These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING,CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manuals that may
apply to the product.
DANGER− Immediate hazards which will result in
severe personal injury or death.
WARNING − Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
!
The signal word CAUTION is used throughout this
manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
INTRODUCTION2...............................
LOCATION2....................................
HEATER PACKAGES2...........................
AIR DUCTS7...................................
ELECTRICAL CONNECTIONS7..................
REFRIGERANT TUBING10........................
REFRIGERANT FLOW−CONTROL DEVICE10......
REFRIGERANT METERING DEVICE11.............
CONDENSATE DRAINS11........................
ACCESSORIES12................................
SEQUENCE OF OPERATIONS13..................
START−UP PROCEDURE13......................
CARE AND MAINTENANCE13.....................
AIRFLOW PERFORMANCE TABLES14.............
R−410A QUICK REFERENCE GUIDE16............
!
PERSONAL INJURY, AND/OR PROPERTY DAMAGE
HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons could
result in equipment malfunction, property damage,
personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test
instruments.
Installation must conform with local building codes and
with the National Electrical Code NFPA70 current edition.
WARNING
496 01 5503 00 4/11/17Specifications are subject to change without notice.
Models FEM4X, FEM4P, and REM4X are for R−410A
refrigerant and can be used for upflow, horizontal left or
right, and downflow applications (accessory kit required for
downflow).
FEM4P models are available for system sizes 1−1/2 − 4 tons
(18,000 − 48,000 BTUH) nominal cooling capacity. FEM4P
use a refrigerant piston metering device with an ECM.
FEM4X models are available for system sizes 1−1/2 − 5 tons
(18,000 − 60,000 BTUH) nominal cooling capacity. All
models use an ECM motor and have a factory−installed and
appropriately sized hard shut−off TXV metering device and
are for R−410A refrigerant ONLY.
REM4X models are available for system sizes 1−1/2
through 5 tons (18,000 − 60,000 BTUH) nominal cooling
capacity. All models use an ECM motor and have a
factory−installed and appropriately sized hard shut−off
R−410A TXV metering device used for R−410A refrigerant
ONLY.
All models require a field supplied air filter. Factory approved
electric heater packages are available in sizes 5kW through
30kW. See Product Specification literature for available
accessory kits.
LOCATION
Select the best position which suits the installation site
conditions. The location should provide adequate structural
support, space in the front of the unit for service access,
clearance for return air and supply duct connections, space
for refrigerant piping connections and condensate drain line
connections. If heaters are being installed make sure
adequate clearance is maintained from supply duct work.
Nuisance sweating may occur if the unit is installed in a high
humidity environment with low airflow. On these installations a
wrap of 2” (51mm) fiberglass insulation with a vapor barrier is
recommended.
NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote filter
is recommended. Refer to ACCA Manual D for remote filter
sizing.
See Clearances
REQUIRED CLEARANCES − ALL MODELS inches
(mm)
No
Heaters
With
Heaters
From Supply Duct0
From First 3 feet of Supply Duct to
From Supply Duct to Combustibles
All Sides0
All Sides0
Combustibles
after 3 feet
1 (25)
0
HEATER PACKAGES
Factory approved, field installed, UL listed heater packages
are available from the equipment supplier. See unit rating
plate for a list of factory approved heaters. Heaters that are
not factory approved could cause damage which would not
be covered under the equipment warranty.
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall.
Allow space for wiring, piping, and servicing unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property
damage.
A field fabricated auxiliary drain pan, with a separate drain
is REQUIRED for all installations over a finished living
space or in any area that may be damaged by overflow
from a restricted main drain pan. In some localities, local
codes require an auxiliary drain pan for ANY horizontal
installation.
Figure 1Modular Unit Assembly
CAUTION
!
FIRE HAZARD
Failure to maintain proper clearances could result in
personal injury, death, and/or property damage.
When heaters are installed, maintain clearances from combustible materials as specified on unit rating plate. Do not
use plastic lined or combustible flexible ducting within 36
inches of the supply end of the fan coil.
2496 01 5503 00
WARNING
2 SCREWS
REAR CORNER
BRACKET
Specifications are subject to change without notice.
