Henny Penny 342 User Manual

Model OFE/OFG/OEA/OGA-341, 342
SECTION 2. MAINTENANCE
2-1. INTRODUCTION
This section provides procedures for the check out and replacement of the various parts used within the fryer. Before replacing any parts refer to the Troubleshooting Section. It will aid you in determining the cause of the malfunction.
1. You may need to use a multimeter to check the electric
components.
2. When the manual refers to the circuit being closed, the multimeter should read zero unless otherwise noted.
3. When the manual refers to the circuit being open, the multimeter will read infinity.
2-3. HIGH TEMPERATURE LIMIT CONTROL
(Gas Units)
which senses the temperature of the shortening. If the short-
This high temperature control is a safety, manual reset control,
ening temperature exceeds 425°F (218°C), this switch opens and shuts off heat to the frypot. When the temperature of the shortening drops to a safe operation limit, the control must be manually reset by pressing the red reset button. The red reset button is located under the control panel, in the front of the fryer. (Figure 2-1). This allows heat to be supplied to the frypot.
Before replacing a high temperature limit control, check to see that its circuit is closed.
Figure 2-1 The shortening temperature must be below 380°F (193°C)
to accurately perform this check.
Checkout
To avoid electrical shock or property damage, move the power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
1. Remove the control panel. Figure 2-2.
Figure 2-2
1003 2-1
Model OFE/OFG/OEA/OGA-341, 342
1-3. HIGH TEMPERATURE 2. Using a Phillip’s head screwdriver, remove the screws securing LIMIT CONTROL (Gas Units) (Continued)
the inner heat shield and remove from unit. Figure 2-3.
Figure 2-3 3. Remove the screw securing the high limit bracket to the frame and remove the high limit and bracket from unit. Figure 2-4.
Figure 2-4 4. Remove the two screws securing the high limit to the bracket and remove the high limit from bracket.
5. Remove the two electrical wires from the high temperature limit control. Figure 2-5.
Figure 2-5
6. Manually reset the control, then check for continuity between the two terminals after resetting the control. If the circuit is open, replace the control, then continue with this procedure. (If the circuit is closed, the high limit is not defective. Re­ connect the two electrical wires.)
2-2 1003
Model OFE/OFG/OEA/OGA-341, 342
2-3. HIGH TEMPERATURE LIMIT CONTROL (Gas Units) (Continued)
Replacement To avoid electrical shock or property damage, move the power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
1. If the tube is broken or cracked, the control opens, shutting off electrical power to the heat circuit. The control cannot be reset, and it continuously clicks when pushed.
2. Drain the shortening from the frypot and discard. A substance from the tube could contaminate the shortening.
Figure 2-6 3. Remove the control panel.
4. Using a 5/16” wrench, loosen small inside screw nut on capillary tube. Figure 2-6.
5. Using a 11/16” crows-foot, remove the larger nut securing the capillary tube to the pot. Figure 2-7.
6. Remove the two screws securing the high limit guard and Figure 2-7 remove guard. Figure 2-8
7. Straighten the capillary tube inside the frypot, and pull the capillary tube through the frypot, from behind the control panel. Remove the defective high limit from the control panel area.
8. Replace new high limit in reverse order.
Figure 2-8
To avoid electrical shock or other injury, run the
capillary line under and away from all electrical power wires and terminals. The tube must never
be in such a position where it could accidentally touch the electrical power terminals.
1003 2-3
Model OFE/OFG/OEA/OGA-341, 342
2-4. COMPLETE CONTROL Should the control board become inoperative, follow these PANEL REPLACEMENT
instructions for replacing the board.
1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move the
power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
2. Remove the two screws securing the control panel and lift out. Figure 2-9 Figure 2-9.
3. Unplug the wire connectors going to the control panel. Figure 2-10.
4. Remove transformer(s) from control panel. They must be installed on the replacement panels.
5. Install new control panel in reverse order.
When plugging connectors onto new control panel, be sure the
connectors are inserted onto all of the pins, and that the connectors are not forced onto the pins backwards. If not Figure 2-10 connected properly, damage to the board could result.
2-5. POWER SWITCH
1. Remove electrical power supplied to fryer.
To avoid electrical shock or property damage, move the power switch to OFF and disconnect main circuit
breaker, or unplug cord at wall receptacle.
2. Remove control panel.
3. Label and remove wires from the switch. With test instrument Figure 2-11 check across the terminals of the switch with switch in the on position, and the circuit should be closed. In the off position, the circuit should be open. If the switch checks defective, replace by continuing with this procedure. Figure 2-11.
2-4 504
Model OFE/OFG/OEA/OGA-341, 342
2-5. POWER SWITCH (Continued)
in on tabs on the switch to remove from panel. Figure 2-12.
5. Replace with new switch, and reconnect wires to switch.
6. Replace the control panel.
Figure 2-12
4. With control panel removed, and the wires off the switch, push
2-6. TEMPERATURE PROBE The temperature probe relays the actual shortening temperature
REPLACEMENT (Gas) to the control board. If it becomes disabled, “E06” shows in the
display. Also, if the shortening temperature is out of calibration more than 10°F or C°, the probe should be replaced. An Ohm check can be performed also. See chart below.
