Hilti CP 617 INSTALLATION

Installation instructions for CP 617
1. Remove label from one side of CP 617
Application of firestop putty
1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad is required.
2. Adhere pad to side of the box, overlapping the stud and all edges of the box. – When drywall is installed: fix pad into gap between electrical
cabinet and gypsum board slightly overlapping the inner wall board surface.
– When drywall will be installed later: overlap front edge of
electrical cabinet so that CP 617 will be compressed around edges of box as gypsum board is installed.
3. Reshape CP 617 to fit around conduit or cables.
4. Press CP 617 to all sides of electrical box. Trim excess at corners and apply to conduit fittings connected to the box.
5. Remove other side of label. To help prevent passage of cold
smoke, CP 617 may optionally be placed into inside of electrical conduit fittings.
2. Adhere CP 617 to application
3. Reshape CP 617 to fit around box
4. Press CP 617 to all sides of application
Notice about approvals
• CP 617 Firestop Putty Pad is classified by Underwriters Laboratories, Inc., (UL) as a “Wall Opening Protective Material.” Therefore, specific UL listings are not required. Specific details can be found in the Hilti Firestop Inspection and Installation Manual and/or current UL Fire Resistance Directory, Volume I.
Not to be used...
• In areas underwater
Safety precautions
• Before handling, read the product Material Safety Data Sheet and product label for detailed use and health information.
• Wear suitable gloves and eye protection.
• Keep out of the reach of children.
Storage
• Store only in the original packaging in a location at temperatures
40°F (5°C) to 104°F (40°C).
5. Remove other side of label