If return air is to be ducted through a floor, set unit on floor
over opening and use 1/8 to 1/4 inch thick (3 to 6 mm thick)
MODELA
fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut
opening per dimensions shown in Figure 2. A
field−supplied bottom closure is required.
B. MODULAR UNITS
FEM4P2400AL12” (305mm)
ALL 30
FEM4X2400CL
REM4X2400BL
FEM4X6000B and REM4X6000B fan coils are two−piece
modular units. This allows for modular units to be
disassembled and components moved separately to
installation area for reassembly. This process
accommodates small scuttle holes and limiting entrances to
installation sites (Figure 1).
Figure 2Upflow Installation
POWER ENTRY
OPTIONS
FRONT SERVICE CLEARANCE
18 − 48 models = 21” (533 mm)
60 model = 24” (610 mm)
A−COIL
UNITS
SLOPE COIL UNITS
1812” (305mm)
17” (432mm)
3617” (432mm)
FIELD SUPPLIED
SUPPLY DUCT
LOW VOLT
ENTRY
OPTIONS
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
1½”
19” (483mm)
2½”
(64mm)
FIELD MODIFIED
SIDE RETURN
A
LOCATION FOR
SLOPE COIL
UNITS ONLY
FIELD SUPPLIED
RETURN PLENUM
496 01 5503 003
Specifications are subject to change without notice.
Failure to follow this caution may result in product or
property damage.
The conversion of the fan coil to downflow requires
special procedures for the condensate drains on both
A−coil and Slope−coil units. The vertical drains have an
overflow hole between the primary and secondary drain
holes. This hole is plugged for all applications except
downflow, and must be used for downflow.
Failure to follow instructions could result in personal injury
or product and property damage.
!WARNING
STRUCTURAL DAMAGE
Failure to follow this warning could result in personal
injury or death, or property damage.
Combustible floor base is required when installing in a
downflow application with electric heat strips.
Structural damage could occur if manufacturer’s
downflow base accessory kit is not use when installing
in a downflow application.
In this application, field conversion of the evaporator coil is
required using accessory Downflow Kit along with an
accessory Base Kit. Set unit on floor over opening and use
1/8” to 1/4” thick fireproof resilient gasket between duct, unit,
and floor. Refer to installation instructions packaged with
accessory kit. See Product Specification literature for kit
part numbers.
During the conversion process, remove the plastic cap
covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the
vertical pan fitting to door joint to retain low air leak
performance of the unit.
NOTE: Gasket kit number (EBAC01GSK) is also required
for all downflow applications to maintain low air leak/low
sweat performance.
D. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up or
down. Access panels must only face to the side.
FEM4X, FEM4P, and REM4X models are factory built for
horizontal left installation (refer to Figure 3 and Figure 4).
They can be field converted to horizontal right (accessory
Gasket Kit required, see Product Specification literature for
part number). Refer to Figure 5 and Figure 6.
NOTE: When suspending unit from ceiling, dimples in
casing indicate suitable location of screws for mounting
metal support straps (refer to Figure 3).
NOTE: For optimum condensate drainage performance in
horizontal installations, unit should be leveled along its
length and width.
Figure 3
LOW VOLT
ENTRY
OPTIONS
Slope Coil In Horizontal Left Application (FEM4X, FEM4P, REM4X factory configuration)
A−COIL
HORIZONTAL LEFT
FIELD
SUPPLIED
HANGING
STRAPS
SECONDARY
DRAIN
SECONDARY
DRAIN
FRONT SERVICE CLEARANCE
(FULL FACE OF UNIT)
18 − 48 models = 21” (533mm)
60 model = 24” (610mm)
1¾” (45mm)
FILTER ACCESS
CLEARANCE
PRIMARY
DRAIN
POWER
ENTRY
OPTIONS
4496 01 5503 00
PRIMARY
DRAIN
Specifications are subject to change without notice.
A−Coil in Horizontal Left Application (FEM4X, FEM4P, REM4X factory configuration)
A
COIL
BRACKET
COIL
SUPPORT
B
C
BRACKET
HORIZONTAL
DRAIN PAN
AIR SEAL
ASSEMBLY
REFRIGERANT
CONNECTIONS
HORIZONTAL LEFT
RAIL
DRAIN PAN
SUPPORT
BRACKET
COIL
PRIMARY DRAIN
SECONDARY DRAIN
HORIZONTAL LEFT
Horizontal Right Conversion of Units With Slope Coils
1. Remove blower and coil access panel and fitting
panel (refer to Figure 5).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
5. Attach coil to casing flange using coil mounting screw
previously removed.
