SPECIFICATIONS ------------------------------------------------------------------- 5
HOW TO USE ------------------------------------------------------------------------ 6
CONSTRUCTION AND DIMENSIONAL DIAGRAM --------------------- 29
MAIN PARTS COMPONENT --------------------------------------------------- 31
WIRING DIAGRAM ---------------------------------------------------------------- 33
CIRCUIT DIAGRAM --------------------------------------------------------------- 35
PRINTED WIRING BOARD LOCATION DIAGRAM --------------------- 41
BLOCK DIAGRAM ----------------------------------------------------------------- 43
BASIC MODE ----------------------------------------------------------------------- 45
REFRIGERATING CYCLE DIAGRAM --------------------------------------- 59
AUTO SWING FUNCTION ------------------------------------------------------ 61
DESCRIPTION OF MAIN CIRCUIT OPERATION ----------------------- 62
SERVICE CALL Q & A ---------------------------------------------------------- 93
TROUBLE SHOOTING ----------------------------------------------------------- 96
PARTS LIST AND DIAGRAM ------------------------------------------------- 116
SPECIFICATIONS
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
COOLING
HEATING
DIMENSIONS
(mm)
NET WEIGHT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
INDOOR UNIT
RAK-25NH4RAC-25NH4
1 PHASE, 50 Hz, 220-230V
695 (155~1,050)
2.50 (0.90 ~ 3.00)
900 (115 ~ 1,400)
3.50 (0.90 ~ 5.00)
860
285
183
9.0
OUTDOOR UNIT
3.20-3.05
8,540
4.15-4.00
11,950
750
570
280
38
DC INVERTER (WALL TYPE)
INDOOR UNIT
RAK-35NH4RAC-35NH4
1 PHASE, 50 Hz, 220-230V
1,080 (155~1,280)
3.50 (0.90 ~ 4.00)
1,320 (115 ~ 1,920)
4.80 (0.90 ~ 6.60)
860
285
183
9.0
OUTDOOR UNIT
4.94-4.72
11,950
6.04-5.77
16,390
750
570
280
38
INDOOR UNIT
RAK-50NH4RAC-50NH4
1 PHASE, 50 Hz, 220-230V
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
OUTDOOR UNIT
1,780 (155~2,200)
8.17-7.82
5.00 (0.90 ~ 5.20)
17,070
1,970 (115 ~ 2,100)
9.04-8.65
6.50 (0.90 ~ 8.10)
22,200
860
285
183
9.0
After installation
850
650
298
60
MAY 2003
ROOM AIR CONDITIONER
INDOOR UNIT + OUTDOOR UNIT
Refrigeration & Air-Conditioning Division
Page 2
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair
the unit in question, be sure to
disconnect the power cord plug
from the power outlet before starting
the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and
the replacement must be effected in correct manner according to the instructions in the Service Manual of
the unit.
If the contacts of electrical parts
are defective, replace the
electrical parts without trying to
repair them.
First, I must disconnect
the power cord plug
from the power outlet.
3. After completion of repairs, the initial state
should be restored.
4. Lead wires should be connected and laid as
in the initial state.
5. Modification of the unit by user himself should
absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as
electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and
grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V
DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe
enough to support the repaired unit again.
If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new
location.
10. Any inflammable thing should never
be placed about the location of
installation.
DANGER
11. Check the grounding to see whether
it is proper or not, and if it is found
improper, connect the grounding
terminal to the earth.
– 1 –
Page 3
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope
The standards provide for items to be generally observed in carrying and handling semiconductors in relative
manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods
such as rejected goods being returned).
2. Object parts
(1) Micro computer
(2) Integrated circuits (IC)
(3) Field-effect transistors (FET)
(4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
A conductive polyvinyl bag
IC
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through
a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
IC
Conductive sponge
Body earth
(Elimik conductive band)
1M
Fig. 2. Body Earth
Clip for connection with a
grounding wire
– 2 –
Page 4
(6) Use a three wire type soldering iron including a grounding wire.
Metal plate (of aluminium, stainless steel, etc.)
Staple
Bare copper wire (for body earth)
Fig. 3. Grounding of the working table
Working
table
Resistor of 1 M (1/2W)
Earth wire
Soldering iron
2
Screw stop at the screwed
part using a rag plate
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Grounding
wire
– 3 –
Page 5
CAUTION
!
1.In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is
heard occasionally, but this noise is not abnormal for the operation.
2.When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3.The room air conditioner does not start automatically after recovery of the electric power failure for
preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4.If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal
and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no
danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5.This room air conditioner should not be used at the cooling operation when the outside temperature is
below 10°C (50°F).
6.This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–10°C (14°F).
If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7.When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
– 4 –
Page 6
SPECIFICATIONS
MODEL
RAK-25NH4
RAK-35NH4
RAK-50NH4
RAC-25NH4RAC-50NH4RAC-35NH4
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
PWM DC35V
NO
NO
–
NO
NO
NO
NO
NO
NO
YES
40 W
NO
NO
JU1012DJU1013D
NO
YES
YES
3.0A
G4A
NO
NO
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
REFRIGERANT CHARGING
VOLUME
(Refrigerant 410A)
UNIT
PIPES (MAX. 20m)
NO
NO
NO
NO
YES(IC)
YES
----------
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
450NR
YES(IC)
1150g1150g
YES
NO
YES
NO
1400g
– 5 –
Page 7
SAFETY PRECAUTION
●
Please read the “Safety Precaution” carefully before operating the unit to ensure correct usage of the unit.
●
Pay special attention to signs of “ Warning” and “ Caution”. The “Warning” section contains matters which,
if not observed strictly, may cause death or serious injury. The “Caution” section contains matters which may
result in serious consequences if not observed properly. Please observe all instructions strictly to ensure safety.
●
The sign indicate the following meanings.
!
!
Make sure to connect earth line.
Indicates the instructions that must be followed.
●
Please keep this manual after reading.
PRECAUTIONS DURING INSTALLATION
●
Do not reconstruct the unit.
Water leakage, fault, short circuit or fire may occur if you reconstruct the
unit by yourself.
●
!
WARNING
!
CAUTION
Please ask your sales agent or qualified technician for the installation of
your unit. Water leakage, short circuit or fire may occur if you install the unit
by yourself.
●
Please use earth line.
Do not place the earth line near water or gas pipes, lightning-conductor, or
the earth line of telephone. Improper installation of earth line may cause
electric shock.
●
A circuit breaker should be installed depending on the mounting site of the
unit. Without a circuit breaker, the danger of electric shock exists.
●
Do not install near location where there is flammable gas. The outdoor unit
may catch fire if flammable gas leaks around it.
●
Please ensure smooth flow of water when installing the drain hose.
The sign in the figure indicates prohibition.
W
A
R
N
N
G
!
W
A
R
N
N
G
PRECAUTIONS DURING SHIFTING OR MAINTENANCE
●
Should abnormal situation arises (like burning smell), please stop operating the unit
!
I
and turn off the circuit breaker. Contact your agent. Fault, short circuit or fire may
occur if you continue to operate the unit under abnormal situation.
●
Please contact your agent for maintenance. Improper self maintenance may cause
electric shock and fire.
●
Please contact your agent if you need to remove and reinstall the unit. Electric
shock or fire may occur if you remove and reinstall the unit yourself improperly.
PRECAUTIONS DURING OPERATION
●
Avoid an extended period of direct air flow for your health.
●
Do not put objects like thin rods into the panel of blower and suction side
because the high-speed fan inside may cause danger.
●
I
Do not use any conductor as fuse wire, this could cause fatal accident.
●
During thunder storm, disconnect and turn off the circuit breaker.
– 6 –
Page 8
PRECAUTIONS DURING OPERATION
●
The product shall be operated under the manufacturer specification and
not for any other intended use.
●
Do not attempt to operate the unit with wet hands, this could cause fatal
accident.
●
When operating the unit with burning equipments, regularly ventilate the
room to avoid oxygen insufficiency.
●
Do not direct the cool air coming out from the air-conditioner panel to face
household heating apparatus as this may affect the working of apparatus
such as the electric kettle, oven etc.
●
Please ensure that outdoor mounting frame is always stable, firm and
without defect. If not, the outdoor unit may collapse and cause danger.
●
Do not splash or direct water to the body of the unit when cleaning it as this
may cause short circuit.
●
!
C
A
Do not use any aerosol or hair sprays near the indoor unit. This chemical
can adhere on heat exchanger fin and blocked the evaporation water flow
to drain pan. The water will drop on tangential fan and cause water splashing
out from indoor unit.
U
T
I
O
●
Please switch off the unit and turn off the circuit breaker during cleaning, the
high-speed fan inside the unit may cause danger.
N
●
Turn off the circuit breaker if the unit is not to be operated for a long period.
●
Do not climb on the outdoor unit or put objects on it.
●
Do not put water container (like vase) on the indoor unit to avoid water
dripping into the unit. Dripping water will damage the insulator inside the unit
and causes short-circuit.
●
Do not place plants directly under the air flow as it is bad for the plants.
●
When operating the unit with the door and windows opened, (the room humidity is always above
80%) and with the air deflector facing down or moving automatically for a long period of time,
water will condense on the air deflector and drips down occasionally. This will wet your furniture.
Therefore, do not operate under such condition for a long time.
●
If the amount of heat in the room is above the cooling or heating capability of the unit (for
example: more people entering the room, using heating equipments and etc.), the preset room
temperature cannot be achieved.
– 7 –
Page 9
NAMES AND FUNCTIONS OF EACH PART
INDOOR UNIT
Air filter
To prevent dust from coming into the indoor unit.
(Refer page 25)
Front panel
Indoor unit indicators
Light indicator showing the operating condition.
(Refer page 9)
Horizontal deflector
(Air Outlet)
(Refer page 20)
●
Vertical deflector
MODEL NAME AND DIMENSIONS
MODEL
RAK-25NH4, RAK-35NH4, RAK-50NH4
Remote controller
Send out operation signal to the indoor unit. So as to
operate the whole unit.
(Refer page 10)
WIDTH (mm)
860
HEIGHT (mm)
295
DEPTH (mm)
183
– 8 –
Page 10
INDOOR UNIT INDICATORS
HITACHI
FILTER LAMP
When the device is operated for a total of about 200
hours, the FILTER lamp lights indicates that it is time to
clean the filter. The lamp goes out when the POWER
SWITCH set to OFF and ON again.
OPERATION LAMP
This lamp lights during operation.
The OPERATION LAMP flashes in the following cases
during heating.
(1) During preheating
For about 2–3 minutes after starting up.
(2) During defrosting
Defrosting will be performed about once an hour
when frost forms on the heat exchanger of the
outdoor unit, for 5–10 minutes each time.
TIMER LAMP
This lamp lights when the timer is working.
OPERATION INDICATOR
● This figure shows the opening condition of
front panel. Refer to page 24 in relation to
how to open or close the front panel.
TEMPORARY SWITCH
TEMPORARY SWITCH
● Use this switch to start and stop when the remote controller does not work.
● By pressing the temporary switch, the operation is done in automatic mode.
TEMPORARY SWITCH
– 9 –
Page 11
NAMES AND FUNCTIONS OF REMOTE CONTROL UNIT
REMOTE CONTROLLER
● This controls the operation of the indoor unit. The range of control is about 7 meters. If indoor lighting is controlled
electronically, the range of control may be shorter.
This unit can be fixed on a wall using the fixture provided. Before fixing it, make sure the indoor unit can be controlled
from the remote controller.
● Handle the remote controller with care. Dropping it or getting it wet may compromise its signal transmission capability.
● After new batteries are inserted into the remote controller, the unit will initially require approximately 10 seconds to
respond to commands and operate.
● Signal emitting window/transmission sign
Point this window toward the indoor unit when controlling it.
CH
˚
CH
˚
RESET
AUTO
HEAT
DEHUMIDIFY
COOL
FAN
FAN SPEED
LOW
MED
HI
SLEEPING
STOP (CANCEL)
START (RESERVE)
START/STOP
TIME
TIMER SET
TIMER SELECTOR
ON TIMER
OFF TIMER
AUTO SWING
The transmission sign blinks when a signal is sent.
● Display
This indicates the room temperature selected, current time, timer status, function
and intensity of circulation selected.
● START/STOP button
Press this button to start operation. Press it again to stop operation.
● SLEEP button
Use this button to set the sleep timer.
● TEMPERATURE buttons
Use these buttons to raise or lower the temperature setting. (Keep pressed, and
the value will change more quickly.)
● TIME button
Use this button to set and check the time and date.
