly on the outdoor unit?
Is the air flow of the outdoor unit obstructed?
Are the doors or windows opened, or is there any source of
heat in the room?
Is the set temperature suitable?
gradually warmed as operation stops.
Please contact your sales agent immediately if the air conditioner still fails to operate normally after the above inspections. Inform your agent of the model of your unit, production number, date of installation. Please also inform him regarding the fault.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
Please note: On switching on the equipment, particularly when the room light is dimmed, a slight brightness fluctuation may occur. This is of no consequence. The conditions of the local Power Supply Companies are to be observed.
Note
Avoid to use the room air conditioner for cooling operation when the outside temperature is below
21°C (70°F). The recommended maximum and minimum operating temperatures of the hot and cold sides should be as below:
Cooling Heating
Minimum Maximum Minimum Maximum
Indoor
Outdoor
Dry bulb °C21322027
Wet bulb °C15231219
Dry bulb °C21 43 2 21
Wet bulb °C15 26 1 15
– 28 –
Page 30
CONSTRUCTION AND DIMENSIONAL DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Air suction grill
183
Mounting plate
860
Top air suction grill
Front panel
Cabinet
285
About
380
350
About
View from back
(Pipe lead-out)
6.5 60
47
47
31 120.5
60 60
240 170450
Drain outlet
Horizontal deflectorDischarge grill
Drain hose
Hole on the wall for ø 65mm pipe
47
Drain
Narrow pipe
Vertical deflector
P
7070140
Drain cap connection port
147
56 17.5
28
47
When piping is drawn horizontally, exchange the drain hose for the drain cap
6.5 60
Connecting cable
– 29 –
Wide pipe
Page 31
CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR
MODEL RAC-25NH4, RAC-35NH4
852
28 750
16556
76
559
570
195
95
2616 280
166
MODEL RAC-50NH4
10464
Handle
Air suction grille
955
26 850
Air outlet
79
638
650
340
201
280
2022 298
Handle
96
340
169.5
Fixing hole
Holes for anchor bolt (2-ø12)
507 198
Notch for anchor bolt (2-ø12 Notchs)
12 37
57
10
1010
320
More than
340
– 30 –
100
700
More than
100
More than
Service space
More than
100
Page 32
MAIN PARTS COMPONENT
RED
360V
BLK
0V
WHT
15V
M
YEL
0~6V
BLU
0~15V
THERMOSTAT
Thermostat Specifications
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4 THERMOSTAT MODEL IC OPERATION MODE COOL HEAT
ON 15.6 (60.1) 20.0 (68.0) OFF 15.3 (59.5) 20.7 (69.3) ON 23.6 (74.5) 28.0 (82.4) OFF 23.3 (73.9) 28.7 83.7) ON 31.6 (88.9) 36.0 (96.8) OFF 31.3 (88.3) 36.7 (98.1)
TEMPERATURE °C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
FAN MOTOR
Fan Motor Specifications
MODEL
RAK-25NH4, RAK-35NH4,
RAK-50NH4
POWER SOURCE DC: 0 ~ 35V OUTPUT 23W
RED BLK
WHT
YEL BLU
CONNECTION
35V
0V 5V
0 ~ 5V
FG
RAC-25NH4, RAC-35NH4,
RAK-50NH4
DC360V
40W
M
(Control circuit built in)
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED BLK : BLACK PNK : PINK VIO : VIOLET
– 31 –
Page 33
COMPRESSOR MOTOR
Compressor Motor Specifications
MODEL COMPRESSOR MODEL
RAC-25NH4 RAC-50NH4RAC-35NH4
JU1012D JU1013D PHASE SINGLE RATED VOLTAGE AC 220 ~ 230 V RATED FREQUENCY 50 Hz POLE NUMBER 4
(U)
WHITE
CONNECTION
M
M
M
(W)
(V)
YELLOW
RESISTANCE VALUE
20°C
(68°F)
2M = 1.05
RED
75°C
(167°F)
YELLOW
2M = 1.28
WHITE
RED
!
CAUTION
( )
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the color has been changed conspicuously, replace the compressor.
– 32 –
Page 34
WIRING DIAGRAM
BLU
POWER RELAY
COIL
NF COIL 1
C003
C001
C002
VARISTOR1
L001
CT1
VARISTOR3
SURGE
ABSORBER
DIODE STACK
R010
L002
R011
C011
C010
FAN
MOTOR
VARISTOR2
CN6 WHT
C008 C013 C015
M
WHT YEL
RED
WHT YEL
YEL
YEL
YEL
DIODE STACK
RED
UVW
REACTOR
SYSTEM POWER
MODULE 2
L2 L1
CN14
CN13
CN11
C503
C502C501
10
CN14
CN10 RED
CN9 BLU
CN8 WHT
CN15 WHT
CN13
CN11
5
5
CN12
CN12
RED
GRY
2A FUSE
ICP RELAY
R008R007
3A FUSE
25A FUSE
C006 R001
BLK GRN WHT
(WHT) (BRN) (RED)(BLK)
CONNECTING
CORD
BRN RED
BLK
BLK
GRN
RED BLK
WHT
YEL
BLU
POWER CIRCUIT
TERMINAL BOARD
(GRN+YEL)
LNCD
SINGLE PHASE
AC220~230V
50Hz
(GRN+YEL)
THERE ARE SOME LEAD WIRES WHICH HAVE SPIRAL STRIPES WITH WHITE IN ADDITION TO THE ORIGINAL COLOR
CN2 RED
MAIN P.W.B.
REVERSING VALVE
R002
C007 C012 C014
ELECTRIC EXPANSION VALVE
OH THERMISTOR
DEFROST THERMISTOR
OUTDOOR TEMPERATURE THERMISTOR
GRY GRY
GRY GRY
RED RED
COMPRESSOR
MODEL RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
INDOOR UNIT
CONNECTING CORD
FROM OUTDOOR UNIT
(BROWN) (RED)
GREEN & YELLOW
INDOOR ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER THERMISTOR
TERMINAL
BOARD
C D
BLACK BLACK
GRAY GRAY
BROWN RED
CN1
CN5 CN9
EEPROM / TEST HA
1234 1 2 3 4
5678
CN12
MAIN P. W. B.
C1 C2 M1 M2
CN4 CN11
4 LINES 5 LINES
CN8
CN10
9 LINES
STEPPING
MOTOR
M
M
INDOOR
FAN MOTOR
WIRELESS
REMOTE CONTROLLER
RECEIVER
P. C. B.
CN3A
CN2A
OUTDOOR UNIT
CN2
LED
P. C. B.
– 33 –
Page 35
CIRCUIT DIAGRAM
Remote Control
Key matrix table
1
SEG5
2
SEG0
3
SEG1
4
SEG2
5
SEG3 SEG4
6 7
SEG5
8
SEG6
9
SEG7
10
COM3
11
COM2
12
COM1
13
COM0
14
SEG14
15
SEG13
16
SEG12
17
SEG11
18
SEG13
19
SEG9
20
SEG8
D3
RB425D(1/2)
C8 50v/1u
LCD 1
K 1
K2K3
K4
K5
P10
P11
K6
K7 K8
K9 K10
K11K12
SEG20 SEG19 SEG18 SEG17 SEG16 SEG21
SEG24
SEG25
SEG26 SEG27 SEG28
P12
40 39 38 37 36 35 34 33 32 31 30 29
NC
28
NC
27
NC
26
NC
25
NC
24
NC
23
NC
22
NC
NC
21
K13 K14
K15 K16
K17
K18
D0
D1
D2
D3
65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
SEG20
SEG21 SEG22 SEG23 SEG24 SEG25 SEG26 SEG27 SEG28 SEG29 SEG30 SEG31 SEG32
SEG33
SEG34 SEG35
1
63
64
SEG19
P40
2
100k
62
SEG18
P42
P41
3
R1
59
60
58
61
SEG17
SEG16
SEG14
SEG15
IC 1
57
56
SEG13
SEG12
54
55
SEG11
SEG10
53
SEG9
M3455OM6A-504FP
P43
P02
P00
P01
P10
4
9
8
P03
6
5
7
10
P11
11
P12
12
P13
52
SEG8
SEG7
D0
13
14
51
D1
50
49
SEG5
SEG6
D2
15
16
48 47
SEG4
D3
D4
17 18
SEG2
SEG3
D5
19
46
D6
45
SEG1
20
Input
P10
P11
P12
43
44
42
SEG0
SEG42
SEG43
NCVL C1
XC OUT
D7
D9
D8
22
21
23
SW1
SW-187-2P
Output
D0
Door open Automatic swingFan speed selectionOperation selectionStart/Stop
Door shut Automatic swingStart/Stop
Door open Day
Door shut Fan speedRoom temperature downRoom temperature up
Door open CancelReservationOff timer
Door shut Sleep
41
SEG41
SEG40
40
P30 P31
39 38 37
VL C2 VL C3
36 35
XC IN
34 33
VDD
32
VSS
X OUT
31
X IN
30 29
RESET
28
CARR
27
P23
26
P22
25
P20
BEEP
24
P21
R2
100k
R3
100k
R5
330
P
R4
100k
R6
D1 D2
EL-1L7
D2D1
R8
R7
R6 R9
24(1/8W)
Q1
2SC3443
or 2SC2982
R9
R10 12M
D3
RB425D
(1/2)
K19
C9
105
X1
910kHz
R11
150k
X2
32.768
kHz
C6
104
present timeHour downHour upOn timer
D3D2D1
R14 220k
220K
R13
C7
104
R15
100k
R16 100k
C1
334
C2
220p
C3 220p
C4 18p
C5 22p
R12
220k
– 35 –
Page 36
CIRCUIT DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
– 37 –
Page 37
CIRCUIT DIAGRAM
MODEL RAC-25NH4/RAC-35NH4/RAC-50NH4
– 39 –
Page 38
PRINTED WIRING BOARD LOCATION DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
MAIN P.W.B.
Marking on P.W.B.
