HID FlexSmart 607, FlexSmart 6075, FlexSmart 6076, FlexSmart 6077, FlexSmart 6073 Installation Manual

...
Page 1
9292 Jeronimo Road Irvine, CA 92618-1905
HID® FlexSmart™
607X Series Readers
INSTALLATION GUIDE
February 5, 2006
Document Number 6075-900
Document Version B.2
Page 2
6075-900, B.2 – FlexSmart™ 607X Series Installation Guide
Contents
1 Overview ............................................................................................................................................... 3
2 Mounting ...............................................................................................................................................4
3 Wiring ................................................................................................................................................... 5
Regulatory ................................................................................................................................................... 7
Models ................................................................................................................................................... 7
Contact ................................................................................................................................................... 8
List of Figures
Figure 1 Reader Dimensions and Mounting........................................................................................................ 4
Figure 2 Keypad Reader Dimensions and Mounting.......................................................................................... 5
Page 2 of 8 February 5, 2007
© 2007 HID Global Corporation. All rights reserved.
Page 3
FlexSmart™ 607X Series Installation Guide – 6075-900, B.2
1 Overview
1.1 Introduction
The HID® FlexSmart™ readers can easily be configured at the site because the readers’ bezel can be interchangeably snapped onto the common reader module (only standard reader).
The FlexSmart readers mount on any North American standard electrical gang box or on any flat surface, with snap-on bezels.
1.2 Parts Included
First, unpack the contents and become familiar with the components. The following items will be included with FlexSmart readers:
1. Installation Guide
2. MIFARE reader module for Slim or Wall switch
3. Cover Bezel (reader only)
1.3 Specifications
Supply Voltage Supply Current
Input Output formats
Operating Frequency Data Transmission
Operating Temperature Non-Operating Temperature Operating Humidity
Finish Dimensions
9VDC to 16VDC 15 / 75mA Keypad 25 / 100mA
1-line LED (red/green), 1-line buzzer Wiegand/ABA, Application dependant
13.56MHz, 106kBaud Contactless
-25oC to +55oC
o
-40
C to +70oC
5% to 95% condensing
Black (Standard)
4.30” x 1.5” x .72” (10.9 x 3.8 x 1.8 cm)
Weight
February 5, 2007 Page 3 of 8
4.70” x 2.9” x 1.1” (11.9 x 7.4 x 2.8 cm) 4 oz (113g) keypad 12 oz (340g)
© 2007 HID Global Corporation. All rights reserved.
Page 4
6075-900, B.2 – FlexSmart™ 607X Series Installation Guide
1.4 Identifying the Reader Format
The reader format is found on the ID label (see below), which is located on the reader electronics module.
Reader Format
2 Mounting
Page 4 of 8 February 5, 2007
Figure 1 Reader Dimensions and Mounting
© 2007 HID Global Corporation. All rights reserved.
Page 5
FlexSmart™ 607X Series Installation Guide – 6075-900, B.2
Figure 2 Keypad Reader Dimensions and Mounting
2.1 Mullion Mounting
The following describes how the readers mount to a mullion.
1. Drill two holes 6-32 or M-3 sheet metal or thread forming screws 3.3” (8.38 cm) apart.
2. Locate and drill a 0.375” (0.95 cm) hole for the reader cable.
3. Route the cable through the center hole to the controller.
4. Using the two 6-32 or M-3 screws, attach the reader to the first two mounting holes.
5. Once the reader module is screwed in place, snap on the bezel.
3 Wiring
3.1 Cable Types and Maximum Lengths
The MIFARE readers require a minimum voltage of 9.0 VDC. Voltage drops, caused by the cable resistance, can be made by increasing the power supply voltage.
CAUTION: DO NOT SET THE POWER SUPPLY VOLTAGE TO HIGHER THAN 16 VDC.
CAUTION: DO NOT USE CABLES WITH GAUGES SMALLER THAN 24 AWG:
February 5, 2007 Page 5 of 8
© 2007 HID Global Corporation. All rights reserved.
Page 6
6075-900, B.2 – FlexSmart™ 607X Series Installation Guide
The following are recommended cable types and maximum cable lengths for a cable connecting the power supply to the reader.