● RESET buttons
● FUNCTION selector
Use this button to select the operating mode. Every time you press it,
the mode will change from (AUTO) to (HEAT) to (DEHUMIDIFY) to
(COOL) and to (FAN) cyclically.
● FAN SPEED selector
This determines the fan speed. Every time you press this button, the intensity
of circulation will change from (AUTO) to (HI) to (MED) to (LOW)
(This button allows selecting the optimal or preferred fan speed for each operation
mode).
● AUTO SWING button
Controls the angle of the horizontal air deflector.
● TIMER control
Use this button to set the timer.
● OFF-TIMER button Select the turn OFF time.
● ON-TIMER button Select the turn ON time.
● RESERVE button Time setting reservation.
● CANCEL button Cancel time reservation.
Precautions for Use
● Do not put the remote controller in the following places.
● Under direct sunlight.
● In the vicinity of a heater.
● Handle the remote controller carefully. Do not drop it on the floor,
and protect it from water.
● Once the outdoor unit stops, it will not restart for about 3 minutes
(unless you turn the power switch off and on or unplug the power
cord and plug it in again).
This is to protect the device and does not indicate a failure.
● If you press the FUNCTION selector button during operation, the
device may stop for about 3 minutes for protection.
– 10 –
Page 12
VARIOUS FUNCTIONS
■ Auto Restart Control
● If there is a power failure, operation will be automatically restarted when the power is resumed with previous operation mode
and airflow direction.
(As the operation is not stopped by remote controller.)
● If you intend not to continue the operation when the power is resumed, switch off the power supply.
When you switch on the circuit breaker, the operation will be automatically restarted with previous operation mode and airflow
direction.
Note: 1. If you do not require Auto Restart Control, please consult your sales agent.
2. Auto Restart Control is not available when Timer or Sleep Timer mode is set.
AUTOMATIC OPERATION
The device will automatically determine the mode of operation, HEAT, COOL or DEHUMIDIFY depending on the initial room
temperature. The selected mode of operation will not change when the room temperature varies.
Press the FUNCTION selector so that the display indicates the (AUTO) mode of operation.
●When AUTO has been selected, the device will automatically determine the mode of
operation, HEAT, COOL or DEHUMIDIFY depending on the initial room temperature.
1
●If the mode automatically selected by the unit is not satisfactory, manually change the
mode setting (heat, dehumidify, cool or fan).
RESET
START
STOP
Press the (START/STOP) button.
Operation starts with a beep.
Press the button again to stop operation.
■ As the settings are stored in memory in the remote controller, you only have to press the
(START/STOP) button next time.
You can raise or lower the temperature setting as necessary by maximum of 3°C.
°C
● The preset temperature and the actual room temperature may vary somewhat depending on
conditions.
● The display does not indicate the preset temperature in the AUTO mode. If you change the
setting, the indoor unit will produce a beep.
Press the (FAN SPEED) button, AUTO and LOW is available.
Press the temperature button and the temperature setting will change by
1°C each time.
■ Condition of Automatic Operation
Initial room temperature
(approx.)
Function
-
Over 27°CCOOL
-
23~27°C
DEHUMIDIFY
-
Under 23°C
HEAT
Temperature setting
27°C
Slightly lower than the
room temperature
23°C
– 11 –
FAN SPEED
HI at start, MED or LOW after the
preset temperature is reached
LOW
HI at start, MED or LOW after the
preset temperature is reached
Page 13
HEATING OPERATION
● Use the device for heating when the outdoor temperature is under 21°C.
When it is too warm (over 21°C), the heating function may not work in order to protect the device.
Press the FUNCTION selector so that the display indicates
(HEAT).
Set the desired FAN SPEED with the (FAN SPEED) button
(the display indicates the setting).
(AUTO) : The fan speed is HI at first and varies to MED
automatically when the preset temperature has
been reached.
(HI): Economical as the room will become warm
quickly.
But you may feel a chill at the beginning.
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
RESET
C
˚
1
2
Set the desired room temperature with the TEMPERATURE
buttons (the display indicates the setting).
3
C
˚
START
STOP
■ As the settings are stored in memory in the remote controller, you only
The temperature setting and the actual room temperature may
vary somewhat depending on conditions.
Press the (START/STOP) button. Heating operation starts
with a beep. Press the button again to stop operation.
have to press the (START/STOP) button next time.
– 12 –
Page 14
DEHUMIDIFYING OPERATION
Use the device for dehumidifying when the room temperature is over 16°C.
When it is under 15°C, the dehumidifying function will not work.
Press the FUNCTION selector so that the display indicates
(DEHUMIDIFY).
The FAN SPEED is set at LOW automatically.
The FAN SPEED button does not work.
Set the desired room temperature with the TEMPERATURE
button (the display indicates the setting).
The range of 20-26˚C is recommended as
the room temperature for dehumidifying.
RESET
C
˚
1
2
C
˚
■ Dehumidifying Function
START
STOP
■ As the settings are stored in memory in the remote controller, you
Press the (START/STOP) button. Dehumidifying operation
starts with a beep. Press the button again to stop operation.
only have to press the
(START/STOP) button next time.
When the room temperature is higher than the temperature setting: The device will dehumidify the room,
reducing the room temperature to the preset level.
When the room temperature is lower than the temperature setting: Dehumidifying will be performed at
the temperature setting slightly lower than the current room temperature, regardless of the temperature
setting. The function will stop (the indoor unit will stop emitting air) as soon as the room temperature
becomes lower than the setting temperature.
– 13 –
Page 15
COOLING OPERATION
Use the device for cooling when the outdoor temperature is 22-42°C.
If in doors humidity is very high (80%), some dew may form on the air outlet grille of the indoor unit.
Press the FUNCTION selector so that the display indicates
C
˚
1
(COOL).
RESET
Set the desired FAN SPEED with the
(the display indicates the setting).
(AUTO): The FAN SPEED is HI at first and varies to
MED automatically when the preset temperature
2
(HI): Economical as the room will become cool
(MED) : Fan speed slow.
(LOW) : Fan speed slower.
Set the desired room temperature with the TEMPERATURE
button (the display indicates the setting).
3
C
˚
START
STOP
The temperature setting and the actual room temperature may
vary some how depending on conditions.
Press the
with a beep. Press the button again to stop operation. The
cooling function does not start if the temperature setting is
higher than the current room temperature (even though the
(OPERATION) lamp lights). The cooling function will start as
soon as you set the temperature below the current room
temperature.
has been reached.
quickly.
(START/STOP) button. Cooling operation starts
(FAN SPEED) button
■ As the settings are stored in memory in the remote controller, you
only have to press the
(START/STOP) button next time.
– 14 –
Page 16
FAN OPERATION
You can use the device simply as an air circulator. Use this function to dry the interior of the indoor
unit at the end of summer.
Press the FUNCTION selector so that the display indicates
1
(FAN).
RESET
FAN SPEED (AUTO)
For the heating operation
2
START
STOP
.....
When the AUTO fan speed mode is set in the cooling/heating operation:
● The fan speed will automatically change according to the temperature
of discharged air.
● When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
● When the room temperature reaches setting temperature, fan speed
changes to LOW automatically.
Press the (FAN SPEED) button.
Press the (START/STOP) button. Fan operation starts with
a beep. Press the button again to stop operation.
For the cooling operation
● When the difference of room temperature and setting temperature is
large, fan starts to run at HI speed.
● After room temperature reaches the preset temperature, the cooling
operation, which changes the fan speed and room temperature to obtain
optimum conditions for natural healthful cooling will be performed.
– 15 –
Page 17
HOW TO SET THE TIMER
RESET
Time, Day, Month
TIME, DAY,
MONTH
After you change the
batteries;
(current time,
day, month)
OFF TIMER
ON TIMER
OFF-Timer
RESERVE
CANCEL
You can set the device to turn off
at the present time.
ON-Timer
● The device will turn on
at the designated times.
Start
MD
STOP
Stop
Start
1
Set the current month and
day with the TIMER control
button.
MD
1
Press the (OFF-TIMER)
button. The (OFF) mark blinks
on the display.
AM
1
Press the (ON-TIMER)
button the (ON) mark blinks
on the display.
AM
3
ON/OFF-Timer
StartStop
● The device will turn on (off) and off
(on) at the designated times.
● The switching occurs first at the
preset time that comes earlier.
● The arrow mark appearing on the
display indicates the sequence of
switching operations.
1
Press the (ON-OFF)
button so that the (OFF)
mark blinks.
PM
2
Set the turn-off time
with the TIMER control
button.
Press the (RESERVE)
button.
PM
Press the (ON-
TIMER) button so that the
(OFF) mark lights and
the (ON) mark blinks.
PM
AM
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL)
button.
The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
NOTE
You can set only one of the OFF-timer,
ON-timer and ON/OFF-timer.
– 16 –
Page 18
2
Press the
(TIME) button.
AM
PMPM
2
Set the turn-off time with the
TIMER control button.
3
TIMER control button.
PM
Set the current time with the
Example: The current time is 1:30 p.m.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (OFF) mark starts lighting instead of flashing and the sign (RESERVED)
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
4
Press the (TIME) button again.
The time indication starts lighting
instead of flashing.
● The time indication will disappear
PM
● To check the current time setting,
automatically in 10 second.
press the (TIME) button twice.
The setting of the current time is
now complete.
2
Set the turn-on time with the
TIMER control button.
AM
4
Set the turn-on time with the
TIMER control button.
PM
AM
PM
The setting of turn-off time is now complete.
3
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (ON) mark starts lighting instead of flashing and the (RESERVED) sign
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
Example:
AM
5
Point the signal window of the remote controller toward the indoor unit, and
press the (RESERVE) button.
The (ON) mark starts lighting instead of flashing and the (RESERVED) sign
lights. A beep occurs and the (TIMER) lamp lights on the indoor unit.
PM
AM
The device will automatically turn on earlier so that the preset
temperature can be reached at 7:00 a.m.
The setting of the turn-on time is now complete.
Example:
The device will turn off at 10:30 p.m. and then automatically
turn on earlier so that the preset temperature can be reached
at 7:00 a.m.
The settings of the turn-on/off times are now complete.
Example: The device will turn off at 11:00p.m.
● The timer may be used in three ways: off-timer, on-timer, and ON/OFF (OFF/ON)-timer. Set
the current time at first because it serves as a reference.
● As the time settings are stored in memory in the remote controller, you only have to press
the (RESERVE) button in order to use the same settings next time.
– 17 –
Page 19
HOW TO SET THE SLEEP TIMER
Set the current time at first if it is not set before (see the pages for setting
the current time). Press the (SLEEP) button, and the display changes as
shown below.
Mode
4444
H
SLEEP
Sleep timer
Sleep Timer: The device will continue working for the designated
number of hours and then turn off.
Point the signal window of the remote controller toward the indoor
unit, and press the SLEEP button.
The timer information will be displayed on the remote controller.
The TIMER lamp lights with a beep from the indoor unit. When the
sleep timer has been set, the display indicates the turn-off time.
H
Sleep
timer
1
Set the ON-timer.
Start
1 hour 2 hours 3 hours 7 hours
The device will be turned off by the sleep
timer and turned on by on-timer.
Indication
Sleep timer off
Example: If you set 3 hours sleep
time at 11:38 p.m., the turn-off
time is 2:38 a.m.
1
2
Press the (SLEEP) button and set the sleep timer.
AM
H
AM
For heating:
In this case, the device will turn off
in 2 hours (at 1:38 a.m.) and turn
on early so that the preset
temperature will be almost reached
at 6:00 next morning.
How to Cancel Reservation
Point the signal window of the remote controller toward the indoor unit, and press the (CANCEL)
button.
The (RESERVED) sign goes out with a beep and the (TIMER) lamp turns off on the indoor unit.
– 18 –
Page 20
Explanation of the sleep timer
The device will control the FAN SPEED and room temperature automatically
so as to be quiet and good for people’s health.
You can set the sleep timer to turn off after 1, 2, 3 or 7 hours. The FAN
SPEED and room temperature will be controlled as shown below.
Operation with the sleep timer
FunctionOperation
Heating
“”
Cooling
“”
and
dehumidifying
“”
Fan
“”
The room temperature will be
controlled 5°C below the
temperature and the FAN
SPEED will be set to LOW
setting 30 minutes after the
setting of the sleep timer.
The room temperature will be
Sleep timer set
30 minutes later
2°C
2 hours
later
1 hour later
controlled 2°C above the
temperature and the FAN
SPEED will be set to LOW
setting 30 minutes after the
setting of the sleep timer.