COMPONENT SIDE
SOLDERING SIDE
1
IVORY
CN5
8 4
1
CN1
WHT
C621
C751
C132
C131 R111
ICP2
1
1
IC402
J29
J30
J17
R631 L751
R751
R114
Q113
WHT
CN4
CN8 WHT
J31
J18
J19
J10
5
IVORY
ZD131
Q111
R122
R121 ICP1
IC111
R112 C112
C111
ZD111
R125
R126
CN6
4
5
BZ
RES1
J33
J32
J34
J20
J11
J12
1
1
HB-098-101A
Q131
R132
Q112
D111
R115
Q115
C103
D821
C823 R825 R823 C822
J39
C133
IVORY
1
CN14
1
J52 J46 J44
J51 J50
J45
J42
J43
J49 J48
J40
J41
J21 J22
J14 J13
J15
CN9
4
BLK
ZD211
R201
R131
ZD121
C123
Q114
C113 R117
R828
R829
Q821
R826
R824
R822
1
IC801
4 Q801
R812 J72
C763
R612
R764
R609
R830
C115
J78
C651
C825
R118
R651
Q803
R119
R761
R120
R658
ID
8
C801
R804
C121
C116
R116 R124
Q116
R123
J79
R827
R821
C803 C804
J801
L801
R806 R805 R803
J23
J16
R811
4
J35
J24
R701
REG2
J37
J36
R606
32
33
R657
R610
C507
R807
R810
C631
R656
R503
J76
J47
R403
R605
R404
Q802
J53
J38
IC501
R500
R654
5
R763
R504
R813
CN11
J54
J25
C821
ICP3C762
R219
R653
WHT
J55
C114
J26
R742
R743
R604
R603
17
C601
R505
J71
AUTO RESTART CANCEL
1
C802
J83
16
R602
R601
J75
R652
J27
R745
R611
C122
Q722
R744R741
C506
R501
C824
R641
R506
L111
C611
R502
R514
R507
R508
L501
C501
IC711
R655
C524
R509
R746
C521
L101
J82
J81
1
R515
R510
R511
Q521
R650
J56
L743 L742 L741
16
1
C522
C302
R512
HB–098–101A
F
No. Lot
C102
J28
C101
D101
CN12
WHT
13
C711
9
8
J80
IC521
C401
R521
R522
C505 C304 R307
R305
R513
J74
R308
C104 R127
R301
C502
R128
C523
D402
IC401
J70
R401
R306 C303 R303 R302
R749 R748 R747
1
CN10
6
R402
J77
D403
IVORY
D401
J73
RECEIVING P.W.B.
Marking on P.W.B.
Lot No.
IR1
1 14
J57
C1
IVORY
CN2A
IVORY CN3A
COMPONENT SIDE
F
SW1
9
HB-098-102A
– 41 –
R1
R2
SOLDERING SIDE
Page 39
MODEL RAC-25NH4, RAC-35NH4, RAC-50NH4 MAIN P.W.B. Marking on P.W.B
COMPONENT SIDE
– 42 –
Page 40
RAK-25NH4 / RAC-25NH4 RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
LCD wireless
Room temperature thermistor
Wireless receive circuit
Filter. Operation. Timer.
Power source 1ø, 50Hz, 220~230V
L N
Outdoor unit Terminal board
SPM2
Trip signal synthesis circuit
Heat exchanger thermistor
Temporary switch
Initial setting circuit
Reset circuit
Auto sweep motor for Air deflector
Indoor microcomputer (AX-7R11)
Outdoor microcomputer / HIC (AX-8N00)
Electric Expansion valve drive circuit
Electric
Expansion
valve
– 43 –
Page 41
BASIC MODE
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Operation mode
Basic operation of start/stop switch
Off-timer
On-timer
Timer functions
Off -> On On -> Off timer
Auto
Hi
Med
Fan speed mode (indoor fan)
Lo
Basic operation of temperature controller
Sleep operation (with sleep button ON)
Operates at Hi regardless of the room temperature.
Operates at Med regardless of the room temperature.
Operates at Lo regardless of the room temperature.
Performs only fan operation at the set speed regardless of the room temperature.
Enters sleep operation after set as on the left.
Action during sleep operation Lo (sleep) operation
Fan
Start/stop switch Operation lamp
Hi Med
Fan
Speed
Lo
Hi Med Lo
Changes from Hi to Med or Lo depending on room temperature.
Temperature set for cooling
Thermo iudgment Compressor
Hi Med Lo
1. Runs at Hi until first thermo off after operation is started.
2. Runs at Lo when thermo is off.
Set to ultra-Hi when the compressor runs at maximum speed, and to Hi in other modes.
Same as at left.
Same as at left.
See page 49.
Same as at left
See page 51.
(Compressor stopped forcibly for 3 minutes)
Dehumidifying
(dehumidifying operation by the function select button only, not including that engaged by the dehumidify button)
Start/stop switch Operation tamp
Start/stop switch Operation tamp
Cancel switch Operation temp Timer tamp
Timer memory
Srart/stop switch Reserve switch Cancel switch Operation temp Timer tamp
Timer memory
Start/stop switch Reserve switch Cancel switch Operation lamp Timer lamp
Timer memory
Start
(Change in reserved time)
Changes between Lo and “Med” depending on the room temperature.
Fan speedTemperature division Division 1 Division 2 Division 3 Division 4
Lo
Lo Med Med
1. The indoor fan also stops when the compressor is in stop status.
Set to Hi in modes other than when the compressor stops.
Set to Med in modes other than when the compressor stops.
Set to Lo in modes other than when the compressor stops.
See page 53.
Same as at left
See page 53.
Stop
Start Stop
(Off-timer during stop)
(On-timer during operation)
ON ONONOFF OFF OFF ONOFF
(Off->On timer) (On->Off timer) (On->Off timer)
(Change in reserved time)
during operation)
(Off->On timer)
during stop)
Set to ultra-Lo, Lo, Med, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, time and heat exchange temperature. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preheating (cooling is recovered at 18.33˚C).
When the compressor is running at maximum speed during hot dash or when recovered from defrosting.
˚C
42. 66
37. 66
32. 66
29. 66
Hi or ultra-HI (fan speed set to auto”)
Med Lo
In modes other than left
Heat exchanger temperature
Set to ultra-Lo, Lo, Med, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, and time. Set to “stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during preheating (cooling is recovered at 18.33˚C). Set to ultra-Hi when the compressor is running at maximum speed during hot dash or when recovered from defrosting.
Set to ultra-Lo, Lo, Med” or stop depending on the room temperature and time. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C).
Set to ultra-Lo, Lo, or stop” depending on the room temperature and time. Set to “stop” if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C). The fan speed is controlled by the heat exchanger temperature; the overload control is executed as in the following diagram:
KAFON KAFOF
Med with overload
Lo
Heat exchanger temperature
See page 55.
Same as at left
See page 57.
N&F autoHeatingCooling
The neuro & fuzzy control allows device to determine optimum operation mode and set temperature. However, during auto cooling, the new cool rhythm starts when the room temperature is less than the set temperature plus 0.66˚C, after dash is finished.
Room temperature
Outdoor temperature
Calendar
Humidity
Neuro pattern recognition
Fuzzy control
Operation mode
Set temperature
Notes: (1) The set temperature can be varied ±3˚C using the
temperature setting buttons and .
v
v
(2) If operation is started by tele-control or by temporary switch
in status where remote control has not been used after power was supplied, the operation mode will be as follows (since there is no stored calendar data):
Cooling Dehumidifying
Heating
Room temparature at
operation start (˚C)
Set temperature: 28˚C Fan mode: Auto
Set temperature: Room temperature at operation Fan mode: Auto
Set temperature: 22˚C Fan mode: Auto
start
Same as at left.
Performs the sleep operation of each operation mode.
Special auto (not normally used)
The special auto mode is based on N&F auto, but the following is different:
Operation mode
N&F auto
Special auto
Mode change during operation
Does not change as long as outdoor temperature or calendar data does not change greatly.
The operation mode will be judged the same as at operation start every hour.
The special auto operation mode is entered when operation is started in the following status:
<Start condition> Power is supplied white the tele-control signal is being input. (Operation starts automatically.)
<End condition> The remote control restores the normal operation mode.
Note (1) Since there is no stored calendar
data, N&F control is not determined. See Note (2) of N&F auto.
– 45 –
Page 42
Table 1 Mode data file
RAK-25NH4 RAK-35NH4 RAK-50NH4
LABEL NAME VALUE
WMAX 4500 min WMAX2 4600 min WSTD 3250 min WBEMAX 2600 min CMAX 2900 min CMAX2 3000 min CSTD 2500 min CKYMAX 2200 min CJKMAX 2000 min CBEMAX 1800 min WMIN 1200 min CMIN 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
5500 min 5600 min 4350 min 2800 min 3700 min 3800 min 3550 min 2800 min 2500 min 2200 min 1200 min 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
6200 min 6250 min 5200 min 2600 min 5700 min 5800 min 5200 min 3550 min 2700 min 2000 min 1200 min 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
STARTMC 60 Seconds 60 Seconds 60 Seconds DWNRATEW 80% 80% 80% DWNRATEC 80% 80% 80% SHIFTW 3.33°C 3.33°C 3.33°C SHIFTC 1.00°C 1.00°C 0.33°C CLMXTP 30.00°C 30.00°C 30.00°C YNEOF 22.00°C 22.00°C 28.00°C TEION 5.00°C 5.00°C 2.00°C TEIOF 9.00°C 9.00°C 9.00°C SFTDSW 1.00°C 1.00°C 1.00°C DFTIM1 45 Minutes 45 Minutes 45 Minutes DFTIM2 60 Minutes 60 Minutes 60 Minutes
– 47 –
Page 43
NOTE (9)
Reversing valve (heating “on” mode)
Notes: (1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode. (3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP. (6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX. (7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX. (8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX. (9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Table 2 ∆TCMAX
Temperature Calculated
difference compressor rpm
1.66 2265 min 2 2435 min
2.33 2600 min
2.66 2765 min 3 2935 min
3.33 3100 min
3.66 3265 min 4 3435 min
4.33 3600 min
4.66 3765 min 5 3935 min
5.33 4100 min
5.66 4265 min 6 4435 min
6.33 4600 min
6.66 4765 min 7 4935 min
7.33 5100 min
7.66 5265 min 8 5435 min
8.33 5600 min
8.66 5765 min 9 5935 min
9.33 6100 min
9.66 6265 min
10 6435 min
10.33 6600 min
10.66 6765 min 11 6935 min
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Note:
1. See the data in Table 1 on page 47 for each constant in capital letters in the diagrams.
– 49 –
Page 44
New Cool Rhythm
Cooling Sleep Operation
Final set temperature
(Cooling/dehumidifying set temperature (temperature set by remote control (+) SHIFTC)
Set temperature during rhythm (temperature set by remote control (+) SFTRZM)
Thermo judgment
Hi
Indoor fan
New cool rhythm
Outdoor fan
Lo
Rhythm Med
Rhythm Lo
Med
Room temperature
See basic operation.
Lo
Minimum 5min.
5 sec. 5 sec.
Minimum 5min. Minimum 5min.
5min.
1 cycle
2.5 sec. 2.5 sec.
4.5 sec.
2.5 sec.
5min.
Minimum
5min.
5min.
Minimum
5min.
Thermo OFF
15 sec.
Minimum
5min.5min.
5min.
Lo
Final set temperature (Cooling/dehumidifying set temperature (+) sleep shift)
(Cooling/dehumidifying set temperature = Remote control set temperature (+) SHIFTC)
Sleep key
Operation lamp
Timer lamp
Indoor fan
Outdoor fan
Horizontal air deflector
Hi
Med
Lo (sleep)
Shut
Horizontal
Facing down
See basic operation
Lo
Set to 7 hours
0.5hr
1.5hr
2.5hr 3.5hr 6hr 7hr
3hr
Maximum speed
P1
Compressor speed
Notes:
(1) New cool rhythm is engaged when the fan speed is “auto” and the room temperature is less than
set one plus 0.66˚C in the “auto” operation mode or cooling mode. (2) The minimum new cool rhythm time is 10 minutes when the temperature falls and rises. (3) Cool rhythm is not engaged during Nice temperature, Sleep operation. (4) Pl control is engaged during new cool rhythm: the speed limit is the same as during normal operation. (5) The new cool rhythm set temperature is also shifted during thermo OFF.