1. Remove electrical power supplied to the fryer.
Figure 2-13
To avoid electrical shock or property damage, move the
power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
2. Drain the shortening from the frypot.
3. Remove the control panel and heat shield from control area. Figure 2-13.
4. Using a ½ inch wrench, remove the nut on the compression Figure 2-14 fitting. Figure 2-14.
806 2-5
Model OFE/OFG/OEA/OGA-341, 342
2-6. TEMPERATURE PROBE 5. Remove the probe from the frypot, and disconnect wire REPLACEMENT (GAS) connector from the control panel. Figure 2-15. (Continued)
6. Place the nut and new ferrule on the new probe and insert the probe into the compression fitting until it extends one (1) inch (2.54cm) into the frypot. Figure 2-16.
7. Tighten hand tight and then a half turn with wrench.
Figure 2-15
Excess force will damage probe.
8. Connect new probe to PC board and replace control panel.
9. Replace shortening, and turn power on to check out fryer.
Figure 2-16
2-7. TEMPERATURE PROBE The temperature probe relays the actual shortening temperature
REPLACEMENT (Gas) to the control board. If it becomes disabled, “E06” shows in the
REPLACEMENT display. Also, if the shortening temperature is out of calibration (ELECTRIC) more than 10°F or C°, the probe should be replaced. An Ohm check
can also be performed. See chart on page 2-5.
1. Remove electrical power supplied to the fryer.
To avoid electrical shock or property damage, move the
power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
2. Drain the shortening from the frypot.
Figure 2-17 3. Remove screws securing rear cover of fryer, and remove rear cover. Figure 2-17.
2-6 1209
Model OFE/OFG/OEA/OGA-341, 342
2-7. TEMPERATURE PROBE 4. Using a ½ inch wrench, remove the nut on the compression REPLACEMENT (ELECTRIC) (Continued)
fitting. Figure 2-18.
5. Remove the probe from the frypot, and disconnect probe.
6. Place the nut and new ferrule on the new probe and insert the probe into the compression fitting until it extends one (1) inch (2.54cm) into the frypot.
7. Reconnect new probe onto wires, replace rear cover, and fryer Figure 2-18 is now ready for use.
2-8. FLAME SENSOR/
PILOT / IGNITOR ASSEMBLY (GAS)
The Henny Penny open fryer (gas) has electronic spark ignition
that lights a standing pilot. The gap between the spark electrode
and the pilot hood should be1/8 of an inch (3.18 mm). The flame sensor recognizes the pilot flame and allows gas to continue to the pilot. The flame sensor must send a minimum of two (2) micro amps to the ignition module. The pilot flame should be split in two by the flame sensor, causing the flame sensor to be bright red in color.
1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move the
power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
TO AVOID PERSONAL INJURY OR PROPERTY
DAMAGE, BEFORE STARTING THIS PROCEDURE, MOVE THE MAIN POWER SWITCH TO THE OFF POSITION. DISCONNECT THE MAIN CIRCUIT BREAKERS AT THE CIRCUIT BREAKER BOX OR UNPLUG SERVICE CORD FROM WALL RECEPTACLE. TURN OFF THE MAIN GAS SUPPLY TO THE FRYER AND DISCONNECT AND CAP THE MAIN SUPPLY LINE TO FRYER, OR POSSIBLE EXPLOSION COULD RESULT.
1003 2-7
Model OFE/OFG/OEA/OGA-341, 342
2-8. FLAME SENSOR/ PILOT / IGNITOR ASSEMBLY (Gas) (Continued)
2. Remove the control panel and heat shield from control area.
Figure 2-19.
Figure 2-19
3. Disconnect the flame sense wire from ignition module. Figure 2-20.
Figure 2-20
4. Using a 7/16” wrench, loosen the nut on the pilot tube and pull tube from assembly. Figure 2-21.
Figure 2-21
5. Remove the two screws securing the assembly and pull assembly from unit. Figure 2-22.
6. Now the flame sensor or or pilot assembly can be removed from bracket.
Figure 2-22
2-8 1003
Model OFE/OFG/OEA/OGA-341, 342
2-9. IGNITION MODULE During normal operation, the ignition modules send 24 volts to the ignitors and gas valve. If a module does not sense a pilot flame, the module starts the ignition process again. But, if a pilot light goes out for longer that 10 seconds, or it goes out 3 times within 10 seconds, the module keeps the 24 volts from reaching the gas valve. The burners shut down.
1. Remove electrical power supplied to the unit.
To avoid electrical shock or property damage, move the
power switch to OFF and disconnect main circuit breaker, or unplug cord at wall receptacle.
Figure 2-23 2. Remove the control panel and heat shield from control area.
Figure 2-23.
3. Using a 3/8 inch socket, remove the two nuts securing the module. Figure 2-24.
Figure 2-24
4. Label and remove the wires at module. Figure 2-25.
5. Install new module in reverse order.
Figure 2-25
1003 2-9
Loading...
+ 21 hidden pages