Sleep
timer set
30 minutes later
2 hours
later
6 hours
later
3 hours later
The settings of room temperature and circulation are varied.
5°C
7 hours
later
3 hours later
7 hours later
NOTE
● If date or current time is not set, sleep timer can not be set.
● If you set the sleep timer after the off-, on/off- or off/on-timer has been set, the sleep timer
becomes effective instead of the off-, on/off- or off/on-timer set earlier.
● You can not set other timer during sleep timer operation.
● After sleep timer time is up and when press sleep button again, the sleep timer will be set as
last setting.
● Sleep timer effective only once.
– 19 –
Page 21
ADJUSTING THE AIR DEFLECTOR
1
Adjustment of the conditioned air in the upward and downward
directions.
The horizontal air deflector is automatically set to the proper
angle suitable for each operation. The deflector can be swung
up and down continuously and also set to the desired angle
using the “ (AUTO SWING)” button.
● If the “ (AUTO SWING)” button is pressed once,
the horizontal air deflector swings up and down. If the
button is pressed again, the deflector stops in its current
position. Several seconds (about 6 seconds) may be
required before the deflector starts to move.
● Use the horizontal air deflector within the adjusting range
shown on the right.
● When the operation is stopped, the horizontal air deflector
moves and stops at the position where the air outlet
closes.
RESET
2
CAUTION
!
● In “Cooling” operation, do not keep the horizontal air
deflector swinging for a long time. Some dew may form
on the horizontal air deflector and dew may drop.
Adjustment of the conditioned air to the left and right.
Hold the vertical air deflector as shown in the figure and adjust
the conditioned air to the left and right.
When cooling
dehumidifying
When heating
– 20 –
Page 22
HOW TO EXCHANGE THE BATTERIES IN THE REMOTE CONTROLLER
Remove the cover as shown in the figure and take out the
1
old batteries.
=
Install the new batteries.
2
The direction of the batteries should match the marks in the
case.
!
CAUTION
1. Do not use new and old batteries, or different kinds of batteries
together.
2. Take out the batteries when you do not use the remote controller
for 2 or 3 months.
Push and pull to the
direction of arrow
– 21 –
Page 23
THE IDEAL WAYS OF OPERATION
Suitable Room TemperatureInstall curtain or blinds
!
Warning
Freezing temperature
is bad for health and a
waste of electric power.
VentilationEffective Usage Of Timer
It is possible to
reduce heat
entering the
room through
windows.
!
Caution
Do not close the room for a long period of
time. Occasionally open the door and windows
to allow the
entrance of
fresh air.
Do Not Forget To Clean The Air Filter
Dusty air filter will reduce the air volume and
the cooling efficiency. To prevent from wasting
electric energy, please clean the filter every 2
weeks.
At night, please use the “OFF or ON timer
operation mode”, together with your wake up
time in the morning. This will enable you to
enjoy a comfortable room temperature. Please
use the timer effectively.
Please Adjust Suitable Temperature
For Baby And Children
Please pay attention to the room temperature
and air flow direction when operating the unit
for baby, children and old folks who have
difficulty in movement.
– 22 –
Page 24
FOR USER’S INFORMATION
OFF
The Air Conditioner And The Heat Source In The Room
!
Caution
If the amount of heat in the room is above the cooling
capability of the air conditioner (for example: more
people entering the room, using heating equipments
and etc.), the preset room temperature cannot be
achieved.
Not Operating For A Long Time
When the indoor unit is not to be used for a long
period of time, please switch off the power from the
mains. If the power from mains remains “ON”, the
indoor unit still consumes about 8W in the operation
control circuit even if it is in “OFF” mode.
When Lightning Occurs
!
Warning
To protect the whole unit during lightning, please
stop operating the unit and remove the plug from the
socket.
Interference From Electrical Products
!
Caution
To avoid noise interference, please place the indoor
unit and its remote controller at least 1m away from
electrical products.
To prevent
interference,
place at least
1m away.
Inverter-type
fluorescent
lamp.
TV
– 23 –
Page 25
ATTACHING THE AIR CLEANSING AND DEODORIZING FILTERS
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning,
stop operation and switch off the power supply.
1
2
3
Open the front panel.
● Pull up the front panel by holding it at both sides
with both hands.
Remove the filter.
● Push upward to release the claws and pull out the
filter.
Attaching the air cleansing and deodorizing filters
to the filter.
● Attach the air cleansing and deodorizing filters to
the frame by gently compress its both sides and
release after insertion into filter frame.
Claws
(4 places)
!
CAUTION
Do not bend the air cleansing
and deodorizing filter as it may
cause damage to the structure.
4
Attach the filters.
● Attach the filters by ensuring that the surface written
“FRONT” is facing front.
● After attaching the filters, push the front panel at
three arrow portion as shown in figure and close it.
NOTE
● In case of removing the air cleansing and deodorizing filters, please follow the above procedures.
● The cooling capacity is slightly weakened and the cooling speed becomes slower when the air cleansing
and deodorizing filters are used. So, set the fan speed to "HIGH" when using it in this condition.
● Air cleansing and deodorizing filters are washable and reusable up to 20 times by using vacuum cleaner
or water rinse under running tap water. Type number for this air cleansing filter is <SPX-CFH7>. Please
use this number for ordering when you want to renew it.
● Do not operate the air conditioner without filter. Dust may enter the air conditioner and fault may occur.
– 24 –
Page 26
MAINTENANCE
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning,
stop operation and switch off the power supply.
1. AIR FILTER
Clean the air filter, as it removes dust inside the room. In case the air filter is full of dust, the air flow
will decrease and the cooling capacity will be reduced. Further, noise may occur. Be sure to clean the
filter following the procedure below.
PROCEDURE
1
2
3
Open the front panel and remove the filter
● Gently lift and remove the air cleansing and
deodorizing filter from the air filter frame.
Vacuum dust from the air filter and air cleansing
and deodorizing filter using vacuum cleaner. If
there is too much dust, rinse under running tap
water and gently brush it with soft bristle brush.
Allow filters to dry in shade.
● Re-insert the air cleansing and deodorizing
filter to the filter frame. Set the filter with
“FRONT” mark facing front, and slot them into
the original state.
● After attaching the filters, push the front panel
at three arrow portions as shown in figure
and close it.
NOTE:
● Air cleansing and deodorizing filter should be cleaned every month or sooner if noticeable loading
occurs. When used overtime, it may loose its deodorizing function. For maximum performance, it is
recommended to replace it every 3-6 months depending on application requirements.
!
CAUTION
● Do not wash with hot water at more than 40°C. The filter may shrink.
● When washing it, shake off moisture completely and dry it in the shade; do not expose it directly to
the sun. The filter may shrink.
● Do not use detergent on the air cleansing and deodorizing filter as some detergent may deteriorate
the filter electrostatic performance.
– 25 –
Page 27
2. Washable Front Panel
● Remove the front panel and wash with clean
water.
Wash it with a soft sponge.
After using neutral detergent, wash thoroughly
with clean water.
● When front panel is not removed, wipe it with
a soft dry cloth. Wipe the remote controller
thoroughly with a soft dry cloth.
● Wipe the water thoroughly.
If water remains at indicators or signal
receiver of indoor unit, it causes trouble.
Method of removing the front panel.
Be sure to hold the front panel with both hands
to detach and attach it.
Removing the Front Panel
Arm
● When the front panel is fully opened with
both hands, push the right arm to the inside
to release it, and while closing the front panel
● Move the projections of the left and right
arms into the Flanges in the unit and
securely insert them into the holes.
Attaching the Front Panel
slightly, put it out forward.
!
CAUTION
● Do not splash or direct water to the body of the unit when cleaning
it as this may cause short circuit.
● Never use hot water (above 40°C), benzine, gasoline, acid, thinner or
a brush, because they will damage the plastic surface and the coating.
Projection
Hole
Flange
– 26 –
Page 28
!
CAUTION
Cleaning and maintenance must be carried out only by qualified service personal. Before cleaning,
stop operation and switch off the power supply.
3. MAINTENANCE AT BEGINNING OF LONG OFF PERIOD
● Run the unit by setting the operation mode to
(COOL), the temperature to 32°C and the fan speed
to HI for about half a day on a fine day, and dry the
whole of the unit.
Air
● Switch off the power plug.
Blow
REGULAR INSPECTION
PLEASE CHECK THE FOLLOWING POINTS BY QUALIFIED SERVICE PERSONAL EITHER
EVERY HALF YEARLY OR YEARLY. CONTACT YOUR SALES AGENT OR SERVICE SHOP.
1
2
3
Confirm
Is the earth line disconnected or broken?
Is the mounting frame seriously affected by rust and is the
outdoor unit tilted or unstable?
Is the plug of power line firmly plugged into the socket?
(Please ensure no loose contact between them).
– 27 –
Page 29
AFTER SALE SERVICE AND WARRANTY
WHEN ASKING FOR SERVICE, CHECK THE FOLLOWING POINTS.
CONDITIONCHECK THE FOLLOWING POINTS
● Is the fuse all right?
When it does not operate
When it does not cool well
When it does not hot well
Notes
● In quiet operation or stopping the operation, the following phenomena
may occassionally occur, but they are not abnormal for the operation.
(1)Slight flowing noise of refrigerant in the refrigerating cycle.
(2)Slight rubbing noise from the fan casing which is cooled and then
● The odor will possibly be emitted from the room air conditioner because
the various odor, emitted by smoke, foodstuffs, cosmetics and so on,
sticks to it. So the air filter and the evaporator regularly must be cleaned
to reduce the odor.
● Is the voltage extremely high or low?
● Is the circuit breaker “ON”?
● Was the air filter cleaned?
● Does sunlight fall directly on the outdoor unit?
● Is the air flow of the outdoor unit obstructed?
● Are the doors or windows opened, or is there any source of
heat in the room?
● Is the set temperature suitable?
gradually warmed as operation stops.
●
Please contact your sales agent immediately if the air conditioner still fails to operate normally after the above
inspections. Inform your agent of the model of your unit, production number, date of installation. Please also
inform him regarding the fault.
●
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the
specified capacity.
Please note:
On switching on the equipment, particularly when the room light is dimmed, a slight brightness fluctuation
may occur. This is of no consequence.
The conditions of the local Power Supply Companies are to be observed.
Note
●Avoid to use the room air conditioner for cooling operation when the outside temperature is below
21°C (70°F).
The recommended maximum and minimum operating temperatures of the hot and cold sides
should be as below:
CoolingHeating
MinimumMaximumMinimumMaximum
Indoor
Outdoor
Dry bulb °C21322027
Wet bulb °C15231219
Dry bulb °C2143221
Wet bulb °C1526115
– 28 –
Page 30
CONSTRUCTION AND DIMENSIONAL DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Air suction grill
183
Mounting plate
860
Top air suction grill
Front panel
Cabinet
285
About
380
350
About
View from back
(Pipe lead-out)
6.560
47
47
31120.5
6060
240170450
Drain outlet
Horizontal deflectorDischarge grill
Drain hose
Hole on the wall
for ø 65mm pipe
47
Drain
Narrow pipe
Vertical deflector
P
7070140
Drain cap
connection port
147
5617.5
28
47
When piping is
drawn horizontally,
exchange the drain
hose for the drain cap
BLU : BLUEYEL : YELLOWBRN : BROWNWHT : WHITE
GRY : GRAYORN : ORANGEGRN : GREENRED : RED
BLK : BLACKPNK : PINKVIO : VIOLET
– 31 –
Page 33
COMPRESSOR MOTOR
Compressor Motor Specifications
MODEL
COMPRESSOR MODEL
RAC-25NH4RAC-50NH4RAC-35NH4
JU1012DJU1013D
PHASESINGLE
RATED VOLTAGEAC 220 ~ 230 V
RATED FREQUENCY50 Hz
POLE NUMBER4
(U)
WHITE
CONNECTION
M
M
M
(W)
(V)
YELLOW
RESISTANCE VALUE
20°C
(68°F)
2M = 1.05
RED
75°C
(167°F)
YELLOW
2M = 1.28
WHITE
RED
!
CAUTION
( )
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed
or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the
color has been changed conspicuously, replace the compressor.