6. Align holes with tubing connections and condensate
pan connections, and reinstall access panels and
fitting panel. After brazing, make sure liquid and
suction tube grommets are in place to prevent air
leaks and cabinet sweating.
4. Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to
Figure 5).
Figure 5Conversion for Horizontal Right Applications − Slope Coil
COIL SUPPORT RAIL
COIL MOUNTING
SCREW
BLOWER
ASSEMBLY
SLOPE COIL
DRAINPAN
496 01 5503 005
REFRIGERANT
CONNECTIONS
Specifications are subject to change without notice.
1. Remove blower and coil access panel and fitting
panel (refer to Figure 6).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to
Figure 6).
5. Remove horizontal drain pan support bracket from
coil support rail on left side of unit and reinstall on coil
support rail on right side of unit.
6. Convert air−seal assembly for horizontal right (refer
to Figure 6).
a. Remove air−seal assembly from coil by removing 4
screws.
b. Remove coil drip flanges from A−coil and reinstall
on right side of coil (same side as horizontal drain
pan).
c. Remove filler plate (A) and install air splitter (B) in
place of filler plate.
d. Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket
on each corner of vertical pan engages coil support
rails.
9. Reinstall 2 snap−in clips to correctly position and
secure coil assembly in unit. Be sure clip with large
offsets is used on right side of unit to secure
horizontal pan.
10. Remove 2 oval coil access panel plugs and reinstall
into holes on left side of coil access panel and fitting
panel.
11. Remove insulation knockouts on right side of coil
access panel.
12. Reinstall access fitting panels, aligning holes with
tubing connections and condensate pan
connections. Be sure to reinstall metal clip between
fitting panel and vertical condensate pan.
13. After brazing, make sure liquid and suction tube
grommets are in place to prevent air leaks and
cabinet sweating.
Figure 6Conversion for Horizontal Right Applications − A−Coil
A
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
REFRIGERANT
CONNECTIONS
AIR SEAL
ASSEMBLY
HORIZONTAL
RIGHT
APPLICATION
B
C
6496 01 5503 00
Specifications are subject to change without notice.
1. Fan coil unit must be secured to the structure using
field−supplied hardware.
2. Allow a minimum of 24 inches (610mm) clearance
from access panels.
3. Recommended method of securing for typical
applications:
a. If fan coil is away from wall, attach pipe strap to top
of fan coil using No. 10 self tapping screws. Angle
strap down and away from back of fan coil, remove
all slack, and fasten to wall stud of structure using
5/16” lag screws. Typical both sides of fan coil.
b. If fan coil is against wall, secure fan coil to wall stud
using 1/8” (3mm) wide right−angle brackets. Attach
brackets to fan coil using No. 10 self tapping screws
and to wall stud using 5/16” lag screws (refer to
Figure 7).
Figure 7
Mobile Home or Manufactured
Housing Applications
4” (102mm) MAX
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
(TYPICAL BOTH SIDES)
OR
UNIT AGAINST WALL
1/8” (3mm) INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
Duct Work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and
10 feet of main duct before first branch takeoff may require
internal acoustical insulation lining. As an alternative,
fibrous duct work may be used if constructed and installed in
accordance with the latest edition of SMACNA construction
standard on fibrous glass ducts. Both acoustical lining and
fibrous duct work shall comply with National Fire Protection
Association as tested by UL Standard 181 for Class 1 air
ducts.
ELECTRICAL CONNECTIONS
FEM4X, FEM4P, and REM4X Fan Coil models do not have a
printed circuit board (PCB), they have a low voltage circuit
protective fuse (3 amp) inline on the wire harness. Speed
selections are made at the fan motor with the Blue wire. The
motor is pre−programmed with the time−delay circuit on some
of the speed taps. (See Page 9, Section D)
Before proceeding with electrical connections, make certain
that supply voltage, frequency, phase, and circuit ampacity are
as specified on the unit rating plate. See unit wiring label for
proper field high and low voltage wiring.