Cable Type Maximum Cable Length
24 AWG (0.60mm), three conductors, with an overall foil shield, 9533 or equivalent.
200’ (61 m)
22 AWG (0.80mm), two conductors, with an overall foil shield, Alpha 5192 or equivalent.
18 AWG (1.20mm), two conductors, with an overall foil shield, 5836 or equivalent.
The following are recommended wiring types at various maximum distances. Variations in distances require different wire gauges, because of system data termination differences. Contact your system manufacturer for its exact requirements. Installation should be in accordance with National Electric Code ANSI/NFPA 70.
22 AWG (0.80mm), six or eight conductor, with an overall foil shield, Alpha 5196, 5198 or equivalent.
18 AWG (1.20mm), six or eight conductor, with an overall foil shield, Alpha 5386, 5388 or equivalent.
3.2 Grounding
Connect the reader directly to an earth ground (an earth ground can be established by driving a copper clad ground rod into the earth). Make certain the DC resistance between your established earth ground and the system ground is 50 Ohms or less. If a direct connection to a ground rod is not possible, connect the reader to an earth grounded cold water metal pipe (do not connect to a copper fire sprinkler system because it may have non-conductive couplings) or steel frames (building beams) that connect to earth. Connection of the shield/drain to an earth ground will provide greater ESD protection of the reader.
Prevent ground loops by connecting both the cable shield and the negative line of the power supply to one common earth ground point. Connecting different points to separate earth grounds may result in a ground loop.
300’ (91 m)
500’ (152 m)
Cable Type Maximum Cable Length
500’(152 m)
500’ (152m)
Note: For the heavy duty keypad readers, the Shield/drain wire should be floating at the power supply. Note: Ground loops may cause poor read range and communication line interference, resulting in no code
or improper code seen by the controller.
Reader Defaults
Card read (LED, beep & backlight) Red +12Vdc One-line control (bi-colour LED) Black 0Vdc Keypad Defaults Green Data 0/Strobe Key-press (LED, beep & backlight) White Data 1/Data 1 0001 2 0010 3 0011 Brown LED Control 4 0100 5 0101 6 0110 Blue Beeper Control 7 0111 8 1000 9 1001 Orange Not Used Θ1010
0 0000 # 1011 Shield/drain Door controller earth ground
Reader Wiring
Page 6 of 8 February 5, 2007
© 2007 HID Global Corporation. All rights reserved.
Page 7
FlexSmart™ 607X Series Installation Guide – 6075-900, B.2
Notes:
Keypad outputs only available
The system must have a single earth ground point.
As shown, do not connect shield (screen) wire at reader cable splice.
For open collector (non-terminated output), consult your system manufacturer for correct cable length
and type.
Regulatory
FCC
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
UL
This reader is intended to be used with UL294 Listed Control Equipment.
CE
Hereby, HID declares that this proximity reader is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
Models
Readers 6075 HID Format MIFARE Reader 6076 Custom MIFARE Reader 6077 Custom DESFire Reader Keypad Readers 6071 HID Format MIFARE Reader 6072 Custom MIFARE Reader 6073 Custom DESFire Reader
February 5, 2007 Page 7 of 8
© 2007 HID Global Corporation. All rights reserved.
Page 8
6075-900, B.2 – FlexSmart™ 607X Series Installation Guide
Contact
Americas
HID Corporation (California, USA) Email:
tech@hidcorp.com
main: (949) 598-1600 support: 1-800-237-7769 fax: (949) 598-1690
Europe, Middle East and Africa
HID Corporation, Ltd. (Haverhill, UK) email:
eusupport@hidcorp.com
main: +44 (0) 1440 714 850 support: +44 (0) 1440 711 822 fax number: +44 (0) 1440 714 840
Asia-Pacific
HID Asia Pacific Ltd. (Hong Kong) email:
asiasupport@hidcorp.com
main: (852) 3160 9800 support: (852) 3160 9802 fax : (852) 3160 4809
Page 8 of 8 February 5, 2007
© 2007 HID Global Corporation. All rights reserved.