– 32 –
Page 34
WIRING DIAGRAM
BLU
POWER
RELAY
COIL
NF
COIL 1
C003
C001
C002
VARISTOR1
L001
CT1
VARISTOR3
SURGE
ABSORBER
DIODE
STACK
R010
L002
R011
C011
C010
FAN
MOTOR
VARISTOR2
CN6
WHT
C008
C013
C015
M
WHT YEL
RED
WHT YEL
YEL
YEL
YEL
DIODE
STACK
RED
UVW
REACTOR
SYSTEM POWER
MODULE 2
L2
L1
CN14
CN13
CN11
C503
C502C501
10
CN14
CN10
RED
CN9
BLU
CN8
WHT
CN15
WHT
CN13
CN11
5
5
CN12
CN12
RED
GRY
2A FUSE
ICP RELAY
R008R007
3A FUSE
25A
FUSE
C006
R001
BLKGRNWHT
(WHT)(BRN)(RED)(BLK)
CONNECTING
CORD
BRNRED
BLK
BLK
GRN
RED
BLK
WHT
YEL
BLU
POWER
CIRCUIT
TERMINAL
BOARD
(GRN+YEL)
LNCD
SINGLE PHASE
AC220~230V
50Hz
(GRN+YEL)
THERE ARE SOME LEAD WIRES
WHICH HAVE SPIRAL STRIPES
WITH WHITE IN ADDITION TO
THE ORIGINAL COLOR
1. The indoor fan also stops when the
compressor is in stop status.
Set to “Hi” in modes other than when the
compressor stops.
Set to “Med” in modes other than when the
compressor stops.
Set to “Lo” in modes other than when the
compressor stops.
See page 53.
• Same as at left
• See page 53.
Stop
StartStop
(Off-timer during stop)
(On-timer during operation)
ONONONOFFOFFOFFONOFF
(Off->On timer)(On->Off timer) (On->Off timer)
(Change in reserved time)
during operation)
(Off->On timer)
during stop)
Set to “ultra-Lo”, “Lo”, “Med”, “Hi”, “ultra-Hi” or “stop” depending on the room temperature,
time and heat exchange temperature. Set to “stop” if the room temperature is 18˚C in the
“ultra-Lo” mode other than during preheating (cooling is recovered at 18.33˚C).
When the compressor is running at maximum speed
during hot dash or when recovered from defrosting.
˚C
42. 66
37. 66
32. 66
29. 66
Hi or ultra-HI
(fan speed set
to “auto”)
Med
Lo
In modes other than
left
Heat exchanger
temperature
Set to “ultra-Lo”, “Lo”, “Med”, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, and
time. Set to “stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during
preheating (cooling is recovered at 18.33˚C).
Set to “ultra-Hi” when the compressor is running at maximum speed during hot dash or when
recovered from defrosting.
Set to “ultra-Lo”, “Lo”, “Med” or “stop” depending on the room temperature and time. Set to“stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during preseating
(cooling is recovered at 18.33˚C).
Set to “ultra-Lo”, “Lo”, or “stop” depending on the room temperature and time. Set to “stop” if
the room temperature is 18˚C in the “ultra-Lo” mode other than during preseating (cooling is
recovered at 18.33˚C). The fan speed is controlled by the heat exchanger temperature; the
overload control is executed as in the following diagram:
KAFON
KAFOF
“Med” with overload
“Lo”
Heat exchanger temperature
See page 55.
• Same as at left
• See page 57.
N&F autoHeatingCooling
The neuro & fuzzy control allows device to determine optimum
operation mode and set temperature. However, during auto
cooling, the new cool rhythm starts when the room temperature
is less than the set temperature plus 0.66˚C, after dash is
finished.
Room
temperature
Outdoor
temperature
Calendar
Humidity
Neuro
pattern
recognition
Fuzzy
control
Operation mode
Set temperature
Notes:
(1) The set temperature can be varied ±3˚C using the
temperature setting buttons and .
v
v
(2) If operation is started by tele-control or by temporary switch
in status where remote control has not been used after
power was supplied, the operation mode will be as follows
(since there is no stored calendar data):
Cooling
Dehumidifying
Heating
Room temparature at
operation start (˚C)
Set temperature: 28˚C
Fan mode: Auto
Set temperature: Room temperature at operation
Fan mode: Auto
Set temperature: 22˚C
Fan mode: Auto
start
• Same as at left.
• Performs the sleep operation of each operation mode.
Special auto (not normally used)
The special auto mode is based on N&F
auto, but the following is different:
Operation mode
N&F auto
Special auto
Mode change during
operation
Does not change as long as
outdoor temperature or
calendar data does not
change greatly.
The operation mode will be
judged the same as at
operation start every hour.
The special auto operation mode is
entered when operation is started in the
following status:
<Start condition>
Power is supplied white the tele-control
signal is being input. (Operation starts
automatically.)
<End condition>
The remote control restores the normal
operation mode.
Note
(1) Since there is no stored calendar
data, N&F control is not determined.
See Note (2) of N&F auto.
– 45 –
Page 42
Table 1 Mode data file
RAK-25NH4RAK-35NH4RAK-50NH4
LABEL NAMEVALUE
WMAX4500 min
WMAX24600 min
WSTD3250 min
WBEMAX2600 min
CMAX2900 min
CMAX23000 min
CSTD2500 min
CKYMAX2200 min
CJKMAX2000 min
CBEMAX1800 min
WMIN1200 min
CMIN1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
5500 min
5600 min
4350 min
2800 min
3700 min
3800 min
3550 min
2800 min
2500 min
2200 min
1200 min
1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
6200 min
6250 min
5200 min
2600 min
5700 min
5800 min
5200 min
3550 min
2700 min
2000 min
1200 min
1500 min
Notes:
(1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode.
(3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP.
(6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX.
(7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX.
(8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX.
(9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Table 2 ∆TCMAX
TemperatureCalculated
differencecompressor rpm
1.662265 min
22435 min
2.332600 min
2.662765 min
32935 min
3.333100 min
3.663265 min
43435 min
4.333600 min
4.663765 min
53935 min
5.334100 min
5.664265 min
64435 min
6.334600 min
6.664765 min
74935 min
7.335100 min
7.665265 min
85435 min
8.335600 min
8.665765 min
95935 min
9.336100 min
9.666265 min
106435 min
10.336600 min
10.666765 min
116935 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
Note:
1. See the data in Table 1 on
page 47 for each constant in
capital letters in the diagrams.
– 49 –
Page 44
New Cool Rhythm
Cooling Sleep Operation
Final set temperature
(Cooling/dehumidifying set
temperature
(temperature set by remote
control (+) SHIFTC)
Set temperature during rhythm
(temperature set by remote
control (+) SFTRZM)
Thermo judgment
Hi
Indoor
fan
New cool rhythm
Outdoor fan
Lo
Rhythm Med
Rhythm Lo
Med
Room temperature
See basic operation.
Lo
Minimum
5min.
5 sec.5 sec.
Minimum 5min.Minimum 5min.
5min.
1 cycle
2.5 sec.2.5 sec.
4.5 sec.
2.5 sec.
5min.
Minimum
5min.
5min.
Minimum
5min.
Thermo OFF
15 sec.
Minimum
5min.5min.
5min.
Lo
Final set temperature
(Cooling/dehumidifying set
temperature (+) sleep shift)
(Cooling/dehumidifying set
temperature = Remote control set
temperature (+) SHIFTC)
Sleep key
Operation lamp
Timer lamp
Indoor fan
Outdoor fan
Horizontal air
deflector
Hi
Med
Lo (sleep)
Shut
Horizontal
Facing down
See basic operation
Lo
Set to 7 hours
0.5hr
1.5hr
2.5hr3.5hr6hr7hr
3hr
Maximum speed
P1
Compressor speed
Notes:
(1) New cool rhythm is engaged when the fan speed is “auto” and the room temperature is less than
set one plus 0.66˚C in the “auto” operation mode or cooling mode.
(2) The minimum new cool rhythm time is 10 minutes when the temperature falls and rises.
(3) Cool rhythm is not engaged during Nice temperature, Sleep operation.
(4) Pl control is engaged during new cool rhythm: the speed limit is the same as during normal operation.
(5) The new cool rhythm set temperature is also shifted during thermo OFF.
Compressor speed
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to “sleep Lo”.
(3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached.
(4) The sleep shift upper value of set temperature is 28˚C.
(5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min.
(6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made.
(7) The indoor fan speed does not change even when the fan speed mode is changed.
(8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted.
(9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted.
(10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Reverse cycle period
MAX. 12min.
min–1
3000
fixed
– 51 –
Page 45
+
–1.33˚C
+
–0.66˚C
Delay
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2°C).
(2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
– 53 –
Page 46
Basic Heating Operation
SFTDSW
Heating set temperature
(remote control set temperature
(+))
Dash period
TWMAX
Fan speed set to "auto"
Ultra-Hi
Hi
Med
10sec.
Lo
Ultra-Lo
Wtd
WMIN
0
Start
Max. 3 min.
Preheating released
30sec. 30sec.
1 min.
WMAX2
ultra Hi
Control by
heat exchanger temperature
NOTE (11)
LoHiHiHi
Start/stop switch
Thermo judgment
Defrost signal
Preheating judgment
Indoor fan
Operation lamp
Max.
(WMAX)
Rating
(WSTD)
Compressor speed
3000
Reversing valve (heating "on" model)
Outdoor fan
Notes:
(1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm (calculated value in Table 3) larger than WMAX.
(2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off.
(3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor temperature
is lower than 18°C and outdoor temperature is lower than 2°C.
(6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”.
(7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C.
(8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX.
(9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode.
(10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2.
(11) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor rpm is actual rpm x DWNRATEW.
1.33˚C.
0.66˚C.
StopStartStartStopStop
Thermo
OFF
30sec.30sec.
10sec.
15sec.15sec.15sec.
10sec.
15sec.15sec.
Control by
heat exchanger temperature
Control by
heat exchanger temperature
18˚C
Thermo OFF
Thermo
Preheat released
30sec.30sec.30sec.30sec.30sec.30sec.
10sec.
Control by
10sec.
150sec. Delay150sec. Delay
heat exchanger temperature
15sec.
15sec.
Control by
heat exchanger temperature
3min.
Hi
OFF
15sec.
150sec. Delay
Table 3 ∆TWMAX
TemperatureCalculated
differencecompressor rpm
1.661965 min
22135 min
2.332300 min
2.662465 min
32635 min
3.332800 min
3.662965 min
43135 min
4.333300 min
4.663465 min
53635 min
5.333800 min
5.663965 min
64135 min
6.334300 min
6.664465 min
74635 min
7.334800 min
7.664965 min
85135 min
8.335300 min
8.665465 min
95635 min
9.335800 min
9.665965 min
106135 min
10.336300 min
10.666465 min
116635 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
Notes:
1. See the data in Table 1 on
page 47 for each constant in
capital letters in the diagrams.
– 55 –
Page 47
WMIN
1 min
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to “sleep Lo”.
(3) 30 minutes after the sleep key is set, the sleep shift of set temperature starts.
(4) The maximum sleep shift of set temperature is 5°C, and the minimum is 12°C.
(5) If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts.
(6) The indoor fan speed does not change even when the fan speed mode is changed. (Lo)
(7) When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting.
(8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted.
(9) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted.
(10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
– 57 –
Page 48
REFRIGERATING CYCLE DIAGRAM
MODEL RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
STRAINER
CHARGING PIPE
ELECTRIC
EXP ANSION VALVE
STRAINER
COMPRESSOR
REVERSING
VALVE
SERVICE V ALVE
SUCTION
TANK
(1/4)
SERVICE V ALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED
UNION (3/8)
SINGLE-ENDED
UNION (1/4)
HEATING
OUTDOOR UNIT
STRAINER
CHARGING PIPE
ELECTRIC
EXP ANSION VALVE
STRAINER
COMPRESSOR
REVERSING
VALVE
SERVICE V ALVE
SUCTION
TANK
(1/4)
SERVICE V ALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED
UNION (3/8)
SINGLE-ENDED
UNION (1/4)
– 59 –
Page 49
REFRIGERATING CYCLE DIAGRAM
MODEL RAK-50NH4 / RAC-50NH4
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
ELECTRIC
EXP ANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING
VALVE
SERVICE V ALVE
SERVICE V ALVE
(1/2)
SUCTION
TANK
(1/4)
INDOOR UNIT
SINGLE-ENDED
UNION (1/2)
SINGLE-ENDED
UNION (1/4)
HEATING
OUTDOOR UNIT
ELECTRIC
EXP ANSION VALVE
STRAINER
STRAINER
COMPRESSOR
REVERSING
VALVE
SERVICE V ALVE
SERVICE V ALVE
(1/2)
SUCTION
TANK
(1/4)
INDOOR UNIT
SINGLE-ENDED
UNION (1/2)
SINGLE-ENDED
UNION (1/4)
– 60 –
Page 50
REFERENCE
INITIALIZE AT NEXT
OPERATION.