!
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, select a
location where drill and fasteners will not contact
electrical or refrigeration components.
WARNING
DOWN FLOW
BASE KIT
SECURE UNIT TO FLOOR
ANGLE BRACKET OR PIPE STRAP
4” (102mm) MAX
AIR DUCTS
Connect supply−air duct over the outside of 3/4” flanges
provided on supply−air opening. Secure duct to flange using
proper fasteners for type of duct used, and seal duct−to−unit
joint.
It is a recommendation, but not a requirement, to use flexible
connections between ductwork and unit to prevent
transmission of vibration. When electric heater is installed,
use heat−resistant material for flexible connector between
duct work and unit at discharge connection. Duct work
passing through unconditioned space must be insulated and
covered with vapor barrier.
Make all electrical connections in accordance with the NEC
and any local codes or ordinances that may apply. Use
copper wire only. The unit must have a separate branch
electric circuit with a field−supplied disconnect switch
located within sight of and readily accessible from the unit.
NOTE: When a pull−out type disconnect is removed from
the unit, only the Load side of the circuit is de−energized.
The Line side remains live until the main (remote)
disconnect is turned off.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Turn off the main (remote) disconnect device before
working on incoming (field) wiring.
Incoming (field) wires on the line side of the disconnect
found in the fan coil unit remain live, even when the
pull−out is removed. Service and maintenance to
incoming (field) wiring cannot be performed until the main
disconnect switch (remote to the unit) is turned off.
496 01 5503 007
Specifications are subject to change without notice.
Fan Coils installed without electric heat require the use of a
factory−authorized Power Plug Kit (accessory part number
EBAC01PLG). This kit provides the electrical connections
necessary to supply the unit with 208/230V power when
electric heat is not present. For units without electric heat:
1. Connect 208/230V power leads from field disconnect
to yellow and black stripped leads on Power Plug
(accessory part number EBAC01PLG).
2. Connect ground wire to unit ground lug.
3. When installing an electric heater, remove and
discard power plug (if equipped) from fan coil and
connect male plug from heater to female plug from
unit wiring harness. (See Electric Heater Installation
Instructions.)
B. 24V CONTROL SYSTEM
Connection to Unit
Wire low−voltage in accordance with wiring label on the
blower (also refer to Figure 8 through Figure 13). Use 18
AWG color−coded, insulated (35 ° C minimum) wire to make
the low−voltage connections between the thermostat, the
unit, and the outdoor equipment. If the thermostat is located
more than 100 feet from the unit (as measured along the low
voltage wire), use 16 AWG color−coded, insulated (35 ° C
minimum) wire. All wiring must be NEC Class 1 and must be
separated from incoming power leads. Refer to outdoor unit
wiring instructions for additional wiring recommendations.
Heater Staging
The controls are factory circuited for single−stage operation
(refer to Figure 9). When 2 stages are desired, cut W3 at
the W2 wire nut, strip, and reconnect according to the
thermostat kit instruction (refer to Figure 11− Outdoor
thermostat optional). When 3 stages are desired, cut the W2
wire nut off and discard. Strip W2, W3, and E, and reconnect
according to the thermostat kit instructions (refer to
Figure 12 − Outdoor thermostats optional).
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
product operation.
If W2, W3, and E on any 3−stage heater (18, 20, 24, or
30kW) are individually connected − as with outdoor
thermostats or any other situation − emergency heat relay
must be used. If relay is not used, blower may not operate
when heaters are energized.
Manufactured Housing
In manufactured housing applications, the Code of Federal
Regulations, Title 24, Chapter XX, Part 3280.714 requires
that supplemental electric heat be locked out at outdoor
temperatures above 40_F (4_C), except for a heat pump
defrost cycle. Refer to Figure 13 for typical low−voltage
wiring with outdoor thermostat.
Figure 8
THERMOSTAT
Figure 9
THERMOSTAT
Wiring Layout − Air Conditioning
Unit (Cooling Only)
FAN COIL
(CONTROL)
WHT
RED
GRY
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
AIR COND.