Compressor speed
Notes:
(1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to sleep Lo”. (3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached. (4) The sleep shift upper value of set temperature is 28˚C. (5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min. (6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made. (7) The indoor fan speed does not change even when the fan speed mode is changed. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted. (9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Reverse cycle period
MAX. 12min.
min–1
3000
fixed
– 51 –
Page 45
+
–1.33˚C
+
–0.66˚C
Delay
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2°C). (2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute. (3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation. (4) The compressor is operated forcedly for 3 minutes after operation is started. (5) The minimum ON time and OFF time of the compressor are 3 minutes.
– 53 –
Page 46
Basic Heating Operation
SFTDSW
Heating set temperature (remote control set temperature (+))
Dash period
TWMAX
Fan speed set to "auto"
Ultra-Hi Hi Med
10sec.
Lo Ultra-Lo
Wtd
WMIN
0
Start
Max. 3 min.
Preheating released
30sec. 30sec.
1 min.
WMAX2
ultra Hi
Control by heat exchanger temperature
NOTE (11)
Lo Hi Hi Hi
Start/stop switch Thermo judgment Defrost signal Preheating judgment
Indoor fan
Operation lamp
Max.
(WMAX)
Rating
(WSTD)
Compressor speed
3000
Reversing valve (heating "on" model)
Outdoor fan
Notes: (1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm (calculated value in Table 3) larger than WMAX. (2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off. (3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor temperature
is lower than 18°C and outdoor temperature is lower than 2°C. (6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”. (7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C. (8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX. (9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode. (10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2. (11) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor rpm is actual rpm x DWNRATEW.
1.33˚C.
0.66˚C.
Stop Start Start StopStop
Thermo
OFF
30sec. 30sec.
10sec.
15sec. 15sec. 15sec.
10sec. 15sec. 15sec.
Control by heat exchanger temperature
Control by heat exchanger temperature
18˚C
Thermo OFF
Thermo
Preheat released
30sec. 30sec.30sec. 30sec. 30sec. 30sec. 10sec.
Control by
10sec.
150sec. Delay150sec. Delay
heat exchanger temperature
15sec.
15sec.
Control by heat exchanger temperature
3min.
Hi
OFF
15sec.
150sec. Delay
Table 3 ∆TWMAX
Temperature Calculated
difference compressor rpm
1.66 1965 min 2 2135 min
2.33 2300 min
2.66 2465 min 3 2635 min
3.33 2800 min
3.66 2965 min 4 3135 min
4.33 3300 min
4.66 3465 min 5 3635 min
5.33 3800 min
5.66 3965 min 6 4135 min
6.33 4300 min
6.66 4465 min 7 4635 min
7.33 4800 min
7.66 4965 min 8 5135 min
8.33 5300 min
8.66 5465 min 9 5635 min
9.33 5800 min
9.66 5965 min
10 6135 min
10.33 6300 min
10.66 6465 min 11 6635 min
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Notes:
1. See the data in Table 1 on page 47 for each constant in capital letters in the diagrams.
– 55 –
Page 47
WMIN
1 min
Notes: (1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to sleep Lo. (3) 30 minutes after the sleep key is set, the sleep shift of set temperature starts. (4) The maximum sleep shift of set temperature is 5°C, and the minimum is 12°C. (5) If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts. (6) The indoor fan speed does not change even when the fan speed mode is changed. (Lo) (7) When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted. (9) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
– 57 –
Page 48
REFRIGERATING CYCLE DIAGRAM
MODEL RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
COOLING, DEHUMIDIFYING, DEFROSTING OUTDOOR UNIT
STRAINER
CHARGING PIPE
ELECTRIC EXP ANSION VALVE
STRAINER
COMPRESSOR
REVERSING VALVE
SERVICE V ALVE
SUCTION TANK
(1/4)
SERVICE V ALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
SINGLE-ENDED UNION (1/4)
HEATING OUTDOOR UNIT
STRAINER
CHARGING PIPE
ELECTRIC EXP ANSION VALVE
STRAINER
COMPRESSOR
REVERSING VALVE
SERVICE V ALVE
SUCTION TANK
(1/4)
SERVICE V ALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
SINGLE-ENDED UNION (1/4)
– 59 –
Page 49
REFRIGERATING CYCLE DIAGRAM
MODEL RAK-50NH4 / RAC-50NH4
COOLING, DEHUMIDIFYING, DEFROSTING OUTDOOR UNIT
ELECTRIC EXP ANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING VALVE
SERVICE V ALVE
SERVICE V ALVE
(1/2)
SUCTION TANK
(1/4)
INDOOR UNIT
SINGLE-ENDED UNION (1/2)
SINGLE-ENDED UNION (1/4)
HEATING OUTDOOR UNIT
ELECTRIC EXP ANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING VALVE
SERVICE V ALVE
SERVICE V ALVE
(1/2)
SUCTION TANK
(1/4)
INDOOR UNIT
SINGLE-ENDED UNION (1/2)
SINGLE-ENDED UNION (1/4)
– 60 –
Page 50
REFERENCE
INITIALIZE AT NEXT
OPERATION.
OPERATING SPECIFICATION
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
STOP AT THE MOMENT.
3 DOWNWARD
START SWING AGAIN.
STOP SWINGING TEMPORARILY.
(SWING MODE IS CLEARED IF SWING COMMAND IS
TRANSMITTED DURING TEMPORARY STOP.)
INITIALIZE
1 DOWNWARD
2 UPWARD
INITIALIZE AT NEXT
INITIALIZE
1 DOWNWARD
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
OPERATION.
STOP SWINGING AND MODE BECOMES INITIALIZING
INITIALIZING CONDITION OF EACH MODE.
2 UPWARD
CONDITION.
STOP
DURING ONE SWING
PRESENT CONDITION
EACH MODE
OPERATION OPERATION MODE AIR DEFLECTOR
INPUT SIGNAL
AUTO SWING FUNCTION
MODEL: RAK-25NH4, RAK-35NH4, RAK-50NH4
STOP
KEY INPUT
STOP
AUTO COOL
COOL
FAN
AUTO DRY
DRY
DURING SWINGING
DURING
OPERATION
STOP
AUTO HEAT
HEAT
CIRCULATOR
DURING SWINGING
TEMPORARY STOP
AUTO DRY
THERMO. ON
(INTERNAL FAN
DURING SWINGING
DRY
AUTO HAET
HEAT
CIRCULATOR
DURING
OPERATION
ON)
THERMO. ON
(INTERNAL FAN
OFF)
STOP
DURING ONE SWING
STOP
DURING ONE SWING
STOP
COOL
FAN
DRY
HEAT
CIRCULATOR
STOP
MAIN SWITCH
ON
DURING SWINGING
DURING
INITIALIZING
STOP
DURING SWINGING
EACH MODE
DURING
OPERATION
MAIN SWITCH
OFF
EACH MODE
DURING
OPERATION
CHANGE OF
OPERATION
– 61 –
Page 51
DESCRIPTION OF MAIN CIRCUIT OPERATION
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
1. Reset Circuit
5V
2
R522
1
C521
R521
5
C524
NORMAL : HI RESET : LO
RES
7
Microcomputer
C522
Voltage
Voltage supply to
2
pin
of IC521
Reset release at 4.4V
3
IC521
0V
Fig. 1-1
5.0V
Reset enter at 4.2V
voltage
Voltage at pin of microcomputer
7
5.0V
Fig. 1-2
The reset circuit initializes the microcomputer program when power is ON or OFF.
Low voltage at pin 7 resets the microcomputer and Hi activates the microcomputer.
When power “ON” 5V voltage rises and reaches 4.4V, pin 1 of IC521 is set to “Hi”. At this time the
microcomputer starts operation.
When power “OFF” voltage drops and reaches 4.2V, pin 1 of IC521 is set to “Low”. This will RESET the
microcomputer.
– 62 –
Page 52
2. Receiver Circuit
12V
C1
ZD211
0V
R1
IR1
VDD
GND
R2 R611
V
out
C611
0V
13 RECEIVER I/P
Microcomputer
R201
Fig. 2-1
The light receiver unit receives the infrared signal from the wireless remote control. The receiver amplifies
and shapes the signal and outputs it.
3. Buzzer Circuit
12V
Microcomputer
Buzzer output
When the buzzer sounds, an approx.
3.9kHz square signal is output from buzzer output pin of the microcomputer. After
30
the amplitude of this signal has been set to 12Vp-p by a transistor, it is applied to the buzzer. The piezoelectric element in the buzzer oscillates to generate the buzzers sound.
R219
30
Fig. 3-1 Buzzer Circuit
Metal diaphragm
BZ
0V
BZ1
Q722
Pizoelectric element
Sound wave
– 63 –
V
Fig. 3-2 Buzzer Operation
V
Page 53
4. Auto Sweep Motor Circuit
12V
IC711
Auto sweep motor for horizontal air defectors
9
Microcomputer
18 17 16 15
C711
7 6 5
4
10
11 12
13
Rotor
8
0V
Fig.4-1
Fig. 4-1 shows the Auto sweep motor drive circuit; the signals shown in Fig.4-2 are output from pins
15 18 of microcomputer.
Microcomputer pins Step width
Horizontal air deflectors
15
16
17
18
12345678
Horizontal air
deflectors: 10ms.
Fig.4-2 Microcomputer Output Signals
As the microcomputer’s outputs change as shown in Fig.4-2, the core of the auto sweep motor is excited
to turn the rotor. Table 4-1 shows the rotation angle of horizontal air deflectors.
Table 4-1 Auto sweep Motor Rotation
Rotation angle per step (˚ ) Time per step (ms.)
0.0882 10Horizontal air deflectors
– 64 –
Page 54
5. Room Temperature Thermistor Circuit
5
4
3
2
1
0
010
Room temperature (˚C)
Fig. 5-2
20 30 40
0V
Room temperature thermistor
0V
5V
Fig. 5-1
62
A
R305
C302
Microcomputer
Room temp. input
Voltage at
(V)
R301
0V
Heat exchanger temperature thermistor
0V
5V
Fig. 6-1
61
A
R306
C303
Microcomputer
Heat exchanger temperature input
R302
A
5
4
3
2
1
0
010
-10 Heat exchanger temperature (˚C)
Fig. 6-2
20 30 40
Voltage at
(V)A
Fig. 5-1 shows the room temperature
thermistor circuit.
6. Heat exchanger temperature thermistor circuit
The voltage at depends on the room
A
temperature as shown in Fig. 5-2.
The circuit detects the indoor heat
exchanger temperature and controls the following.
(1) Preheating. (2) Low-temperature defrosting
during cooling and dehumidifying operation.
(3) Detection of the reversing valve non-operation or heat exchanger temperature thermistor open.
The voltage at depends on the
A
heat exchanger temperature as shown in Fig. 6-2.
