Hewlett-Packard 217823-002 User Manual

HP Uninterruptible Power System
R1500 XR Models
User Guide
August 2002 (Second Edition)
Part Number 217823-002
Hewlett-Packard Company shall not be liable for technical or editorial errors or omissions contained herein. The information in this document is provided “as is” without warranty of any kind and is subject to change without notice. The warranties for HP products are set forth in the express limited warranty statements accompanying such products. Nothing herein should be construed as constituting an additional warranty.
HP Uninterruptible Power System R1500 XR Models User Guide
August 2002 (Second Edition) Part Number 217823-002

Contents

About This Guide
Audience Assumptions............................................................................................................................... vii
Important Safety Information .....................................................................................................................vii
Symbols on Equipment............................................................................................................................... vii
Rack Stability.............................................................................................................................................viii
Symbols in Text......................................................................................................................................... viii
Related Documents....................................................................................................................................viii
Getting Help................................................................................................................................................. ix
Technical Support ................................................................................................................................. ix
HP Website............................................................................................................................................ ix
Authorized Reseller............................................................................................................................... ix
Reader’s Comments..................................................................................................................................... ix
Chapter 1
Overview
Standard UPS Features ..............................................................................................................................1-1
Communications Port.......................................................................................................................... 1-1
Network Transient Protector ...............................................................................................................1-2
Overcurrent Protection........................................................................................................................ 1-2
UPS R1500 XR Models............................................................................................................................. 1-2
Front Panel ..........................................................................................................................................1-3
Rear Panels.......................................................................................................................................... 1-4
Power Management Software.................................................................................................................... 1-7
UPS Hardware Options.............................................................................................................................. 1-7
Remote Emergency Power Off Port ..........................................................................................................1-8
Warranties.................................................................................................................................................. 1-8
$25,000 Computer Load Protection Guarantee................................................................................... 1-8
Pre-Failure Battery Warranty..............................................................................................................1-9
Chapter 2
Operation
Front Panel Controls and LED Indicators..................................................................................................2-1
Modes of Operation ...................................................................................................................................2-2
Charging the Batteries ...............................................................................................................................2-3
Placing the UPS in Operate Mode............................................................................................................. 2-3
Returning to Standby Mode....................................................................................................................... 2-4
Initiating a Self-Test ..................................................................................................................................2-5
HP Uninterruptible Power System R1500 XR Models User Guide iii
Contents
Audible Alarms ......................................................................................................................................... 2-6
Silencing an Audible Alarm ............................................................................................................... 2-6
Shutting Down the System........................................................................................................................ 2-6
Chapter 3
Configuration
Placing the UPS in Configure Mode......................................................................................................... 3-1
Configuration Parameters.......................................................................................................................... 3-2
Changing Configuration Parameters................................................................................................... 3-3
Chapter 4
Battery Maintenance
Precautions ................................................................................................................................................ 4-1
Charging Batteries..................................................................................................................................... 4-1
Determining When to Replace Batteries................................................................................................... 4-2
Obtaining New Batteries........................................................................................................................... 4-2
Replacing Batteries ................................................................................................................................... 4-3
Preparing the UPS............................................................................................................................... 4-3
Removing the Battery Pack ................................................................................................................ 4-3
Installing a New Battery Pack ............................................................................................................ 4-6
Testing the New Battery Pack ............................................................................................................ 4-6
Disposing of Used Batteries ............................................................................................................... 4-6
Care and Storage of Batteries.................................................................................................................... 4-7
Pre-Failure Battery Warranty.............................................................................................................. 4-7
Chapter 5
Troubleshooting
Troubleshooting ........................................................................................................................................ 5-1
Repairing the UPS..................................................................................................................................... 5-4
Appendix A
Regulatory Compliance Notices
Regulatory Compliance Identification Numbers.......................................................................................A-1
Federal Communications Commission Notice..........................................................................................A-1
Class A Equipment .............................................................................................................................A-1
Class B Equipment .............................................................................................................................A-2
Declaration of Conformity for Products Marked with the FCC Logo, United States Only................A-2
Modifications......................................................................................................................................A-2
Cables .................................................................................................................................................A-3
Canadian Notice (Avis Canadien).............................................................................................................A-3
Class A Equipment .............................................................................................................................A-3
Class B Equipment .............................................................................................................................A-3
European Union Notice.............................................................................................................................A-3
Japanese Notice.........................................................................................................................................A-4
China Taiwan Notice.................................................................................................................................A-4
Battery Replacement Notice......................................................................................................................A-5
iv HP Uninterruptible Power System R1500 XR Models User Guide
Appendix B
Electrostatic Discharge
Grounding Methods.................................................................................................................................. B-1
Appendix C
Specifications
Physical Specifications............................................................................................................................. C-1
Input Specifications .................................................................................................................................. C-2
Output Specifications................................................................................................................................ C-3
Battery Specifications............................................................................................................................... C-4
Environmental Specifications................................................................................................................... C-4
Index
Contents
HP Uninterruptible Power System R1500 XR Models User Guide v
This guide provides step-by-step instructions for configuration, and reference information for operation, battery maintenance, and troubleshooting for the Uninterruptible Power System (UPS).