R
G
W
Y
Wiring Layout − Air Conditioning
Unit (Cooling and 1−Stage Heat)
FAN COIL
(CONTROL)
RED
GRY
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
R
G
W
WHT
Y
C
Y
AIR COND.
C
Y
Wiring Layout − Heat Pump Unit
Figure 10
(Cooling and 2−Stage Heat with No
Outdoor Thermostat)
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN COIL
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
R
G
C
W
2
W
3
E
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
8496 01 5503 00
Specifications are subject to change without notice.
Transformer is factory wired for 230V operation. For 208V
applications, disconnect the black wire from the 230V terminal
on transformer and connect it to the 208V terminal (refer to
Figure 14).
Figure 14Transformer Connections
SECONDARY
BROWN
RED
C
208
230
YELLOW
BLACK
PRIMARY
C. GROUND CONNECTIONS
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground
could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground
in order to minimize potential for personal injury or death
if an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground
wire must be used.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs
provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed
selected is not lower than the minimum fan speed indicated.
FEM4X, FEM4P, and REM4X models: fan speed is
selected at the motor connector. Units with or without
electric heaters require a minimum CFM. Refer to the unit
wiring label to ensure that the fan speed selected is not lower
than the minimum fan speed indicated.
SPEED TAP SELECTION AT MOTOR CONNECTOR
Tap 1Low90 sec off delay
Tap 2Medium90 sec off delay
Tap 3High90 sec off delay
Tap 4Electric Heat †0 sec off delay
Tap 5Max ‡0 sec off delay
† Electric heat airflow is same CFM as Tap 3, but with 0
sec off delay.
‡ For high static applications, see Airflow Performance
Tables for max airflow.
496 01 5503 009
Specifications are subject to change without notice.
To change motor speeds disconnect the BLUE fan lead from
motor connector terminal #2 (factory default position) and
move to desired speed tap; 1, 2, 3, or 5 (see Figure 15).
Speed taps 1, 2, and 3 have a 90 second blower off time
delay pre−programmed into the motor. Speed tap 4 is used
for electric heat only (with 0 second blower time delay) and
the WHITE wire should remain on tap 4. Speed tap 5 is used
for high static applications, but has a 0 second blower time
delay pre−programmed into the motor (see Airflow
Performance Tables for actual CFM for each tap). Also, see
Figure 15 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap
should be used to reduce possibility of water being blown off
coil.
Figure 15
1 2 3 4 5
Speed Taps may be located on motor,
or on plug close to motor.
FEM4X, FEM4P, REM4X
Motor Speed Selection
2. Insert tube into sweat connection on unit until it
bottoms.
3. Braze connection using silver bearing or non−silver
bearing brazing materials. Do not use solder
(materials which melt below 800_F / 427_C). Consult
local code requirements.
4. Evacuate coil and tubing system to 500 microns using
deep vacuum method.
Size and install refrigerant lines according to information
provided with outdoor unit. Route refrigerant lines to the fan
coil in a manner that will not obstruct service access to the
unit or removal of the filter.
1. Find the liquid tube grommet in the small−parts bag
and slide it onto the liquid refrigerant line (field
line−set).
2. Remove the lower door. Remove the tubing plate (with
suction tube grommet) and slide the plate with
grommet onto the refrigerant lines (field line−set),
away from braze joints.
3. Remove rubber plugs from coil stubs using a pulling
and twisting motion. Hold coil stubs steady to avoid
bending or distorting.
4. Wrap TXV and nearby tubing with a heat−sinking
material such as a wet cloth.
5. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
6. Braze using a Sil−Fos or Phos−copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate
back into place and position grommets around suction
and liquid tubes to ensure air seal.
1 2 3 4 5
CLGN
REFRIGERANT TUBING
Refrigerant Tubing Connection and Evacuation
Use accessory tubing package or field−supplied tubing of
refrigerant grade. Suction tube must be insulated. Do not
use damaged, dirty, or contaminated tubing because it may
plug refrigerant flow−control device. ALWAYS evacuate the
coil and field−supplied tubing to 500 microns before opening
outdoor unit service valves.
Units have sweat suction and liquid tube connections. Make
suction tube connection first.
1. Cut tubing to correct length.
10496 01 5503 00
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or
property damage.
