3-7. Recommended Spare Parts for Distributors ....................................................... 3-1
FM06-015
Revised 08-12-10
810 i
Model HMI-103/105
Model HMI-103/105
SECTION 1. TROUBLESHOOTING
1-1. INTRODUCTION This section provides troubleshooting information in the form
of an easy to read table.
If a problem occurs during the fi rst operation of a new cabinet,
recheck the Installation Section of the Operator’s Manual.
Before troubleshooting always recheck the Operating
Instructions Section of the Operator’s manual.
1-2. SAFETY Where information is of particular importance or is safety
related, the words NOTICE, CAUTION, or WARNING are
used. Their usage is described below.
SAFETY ALERT SYMBOL is used with DANGER,
WARNING, or CAUTION which indicates a personal
injury type hazard.
NOTICE is used to highlight especially important
information.
CAUTION used without the safety alert symbol indicates
a potentially hazardous situation which, if not avoided,
may result in property damage.
CAUTION used with the safety alert symbol indicates a
potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
203 1-1
Model HMI-103/105
1-3. TROUBLESHOOTING To isolate a malfunction proceed as follows:
1. Clearly defi ne the problem or symptom.
2. Locate the problem in the troubleshooting table.
3. Review all possible causes, then work through the list
of corrections one-at-a-time until the problem is solved.
Refer to maintenance procedures in Section 2 to safely
and properly make the checkout and repair needed.
PROBLEM CAUSE CORRECTION
OPERATIONS
Product not holding
temperature
A. Lights will not
turn on
• Product held too long
• Only hold product for specifi ed times
• Radiant heat too low
• Radiant heat not working
• Turn to a higher setting
• Check radiant heaters per Radiant
Heaters Section
• Air heat too low
• Air heaters not working
• High limit open
• Turn to a higher setting
• Check heaters per Air Heaters Section
• Check cooling fan
• Check high limits
LIGHTING
• Defective fuse • Check fuse and replace if necessary
• Faulty switch • Check switch and replace if necessary
• Check fi eld wiring to be sure a true
• No neutral supplied in fi eld wiring neutral has been connected
• Loose or defective wiring
• Check wiring and repair or replace
if necessary
1-2 203
Model HMI-103/105
1-3. TROUBLESHOOTING (Continued)
PROBLEM CAUSE CORRECTION
B. Not all lights turn
on
• Faulty light bulb
• Faulty light socket
• Faulty switch
HEATING SECTION
A. Radiant heat not
• Faulty infi nite regulator
working
• Faulty power switch• Check switch and replace if necessary
• Faulty heater• Check heater and replace if necessary
• Faulty contactor• Check contactor and replace if
• High limit opened• Check cooling fans
B. Air heat not
• Faulty infi nite regulator• Replace infi nite regulator per
working
• Faulty power switch• Check switch and replace if
• Replace with recommended bulb
• Replace socket per Light Socket Section
• Check switch and replace if necessary
• Replace infi nite regulator per
Infi nite Regulator Section
necessary
• Check high limits (reset)
Infi nite Regulator Section
necessary
• Faulty heater• Check heater and replace if necessary
• Faulty contactor• Check contactor and replace if
necessary
• High limit opened• Check cooling fans
• Check high limits (reset)
203 1-3
Model HMI-103/105
Model HMI-103/105
SECTION 2. MAINTENANCE
2-1. INTRODUCTION This section provides procedures for check out and replacement
of the various parts used within the cabinet. Before replacing
any parts, refer to the Troubleshooting Section. It will aid you
in determining the cause of the malfunction.
2-2. TEST INSTRUMENTS You may want to use two test instruments to check the electric
components.
1. A continuity light
2. An ohmmeter
When the manual refers to a circuit being closed, the continuity
light will be illuminated or the ohmmeter should read zero
unless otherwise noted.
When the manual refers to a circuit being open, the continuity
light will not illuminate or the ohmmeter will read 1 (one) or
infi nite resistance.
A continuity tester cannot be used to check coils.
2-3. FUSE 1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move
power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Open the control panel cover and locate both fuse holders.
Step 2
3. Unscrew the caps, counterclockwise, and pull fuses from
holders.
4. Place leads of meter on each end of a fuse, and check for
continuity on both fuses. If one shows an open circuit,
replace it with a 15 amp fuse (HP no. EF02-007).
Step 3
203 2-1
Model HMI-103/105
2-4. RADIANT HEATERS 1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move
power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Remove screws from access panel on both sides of radiant
Step 2
heater and let light socket and heater hang down.
3. Remove screw from inner side of access panel.
4. Remove wires from heater; pull radiant heater from panel.
5. Install new radiant heaters.
Step 3
The radiant heaters are paired and wired in series. If one
heater is bad, two won’t heat.
Step 4
2-5. LIGHT SOCKET 1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move
power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Remove screws from access panel on both sides of light
Step 3
socket, as shown above in the Radiant Heaters Section.
3. Remove wires from light socket.
4. Depress retainer on light socket and push through panel.
5. Install new light socket.
Step 4
2-2 203
Model HMI-103/105
2-6. AIR HEATERS 1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move
power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Remove pans and pan supports from unit.
Step 3
3. Remove heater screws from inside of well.
4. Pull heater terminals out into interior of unit to access wires.
5. Remove wires from heater and pull heater from unit.
6. Install new heater.
Step 5
2-7. POWER SWITCH 1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move
power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Open control panel cover and remove the four screws
Step 2
securing the control panel.
3. Pull control panel out to access back of switch. Pull and
label the wires of switch.
Step 3
203 2-3
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.