Audience Assumptions

This guide is intended for individuals requiring information about the use of HP UPSs. HP assumes you are qualified in the servicing of computer equipment and trained in recognizing hazards in products with hazardous energy levels.

Important Safety Information

Before installing this product, read the Important Safety Information document included with the UPS.

About This Guide

Symbols on Equipment

The following symbols may be placed on equipment to indicate the presence of potentially hazardous conditions:
WARNING: This symbol, in conjunction with any of the following symbols, indicates the presence of a potential hazard. The potential for injury exists if warnings are not observed. Consult your documentation for specific details.
This symbol indicates the presence of hazardous energy circuits or electric shock hazards. Refer all servicing to qualified personnel.
WARNING: To reduce the risk of injury from electric shock hazards, do not open this enclosure. Refer all maintenance, upgrades, and servicing to qualified personnel.
This symbol indicates that the component exceeds the recommended weight for one individual to handle safely.
Weight in kg
Weight in lb
WARNING: To reduce the risk of personal injury or damage to the equipment, observe local occupational health and safety requirements and guidelines for manual material handling.
HP Uninterruptible Power System R1500 XR Models User Guide vii
About This Guide

Rack Stability

WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that:
The leveling feet are extended to the floor.
The full weight of the rack rests on the leveling jacks.
The stabilizing feet are attached to the rack in single-rack installations.
The racks are coupled together in multiple-rack installations.
Only one component is extended at a time. A rack may become unstable if more

Symbols in Text

These symbols may be found in the text of this guide. They have the following meanings.
WARNING: Text set off in this manner indicates that failure to follow directions in the warning could result in bodily harm or loss of life.
than one component is extended for any reason.
CAUTION: Text set off in this manner indicates that failure to follow directions could result in
damage to equipment or loss of information.
IMPORTANT: Text set off in this manner presents essential information to explain a concept or complete a task.
NOTE: Text set off in this manner presents additional information to emphasize or supplement important points of the main text.

Related Documents

For additional information on the topics covered in this guide, refer to the following documents:
HP Uninterruptible Power System R1500 XR Models Installation Instructions
HP UPS R1500 XR Models Extended Runtime Module Installation Instructions
HP UPS XR Products Power Cord and Options Reference Guide
Industry Standard Terminology Glossary
These documents are located on the Power Products Documentation CD or at
www.hp.com.
viii HP Uninterruptible Power System R1500 XR Models User Guide

Getting Help

If you have a problem and have exhausted the information in this guide, you can get further information and other help in the following locations.

Technical Support

In North America, call the HP Technical Support Phone Center at 1-800-652-6672. This service is available 24 hours a day, 7 days a week. For continuous quality improvement, calls may be recorded or monitored. Outside North America, call the nearest HP Technical Support Phone Center. For telephone numbers of worldwide Technical Support Centers, go to
www.hp.com.
Have the following information available before you call:
Technical support registration number (if applicable)
Product serial number
Product model name and number
Applicable error messages
About This Guide
Add-on boards or hardware
Third-party hardware or software
Operating system type and revision level
Power management software type and version

HP Website

For information on this product as well as the latest drivers, firmware updates, and service packs, go to
www.hp.com.

Authorized Reseller

For the name of your nearest authorized reseller:
In the United States, call 1-800-345-1518.
In Canada, call 1-800-263-5868.
Elsewhere, see the HP website for locations and telephone numbers.

Reader’s Comments

To comment on this guide, send e-mail to ServerDocumentation@hp.com.
HP Uninterruptible Power System R1500 XR Models User Guide ix
This chapter contains a general overview of the HP UPS, including an introduction to the model configurations, power management software, available hardware options, and warranties. Read this chapter to become familiar with the features of the UPS before operating the unit.

Standard UPS Features

The following features make this UPS versatile and easy to use:
Communications port for data exchange with the host computer
Network Transient Protector
Load segment control
Load power protection up to 1440 VA/1340 W (R1500 XR NA model) or
1500 VA/1340 W (R1500 XR JPN and R1500 XR H INT’L models)
1
Overview
Support for UPS power management software
Support for HP hardware option cards, extending the power management capabilities of
the UPS
Support for HP Extended Runtime Modules (ERMs), options that extend the available runtime of the UPS
Support for HP Power Distribution Units (PDUs), options that allow distribution of power
Remote Emergency Power Off (REPO) port
Ease of use and configuration

Communications Port

The UPS includes a communications port for data exchange with a host computer.
CAUTION: Use only the specific cables supplied with the UPS to connect the communications port to the host computer.
HP Uninterruptible Power System R1500 XR Models User Guide 1-1
Overview

Network Transient Protector

The UPS includes a Network Transient Protector (NTP) that provides surge protection for connected communication devices.
CAUTION: To avoid damaging the equipment, do not connect the Network Transient Protector to a digital PBX line. Connect either to an analog phone line or to a network.