Wrap a wet cloth around rear of fitting to prevent
damage to piston assembly or TXV and
factory−made joints.
REFRIGERANT FLOW−CONTROL
DEVICE
L11S018
Specifications are subject to change without notice.
FEM4P Models:
These units come equipped with a factory installed Piston
metering device with Teflon ring
required, check piston size shown on indoor unit rating plate
to see if it matches required outdoor piston size. The outdoor
piston size will be found on the outdoor unit rating plate,
product data or installation instructions depending on the
model shown on outdoor unit rating plate. If the fan coil
piston does not match, replace indoor piston with correct
outdoor piston. With some outdoor units a piston is shipped
with outdoor unit.
When changing piston, use a back−up wrench. Hand tighten
hex nut, then tighten with wrench 1/2 turn. Do not exceed 30
ft−lbs.
NOTE: The indoor piston contains a Teflon ring (or seal)
which is used to seat against the inside of distributor body,
and must be installed properly to ensure proper seating in
the direction for cooling operation.
Always use outdoor units designed to match indoor fan coil
applications.
REFRIGERANT METERING DEVICE
FEM4X, REM4X Models:
These Fan Coils have a factory installed hard shut−off TXV
designed only for use with R−410A refrigerant. Use only with
outdoor units designed for R−410A.
TXV is factory set and not field adjustable.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
This Fan Coil has a hard shut−off TXV metering device.
A compressor Hard Start Kit is REQUIRED in all
applications where the matching outdoor unit has a
single−phase reciprocating compressor.
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If using a TXV in conjunction with a single−phase reciprocating compressor, a compressor start capacitor and
relay are required. Consult outdoor unit pre−sale literature for start assist kit part number.
Figure 16Refrigerant Flow−Control Device
BRASS
HEX NUT
CAUTION
CAUTION
TEFLON SEAL
TEFLON RING
PISTON
FLOW IN
COOLING
PISTON
RETAINER
STRAINER
DISTRIBUTOR
BRASS
HEX BODY
CONDENSATE DRAINS
Unit is provided with primary and secondary 3/4” (19mm)
NPT drain connections. Refer to Figure 2, Figure 3,
Figure 4, Figure 5, and Figure 6 to identify the primary and
secondary locations. To prevent property damage and
achieve optimum drainage performance, BOTH primary
and secondary drain lines should be installed and include
properly sized condensate traps (refer to Figure 17).
Factory approved condensate traps are available
(accessory part number EBAC01CTK).
To connect drainlines, the drain connection knock−outs
must be removed. Use a knife to start the opening near the
tab and using pliers, pull the tab to remove the knock−out.
Clean the edge of the opening if necessary. After drain
fittings are installed, caulk the seam between the fitting and
the cover to retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic
condensate pan. Do not over−tighten. Finger−tighten plus
1−1/2 turns. Use pipe dope to ensure proper seal.
Install traps in the condensate lines as close to the coil as
possible (refer to Figure 19), but avoid blocking filter access
panel.
Install drain lines below the bottom of the drain pan and pitch
the drain lines down from the coil at least 1/4 inch per foot of
run (6mm per 0.3m). Horizontal runs over 15 feet (5m) long
must also have an anti−siphon air vents (stand pipes),
installed ahead of the horizontal runs. Extremely long
horizontal runs may require oversized drain lines to
eliminate air trapping.
Route primary drain line to the outside or to a floor drain.
Check local codes before connecting to a waste (sewer)
line.
Route the secondary drain line to a place in compliance with
local installation codes where it will be noticed when unit is
operational. Condensate flowing from secondary (overflow)
drain indicates a plugged primary drain − unit requires
service or water damage will occur.
Prime all traps, test for leaks, and insulate in areas where
sweating of the traps and drain lines could potentially cause
water damage. Consult local codes for additional
requirements or precautions.
If a gravity drain cannot be used, install a condensate pump.
Install the pump as close to the indoor section as possible.
!
PRODUCT or PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or
property damage.
Use only full size P−traps in the condensate line (refer to
Figure 17). Shallow, running traps are inadequate and
DO NOT allow proper condensate drainage (refer to
Figure 18).
CAUTION
496 01 5503 0011
Specifications are subject to change without notice.