– 65 –
Page 55
7. Initial Setting Circuit (IC401)
When power is supplied, the microcomputer reads the data in IC401 or IC402 (E
2
PROM) and sets the preheating activation value and the rating and maximum speed of the compressor, etc. to their initial values.
Data of self-diagnosis mode is stored in IC401 or IC402; data will not be erased even when power is
turned off.
5V
5V 5V
1 2 3 4
IC401 or IC402 (E
0V
8 7 6 5
2
0V
PROM)
C401
0V
R404
R403
27 26
SCL SDA
Microcomputer
External ROM
}
Fig. 7-1
– 66 –
Page 56
Model RAC-25NH4, RAC-35NH4, RAC-50NH4
1. Power Circuit
TERMINAL
BOARD
L
N
25A FUSE
SURGE­ABSORBER
VARISTOR3
L001
NF COIL1
C001
VARISTOR1
R001
C003
C002
CT1 C009
0V
0V
COIL
C004C005
C006
POWER RELAY
R007
R008
ICP RELAY
DIODE
STACK 1
(D25VB60)
SPM2
TB8
TB2
REACTOR
L1 L2
TB7 TB6
TB10
U
Vdba
N1
P1
TB11 TB12
V W
3A FUSE
VARISTOR2
STACK 2 (RC2)
C010
C011
POWER CIRCUIT
R010R011
DIODE
L002
C014 C015
C012 C013
C007 C008
JW6
R002
Fig. 1-1
This circuit full-wave rectifies 220-230V AC applied between terminals L and N, and boosts it to a required
voltage with the active module, to create a DC voltage.
The voltage becomes 260-360V when the compressor is operated
(1) Active module
The active filter, consisting of a reactor and switching element, eliminates higher harmonic components contained in the current generated when the compressor is operated, and improves the power-factor.
< Reference >
In case of malfunction or defective connection:
Immediately after the compressor starts, it may stop due to abnormally low speed active error, etc.
The compressor may continue to operate normally, but the power-factor will decrease, the operation current will increase, and the overcurrent breaker
(2) Diode stacks
These rectify the 220-230V AC from terminals L and N to a DC power supply.
of the household power board will probably activate.
In case of active module faulty or defective
connection: Although the compressor continues to operate
normally, the power-factor will decrease, the operation current will increase, and the overcurrent breaker of the household power board will probably activate.
< Reference >
If diode stack 1 is faulty, the compressor may stop
due to lp, anbormally low speed, etc. immediately after it starts, or it may not operate at all because no DC voltage is generated between the positive e and negative d terminals.
If diode stack 1 is faulty, be aware that the 25A fuse might also have blown.
If diode stack 2 is faulty, DC voltage may not be
generated and the compressor may not operate at all. Also, be aware that the 3A fuse might have blown.
– 67 –
Page 57
(3) Smoothing capacitor (C501, C502, C503)
This smoothes (averages) the voltage rectified by the diode stacks. <Notes > Smoothing capacitor C501 is not available for model RAC-25NH4 and RAC-35NH4.
Smoothing Capacitors
SPM2
Fig. 1-2
a
b
DC voltage
Vd
(approx. 260-360V during operation)
OV
OV
OV
Fig. 1-3
(4) Smoothing capacitor (C010, C011)
This smoothes (averages) the voltage rectified by the diode stack2. A DC voltage is generated in the same way as in Fig. 1-3. Voltage between + side of C010 and – side of C011 is about 330V.
(5) C001 to C003, C012 to C015, C007, C008, NF COIL1, COIL,
absorb electrical noise generated during operation of compressor, and also absorb external noise entering from power line to protect electronic parts.
(6) Surge absorber, Varistor 1, 2, 3,
absorbs external power surge.
(7) Inrush protective resistor (R007, R008)
This works to protect from overcurrent when power is turned on.
Be careful to avoid an electric shock as a
high voltage is generated. Also take care not to cause a short-circuit through incorrect connection of test equipment terminals. The circuit board could be damaged.
< Reference >
When inrush protective resistor is
defective, diode stack may malfunction. As a result, DC voltage is not generated and no operation can be done.
– 68 –
Page 58
2. Indoor/Outdoor Interface Circuit
The interface circuit superimposes an interface signal on the DC 35V line supplied from the outdoor unit
to perform communications between indoor and outdoor units. This circuit consists of a transmiting circuit which superimposes an interface signal transmit from the microcomputer on the DC 35V line and a transmiting circuit which detects the interface signal on the DC 35V line and outputs it to the microcomputer.
Communications are performed by mutually transmiting and receiving the 4-frame outdoor request signal
one frame of which consists of a leader of approx. 100 ms., start bit, 8-bit data and stop bit and the command signal with the same format transmit from the indoor unit.
Communication signal from outdoor microcomputer to indoor microcomputer. At first outdoor microcomputer
will send a request signal (SDO) to indoor microcomputer. A high-frequency IF signal approx. 38 KHz is generated and modulated by the request signal (SDO) inside the outdoor microcomputer then output to pin 11 of microcomputer. This modulated IF signal is output to pin 30 of HIC and amplified by amp. This signal is superimposed to DC 35V line via C801 and L801. To prevent erroneous reception, the outdoor microcomputer is designed so that it cannot receive a signal while it is outputting a request signal. The receiving circuit in the indoor unit consists of a comparator and transistor. The interface signal from the outdoor unit on the DC 35V line is supplied to C821, where DC components are eliminated, and is then shaped by the comparator. The shaped signal is detected by diode, amplified by amp, and output to pin 49 of the indoor microcomputer. Fig. 2-2 shows the voltages at each component when data is transferred from the outdoor microcomputer to the indoor microcomputer.
Communication signal from indoor microcomputer to outdoor microcomputer. The request signal (SDO)
generates by indoor microcomputer is output to pin 50 , and amplifies by C801. IF signal approx. 38 kHz is generated by comparator, then modulate by the request signal from pin 50 of indoor microprocessor. This modulated IF signal is then amplified and superimposed to DC 35V line via L801 and C802 of indoor interface circuit. Fig. 2-3 shows the voltages at each component when data is transferred from outdoor microcomputer to indoor microcomputer. The circuit operation of the outdoor receiving circuit is same as indoor receiving circuit.
– 69 –
Page 59
Fig. 2-1 shows the interface circuit used for the indoor and outdoor microcomputers to communicate with
each other.
C802
I/F 0V
D101
L801
C803
5V
C804
0V
C821 R821
Terminal board
CD
CD
Terminal board
R813
R812
Q803
0V
C822
R810
Q802
R811
5V 5V 5V
R822
R823
0V 0V0V
Indoor P.W.B.
Outdoor P.W.B.
35V
R824
3 2
IC801
R825
5V5V
R807
1
R805
IC801
7
R806
C823
R826 D821
5V
R828
5V
0V
0V
R803
R804
Q821
5V
0V
R829
R830
Q801
0V
HIC
C824
IF transmit
50
output (SDO)
MICROCOMPUTER
IF receive
49
input (SDI)
5
6
C801
0V
R827
0V
Interface relay
0V
L802
12V
C811
C812
C807
C808
0V
L801
C801
0V
C806
NF COIL2
5V
C809
C810
I/F 0V
R801
R802 Q801
29
C802
IF transmit
11
output (SDO)
0V
0V0V
0V
30
R803
5V
0V
5V 5V
0V
0V
0V
5V
0V
MICROCOMPUTER
68
0V
IF receive input (SDI)
(Communications from outdoor microcomputer to indoor microcomputer)
(Communications from indoor microcomputer to outdoor microcomputer)
Fig. 2-1 Indoor/outdoor interface Circuit
– 70 –
Page 60
Outdoor HIC
Pin
Pin
30
29
0.7V 0V
5V 0V
Indoor microcomputer
DC 35V line
Pin
Pin
50
49
100ms. Leader
33ms. 1 frame
5V 0V
5V 0V
35V
Fig. 2-2 Voltages Waveforms of indoor / Outdoor Microcomputers (Outdoor to Indoor Communications)
Outdoor HIC
Pin
30
0V
29
Indoor microcomputer
DC 35V line
Pin
Pin
Pin
50
49
4.95ms. Transmit / receive switching time
33ms. 1 frame
5V 0V
5V 0V
5V 0V
35V
Fig. 2-3 Voltages Waveforms of indoor / Outdoor Microcomputers (Indoor to Outdoor Communications)
– 71 –
Page 61
[Serial Communications Format during Normal Communications]
(1) Outdoor microcomputer (HIC) to indoor microcomputer
(2) Indoor microcomputer to outdoor microcomputer (HIC)
(3) Communications waveforms
1 frame = 100ms. + 33.3ms. x 8 + 4.95ms. = 371.35ms.
Outdoor message
Indoor message
[Example] When the outdoor message is all 0s
and indoor message is all 1s:
36 (V)
35 (V)
34 (V)
When reset
(approx. 10ms.)
Transmit/
receive
switching time
(4.95ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Bit No = 0
Bit No = 0
07
0707077
07077
Leader
(100ms.)
When reset
(approx. 10ms.)
Leader
(100ms.)
Fig. 2-4
– 72 –
Page 62
7 6 5 4
3
3 2 1
Fan-7-step request 0 7
Actual compressor rotation speed (5 MSB) 6
Actual compressor rotation speed (4) 5
Actual compressor rotation speed (3) 4
2
1
0
Actual compressor rotation speed (2) 3
Actual compressor rotation speed (1) 2
Actual compressor rotation speed (0 LSB) 1
Compressor during operation 0
Compressor during operation 7
Outside temperature (7 MSB) 6
Outside temperature (6) 5
Outside temperature (5) 4
Outside temperature (4) 3
Outside temperature (3) 2
Outside temperature (2) 1
Outside temperature (1 0
Outside temperature (0 LSB) 7
Self-diagnosis (3 MSB) 6
Self-diagnosis (2) 5
Self-diagnosis (1) 4
Self-diagnosis (0 LSB) 3
Defrost request signal 2
During forced operation 1 0
Multi-bit
0 0 0 0 0 0 1 0
1/0 1/0 1/0 1/0
1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0
0 1/0
7
Compressor minimum rotation speed (4 MSB)
6
Compressor minimum rotation speed (3)
5
Compressor minimum rotation speed (2)
4
3
2
1
0
Compressor minimum rotation speed (1)
3
Compressor minimum rotation speed (0 LSB)
2 1
OVL up
0
15/20(A)
7
Compressor command speed (7 MSB)
6
Compressor command speed (6)
5
Compressor command speed (5)
4
Compressor command speed (4)
3
Compressor command speed (3)
2
Compressor command speed (2)
1
Compressor command speed (1)
0
Compressor command speed (0 LSB)
7
Compressor ON 6 5 4
Reversing valve 3
2-way valve 2
Fan (2 MSB) 1
Fan (1 0
Fan (0 LSB) 7
Capacity code (3 MSB) 6
Capacity code (2) 5
Capacity code (1) 4
Capacity code (0 LSB) 3
Indoor in-operation bit 2
Operation mode (2 MSB) 1
Operation mode (1) 0
Operation mode (0 LSB)
1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0
0 0 0 1/0 1/0 1/0 0 1/0 0 0 1/0 1/0 1/0 1/0 1/0 0
1/0 1/0 1/0 1/0
Bit No.