OPERATING SPECIFICATION
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
STOP AT THE MOMENT.
3 DOWNWARD
START SWING AGAIN.
STOP SWINGING TEMPORARILY.
(SWING MODE IS CLEARED IF SWING COMMAND IS
TRANSMITTED DURING TEMPORARY STOP.)
INITIALIZE
1 DOWNWARD
2 UPWARD
INITIALIZE AT NEXT
INITIALIZE
1 DOWNWARD
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
OPERATION.
STOP SWINGING AND MODE BECOMES INITIALIZING
INITIALIZING CONDITION OF EACH MODE.
2 UPWARD
CONDITION.
STOP
DURING ONE SWING
PRESENT CONDITION
EACH MODE
OPERATIONOPERATION MODEAIR DEFLECTOR
INPUT SIGNAL
AUTO SWING FUNCTION
MODEL: RAK-25NH4, RAK-35NH4, RAK-50NH4
STOP
KEY INPUT
STOP
AUTO COOL
COOL
FAN
AUTO DRY
DRY
DURING SWINGING
DURING
OPERATION
STOP
AUTO HEAT
HEAT
CIRCULATOR
DURING SWINGING
TEMPORARY STOP
AUTO DRY
THERMO. ON
(INTERNAL FAN
DURING SWINGING
DRY
AUTO HAET
HEAT
CIRCULATOR
DURING
OPERATION
ON)
THERMO. ON
(INTERNAL FAN
OFF)
STOP
DURING ONE SWING
STOP
DURING ONE SWING
STOP
COOL
FAN
DRY
HEAT
CIRCULATOR
STOP
MAIN SWITCH
ON
DURING SWINGING
DURING
INITIALIZING
STOP
DURING SWINGING
EACH MODE
DURING
OPERATION
MAIN SWITCH
OFF
EACH MODE
DURING
OPERATION
CHANGE OF
OPERATION
– 61 –
Page 51
DESCRIPTION OF MAIN CIRCUIT OPERATION
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
1. Reset Circuit
5V
2
R522
1
C521
R521
5
C524
NORMAL : HI
RESET: LO
RES
7
Microcomputer
C522
Voltage
Voltage supply to
2
pin
of IC521
Reset release at 4.4V
3
IC521
0V
Fig. 1-1
5.0V
Reset enter at 4.2V
voltage
Voltage at pin
of microcomputer
7
5.0V
Fig. 1-2
● The reset circuit initializes the microcomputer program when power is ON or OFF.
● Low voltage at pin 7 resets the microcomputer and Hi activates the microcomputer.
● When power “ON” 5V voltage rises and reaches 4.4V, pin 1 of IC521 is set to “Hi”. At this time the
microcomputer starts operation.
● When power “OFF” voltage drops and reaches 4.2V, pin 1 of IC521 is set to “Low”. This will RESET the
microcomputer.
– 62 –
Page 52
2. Receiver Circuit
12V
C1
▲
ZD211
0V
R1
IR1
VDD
GND
R2R611
V
out
C611
0V
13RECEIVER I/P
Microcomputer
R201
Fig. 2-1
● The light receiver unit receives the infrared signal from the wireless remote control. The receiver amplifies
and shapes the signal and outputs it.
3. Buzzer Circuit
12V
Microcomputer
Buzzer output
●When the buzzer sounds, an approx.
3.9kHz square signal is output from buzzer
output pin of the microcomputer. After
30
the amplitude of this signal has been set
to 12Vp-p by a transistor, it is applied to
the buzzer. The piezoelectric element in
the buzzer oscillates to generate the
buzzer’s sound.
R219
30
Fig. 3-1 Buzzer Circuit
Metal diaphragm
BZ
0V
BZ1
Q722
Pizoelectric element
Sound wave
– 63 –
V
Fig. 3-2 Buzzer Operation
V
Page 53
4. Auto Sweep Motor Circuit
12V
IC711
Auto sweep motor for
horizontal air defectors
9
Microcomputer
18
17
16
15
C711
7
6
5
4
10
11
12
13
Rotor
8
0V
Fig.4-1
● Fig. 4-1 shows the Auto sweep motor drive circuit; the signals shown in Fig.4-2 are output from pins
15 – 18 of microcomputer.
Microcomputer pinsStep width
Horizontal air deflectors
15
16
17
18
12345678
Horizontal air
deflectors: 10ms.
Fig.4-2 Microcomputer Output Signals
● As the microcomputer’s outputs change as shown in Fig.4-2, the core of the auto sweep motor is excited
to turn the rotor. Table 4-1 shows the rotation angle of horizontal air deflectors.
Table 4-1 Auto sweep Motor Rotation
Rotation angle per step (˚ )Time per step (ms.)
0.088210Horizontal air deflectors
– 64 –
Page 54
5. Room Temperature Thermistor Circuit
5
4
3
2
1
0
010
Room temperature (˚C)
Fig. 5-2
203040
0V
Room
temperature
thermistor
0V
5V
Fig. 5-1
62
A
R305
C302
Microcomputer
Room
temp. input
Voltage at
(V)
R301
0V
Heat exchanger
temperature thermistor
0V
5V
Fig. 6-1
61
A
R306
C303
Microcomputer
Heat
exchanger
temperature
input
R302
A
5
4
3
2
1
0
010
-10
Heat exchanger temperature (˚C)
Fig. 6-2
203040
Voltage at
(V)A
● Fig. 5-1 shows the room temperature
thermistor circuit.
6. Heat exchanger temperature thermistor circuit
● The voltage at depends on the room
A
temperature as shown in Fig. 5-2.
● The circuit detects the indoor heat
exchanger temperature and controls
the following.
(1)Preheating.
(2)Low-temperature defrosting
during cooling and dehumidifying
operation.
(3)Detection of the reversing valve
non-operation or heat exchanger
temperature thermistor open.
The voltage at depends on the
A
heat exchanger temperature as shown
in Fig. 6-2.
– 65 –
Page 55
7. Initial Setting Circuit (IC401)
● When power is supplied, the microcomputer reads the data in IC401 or IC402 (E
2
PROM) and sets the
preheating activation value and the rating and maximum speed of the compressor, etc. to their initial
values.
● Data of self-diagnosis mode is stored in IC401 or IC402; data will not be erased even when power is
turned off.
5V
5V5V
1
2
3
4
IC401 or IC402 (E
0V
8
7
6
5
2
0V
PROM)
C401
0V
R404
R403
27
26
SCL
SDA
Microcomputer
External ROM
}
Fig. 7-1
– 66 –
Page 56
Model RAC-25NH4, RAC-35NH4, RAC-50NH4
1. Power Circuit
TERMINAL
BOARD
L
N
25A FUSE
SURGEABSORBER
VARISTOR3
L001
NF COIL1
C001
VARISTOR1
R001
C003
C002
CT1
C009
0V
0V
COIL
C004C005
C006
POWER RELAY
R007
R008
ICP RELAY
DIODE
STACK 1
(D25VB60)
SPM2
TB8
TB2
REACTOR
L1L2
TB7TB6
TB10
U
Vdba
N1
P1
TB11
TB12
V
W
3A FUSE
VARISTOR2
STACK 2 (RC2)
C010
C011
POWER CIRCUIT
R010R011
DIODE
L002
C014
C015
C012
C013
C007
C008
JW6
R002
Fig. 1-1
● This circuit full-wave rectifies 220-230V AC applied between terminals L and N, and boosts it to a required
voltage with the active module, to create a DC voltage.
The voltage becomes 260-360V when the compressor is operated
(1) Active module
The active filter, consisting of a reactor and
switching element, eliminates higher
harmonic components contained in the
current generated when the compressor is
operated, and improves the power-factor.
< Reference >
● In case of malfunction or defective connection:
Immediately after the compressor starts, it may stop
due to “abnormally low speed” active error, etc.
The compressor may continue to operate normally,
but the power-factor will decrease, the operation
current will increase, and the overcurrent breaker
(2) Diode stacks
These rectify the 220-230V AC from
terminals L and N to a DC power supply.
of the household power board will probably activate.
● In case of active module faulty or defective
connection:
Although the compressor continues to operate
normally, the power-factor will decrease, the
operation current will increase, and the overcurrent
breaker of the household power board will probably
activate.
< Reference >
● If diode stack 1 is faulty, the compressor may stop
due to “lp”, “anbormally low speed”, etc. immediately
after it starts, or it may not operate at all because
no DC voltage is generated between the positive e
and negative d terminals.
If diode stack 1 is faulty, be aware that the 25A
fuse might also have blown.
● If diode stack 2 is faulty, DC voltage may not be
generated and the compressor may not operate at
all. Also, be aware that the 3A fuse might have
blown.
– 67 –
Page 57
(3) Smoothing capacitor (C501, C502, C503)
This smoothes (averages) the voltage rectified by the diode stacks.
<Notes > Smoothing capacitor C501 is not available for model RAC-25NH4 and RAC-35NH4.
Smoothing Capacitors
SPM2
Fig. 1-2
a
b
DC voltage
Vd
(approx. 260-360V during operation)
OV
OV
OV
Fig. 1-3
(4) Smoothing capacitor (C010, C011)
This smoothes (averages) the voltage rectified by the diode
stack2. A DC voltage is generated in the same way as in
Fig. 1-3.
Voltage between + side of C010 and – side of C011 is about
330V.
(5) C001 to C003, C012 to C015, C007, C008, NF COIL1, COIL,
absorb electrical noise generated during operation of
compressor, and also absorb external noise entering from
power line to protect electronic parts.
(6) Surge absorber, Varistor 1, 2, 3,
absorbs external power surge.
(7) Inrush protective resistor (R007, R008)
This works to protect from overcurrent when power is turned
on.
● Be careful to avoid an electric shock as a
high voltage is generated. Also take care
not to cause a short-circuit through incorrect
connection of test equipment terminals. The
circuit board could be damaged.
< Reference >
● When inrush protective resistor is
defective, diode stack may
malfunction. As a result, DC voltage
is not generated and no operation can
be done.
– 68 –
Page 58
2. Indoor/Outdoor Interface Circuit
● The interface circuit superimposes an interface signal on the DC 35V line supplied from the outdoor unit
to perform communications between indoor and outdoor units. This circuit consists of a transmiting circuit
which superimposes an interface signal transmit from the microcomputer on the DC 35V line and a
transmiting circuit which detects the interface signal on the DC 35V line and outputs it to the microcomputer.
● Communications are performed by mutually transmiting and receiving the 4-frame outdoor request signal
one frame of which consists of a leader of approx. 100 ms., start bit, 8-bit data and stop bit and the
command signal with the same format transmit from the indoor unit.
● Communication signal from outdoor microcomputer to indoor microcomputer. At first outdoor microcomputer
will send a request signal (SDO) to indoor microcomputer. A high-frequency IF signal approx. 38 KHz is
generated and modulated by the request signal (SDO) inside the outdoor microcomputer then output to
pin 11 of microcomputer. This modulated IF signal is output to pin 30 of HIC and amplified by amp. This
signal is superimposed to DC 35V line via C801 and L801.
To prevent erroneous reception, the outdoor microcomputer is designed so that it cannot receive a signal
while it is outputting a request signal.
The receiving circuit in the indoor unit consists of a comparator and transistor. The interface signal from
the outdoor unit on the DC 35V line is supplied to C821, where DC components are eliminated, and is
then shaped by the comparator. The shaped signal is detected by diode, amplified by amp, and output
to pin 49 of the indoor microcomputer.
Fig. 2-2 shows the voltages at each component when data is transferred from the outdoor microcomputer
to the indoor microcomputer.
● Communication signal from indoor microcomputer to outdoor microcomputer. The request signal (SDO)
generates by indoor microcomputer is output to pin 50 , and amplifies by C801. IF signal approx. 38 kHz
is generated by comparator, then modulate by the request signal from pin 50 of indoor microprocessor.
This modulated IF signal is then amplified and superimposed to DC 35V line via L801 and C802 of indoor
interface circuit.
Fig. 2-3 shows the voltages at each component when data is transferred from outdoor microcomputer to
indoor microcomputer.
The circuit operation of the outdoor receiving circuit is same as indoor receiving circuit.
– 69 –
Page 59
● Fig. 2-1 shows the interface circuit used for the indoor and outdoor microcomputers to communicate with
each other.
C802
I/F 0V
D101
L801
C803
5V
C804
0V
C821R821
Terminal board
CD
CD
Terminal board
R813
R812
Q803
0V
C822
R810
Q802
R811
5V5V5V
R822
R823
0V0V0V
Indoor P.W.B.