Overcurrent Protection

Select models feature overcurrent protection provided through resettable circuit protectors located on the UPS rear panel.

UPS R1500 XR Models

The UPS models include the following.
Table 1-1: UPS R1500 XR Models
UPS Model Kit Part
Number
R1500 XR NA 204404-001 204405-001 EO3008 Domestic, low-voltage
R1500 XR JPN 204404-291 204405-191 EO3008j Japanese, low-voltage
R1500 XR H INT’L 204404-B31 204405-002 EO3008i International, high-voltage
Unit Part Number
Series Number
Comments
rack-mountable UPS with non-detachable NEMA 5-15 plug
rack-mountable UPS with non-detachable NEMA 5-20 plug
rack-mountable UPS with detachable country-specific plug
1-2 HP Uninterruptible Power System R1500 XR Models User Guide

Front Panel

Overview
The front panel of the UPS is shown in Figure 1-1.
2 31
Figure 1-1: Front panel configuration
1 Battery compartment
2 Control buttons
3 LED display
For detailed information on using the control buttons and LED indicators, refer to the section, “Front Panel Controls and LED Indicators,” in Chapter 2.
HP Uninterruptible Power System R1500 XR Models User Guide 1-3
Overview

Rear Panels

The rear panel configurations of the UPS are shown in Figures 1-2, 1-3, and 1-4.
1 3
8
2
Figure 1-2: Rear panel of R1500 XR NA
1 Communications port/option slot
2 Load segment circuit protectors
3 Load segment 2 (three NEMA 5-15 receptacles)
4 Load segment 1 (three NEMA 5-15 receptacles)
5 Network Transient Protector OUT jack
6 Network Transient Protector IN jack
7 REPO port
8 Power cord with NEMA 5-15 plug
9 ERM connector
10 Ground bonding screw
467910 5
1-4 HP Uninterruptible Power System R1500 XR Models User Guide
Overview
1 3
8
2
Figure 1-3: Rear panel of R1500 XR JPN
1 Communications port/option slot
2 Load segment circuit protectors
3 Load segment 2 (three NEMA 5-15 receptacles)
4 Load segment 1 (three NEMA 5-15 receptacles)
5 Network Transient Protector OUT jack
6 Network Transient Protector IN jack
7 REPO port
8 Power cord with NEMA 5-20 plug
9 ERM connector
10 Ground bonding screw
467910 5
HP Uninterruptible Power System R1500 XR Models User Guide 1-5
Overview
1 42 3
78910 6 5
Figure 1-4: Rear panel of R1500 XR H INT’L
1 Communications port/option slot
2 Circuit protector
3 IEC-320-C14 input power receptacle
4 Load segment 1 (three IEC-320-C13 receptacles)
5 Load segment 2 (three IEC-320-C13 receptacles)
6 Network Transient Protector OUT jack
7 Network Transient Protector IN jack
8 REPO port
9 ERM connector
10 Ground bonding screw
WARNING: Risk of personal injury from electric shock. This model is not suitable for installation where the total earth (ground) conductor leakage current for all connected devices exceeds 3.5 mA. Use RackBuilder Pro (obtainable at www.hp.com) to find the total system leakage current.
1-6 HP Uninterruptible Power System R1500 XR Models User Guide

Power Management Software

Power management software ensures maximum power reliability of HP computer systems through comprehensive control of HP UPSs. Specifically, power management software performs the following:
IMPORTANT: Not all UPSs are equipped to support the entire feature set listed.
Manages a graceful shutdown of attached equipment during utility power failures
Manages independent UPS load segments to provide separate power control of connected
equipment
Prioritizes the timing of equipment shutdowns, and reboots connected equipment by load segment
Shuts down and reboots HP UPSs and attached equipment based on a user-specified schedule
Delays restart by load segment after a power outage to sequence the startup of system components
Customizes alert generation with modifiable popup dialog boxes, command execution, and email and broadcast messages
Overview
Monitors the status of the UPS and performs UPS diagnostics
Displays power logs for analysis
For more information, refer to the power management CD provided with the UPS. For the most up-to-date information, refer to

UPS Hardware Options

Table 1-2 lists the available hardware options for this UPS.
Table 1-2: Hardware Options
Option Part Number
HP ERM 218971-B21
HP Six Port Card 192185-B21
HP SNMP / Serial Port Card 192189-B21
For a list of supported PDUs and more information on the available hardware options, refer to the HP UPS XR Products Power Cord and Options Reference Guide included on the Power Products Documentation CD and at
www.hp.com.
www.hp.com.
HP Uninterruptible Power System R1500 XR Models User Guide 1-7