Character No.
(1) Outdoor message
[ Serial Communications Data ]
Contents
– 73 –
Data
Character No.
(2) Indoor message
Bit No.
Contents
Data
Page 63
3. Power Module Circuit
+
W
U
V
W
W
+
V
V
+
U
U
A
+
DC
Compressor
motor
U coil
V coil
W coil
System Power module 2
+
C501
+
C502
+
C503
R24
0.35
m
H
Power relay
Coil
R007
R008
Inrush current
protection
relay
C006
R001
Noise filter
coil
L
N
Terminal
board
FUSE (25A)
is ON)
is ON, V
+
Fig. 3-1 shows the system power module and its peripheral circuit.
The three transistors on the positive e side are called the upper arm, and the three transistors on the negative d side, the lower arm.
– 74 –
Fig. 3-1 Power module circuit (U
Page 64
DC 260-360V is input to system power module and system power module switches power supply current
according to rotation position of magnet rotor. The switching order is as shown in Fig. 3-2.
At point E: U+ is ON, V– is ON (circuit in Fig. 3-1) At point F: U+ is chopped (OFF), V– is ON (circuit in Fig. 3-4)
[]
E
F
+
Upper arm transistor
++T+
UVVW
Lower arm transistor
U
V
W
Time
Fig. 3-2 Switching order of power module
Upper arm transistor is controlled to ON/OFF by 3.3kHz chopper signal. Rotation speed of the compress
is proportional to duty ratio (ON time/ ON time + OFF time) of this chopper signal.
Time T in Fig. 3-2 shows the switching period, and relation with rotation speed (N) of the compressor is
shown by formula below;
N = 60/2 X 1/T
Fig. 3-3 shows voltage waveform at each point shown in Figs. 3-1 and 3-4. First half of upper arm is
chopper, second half is ON, and first half of lower arm is chopper, second half is ON.
Voltage at
260V-360V
+
U transistor chopped
A
-
U transistor ON
Upper arm transistor
Current at
B
Chopping period
ON
T
Fig. 3-3 Voltage waveform at each point
When power is supplied U
+
[ U–, because of that U+ is chopped, current flows as shown below;
(1) When U+ transistor is ON: U+ transistor [ U coil [ V coil [ V– transistor [ DC current detection
resistor [ Point (Fig. 3-1)
B
(2) When U+ transistor is OFF: (by inductance of motor coil) U coil [ V coil [ V– transistor [ Return
diode [ Point (Fig. 3-4)
A
B
– 75 –
Page 65
260V-360V
+
System Power Module 2
+
U
B
R24
U
_
+
V
V
+
W
W
A U V
W
U coil
V coil
DC compressor motor
W coil
DC current (Id) detection resistor
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
Since current flows at point only when U+ transistor is ON, the current waveform at point becomes
intermittent waveform as shown in Fig. 3-3. Since current at point is approximately proportional to the
B B
B
input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
Table 3-1
Self-diagnosis lamp and mode
LD301
LD301
LD301
Blinks 2 times
Blinks 3 times
Blinks 4 times
P.W.B (Main)
Self diagnosis lamps (LD303, 302, 301)
Self-diagnosis
lp (peak current cut)
Abnormal low speed
rotation
Switching incomplete
Fig. 3-5
Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
Refer to other item (troubleshooting on page 94) for independent checking of power module.
– 76 –
Page 66
4. Power Circuit for P.W.B.
22
18
19
+
D908
R917
R915
D909
R918
L903
REG1
C911
20 21
+
D907
C910
R914
C912
16
17
+
C903
C907
+
+
C914
14
13
R916
L902
35V
17V
5V
FM–15V
I/F0V
0V
0V
0V
FM–0V
C913
D910
REG2
Q706
C924
R920
R921
R922
PQ2
1
1
2
4 3
4
3
1
2
2
3
PQ1
VR1
R923
C906
C918
R911
D906
C908
PQ1
12
C
11
D904
R908
R909
D903
D905
D911
R910
R901
C901
R902
R903
R002
Diode stack 2
(RC2)
R904
2 5
3 4
1
+
+
IC901
C011
C010
R011
R010
C905
D902
R906
L901
R907
Switching transformer (T1)
Fig. 4-1 Power circuit for P.W.B.
1
9
+
C919
+
C921
C920
12V
D912
R919
R925
R924 ZD904
C909
15
1 2
JW8
JW8
4 3
Fig. 4-1 shows the power circuit for P.W.B. and waveform at each point.
In the power circuit for P.W.B., power supply for microcomputer, peripheral circuits, and system power
module driver circuit and, as well as DC 35V, are produced by switching power circuit.
Switching power circuit performs voltage conversion effectively by switching transistor IC901 to convert
DC 330V voltage to high frequency of about 20kHz to 200kHz.
Transistor IC901 operates as follows:
(1) Shifting from OFF to ON
DC about 330V is applied from smoothing capacitors C010 Œ and C011 œ in the control power circuit.
With this power, current flows to pin of IC901 via R903 and R904 and IC901 starts to tum ON. Since voltage in the direction of arrow generates at point at the same time, current passing through R910 and D903 is positive-fed back to IC901.
4
C
– 77 –
Page 67
(2) During ON
The drain current at IC901 increases linearly. During this period, the gate voltage and current become
constant because of the saturation characteristics of the transformer.
(3) Shifting from ON to OFF
This circuit applies a negative feedback signal from the 12V output. When the voltage across C919
reaches the specified value, REG2 turns on and current flows to PQ2 1-2. This turns the secondary circuits on, sets IC901 pin 1 to “Hi”, and turns IC901 off.
(4) During OFF
While IC901 is on, the following energy charges the primary windings of the transformer:
Energy=LI2/2. Here, L : Primary inductance
I : Current when IC1 is off
This energy discharges to the secondary windings during power off. That is, C910, C911, C912, C914 is charged according to the turn ratio of each winding.
At the start, an overcurrent flows to IC901 because of the charged current at C910, C911, C912, C914.
The drain current at IC901 generates a voltage across R906. If it exceeds the IC901 base voltage, it sets
the IC901 gate voltage to “HI”.
R906 limits the gate voltage to prevent excessive collector current from flowing to IC901.
<Reference>
If the power circuit for P.W.B. seems to be faulty: (1) Make sure that 5V and 12V on the control P.W.B., upper arm U, V and W, and the lower arm power
voltage are the specified values.
(2) When only the 5V output is low:
REG 1 (regulator) faulty, 5V-0V shorted, output is too high, or REG 1 is abnormal.
(3) When 12V and 5V are abnormal:
The following defects can be considered:
1 Fan, operation, power, rush prevention relay (shorting in relay, etc.) 2 Microcomputer is abnormal. 3 REG 1 (regulator is abnormal), etc.
Shorting on primary circuits. When shorting occurs in the secondary circuits, there is no abnormality in the primary circuits because of overcurrent protection. The voltage rises when an opening occurs in the primary circuits, or the feedback system is abnormal.
(4) When 15V and 17V are abnormal:
D908, D909 or drive circuit is abnormal.
(5) When all voltage are abnormal:
IC901, R906, etc. are possibly abnormal.
* If IC901 is abnormal, be aware that other components, such as the power module, REG (regulator), etc.
are possibly defective.
[When the switching power supply seems to be abnormal, the voltage between IC901 pin 4 (to be measured at the leads of R904 and R903) and IC901 pin 5 (to be measured at R906 lead) may be between 11 and 16V. This is because the protection circuit of IC901 is operating.]
– 78 –
Page 68
5. Reversing valve control circuit
I/F 35V
Reversing valve
DC voltmeter or tester
5V
CN2
3
1
V
I/F 0V
FUSE RESISTOR
D702
Q701
R701
R702
4
1
PQ701
23
R703
Q705
16
0V
HIC
R219
24
MICROCOMPUTER
Fig. 5 – 1
Reversing valve control circuit can switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 5-1. Voltage at each point in each operation condition is approximately as shown below when measured by
tester. (When collector voltage of Q701 is measured)
Table 5-1
Operation condition Collector voltage of Q701
Cooling
General operation of Cooling In normal heating operation
About 35V
About 0.8V
MAX. rotation speed instructed
Heating
by indoor microcomputer after
About 0.8V
defrost is completed
Dehumidifying
Defrosting Sensor dry
About 35V About 35V
– 79 –
Page 69
6. Rotor magnetic pole position detection circuit
0V 0V 0V
R601
C605 C606 C607
18 19 20
Outdoor microcomputer
R602
C501
+5V
R603
C
D E
C502
C608
0V
C503
+12V
HIC
System power module
B
36
R604 R605 R606
R607
R604
R603
R602
WV U
33
34
R608
R611
DC brushless motor for compressor
A
0V
47
35
R610
R609
U phase terminal voltage
Spike voltage
Pole position detection signal
Drive signal
No power supplied
60 120 60 120
A
C
D
E
+
W
Upper armONNo power
(B) reference voltage (1/2Vd)
Detection point
+
U
V
W
supplied
Induced voltage
Comparing process
+
V
Lower arm
ON
U
No power supplied
60
+
W
Vd 150~330
+
U
V
Fig. 6-1 Rotor magnetic pole position detection circuit and voltage waveform at each point
To detect U phase, voltage at point C is produced by driving motor induced voltage signal (voltage at point A ) and
1/2 voltage of Vd (voltage at point B ), and comparing with comparator.
For V phase and W phase, voltage at point
D
and voltage at point E are produced in the same way as above. Voltage at point C is taken into indoor unit microcomputer, switching timing to U+ transistor from W+ transistor is produced by delaying 30° from rise waveform, ignoring spike voltage. In addition, switching timing to U-transistor from W-transistor is produced by delaying 30° from fall waveform.
For V phase and W phase, in the same way as above, drive signals are produced from voltages at point
E
. Phases are shifted by 120° and 240°, respectively, comparing with U phase.
D
and point
– 80 –
Page 70
7. Drive Circuit
6
5
4
3
2
1
MICROCOMPUTER
A
R512
R521
R511
R510
R509
R508
R507
10
9
4
3
2
1
8
7
6
5
1
13
14
15
16
17
18
1
23
11
8
7
5
4
10
6
3
9
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
19
20
21
2
3
4
5
6
7
8
9
10
12
22
B
B
B
45
44
43
42
41
38
39
40
46
IP CUTTER Id CONTROL CIRCUIT
0V
17V
R501
C404
CN14
17V
0V
PWB (MAIN)
SPM2
0V
17V
U
+
V
+
W
+
U
V
W
IP
Id
IC1
VCC
VCU
PGU
U
VCV
PGV
V
VCW
PGW
W
NGU
NGV
NGW
SVT
SWT
SUB
SVB
SWB
F
OC
CB
A
0
A
GL1
GL2
SUT
R502
R503
R504
R505
R506
Q506
R536
R535
R525
Q504
R534
Q503
R524
R533
Q502
Q501
R522
R532
R531
R526
Q505
R523
HIC
P2
N1
HIC
+
GRY
R24
U
COMPRESSOR MOTOR
V
W
Fig. 7-1 shows the drive circuit. The circuits for U phase, V phase and W phase have the same Configuration.
th
ignal
nsistor
drive
Fig.. 7-1
In low speed rotation mode (PWM range), as shown in Fig. 7-2, 0-5V chopper signal is ouput from microcomputer for each phase. S
output from microcomputer is ouput to IC1 and is inverted by active Lo to become 0-15V chopper signal; it is then drive the tra
of each phase.