Outdoor P.W.B.
35V
R824
3
2
IC801
R825
5V5V
R807
1
R805
IC801
7
R806
C823
R826
D821
5V
R828
5V
0V
0V
R803
R804
Q821
5V
0V
R829
R830
Q801
0V
HIC
C824
IF transmit
50
output (SDO)
MICROCOMPUTER
IF receive
49
input (SDI)
5
6
C801
0V
R827
0V
Interface
relay
0V
L802
12V
C811
C812
C807
C808
0V
L801
C801
0V
C806
NF COIL2
5V
C809
C810
I/F 0V
R801
R802 Q801
29
C802
IF transmit
11
output (SDO)
0V
0V0V
0V
30
R803
5V
0V
5V5V
0V
0V
0V
5V
0V
MICROCOMPUTER
68
0V
IF receive
input (SDI)
(Communications from outdoor microcomputer to indoor
microcomputer)
(Communications from indoor microcomputer to outdoor
microcomputer)
Fig. 2-1 Indoor/outdoor interface Circuit
– 70 –
Page 60
Outdoor HIC
Pin
Pin
30
29
0.7V
0V
5V
0V
Indoor microcomputer
DC 35V line
Pin
Pin
50
49
100ms.
Leader
33ms.
1 frame
5V
0V
5V
0V
35V
Fig. 2-2 Voltages Waveforms of indoor / Outdoor Microcomputers (Outdoor to Indoor Communications)
Outdoor HIC
Pin
30
0V
29
Indoor microcomputer
DC 35V line
Pin
Pin
Pin
50
49
4.95ms.
Transmit / receive
switching time
33ms.
1 frame
5V
0V
5V
0V
5V
0V
35V
Fig. 2-3 Voltages Waveforms of indoor / Outdoor Microcomputers (Indoor to Outdoor Communications)
– 71 –
Page 61
[Serial Communications Format during Normal Communications]
(1) Outdoor microcomputer (HIC) to indoor microcomputer
(2) Indoor microcomputer to outdoor microcomputer (HIC)
Fig. 3-1 shows the system power module and its peripheral circuit.
The three transistors on the positive e side are called the upper arm, and the three transistors on the negative d side, the lower arm.
●
– 74 –
Fig. 3-1 Power module circuit (U
Page 64
● DC 260-360V is input to system power module and system power module switches power supply current
according to rotation position of magnet rotor. The switching order is as shown in Fig. 3-2.
At point E: U+ is ON, V– is ON (circuit in Fig. 3-1)
At point F: U+ is chopped (OFF), V– is ON (circuit in Fig. 3-4)
[]
E
F
+
Upper arm
transistor
++T+
UVVW
Lower arm
transistor
–
U
–
V
–
W
Time
Fig. 3-2 Switching order of power module
● Upper arm transistor is controlled to ON/OFF by 3.3kHz chopper signal. Rotation speed of the compress
is proportional to duty ratio (ON time/ ON time + OFF time) of this chopper signal.
● Time T in Fig. 3-2 shows the switching period, and relation with rotation speed (N) of the compressor is
shown by formula below;
N = 60/2 X 1/T
● Fig. 3-3 shows voltage waveform at each point shown in Figs. 3-1 and 3-4. First half of upper arm is
chopper, second half is ON, and first half of lower arm is chopper, second half is ON.
Voltage at
260V-360V
+
U transistor chopped
A
-
U transistor ON
Upper arm transistor
Current at
B
Chopping period
ON
T
Fig. 3-3 Voltage waveform at each point
● When power is supplied U
+
[ U–, because of that U+ is chopped, current flows as shown below;
(1) When U+ transistor is ON: U+ transistor [ U coil [ V coil [ V– transistor [ DC current detection
resistor [ Point (Fig. 3-1)
B
(2) When U+ transistor is OFF: (by inductance of motor coil) U coil [ V coil [ V– transistor [ Return
diode [ Point (Fig. 3-4)
A
B
– 75 –
Page 65
260V-360V
+
System Power Module 2
+
U
—
B
R24
U
_
+
V
—
V
+
W
—
W
A
U
V
W
U coil
V coil
DC compressor
motor
W coil
DC current (Id)
detection resistor
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
● Since current flows at point only when U+ transistor is ON, the current waveform at point becomes
intermittent waveform as shown in Fig. 3-3. Since current at point is approximately proportional to the
BB
B
input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
Table 3-1
Self-diagnosis lamp
and mode
LD301
LD301
LD301
Blinks 2
times
Blinks 3
times
Blinks 4
times
P.W.B (Main)
Self diagnosis lamps
(LD303, 302, 301)
Self-diagnosis
lp (peak current cut)
Abnormal low speed
rotation
Switching incomplete
Fig. 3-5
● Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
❈ Refer to other item (troubleshooting on page 94) for independent checking of power module.
– 76 –
Page 66
4. Power Circuit for P.W.B.
22
18
19
+
D908
R917
R915
D909
R918
L903
REG1
C911
20
21
+
D907
C910
R914
C912
16
17
+
C903
C907
+
+
C914
14
13
R916
L902
35V
17V
5V
FM–15V
I/F0V
0V
0V
0V
FM–0V
C913
D910
REG2
Q706
C924
R920
R921
R922
PQ2
1
1
2
4
3
4
3
1
2
2
3
PQ1
VR1
R923
C906
C918
R911
D906
C908
PQ1
12
C
11
D904
R908
R909
D903
D905
D911
R910
R901
C901
R902
R903
R002
Diode stack 2
(RC2)
R904
25
34
1
+
+
IC901
C011
C010
R011
R010
C905
D902
R906
L901
R907
Switching transformer (T1)
Fig. 4-1 Power circuit for P.W.B.
1
9
+
C919
+
C921
C920
12V
D912
R919
R925
R924 ZD904
C909
15
12
JW8
JW8
43
● Fig. 4-1 shows the power circuit for P.W.B. and waveform at each point.
● In the power circuit for P.W.B., power supply for microcomputer, peripheral circuits, and system power
module driver circuit and, as well as DC 35V, are produced by switching power circuit.
● Switching power circuit performs voltage conversion effectively by switching transistor IC901 to convert
DC 330V voltage to high frequency of about 20kHz to 200kHz.
● Transistor IC901 operates as follows:
(1) Shifting from OFF to ON
● DC about 330V is applied from smoothing capacitors C010 Œ and C011 œ in the control power circuit.
With this power, current flows to pin of IC901 via R903 and R904 and IC901 starts to tum ON. Since
voltage in the direction of arrow generates at point at the same time, current passing through R910 and
D903 is positive-fed back to IC901.
4
C
– 77 –
Page 67
(2) During ON
● The drain current at IC901 increases linearly. During this period, the gate voltage and current become
constant because of the saturation characteristics of the transformer.
(3) Shifting from ON to OFF
● This circuit applies a negative feedback signal from the 12V output. When the voltage across C919
reaches the specified value, REG2 turns on and current flows to PQ2 1-2. This turns the secondary
circuits on, sets IC901 pin 1 to “Hi”, and turns IC901 off.
(4) During OFF
● While IC901 is on, the following energy charges the primary windings of the transformer:
Energy=LI2/2. Here, L : Primary inductance
I : Current when IC1 is off
This energy discharges to the secondary windings during power off. That is, C910, C911, C912, C914 is
charged according to the turn ratio of each winding.
● At the start, an overcurrent flows to IC901 because of the charged current at C910, C911, C912, C914.
● The drain current at IC901 generates a voltage across R906. If it exceeds the IC901 base voltage, it sets
the IC901 gate voltage to “HI”.
● R906 limits the gate voltage to prevent excessive collector current from flowing to IC901.
<Reference>
If the power circuit for P.W.B. seems to be faulty:
(1) Make sure that 5V and 12V on the control P.W.B., upper arm U, V and W, and the lower arm power
voltage are the specified values.
(2) When only the 5V output is low:
REG 1 (regulator) faulty, 5V-0V shorted, output is too high, or REG 1 is abnormal.
(3) When 12V and 5V are abnormal:
The following defects can be considered:
1 Fan, operation, power, rush prevention relay (shorting in relay, etc.)
2 Microcomputer is abnormal.
3 REG 1 (regulator is abnormal), etc.
Shorting on primary circuits.
When shorting occurs in the secondary circuits, there is no abnormality in the primary circuits because
of overcurrent protection.
The voltage rises when an opening occurs in the primary circuits, or the feedback system is abnormal.
(4) When 15V and 17V are abnormal:
D908, D909 or drive circuit is abnormal.
(5) When all voltage are abnormal:
IC901, R906, etc. are possibly abnormal.
* If IC901 is abnormal, be aware that other components, such as the power module, REG (regulator), etc.
are possibly defective.
[When the switching power supply seems to be abnormal, the voltage between IC901 pin 4 (to be measured
at the leads of R904 and R903) and IC901 pin 5 (to be measured at R906 lead) may be between 11 and
16V. This is because the protection circuit of IC901 is operating.]
– 78 –
Page 68
5. Reversing valve control circuit
I/F 35V
Reversing
valve
DC voltmeter
or tester
5V
CN2
3
1
V
I/F 0V
FUSE RESISTOR
D702
Q701
R701
R702
4
1
PQ701
23
R703
Q705
16
0V
HIC
R219
24
MICROCOMPUTER
Fig. 5 – 1
● Reversing valve control circuit can switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 5-1.
Voltage at each point in each operation condition is approximately as shown below when measured by
tester. (When collector voltage of Q701 is measured)
Table 5-1
Operation conditionCollector voltage of Q701
Cooling
General operation of Cooling
In normal heating operation
About 35V
About 0.8V
MAX. rotation speed instructed
Heating
by indoor microcomputer after
About 0.8V
defrost is completed
Dehumidifying
Defrosting
Sensor dry
About 35V
About 35V
– 79 –
Page 69
6. Rotor magnetic pole position detection circuit
0V
0V
0V
R601
C605
C606
C607
18
19
20
Outdoor microcomputer
R602
C501
+5V
R603
C
D
E
C502
C608
0V
C503
+12V
HIC
System power module
B
36
R604
R605
R606
R607
R604
R603
R602
WV U
33
34
R608
R611
DC brushless
motor for compressor
A
0V
47
35
R610
R609
U phase
terminal voltage
Spike voltage
Pole position
detection signal
Drive signal
No power
supplied
6012060120
A
C
D
E
+
W
Upper armONNo power
(B) reference
voltage (1/2Vd)
Detection point
+
U
—
V
W
supplied
Induced voltage
Comparing process
+
V
—
Lower arm
ON
—
U
No power
supplied
60
+
W
Vd 150~330
+
U
—
V
Fig. 6-1 Rotor magnetic pole position detection circuit and voltage waveform at each point
To detect U phase, voltage at point C is produced by driving motor induced voltage signal (voltage at point A ) and
1/2 voltage of Vd (voltage at point B ), and comparing with comparator.
For V phase and W phase, voltage at point
D
and voltage at point E are produced in the same way as above. Voltage
at point C is taken into indoor unit microcomputer, switching timing to U+ transistor from W+ transistor is produced by
delaying 30° from rise waveform, ignoring spike voltage. In addition, switching timing to U-transistor from W-transistor is
produced by delaying 30° from fall waveform.
For V phase and W phase, in the same way as above, drive signals are produced from voltages at point
E
. Phases are shifted by 120° and 240°, respectively, comparing with U phase.
D
and point
– 80 –
Page 70
7. Drive Circuit
6
5
4
3
2
1
MICROCOMPUTER
A
R512
R521
R511
R510
R509
R508
R507
10
9
4
3
2
1
8
7
6
5
1
13
14
15
16
17
18
1
23
11
8
7
5
4
10
6
3
9
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
19
20
21
2
3
4
5
6
7
8
9
10
12
22
B
B
B
45
44
43
42
41
38
39
40
46
IP CUTTERId CONTROL CIRCUIT
0V
17V
R501
C404
CN14
17V
0V
PWB (MAIN)
SPM2
0V
17V
U
+
V
+
W
+
U
–
V
–
W
–
IP
Id
IC1
VCC
VCU
PGU
U
VCV
PGV
V
VCW
PGW
W
NGU
NGV
NGW
SVT
SWT
SUB
SVB
SWB
F
OC
CB
A
0
A
–
GL1
GL2
SUT
R502
R503
R504
R505
R506
Q506
R536
R535
R525
Q504
R534
Q503
R524
R533
Q502
Q501
R522
R532
R531
R526
Q505
R523
HIC
P2
N1
HIC
–
+
GRY
R24
U
COMPRESSOR MOTOR
V
W
Fig. 7-1 shows the drive circuit.