Connect humidifier and humidistat to fan coil unit as shown
in Figure 20 and Figure 21.
Figure 20
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN HUMIDIFIER
Wiring Layout of Humidifier to Heat
Pump
WHT
FAN COIL
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
R
G
C
W
W
E
2
3
RELAY
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 19Condensate Drain
SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD−SUPPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD−SUPPLIED TRAP OF PROPER DEPTH.
STANDARD P−TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
FILTER
ACCESS
PANEL
115VM
Figure 21
THERMOSTAT
R
G
W
Y
HUMIDISTAT
Wiring Layout of Humidifier to Fan
Coil with Electric Heat
FAN COIL
(CONTROL)
RED
GRY
WHT
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
HUMIDISTAT
AIR COND.
C
Y
12496 01 5503 00
115V
Specifications are subject to change without notice.
Thermostat closes R to G. G sends signal direct to motor
which completes circuit to indoor blower motor. When G is
de−energized, there is a 90 second off delay before indoor
blower motor stops.
B. COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump
only). G sends signal direct to motor, which completes circuit to
indoor blower motor. When G is de−energized, there is a 90
second off delay before indoor blower motor stops.
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G sends signal direct
to motor, which completes circuit to indoor blower motor.
When G is de−energized, there is a 90 second off delay before
indoor blower motor stops.
D. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G
energizes indoor blower motor. W energizes electric heat
relay(s) which completes circuit to heater element(s). When
W is de−energized, electric heat relay(s) open, turning off
heater elements. When G is de−energized, the indoor
blower motor is de−energized and stops.
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat
relay(s) which completes circuit to heater element(s). W
also energizes the indoor blower motor. When W is
de−energized, electric heat relay(s) opens and the indoor
blower motor is de−energized and stops.
START−UP PROCEDURE
Refer to outdoor unit Installation Instructions for system
start−up instructions and refrigerant charging method
details.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified
service technician. Consult the servicing dealer for
recommended frequency.
Between visits, the only consumer service recommended or
required is air filter maintenance and condensate drain
operation.
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable type filters should be replaced.
Reusable type filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Install filters with the
arrows on the side pointing in the direction of air flow.
Condensate Drain
During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit
performance and/or product damage.
Never operate unit without a filter. Factory authorized
filter kits must be used when locating the filter inside the
unit. For those applications where access to an internal
filter is impractical, a field−supplied filter must be installed
in the return duct system.
CAUTION
496 01 5503 0013
Specifications are subject to change without notice.
1. Airflow based upon dry coil at 230v with factory−approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes
4200 through 6000). For FEM4X, FEM4P, and REM4X models, airflow at 208 volts is approximately the same as 230 volts because the ECM motor is
a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 4200 − 6000 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 4800 − 6000 size could result in condensate blowing off coil or splashing out of drain pan.
Tap 3701660616581537499
Tap 2614569534486436398
Tap 1410350304261228203
Tap 5969936892835763676
Tap 4826795766743706660
Tap 3826795766743706660
Tap 2701660616581537499
Tap 1617592552507472420
Tap 5965920870823780740
Tap 4820783740680630575
Tap 3820783740680630575
Tap 2720655610555485450
Tap 1716600540495430328
Tap 511081090106510341009974
Tap 410261000969938899865
Tap 310261000969938899865
Tap 2909873842799762724
Tap 1825795757722674634
Tap 5130112761245121811761121
Tap 4122711911169114311051074
Tap 3122711911169114311051074
Tap 21087106210301001966930
Tap 110261000969938899865
Tap 5156015441507146414241358
Tap 4141913971358132012791239
Tap 3141913971358132012791239
Tap 2124912201184114210931052
Tap 1124212051158111010691026
Tap 5174317121679164216101574
Tap 4166916341599156415311499
Tap 3166916341599156415311499
Tap 2145214131377133913081271
Tap 1130012561221118211421101
Tap 5189718671836180817741736
Tap 4181717851757172416931655
Tap 3181717851757172416931655
Tap 2165716211589155715181474
Tap 1144314121377133212861243
0.100.200.300.400.500.60
TOTAL STATIC (inches water column)
14496 01 5503 00
Specifications are subject to change without notice.