In high speed rotation mode (PWM range), as shown in Fig. 7-3, 0-5V drive signal is ouput from microcomputer for each phase (wi
no chopper because of full duty). Signal output from microcomputer is input to IC1 and is inverted by active Lo to become 0-15V
signal; it is then drive the transistor of each phase.
81
Page 71
[Low speed rotation mode]
+
U
-
V
5V
+
U
0V
+
V
+
W
-
U
-
V
-
W
15V
+
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point B Drive signal at point A
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
Fig. 7-2
[High speed rotation mode]
5V
+
A
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point
15V
+
U
0V
+
B
V
+
W
-
U
-
V
-
W
Drive signal at point
+
U
-
V
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
Fig. 7-3
– 82 –
Page 72
8. HIC and Peripheral Circuits
Fig. 8-1 shows the micro computer and its peripheral circuits, Table 8-1, the basic operations of each
circuit block, and Fig. 8-2, the system configuration.
Detection Resistor
R24
N1
R41
R43
DC Current
C34
0V0V
SPM2 – HIC
OC
99
F 8
20
IC1
R42
P2
Direct Current DC260-380V
10
3938
6
R222
+
5
R247
0V
7
IC4
C225
R245
0V
12V
0V
R221
R284
R292
+
C217
R286
C2260VR285
0V
L
Is
N
CT1
D104
R005
0V
C009
0V0V
R006
+
C107
0V
C105
+
58
62
JW10
Fig. 8-1 Microcomputer and Peripheral Circuits
0V
2
+
3
R288
0V
IC5
CN13CN14
C205
R249
R248
C215
1
+
D205
37
0V
5V
R252
19
521
5V
C218
R289
R500
R253
D204
0V
SPM2
MAIN P.W.B
HIC
59
Vd
C222
0V
17
Ip
60
Id
C224
0V
C204
0V
IC1
MICROCOMPUTER
61
Is
48
RESET
Table 8-1
Circuit block
Peak current cutoff circuit
Set value circuit
Voltage amplifier circuit
Reset circuit Trip signal
synthesis circuit
Basic operation
Detects DC current flowing power module and during overcurrent (instantaneous value) flows, stops upper/lower arm drive circuits and also produces lp signal by which drive signal output is stopped.
Compares voltage detected, amplified and input to HIC with set voltage value in microcomputer, and controls overload when set value exceeds input voltage.
Voltage-amplifies DC current level detected by the detection resistor and inputs this to microcomputer. Internal or external overload is judged in microcomputer.
Produces reset voltage. Modulates chopper signal to drive signal and stops according to presence/ab-
sence of lp signal or reset signal.
– 83 –
Page 73
5V
Reset Voltage
Chopper
signal
Chopper
Trip signal
synthesis circuit
signal
DC 260V
Reset circuit
Over-load external
setting circuit
-360V
IP signal
Current amplified
circuit
DC Current level
Outdoor microcomputer
Fig. 8-2
The following describes the operations of each circuit in detail.
(1) Peak current cut off circuit Fig.8-3 Peak Current Cut off Circuit and Waveforms at Each Section.
Drive
Circuit
Peak current cut off circuit
Detection
resistor
Drive
signal
DC current
Compressor
motor
Power module
DC current Id
21A (27A, for RAC-50NH4)
Voltage at point
1.05V (1.35V for RAC-50NH4)
Voltage at point
SPM2
Negative Terminal
DC current
A
R41
A
Detection
resistor
B
0V
9 9
SPM2 – HIC
R43
0V
IC1
QC
R43
0V
B
R42
20 9 2 39 17
8
F
Main P.W.B
CN14
Fig.8-3
The Ip cut off circuit detects an instantaneous excessive current and stops inverter to protect parts such
as SPM2, etc.
As shown in diagram, if current exceeding 21A (27A for RAC-50NH4) flows, voltage at point recognized
by detecting resistor is input to pin of SPM2 – HIC, and voltage divided by R41 and R43 is input to pin
9
of IC1. Since threshold of IC1 is exceeded in this case, Lo signal is input from pin (Voltage at point
B
. When Lo signal is input to pin of microcomputer, microcomputer stops drive output.
When drive output from microcomputer is stopped, all drive output goes Hi, and microcomputer is initialized
10
17
A
8
to enter drive signal standby mode. 3 minutes later, microcomputer outputs drive signal again, to start operation.
HIC
IP Outdoor microcomputer
– 84 –
Page 74
(2) Overload control circuit (OVL control circuit)
Overload control is to decrease the speed of the compressor and reduce the load when the load on the
air conditioner increases to an overload state, in order to protect the compressor, electronic components and power breaker.
Overloads are judged by comparing the DC current level and set value.
Fig. 8-4 shows the overload control system configuration and Fig. 8-5 is a characteristic diagram of
overload judgement values. There are two judgement methods-external judgement which compares the externally set value with the DC current value regardless of the rotation speed and internal judgement which compares the set value that varies according to the rotation speed programmed in the microcomputer software with the DC current value.
Microcomputer
To power module negative terminal
(R24)
DC current
Detection
resistor
Voltage amp
circuit
(Internal judgement)
DC voltage
OVL judgement with respect to externally set value
A/D
converter
A/D
converter
Judgement OVL according to the rotation speed
Selects data according to the rotation speed and DC voltage
Motor control process
Rotation speed data
OVL start current data
Fig. 8-4 Overload Control System Configuration
DC current
Judgement value according to the rotation speed
(internal judgement value)
Rotation speed
Fig. 8-5
1. Overload external judgement circuit
Fig. 8-1. The filter consisting of R245 and C217 removes high harmonic components from the voltage
generated by the current flowing to Detection resistor; R245 and C217 average the voltage. This voltage is then input to IC4 pin is then amplified and supplied to microcomputer pin . The microcomputer
5
compares this input with the internally set value, and if the input exceeds the set value, it enters overload control status.
Fig. 8-7 shows the rotation speed control. When the voltage at pin of the microcomputer exceeds the
60
set value, the microcomputer decreases the rotation speed of the compressor and reduces the load regardless of the rotation speed commanded by the indoor microcomputer.
60
– 85 –
Page 75
Detection Resistor
R24
N1
L
Is
N
0V
CT1
C009
0V0V
D104
R006
R005
DC Current
58
+
C105
1
5
373938
5V
5V
C218
Direct Current DC 260-380V
R500
SPM2
MAIN P.W.B.
R253
C222
0V0V
D204
C224
0V
0V0V
59
Vd
60
Id
61
Is
HIC
IC1
Microcomputer
P2
10
1
R245
0V
R221
CN14
+
C217
R222
6
+
5
R247
CN13
+
C205
0V
R249
7
R248IC4
D205
Fig. 8-6
Voltage at microcomputer pin
Rotation speed of compressor
60
Commanded rotation speed Actual rotation speed
Deceleration DecelerationAcceleration Acceleration
Fig. 8-7
2. Voltage amp. circuit
The voltage amp. circuit amplifies the DC current level detected by the detection resistor after being
converted to a voltage and supplies it to the microcomputer. Receiving this, the microcomputer converts it to a digital signal and compares it with the internal data to judge whether or not overload control is required.
< During overload control >
The filter consisting of R245 and C217 removes high harmonic components from the voltage generated
from the DC current flowing to the detection resistor, and supplies it to IC4 pin 5 IC4 forms a non-inverting voltage amp. circuit together with the peripheral elements.
The microcomputer stores the set values which vary according to the rotation speed. When the DC current
level exceeds the set value, the microcomputer enters the overload control state.
The set Value is determined by the amplification of the voltage amp. circuit.
Amplification : high [ DC current : low
{
Amplification : low [ DC current: high
86
Page 76
R500, R253, detect the DC voltage at the power circuit. The microcomputer receives a DC voltage (260-
380V) via HIC U and applies correction to the overload set value so the DC current is low (high) when the DC voltage is high (low).
(Since the load level is indicated by the DC voltage multiplied by DC current, R247, R248, R249 are provided to perform the same overload judgement even when the voltage varies.)
Amplification : low DC voltage : low DC current : high
Amplification : 8.5 times DC voltage : 260V
Amplification : high
DC current
0
G
0
Rotation speed
DC voltage : high DC current : low
Fig. 8-8
< During start current control >
It is required to maintain the start current (DC current) constant to smooth the start of the DC motor for
the compressor.
RAC-25NH4, RAC-35NH4, RAC-50NH4 uses software to control the start current.
The start current varies when the supply voltage varies. This control method copes with variations in the
voltages as follows. (1) Turns on the power module's U+ and V– transistors so the current flows to the motor windings as
shown in Fig8-9. (2) Varies the turn-ON time of the W+ transistor according to the DC voltage level and the start is
controlled so the start current is approx. 10A as shown in Fig. 8-10.
DC 260-360V
Detection
resistor
Chopper duty: high
ON-time
W transistor
20 15 10
5
DC current (A)
0
DC current
Power module
+
U
U
+
V
V
+
W
W
Compressor motor
U V W
Fig. 8-9
DC voltage: low DC voltage: 280V DC voltage: high
DC voltage (start current)
Start
Set value
Time
Fig. 8-10
– 87 –
Page 77
9. Temperature Detection Circuit
+5V
O.H. thermistor
CN8
Normal 2.7V or less Over heat 2.7V or more Reset 2.3V or less
HIC
O.H.
627
Microcomputer
DEF.
636
Outdoor
645
temperature
DEF. thermistor
CN9
Outdoor temperature thermistor
CN10
+5V
0V
Normal 2.4V or more Over heat 2.4V or less Reset 2.9V or more
+5V
0V
Refer to the table 10-1
0V
Fig. 9-1
The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the
Defrost. thermistor circuit detects the defrosting operation temperature.
A thermistor is a negative resistor element which has the characteristics that the higher (lower) the
temperature, the lower (higher) the resistance.
When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage at
pin 62 of microcomputer is increased.
Microcomputer compares the voltage present at pin
62
with the internal set value, if it is exceeded the
set value microcomputer judges that the compressor is overheated and stops operation.
When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly.
Therefore the resistance of the Defrost. thermistor becomes high and the voltage at pin
63
of microcomputer drops. If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
64
), and transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set at the EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dry mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
Table 9-1
Outdoor temperature (°C)
Microcomputer pin 5 voltage (V)
-10
1.1901.69102.23
20
2.75
30
3.22403.62
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins 62 – 64 are approx. 0V; when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode is entered 12 minutes after the compressor starts operation.