The circuits for U phase, V phase and W
phase have the same Configuration.
th
ignal
nsistor
drive
Fig.. 7-1
In low speed rotation mode (PWM range), as shown in Fig. 7-2, 0-5V chopper signal is ouput from microcomputer for each phase. S
output from microcomputer is ouput to IC1 and is inverted by active Lo to become 0-15V chopper signal; it is then drive the tra
of each phase.
●
In high speed rotation mode (PWM range), as shown in Fig. 7-3, 0-5V drive signal is ouput from microcomputer for each phase (wi
no chopper because of full duty). Signal output from microcomputer is input to IC1 and is inverted by active Lo to become 0-15V
signal; it is then drive the transistor of each phase.
●
– 81 –
Page 71
[Low speed rotation mode]
+
U
-
V
5V
+
U
0V
+
V
+
W
-
U
-
V
-
W
15V
+
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point BDrive signal at point A
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
Fig. 7-2
[High speed rotation mode]
5V
+
A
U
0V
+
V
+
W
-
U
-
V
-
W
Drive signal at point
15V
+
U
0V
+
B
V
+
W
-
U
-
V
-
W
Drive signal at point
+
U
-
V
W
-
+
V
-
U
W
+
-
V
+
U
W
-
+
V
Fig. 7-3
– 82 –
Page 72
8. HIC and Peripheral Circuits
● Fig. 8-1 shows the micro computer and its peripheral circuits, Table 8-1, the basic operations of each
circuit block, and Fig. 8-2, the system configuration.
Detection Resistor
R24
N1
R41
R43
DC Current
C34
0V0V
SPM2 – HIC
OC
99
F
8
20
IC1
R42
P2
Direct Current
DC260-380V
10
3938
6
–
R222
+
5
R247
0V
7
IC4
C225
R245
0V
12V
0V
R221
R284
R292
+
C217
R286
C2260VR285
0V
L
Is
N
CT1
D104
R005
0V
C009
0V0V
R006
+
C107
0V
C105
+
58
62
JW10
Fig. 8-1 Microcomputer and Peripheral Circuits
0V
2
–
+
3
R288
0V
IC5
CN13CN14
C205
R249
R248
C215
1
+
D205
37
0V
5V
R252
19
521
5V
C218
R289
R500
R253
D204
0V
SPM2
MAIN P.W.B
HIC
59
Vd
C222
0V
17
Ip
60
Id
C224
0V
C204
0V
IC1
MICROCOMPUTER
61
Is
48
RESET
Table 8-1
Circuit block
Peak current
cutoff circuit
Set value circuit
Voltage amplifier
circuit
Reset circuit
Trip signal
synthesis circuit
Basic operation
Detects DC current flowing power module and during overcurrent (instantaneous
value) flows, stops upper/lower arm drive circuits and also produces lp signal by
which drive signal output is stopped.
Compares voltage detected, amplified and input to HIC with set voltage value in
microcomputer, and controls overload when set value exceeds input voltage.
Voltage-amplifies DC current level detected by the detection resistor and inputs
this to microcomputer. Internal or external overload is judged in microcomputer.
Produces reset voltage.
Modulates chopper signal to drive signal and stops according to presence/ab-
sence of lp signal or reset signal.
– 83 –
Page 73
5V
Reset Voltage
Chopper
signal
Chopper
Trip signal
synthesis circuit
signal
DC 260V
Reset circuit
Over-load external
setting circuit
-360V
IP signal
Current amplified
circuit
DC
Current
level
Outdoor microcomputer
Fig. 8-2
● The following describes the operations of each circuit in detail.
(1) Peak current cut off circuit
Fig.8-3 Peak Current Cut off Circuit and Waveforms at Each Section.
Drive
Circuit
Peak current
cut off circuit
Detection
resistor
Drive
signal
DC current
Compressor
motor
Power
module
DC current Id
21A (27A, for RAC-50NH4)
Voltage at point
1.05V (1.35V for RAC-50NH4)
Voltage at point
SPM2
–
Negative
Terminal
DC
current
A
R41
A
Detection
resistor
B
0V
99
SPM2 – HIC
R43
0V
IC1
QC
R43
0V
B
R42
20 923917
8
F
Main P.W.B
CN14
Fig.8-3
● The Ip cut off circuit detects an instantaneous excessive current and stops inverter to protect parts such
as SPM2, etc.
● As shown in diagram, if current exceeding 21A (27A for RAC-50NH4) flows, voltage at point recognized
by detecting resistor is input to pin of SPM2 – HIC, and voltage divided by R41 and R43 is input to pin
9
of IC1. Since threshold of IC1 is exceeded in this case, Lo signal is input from pin (Voltage at point
B
. When Lo signal is input to pin of microcomputer, microcomputer stops drive output.
● When drive output from microcomputer is stopped, all drive output goes Hi, and microcomputer is initialized
10
17
A
8
to enter drive signal standby mode. 3 minutes later, microcomputer outputs drive signal again, to start
operation.
HIC
IP
Outdoor
microcomputer
– 84 –
Page 74
(2) Overload control circuit (OVL control circuit)
● Overload control is to decrease the speed of the compressor and reduce the load when the load on the
air conditioner increases to an overload state, in order to protect the compressor, electronic components
and power breaker.
● Overloads are judged by comparing the DC current level and set value.
● Fig. 8-4 shows the overload control system configuration and Fig. 8-5 is a characteristic diagram of
overload judgement values. There are two judgement methods-external judgement which compares the
externally set value with the DC current value regardless of the rotation speed and internal judgement
which compares the set value that varies according to the rotation speed programmed in the microcomputer
software with the DC current value.
Microcomputer
To power module
negative terminal
(R24)
DC current
Detection
resistor
Voltage amp
circuit
(Internal judgement)
DC voltage
OVL judgement
with respect to
externally set
value
A/D
converter
A/D
converter
Judgement OVL
according to the rotation
speed
Selects data according
to the rotation speed and
DC voltage
Motor control
process
Rotation speed data
OVL start current data
Fig. 8-4 Overload Control System Configuration
DC current
Judgement value according to the rotation speed
(internal judgement value)
Rotation speed
Fig. 8-5
1. Overload external judgement circuit
● Fig. 8-1. The filter consisting of R245 and C217 removes high harmonic components from the voltage
generated by the current flowing to Detection resistor; R245 and C217 average the voltage. This voltage
is then input to IC4 pin is then amplified and supplied to microcomputer pin . The microcomputer
5
compares this input with the internally set value, and if the input exceeds the set value, it enters overload
control status.
● Fig. 8-7 shows the rotation speed control. When the voltage at pin of the microcomputer exceeds the
60
set value, the microcomputer decreases the rotation speed of the compressor and reduces the load
regardless of the rotation speed commanded by the indoor microcomputer.
60
– 85 –
Page 75
Detection Resistor
R24
N1
L
Is
N
0V
CT1
C009
0V0V
D104
R006
R005
DC Current
58
+
C105
1
5
373938
5V
5V
C218
Direct Current
DC 260-380V
R500
SPM2
MAIN P.W.B.
R253
C222
0V0V
D204
C224
0V
0V0V
59
Vd
60
Id
61
Is
HIC
IC1
Microcomputer
P2
10
1
R245
0V
R221
CN14
+
C217
R222
6
–
+
5
R247
CN13
+
C205
0V
R249
7
R248IC4
D205
Fig. 8-6
Voltage at microcomputer pin
Rotation speed of compressor
60
Commanded rotation speed
Actual rotation speed
DecelerationDecelerationAccelerationAcceleration
Fig. 8-7
2. Voltage amp. circuit
● The voltage amp. circuit amplifies the DC current level detected by the detection resistor after being
converted to a voltage and supplies it to the microcomputer. Receiving this, the microcomputer converts
it to a digital signal and compares it with the internal data to judge whether or not overload control is
required.
< During overload control >
● The filter consisting of R245 and C217 removes high harmonic components from the voltage generated
from the DC current flowing to the detection resistor, and supplies it to IC4 pin 5 IC4 forms a non-inverting
voltage amp. circuit together with the peripheral elements.
● The microcomputer stores the set values which vary according to the rotation speed. When the DC current
level exceeds the set value, the microcomputer enters the overload control state.
● The set Value is determined by the amplification of the voltage amp. circuit.
● Amplification : high [ DC current : low
{
● Amplification : low [ DC current: high
– 86 –
Page 76
● R500, R253, detect the DC voltage at the power circuit. The microcomputer receives a DC voltage (260-
380V) via HIC U and applies correction to the overload set value so the DC current is low (high) when
the DC voltage is high (low).
(Since the load level is indicated by the DC voltage multiplied by DC current, R247, R248, R249 are
provided to perform the same overload judgement even when the voltage varies.)
Amplification : low
DC voltage : low
DC current : high
Amplification : 8.5 times
DC voltage : 260V
Amplification : high
DC current
0
G
0
Rotation speed
DC voltage : high
DC current : low
Fig. 8-8
< During start current control >
● It is required to maintain the start current (DC current) constant to smooth the start of the DC motor for
the compressor.
● RAC-25NH4, RAC-35NH4, RAC-50NH4 uses software to control the start current.
● The start current varies when the supply voltage varies. This control method copes with variations in the
voltages as follows.
(1) Turns on the power module's U+ and V– transistors so the current flows to the motor windings as
shown in Fig8-9.
(2) Varies the turn-ON time of the W+ transistor according to the DC voltage level and the start is
controlled so the start current is approx. 10A as shown in Fig. 8-10.
DC 260-360V
Detection
resistor
Chopper duty: high
ON-time
W transistor
20
15
10
5
DC current (A)
0
DC current
Power module
+
U
—
U
+
V
—
V
+
W
—
W
Compressor motor
U
V
W
Fig. 8-9
DC voltage: low
DC voltage: 280V
DC voltage: high
DC voltage (start current)
Start
Set value
Time
Fig. 8-10
– 87 –
Page 77
9. Temperature Detection Circuit
+5V
O.H. thermistor
CN8
Normal 2.7V or less
Over heat 2.7V or more
Reset 2.3V or less
HIC
O.H.
627
Microcomputer
DEF.
636
Outdoor
645
temperature
DEF. thermistor
CN9
Outdoor temperature
thermistor
CN10
+5V
0V
Normal 2.4V or more
Over heat 2.4V or less
Reset 2.9V or more
+5V
0V
Refer to the table 10-1
0V
Fig. 9-1
● The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the
Defrost. thermistor circuit detects the defrosting operation temperature.
● A thermistor is a negative resistor element which has the characteristics that the higher (lower) the
temperature, the lower (higher) the resistance.
● When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage at
pin 62 of microcomputer is increased.
● Microcomputer compares the voltage present at pin
62
with the internal set value, if it is exceeded the
set value microcomputer judges that the compressor is overheated and stops operation.
● When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly.
Therefore the resistance of the Defrost. thermistor becomes high and the voltage at pin
63
of microcomputer
drops.
If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
● During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
● The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
64
), and
transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set
at the EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dry
mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
Table 9-1
Outdoor temperature (°C)
Microcomputer pin 5 voltage (V)
-10
1.1901.69102.23
20
2.75
30
3.22403.62
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins 62 – 64 are approx. 0V;
when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode is
entered 12 minutes after the compressor starts operation.
– 88 –
Page 78
10. Reset Circuit
Main
HIC
P.W. B
12V
5V
Microcomputer
C107
0V
R284
R286
62
+
JW10
R292
C226
R285
0V
0V
0V
2
3
IC5 (1/2)
C225
R288
8
C215
–
1
+
R289
R252
C204
0V0V
48
RESET
Fig. 10-1
● The reset circuit initializes the microcomputer program when Power is “ON” or “OFF”.
● Low voltage at pin
● Fig. 10-1 shows the reset circuit and Fig. 10-2 shows waveform at each point when power is turned on
48
resets the microcomputer, and HI activates the microcomputer.
and off.
● When power is turned on, 12V line and 5V line voltages rise and 12V line voltage reaches 10.9V and
reset voltage input to pin 48 of microcomputer is set to Hi.
● Reset voltage will be hold “Hi” until the 12V line voltage drops to 9.90V even though the power shuts down.