– 88 –
Page 78
10. Reset Circuit
Main
HIC
P.W. B
12V
5V
Microcomputer
C107
0V
R284
R286
62
+
JW10
R292
C226
R285
0V
0V
0V
2 3
IC5 (1/2)
C225
R288
8
C215
1
+
R289
R252
C204
0V0V
48
RESET
Fig. 10-1
The reset circuit initializes the microcomputer program when Power is ON or OFF”.
Low voltage at pin
Fig. 10-1 shows the reset circuit and Fig. 10-2 shows waveform at each point when power is turned on
48
resets the microcomputer, and HI activates the microcomputer.
and off.
When power is turned on, 12V line and 5V line voltages rise and 12V line voltage reaches 10.9V and
reset voltage input to pin 48 of microcomputer is set to Hi.
Reset voltage will be hold “Hi until the 12V line voltage drops to 9.90V even though the power shuts down.
12
6
Voltage (V)
Power is ON
0
12
6
Voltage (V)
Power is OFF
0
12V line
5V line
Reset voltage
Time
12V line
5V line
Reset voltage
Time
Fig. 10-2
– 89 –
Page 79
11. Outdoor DC Fan Motor control circuit.
System power module
PQ102
FM-15V
C103
5V
0V
14
23
R114
R106
Main P.W.B
R115
+
ZD101
R105
C106
R104
R103
FM-15V
Q101
D101
R101
FM-0V
Ap 7V
33.3KHz
5V
T/2
R102
5V
t
T
+++
Smoothing Capacitor
123 4 5321
CN12
321
2A-FUSE
C101
R107
FM-0V
1
2
3
4
5
6
7
R108
0V
Fig. 11-1
U V W
0V
Vcc
PWM control voltage
FG Pulse
CN6
C104
D105
0V
61 60 59
Power supply for DC fan motor from smoothing capacitor in system power module
RC Filter
VSD
BOARD
DC Fan motor with control board
IC4
R246 0V
C208
2 3
12V
0V
8
+
Q201
0V
HIC
R283
R242
0V
C219
+
C209
ONE CHIP DRIVER IC
Microcomputer
R243
R244
1
R298
R297
65
75
15
Motor coil
FM–60˚ el FG Pulse input
This model uses DC Fan Motor which has a controller circuit in the Motor.
This DC Fan Motor will rotate by control voltage apply to Vsp input. (Voltage range: 1.7 to 7V DC)
Vsp high : Faster ; Vsp low : slower ; Vsp lower than 1.7V : stop
Motor will output FG pulse by following this motor revolution.
Outdoor Microprocessor will output PWM control signal from FMCHOP terminal by following the instruction
from indoor Microprocessor.
This PWM control signal will convert to Vsp voltage by smoothing circuit (Q101 & RC filter)
Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by rotation
speed.
FG pulse will feed back to Outdoor Microprocessor through PQ102.
PQ102 is the isolator between Microprocessor circuit and DC Fan Motor circuit, which has to match the Fan
Motor revolution with instructed revolution. Such as...
FG feedback: Faster – Instruction: Slower ... Decrease pulse width FG feedback: Slower – Instruction: Faster ... Increase pulse width
FG pulse is also used for Fan Motor failure detection
Microprocessor will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected, it
will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on control PWB will blink 12 times. (Fan Motor lock detected)
R107 and IC4 are used for Fan Motor over current
– 90 –
Page 80
< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
It will makes Fan Lock Stopwhen something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make Fan Lock Stop by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
In case of Fan Lock Stop even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes, Fan Motor may be broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
91
Page 81
12. Power Factor Control Circuit
Power factor is controlled to almost 100%. (Effective use of power) With IC in ACT module, control is performed so that input current waveform will be similar to waveform of input
voltage
I (input current)
V (input voltage)
Effective
voltage
area
Invalid power area
(Even if voltage is applied. current does not flow)
input voltage
input current
Effective
voltage area
* Assuming the same current capacity (20A), power can be used about 10% effective, comparing with curent use (power factor of 90%), and maximum capacity is thereby improved.
– 92 –
Page 82
SERVICE CALL Q & A
Model RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
COOLING MODE
Q1
The compressor has stopped suddenly during cooling operation.
DEHUMIDIFYING MODE
Q2
Q3
Sound of running water is heard from indoor unit during dehumidifying.
Compressor occasionally does not operate during dehumidifying.
HEATING MODE
Q4
The circulation stops occasionally during Heating mode.
A1
Check if the indoor heat exchanger is frosted. Wait for 3-4 minutes until it is defrosted.
A2
A3
A4
It occurs during defrost­ing. Wait for 5-10 minutes until the condenser is defrosted.
If the air conditioner operates in cooling mode when it is cold, the evaporator may get frosted.
Normal sound when refrigerant flows in pipe.
Compressor may not operate when room temperature is 10°C or less. It also stops when the humidity is preset humidity or less.
Q5
Q6
When the fan speed is set at HIGH or MED, the flow is actually Weak.
Heating operation stops while the temperature is preset at "30".
A5
A6
At the beginning of heating, the fan speed remains LOW for 30 seconds. If HIGH is selected, it switches to LOW and again to MED after additional 30 seconds.
If temperature is high in the outdoor, heating operation may stop to protect internal devices.
– 93 –
Page 83
AUTO FRESH DEFROSTING
Q7
After the ON/OFF button is pressed to stop heating, the outdoor unit is still working with the OPERATION lamp lighting.
AUTO OPERATION
Q8
Fan speed does not change when fan speed selector is changed during auto operation.
NICE TEMPERATURE RESERVATION
Q9
When on-timer has been programmed, operation starts before the preset time has been reached.
A7
A8
A9
Auto Fresh Defrosting is carried out : the system checks the outdoor heat exchanger and defrosts it as necessary before stopping operation.
At this point fan speed is automatic.
This is because “Nice temperature reservation” function is operating. This function starts operation earlier so the preset temperature is reached at the preset time. Operation may start maximum 60 minutes before the preset time.
Q10
Q1 1
Does “Nice temperature reservation” function operate during dehumidifying?
Even if the same time is preset, the operation start time varies.
INFRARED REMOTE CONTROL
Q12
Q13
Q14
Timer cannot be set.
The current time display disappears soon.
The timer has been programmed, but the preset time disappears.
A10
A11
It does not work. It works only during cooling and heating.
This is because “Nice temperature reservation” function is operating. The start time varies according to the load of room. Since load varies greatly during heating, the operation start time is corrected, so it will vary each day.
A12
Has the clock been set? Timer cannot be set unless the clock has been set.
The current time disappears
A13
in approx. 10 seconds. The time set display has priority.
A14
Is the current time past the preset time? When the preset time reaches the current time, it disappears.
When the current time is set the display flashes for approx 3 minutes.
– 94 –
Page 84
OTHERS
The indoor fan varies among
Q15
high air flow, low air flow and breeze in the auto fan speed mode. (Heating operation)
Q16
Q17
Q18
Q19
Loud noise from the outdoor unit is heard when operation is started.
Noise from the outdoor unit occasionally changes.
There is a difference between the set temperature and room temperature.
Air does not flow immediately after operation is started.
A15
This is because the cool wind prevention function is operating, and does not indicate a fault.
A16
A17
A18
A19
When operation is started, the compressor rotation speed goes to maximum to increase the heating or cooling capability, so noise becomes slightly louder. This does not indicate a fault.
The compressor rotation speed changes according to the difference between the thermostat set temperature and room temperature. This does not indicate a fault.
There may be a difference between the set temperature and room temperature because of construction of room, air current, etc. Set the temperature at a comfortable for the space.
Preliminary operation is performed for one minute when the power switch on and heating or dehumidifying is set. The operation lamp blinks during this time for heating. This does not indicate a fault.
The heat exchanger temperature is sensed in the auto speed mode. When the temperature is low, the fan speed varies among high air flow, low air flow and breeze.
– 95 –
Page 85
TROUBLE SHOOTING
Model RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
PRECAUTIONS FOR CHECKING
DANGER
1. Remember that the 0V line is biased to 155-170V in reference to the ground level.
2. Also note that it takes about 10 minutes until the voltage fall after the power switch is turned off.
Power source
L
Indoor unit electric parts
Control P.W.B.
System power module 2
a
N
+
~
~
ACT Module
DC35V
C
0V
D
+–+
(0V)
b
MAIN P.W.B.
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
+
Power module
M
Compressor motor
approx 260-360V approx 155-170V approx 155-170V
DANGER
When using an oscilloscope, never ground it. Don't forget that high voltages as noted above may apply to the oscilloscope.
Outdoor unit P.W.B.
Always keep your hands and metallic things away from the enclosure of the oscilloscope.
Oscilloscope
DANGER!
Dont install
the ground
line.
– 96 –
Page 86
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
Caution
Voltage of about 300-330V is charged between both ends of smoothing capacitors
WARNING
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before performing operation chech of each circuit.
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray lead wire connected from diode stack to system power module (SPM2) to prevent secondary trouble. (Be sure to discharge smoothing capacitor)
P1
N1
System power module
RAC-25NH4, RAC-35NH4
Smoothing capacitors
SPM2
Soldering iron
Do not use a soldering iron with transformer: If one is used, thermal fuse inside transformer will be blown
As shown above, apply soldering iron to metal parts (receptable) inside the sleeve corresponding to P1 and N1 terminals of system power module: Do this with smoothing capacitors kept connected. By removing red/ gray lead wire from diode stack, power supply can be shut off. (corresponding to + and – terminals of system power module)
RAC-50NH4
SPM2
Smoothing capacitors
– 97 –
Page 87
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
Timer lamp
Does the timer lamp on the indoor unit blink?
No
See Troubleshooting when the timer lamp blinks.
Remove the terminal cover and check the voltage between terminal (C) and terminal (D)
Does the operation lamp on the indoor unit start to light or blink?
Yes
Is the compressor in the outdoor unit operating?
Yes No
Remove the outdoor unit cover and electrical parts cover, and check self-diagnosis lamp LD301
CN17
022527
IC3
P.W.B
Service switch
Self diagnosis lamps (LD303, 302, 301)
Does LD301 blink one time ? * Repeats 0.25-second on and 2-second off.
No
Terminal C (+35V)
Terminal D (0V)
Is approx. DC 33 to 37V being generated? Is the polarity correct?
No
Yes
Check to see whether the F­cable is connected incorrectly or disconnected
Normal
Blinking other than one time
Press the service switch for 1 sec. Does the compressor operate? (After checking, be sure to press the service switch to stop the operation).
See Out door unit self-diagnosis lamp lighting mode.
Check the refrigerating cycle.
One-time blinking
Yes
No
Check the outdoor electrical parts.
– 98 –
Check the indoor electrical parts.
Page 88
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
sec.
sec.
Model RAK-25NH4, RAK-35NH4, RAK-50NH4 Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
SELF-DIAGNOSIS LIGHTING MODE Model: RAK-25NH4, RAK-35NH4, RAK-50NH4
No. Blinking of Timer lamp Reason for indication Possible cause
Reversing valve defective When the indoor heat exchanger
1
5sec.
– ––––––– 1 time
temperature is too low in the heating mode or it is too high in the cooling mode.
(1) Reversing valve defective (2) Heat exchanger thermistor
disconnected
(only in the heating mode) (Note) The malfunction mode is entered the 3rd time this abnormal indication appears (read every 3 minutes).
Outdoor unit forced operation
2
3
4
5
1
6
5sec.
–––––– 2 time
5sec.
– ––––– 3 times
5sec.
5sec.
5sec.
–– 9 times
–– 10 times
–– 13 times
When the outdoor unit is in forced operation or balancing operation after forced operation
Indoor/outdoor interface defective When the interface signal from the outdoor unit is interrupted.
Room thermistor or heat exchanger thermistor is faulty When room thermistor or heat exchanger thermistor is opened circuit or short circuit.
Over-current detection at the DC fan motor when over-current is detected at the DC fan motor of the indoor unit.
IC401 or IC402 data reading error When data read from IC401 or IC402 is incorrect.
Electrical parts in the outdoor unit
(1) Indoor interface circuit (2) Outdoor interface circuit
(1) Room thermistor (2) Heat exchanger thermistor
(1) Indoor fan locked (2) Indoor fan motor (3) Indoor control P.W.B.
IC401 or IC402 abnormal
( – – Lights for 0.5 sec. at interval of 0.5 sec..)
<Cautions>
(1) If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed. (2) If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected. (3) To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
– 99 –
Page 89
SELF-DIAGNOSIS LIGHTING MODE
MODEL: RAC-25NH4, RAC-35NH4 & RAC-50NH4
– 100 –
Page 90
CHECKING INDOOR UNIT ELECTRICAL PARTS
1. Power does not come on (no operation)
No No Is DC 35V being generated between terminals C and D on the terminal board?
Is AC 220-240V AC being generated between terminals L and N on the outdoor unit terminal board?
Yes
Is DC 35V being generated between terminals C and D on the outdoor unit terminal board?
Check AC outlet and breaker, and repair any defective part.
Yes
Check the indoor/outdoor unit connection cable, and correct any defective section (wrong connection, incomplete insertion reversed).
Are control voltages (12V, 5V) being generated normally?
Yes
Do the air deflectors perform initial operation when the power supply is turned on and off?
No
Is the microcomputer reset input (pin 7 )Hi?
Yes
Is the microcomputer clock signal 10MHz at pin generated normally?
10 11
being
Yes
No
Yes
No
No
No
Check the outdoor unit power circuit, and repair the defective section.
Check according to the proper method for checking the power circuit.
Check the indication P.W.B. connection cord and light receiving unit.
Check the reset circuit, and repair any defective section.
Replace the microcomputer and oscillator.
Replace the control P.W.B
Perform final operation check.
– 101 –
Page 91
2. Outdoor unit does not operate (but receives remote infrared signal)
Set to room temperature 16°C in the cooling mode or to 32°C in the heating mode, and press the start/stop button.
Remove the outdoor unit cover and electrical parts cover, and check self­diagnosis lamp LD301.
Self diagnosis lamps (LD303, 302, 301)
Does LD301 blink one time? *Repeats 0.25-second on and 2-second off.
No
Yes Does outdoor electrical part LD301 blink nine times?
Yes
Is the indoor/outdoor unit communication signal superimposed on 35V DC of connection wires C and D?
Approx.
35V
0V
38kHz Approx. 2Vp-p
Yes
Check the room temperature thermistor; if it is defective, replace it. <Normal values>
10°C approx. 20k 25°C approx. 10k 30°C approx. 8k
Check the heat exchanger thermistor; if it is defective, replace it. <Normal values>
10°C approx. 20k 25°C approx. 10k 30°C approx. 8k
No
Check outdoor electrical parts, and repair any defective parts (around the outdoor interface transmitting circuit).
No
Does LD303 switch off several second after it lights?
Is the indoor transmitting signal being generated at Q801s collector?
38kHz Approx. 2Vp-p
Approx.
35V
0V
Transmission waveform
Yes
Perform final operation check.
– 102 –
Yes
No
Check the indoor interface transmitting circuit. Replace IC801.
Check outdoor electrical parts, and repair any defective parts (around the outdoor interface transmitting circuit).
Check outdoor electrical parts, and repair any defective parts.
Page 92
3. Only indoor fan does not operate (other is normal)
Can the fan be stopped by remote control?
No
Yes Yes
The microcomputer fan PWM output (pin) is Hi
Perform final operation check.
4. Air deflector does not move (others are normal)
Are pulse signals output at microcomputer pin swing is turned on in the fan mode?
Is a voltage over 15V or below 10V being generated on the 12V line
15
Yes
-
18
when auto
No
Yes
Replace IC111
Replace the microcomputer.
No
Replace the indoor fan motor.
Replace the microcomputer.
Replace the microcomputer
Yes
Check IC711. If it is normal, replace the air deflector motor.
Perform final operation check.
5. All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
Set to the Hi fan mode.
The operation lamp lights once and goes out in 5-10 seconds.
Yes
Disconnect CN10 and set to the fan mode again.
The operation lamps lights once and goes out in 5-10 seconds.
No
Can the indoor fan be lightly turned by hand? (Switch of main power before check)
Yes
Replace the indoor fan motor.
Yes
No
Check to see if shorting etc. has occurred in the P.W.B pattern
Check to see if the indoor fan is touching the chassis, etc. If it does repair
– 103 –
Page 93
6. Check the main P.W.B (power circuit)
Is DC 35V being output between cathode and anode of D101?
Yes
Is DC 12V being output?
Is DC 5V being output?
No
No
Is ICP2 normal? Normal if it is less than 1. Blown (open) if it is 1 or more
Is ICP1 normal? Normal if it is less than 1. Blown (open) if it is 1 or more
YesYes
Replace IC111.
No
No
Replace ICP2. Check if shorting has occurred in fan motor circuit and 35V interface circuit. If these are defective, ICP2 will be open again.
Replace ICP1. Check if shorting has occurred in the air deflector motor. If these are defective, ICP1 will be open again.
Replace REG2. Check the 5V line: if the 5V line is shorted, ICP1 will be open again.
Perform final operation check.
– 104 –
Page 94
Turn on an AM radio, bring
the remote control switch within
15 cm of the radio, and press
the ON/OFF button.
Check the indoor unit signal
receiving P. W. B..
If it is good, check the main P. W. B..
You can check the remote control switch by other methods as explained below.
Using the test card
The sensible area should flash in orange when you operate the remote control unit if it is good.
Ultra redray test card
Sensible area
Within 2 cm
Check functions again.
If it does not work, replace
the remote controller.
Buzz
Within 15 cm
[AM radio]
Check the LED (D1) with
a multimeter.
Replace the battery.
Install the battery in the correct polarity.
Yes
Yes
No
No
No
Yes
Does the radio buzz noisily?
Is battery polarity correct?
Is the battery check sign + –
flashing?
CHECKING THE REMOTE CONTROLLER
105
Page 95
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
MODEL RAC-25NH4, RAC-35NH4, RAC-50NH4
Check to see whether the
connected C and D cable
Replace any defective parts.
If the 25A fuse has blown, be aware
that other parts may also be
defective (mainly, varistor 2, diode
stack, smoothing capacitors, system
power module, etc.).
No
correctly? If reversed, correct the
If the 3A fuse has blown, the
switching transformer (T1),
R906, etc. may also be
cable connection.
Replace any defective parts.
Yes
No
Is the switching power circuit OK?
Has the 3A fuse blown?
No
defective.
()
See the self-diagnosis lamp
lighting mode.
Yes
Is AC220-240V being
supplied to terminal L and N?
[No operation or abnormal operation]
Is the 25A fuse normal?
Yes
Is the power circuit normal?
See the description on
power circuit for details.
Is 5V being generated
between Pin 4 (0V) and pin
3 (5V) at CN 18 (test pin)?
– 106 –
Yes
.
Operate the outdoor unit
according to the instruction
How to operate the outdoor
unit independently
How did the self-diagnosis
lamp (LD301) light?
Page 96
There is a defective section between the
12V output of switching power supply on
the main P .W .B. and interface relay (also,
D907 and C910 may be defective.
check for contact with solder, etc.).
Repalce the interface relay.
No
Yes
Is DC 35V being output at
terminals C and D? (Normally,
DC 33-38.5V is output.)
No
Yes
Is DC 35V being output across R914?
Is DC 12V being supplied across
Yes
the control side (coil terminal) of
interface relay?
Coil terminal
Interface relay
Yes
No
Is a voltage (at least 10V) being
generated between the contact
terminals of interface relay?
Contact terminal
Check the interface curcuit.
LD301 blinks 9 time.
Communication error.
– 107 –
Page 97
Yes No
No
Yes
Yes
Yes
No
No
No
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Replace the power module.
Replace any defective parts.
Connect the thermistor.
”.
forgetting
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Replace parts in the
Replace the thermistor.
thermistor circuit.
Is the power module normal?
LD301 blinks 8 time.
Acceleration defect.
Is the drive circuit normal?
Is the thermistor connector
to connect after servicing
The problem may be
disconnected?
Thermistor abnormal.
LD301 blinks 7 time.
Is the continuity of thermistor normal?
Is the thermistor circuit normal?
– 108 –
Page 98
Check continuity of new parts.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Replace parts in the
thermistor circuit.
No
Is the thermistor circuit normal?
Replace system power
module or defective parts.
No
Are R503, R541, R542, R549
and peripheral circuits of
system power module normal?
Replace the system power
module.
No
Yes
Replace the main P.W.B.
Is the system power module
normal?
Yes
Replace any defective
parts.
Is the drive circuit normal?
The temperature at the
OH thermistor rises.
LD301 blinks 6 time.
LD301 blinks 5 time.
Overload lower limit cut.
– 109 –
LD301 blinks 4 time.
Failure of switching.
LD301 blinks 3 time.
Abnormal low speed.
Page 99
LD301 blinks 2 time.
Peak current-cut.
LD301 blinks 1 time.
Reset stop.
However, the unit always resets and
stops just after power is supplied:
this does not indicate a fault.
Is the system power module
normal?
Is the drive circuit normal?
Are R503, R541, R542, R549
and peripheral circuits of system
power module normal?
Is the microcomputer IP input
signal normal?
(Normally, pin
17
is approx. 5V.)
Is the reset circuit normal?
(Normally, microcomputer
pin
48
is approx. 5V.)
Replace any defective parts.
Replace any defective parts.
Replace any defective parts.
Operate the unit again.
is it normal?
Make sure again that
connectors are connected
securely.
Perform final operation check.
Replace the system power
module.
No
Yes
Yes
No
No
No
()
– 110 –
Page 100
POWER CIRCUIT
Phenomenon 1 <Rotation speed does not increase>
Is the DC voltage at least 350V?
Yes
Is the OVL lamp lit? If the lamp is lit, it does not indicate fault, but the unit is overload status.
Overvoltage defect: system power module faulty (15-times blinking)
No
Recheck cord, etc. of the system power module. If they are disconnected, connect them securely.
If abnormality continues, replace the system power module.
– 111 –
Loading...