12
6
Voltage (V)
Power is ON
0
12
6
Voltage (V)
Power is OFF
0
12V line
5V line
Reset voltage
Time
12V line
5V line
Reset voltage
Time
Fig. 10-2
– 89 –
Page 79
11. Outdoor DC Fan Motor control circuit.
System power module
PQ102
FM-15V
C103
5V
0V
14
23
R114
R106
Main P.W.B
R115
+
ZD101
R105
C106
R104
R103
FM-15V
Q101
D101
R101
FM-0V
Ap 7V
33.3KHz
5V
T/2
R102
5V
t
T
+++
Smoothing Capacitor
1234 5321
CN12
321
2A-FUSE
C101
R107
FM-0V
1
2
3
4
5
6
7
R108
0V
Fig. 11-1
U
V
W
0V
Vcc
PWM control voltage
FG Pulse
CN6
C104
D105
0V
61
60
59
Power supply for DC fan motor from smoothing
capacitor in system power module
RC Filter
VSD
BOARD
DC Fan motor with control board
IC4
R246
0V
C208
2
3
12V
0V
8
–
+
Q201
0V
HIC
R283
R242
0V
C219
+
C209
ONE CHIP DRIVER IC
Microcomputer
R243
R244
1
R298
R297
65
75
15
Motor coil
FM–60˚ el
FG Pulse
input
●This model uses DC Fan Motor which has a controller circuit in the Motor.
●This DC Fan Motor will rotate by control voltage apply to Vsp input. (Voltage range: 1.7 to 7V DC)
Vsp high : Faster ; Vsp low : slower ; Vsp lower than 1.7V : stop
●Motor will output FG pulse by following this motor revolution.
●Outdoor Microprocessor will output PWM control signal from FMCHOP terminal by following the instruction
from indoor Microprocessor.
●This PWM control signal will convert to Vsp voltage by smoothing circuit (Q101 & RC filter)
●Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by rotation
speed.
●FG pulse will feed back to Outdoor Microprocessor through PQ102.
●PQ102 is the isolator between Microprocessor circuit and DC Fan Motor circuit, which has to match the Fan
Motor revolution with instructed revolution. Such as...
●FG pulse is also used for Fan Motor failure detection
●Microprocessor will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected, it
will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on control PWB
will blink 12 times. (Fan Motor lock detected)
●R107 and IC4 are used for Fan Motor over current
– 90 –
Page 80
< Reference >
● When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
● In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
● DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
● It will makes “Fan Lock Stop”when something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
● It may make “Fan Lock Stop” by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
● In case of “Fan Lock Stop” even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes,
Fan Motor may be broken.
< Caution >
● Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
● You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
– 91 –
Page 81
12. Power Factor Control Circuit
Power factor is controlled to almost 100%. (Effective use of power)
With IC in ACT module, control is performed so that input current waveform will be similar to waveform of input
voltage
I (input current)
V (input voltage)
Effective
voltage
area
Invalid power area
(Even if voltage is applied. current does not flow)
input voltage
input current
Effective
voltage area
* Assuming the same current capacity (20A), power can be used about 10% effective, comparing with curent use
(power factor of 90%), and maximum capacity is thereby improved.
– 92 –
Page 82
SERVICE CALL Q & A
ModelRAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
RAK-50NH4 / RAC-50NH4
COOLING MODE
Q1
The compressor has
stopped suddenly during
cooling operation.
DEHUMIDIFYING MODE
Q2
Q3
Sound of running water is heard from
indoor unit during dehumidifying.
Compressor occasionally does not
operate during dehumidifying.
HEATING MODE
Q4
The circulation stops
occasionally during
Heating mode.
A1
Check if the indoor heat
exchanger is frosted.
Wait for 3-4 minutes
until it is defrosted.
A2
A3
A4
It occurs during defrosting. Wait for 5-10
minutes until the
condenser is defrosted.
If the air conditioner operates
in cooling mode when it is
cold, the evaporator may get
frosted.
Normal sound when refrigerant flows in pipe.
Compressor may not operate when room
temperature is 10°C or less. It also stops
when the humidity is preset humidity or less.
Q5
Q6
When the fan speed is set
at HIGH or MED, the flow
is actually Weak.
Heating operation stops
while the temperature is
preset at "30".
A5
A6
At the beginning of heating,
the fan speed remains
LOW for 30 seconds. If
HIGH is selected, it
switches to LOW and again
to MED after additional 30
seconds.
If temperature is high in
the outdoor, heating
operation may stop to
protect internal devices.
– 93 –
Page 83
AUTO FRESH DEFROSTING
Q7
After the ON/OFF button is pressed
to stop heating, the outdoor unit is
still working with the OPERATION
lamp lighting.
AUTO OPERATION
Q8
Fan speed does not change when
fan speed selector is changed
during auto operation.
NICE TEMPERATURE RESERVATION
Q9
When on-timer has been
programmed, operation starts before
the preset time has been reached.
A7
A8
A9
Auto Fresh Defrosting is carried out : the
system checks the outdoor heat exchanger
and defrosts it as necessary before stopping
operation.
At this point fan speed is automatic.
This is because “Nice temperature reservation”
function is operating. This function starts
operation earlier so the preset temperature is
reached at the preset time. Operation may start
maximum 60 minutes before the preset time.
Q10
Q1 1
Does “Nice temperature reservation”
function operate during dehumidifying?
Even if the same time is preset,
the operation start time varies.
INFRARED REMOTE CONTROL
Q12
Q13
Q14
Timer cannot be set.
The current time display
disappears soon.
The timer has been programmed,
but the preset time disappears.
A10
A11
It does not work. It works only during cooling
and heating.
This is because “Nice temperature reservation”
function is operating. The start time varies
according to the load of room. Since load varies
greatly during heating, the operation start time is
corrected, so it will vary each day.
A12
Has the clock been set? Timer cannot be set
unless the clock has been set.
The current time disappears
A13
in approx. 10 seconds. The
time set display has priority.
A14
Is the current time past the preset time?
When the preset time reaches the current
time, it disappears.
When the current time is
set the display flashes for
approx 3 minutes.
– 94 –
Page 84
OTHERS
The indoor fan varies among
Q15
high air flow, low air flow and
breeze in the auto fan speed
mode. (Heating operation)
Q16
Q17
Q18
Q19
Loud noise from the outdoor unit is
heard when operation is started.
Noise from the outdoor unit
occasionally changes.
There is a difference between the set
temperature and room temperature.
Air does not flow immediately
after operation is started.
A15
This is because the cool
wind prevention function
is operating, and does
not indicate a fault.
A16
A17
A18
A19
When operation is started, the compressor
rotation speed goes to maximum to increase the
heating or cooling capability, so noise becomes
slightly louder. This does not indicate a fault.
The compressor rotation speed changes according to
the difference between the thermostat set temperature
and room temperature. This does not indicate a fault.
There may be a difference between the set
temperature and room temperature because of
construction of room, air current, etc. Set the
temperature at a comfortable for the space.
Preliminary operation is performed for one
minute when the power switch on and heating
or dehumidifying is set. The operation lamp
blinks during this time for heating. This does
not indicate a fault.
The heat exchanger temperature
is sensed in the auto speed mode.
When the temperature is low, the
fan speed varies among high air
flow, low air flow and breeze.
– 95 –
Page 85
TROUBLE SHOOTING
ModelRAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
RAK-50NH4 / RAC-50NH4
PRECAUTIONS FOR CHECKING
DANGER
1. Remember that the
0V line is biased to
155-170V in
reference to the
ground level.
2. Also note that it takes
about 10 minutes
until the voltage fall
after the power switch
is turned off.
Power source
L
Indoor unit
electric parts
Control
P.W.B.
System power module 2
a
N
+
~
~
ACT Module
DC35V
C
0V
D
+–+
–
(0V)
b
MAIN P.W.B.
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
+
–
Power module
M
Compressor motor
approx 260-360V
approx 155-170V
approx 155-170V
DANGER
When using an
oscilloscope, never
ground it. Don't forget
that high voltages as
noted above may
apply to the
oscilloscope.
Outdoor unit P.W.B.
Always keep your hands
and metallic things away
from the enclosure of the
oscilloscope.
Oscilloscope
DANGER!
Don’t install
the ground
line.
– 96 –
Page 86
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
Caution
●
Voltage of about 300-330V is charged between both ends of smoothing capacitors
WARNING
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering
iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to
discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before
performing operation chech of each circuit.
●
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray
lead wire connected from diode stack to system power module (SPM2) to prevent secondary
trouble. (Be sure to discharge smoothing capacitor)
P1
N1
System power module
RAC-25NH4, RAC-35NH4
Smoothing capacitors
SPM2
Soldering
iron
Do not use a soldering iron with
transformer: If one is used, thermal fuse
inside transformer will be blown
As shown above, apply soldering iron to metal
parts (receptable) inside the sleeve
corresponding to P1 and N1 terminals of
system power module: Do this with smoothing
capacitors kept connected. By removing red/
gray lead wire from diode stack, power supply
can be shut off. (corresponding to + and –
terminals of system power module)
RAC-50NH4
SPM2
Smoothing capacitors
– 97 –
Page 87
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4
RAK-50NH4 / RAC-50NH4
Timer
lamp
Does the timer lamp on the indoor unit blink?
No
See “Troubleshooting when the timer lamp
blinks”.
Remove the terminal cover and check the voltage
between terminal (C) and terminal (D)
Does the operation lamp on the indoor unit
start to light or blink?
Yes
Is the compressor in the outdoor unit operating?
YesNo
Remove the outdoor unit cover and
electrical parts cover, and check
self-diagnosis lamp LD301
CN17
022527
IC3
P.W.B
Service switch
Self diagnosis lamps
(LD303, 302, 301)
Does LD301 blink one time ?
* Repeats 0.25-second on and
2-second off.
No
Terminal C
(+35V)
Terminal D
(0V)
Is approx. DC 33 to 37V being generated? Is the
polarity correct?
No
Yes
Check to see whether the Fcable is connected incorrectly
or disconnected
Normal
Blinking other than
one time
Press the service switch for 1 sec.
Does the compressor operate?
(After checking, be sure to press
the service switch to stop the
operation).
See “Out door unit self-diagnosis lamp
lighting mode”.
Check the refrigerating cycle.
One-time blinking
Yes
No
Check the outdoor electrical parts.
– 98 –
Check the indoor electrical parts.
Page 88
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
sec.
sec.
Model RAK-25NH4, RAK-35NH4, RAK-50NH4
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
(1) Indoor fan locked
(2) Indoor fan motor
(3) Indoor control P.W.B.
IC401 or IC402 abnormal
( – – Lights for 0.5 sec. at interval of 0.5 sec..)
<Cautions>
(1)If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2)If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected.
(3)To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
– 99 –
Page 89
SELF-DIAGNOSIS LIGHTING MODE
MODEL: RAC-25NH4, RAC-35NH4 & RAC-50NH4
– 100 –
Page 90
CHECKING INDOOR UNIT ELECTRICAL PARTS
1. Power does not come on (no operation)
NoNo
Is DC 35V being generated between
terminals C and D on the terminal
board?
Is AC 220-240V AC being generated
between terminals L and N on the
outdoor unit terminal board?
Yes
Is DC 35V being generated between
terminals C and D on the outdoor
unit terminal board?
Check AC outlet and breaker, and
repair any defective part.
Yes
Check the indoor/outdoor unit
connection cable, and correct any
defective section (wrong connection,
incomplete insertion reversed).
Are control voltages (12V, 5V)
being generated normally?
Yes
Do the air deflectors perform initial
operation when the power supply is
turned on and off?
No
Is the microcomputer reset input
(pin 7 )“Hi”?
Yes
Is the microcomputer clock signal
10MHz at pin
generated normally?
10 11
being
Yes
No
Yes
No
No
No
Check the outdoor unit power circuit,
and repair the defective section.
Check according to the proper method
for checking the power circuit.
Check the indication P.W.B.
connection cord and light receiving
unit.
Check the reset circuit, and repair
any defective section.
Replace the microcomputer and
oscillator.
Replace the control P.W.B
Perform final operation check.
– 101 –
Page 91
2. Outdoor unit does not operate (but receives remote infrared signal)
Set to room temperature 16°C in the cooling
mode or to 32°C in the heating mode, and
press the start/stop button.
Remove the outdoor unit cover and
electrical parts cover, and check selfdiagnosis lamp LD301.
Self diagnosis lamps
(LD303, 302, 301)
Does LD301 blink one time?
*Repeats 0.25-second on and 2-second off.
No
Yes
Does outdoor electrical part
LD301 blink nine times?
Yes
Is the indoor/outdoor unit
communication signal superimposed
on 35V DC of connection wires C
and D?
Approx.
35V
0V
38kHz Approx. 2Vp-p
Yes
Check the room temperature
thermistor; if it is defective,
replace it.
<Normal values>