HEIL FEM4X, FEM4P, REM4X Installation Instructions Manual

INSTALLATION INSTRUCTIONS
Fan Coils
FEM4X, FEM4P, REM4X
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
INTRODUCTION 2...............................
LOCATION 2....................................
HEATER PACKAGES 2...........................
AIR DUCTS 7...................................
ELECTRICAL CONNECTIONS 7..................
REFRIGERANT TUBING 10........................
REFRIGERANT FLOWCONTROL DEVICE 10......
REFRIGERANT METERING DEVICE 11.............
CONDENSATE DRAINS 11........................
ACCESSORIES 12................................
SEQUENCE OF OPERATIONS 13..................
STARTUP PROCEDURE 13......................
CARE AND MAINTENANCE 13.....................
AIRFLOW PERFORMANCE TABLES 14.............
R410A QUICK REFERENCE GUIDE 16............
!
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition.
WARNING
496 01 5503 00 4/11/17Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
INTRODUCTION
Models FEM4X, FEM4P, and REM4X are for R−410A refrigerant and can be used for upflow, horizontal left or right, and downflow applications (accessory kit required for downflow).
FEM4P models are available for system sizes 11/2 4 tons (18,000 48,000 BTUH) nominal cooling capacity. FEM4P use a refrigerant piston metering device with an ECM.
FEM4X models are available for system sizes 11/2 5 tons (18,000 60,000 BTUH) nominal cooling capacity. All models use an ECM motor and have a factoryinstalled and appropriately sized hard shutoff TXV metering device and are for R−410A refrigerant ONLY.
REM4X models are available for system sizes 1−1/2 through 5 tons (18,000 60,000 BTUH) nominal cooling capacity. All models use an ECM motor and have a factoryinstalled and appropriately sized hard shutoff R410A TXV metering device used for R410A refrigerant ONLY.
All models require a field supplied air filter. Factory approved electric heater packages are available in sizes 5kW through 30kW. See Product Specification literature for available accessory kits.
LOCATION
Select the best position which suits the installation site conditions. The location should provide adequate structural support, space in the front of the unit for service access, clearance for return air and supply duct connections, space for refrigerant piping connections and condensate drain line connections. If heaters are being installed make sure adequate clearance is maintained from supply duct work.
Nuisance sweating may occur if the unit is installed in a high humidity environment with low airflow. On these installations a wrap of 2” (51mm) fiberglass insulation with a vapor barrier is recommended.
NOTE: Internal filter can be accessed from separate filter door. If the filter can NOT be easily accessed, a remote filter is recommended. Refer to ACCA Manual D for remote filter sizing.
See Clearances
REQUIRED CLEARANCES ALL MODELS inches
(mm)
No
Heaters
With
Heaters
From Supply Duct 0
From First 3 feet of Supply Duct to
From Supply Duct to Combustibles
All Sides 0
All Sides 0
Combustibles
after 3 feet
1 (25)
0
HEATER PACKAGES
Factory approved, field installed, UL listed heater packages are available from the equipment supplier. See unit rating plate for a list of factory approved heaters. Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty.
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
A field fabricated auxiliary drain pan, with a separate drain is REQUIRED for all installations over a finished living space or in any area that may be damaged by overflow from a restricted main drain pan. In some localities, local codes require an auxiliary drain pan for ANY horizontal installation.
Figure 1 Modular Unit Assembly
CAUTION
!
FIRE HAZARD
Failure to maintain proper clearances could result in personal injury, death, and/or property damage.
When heaters are installed, maintain clearances from com­bustible materials as specified on unit rating plate. Do not use plastic lined or combustible flexible ducting within 36 inches of the supply end of the fan coil.
2 496 01 5503 00
WARNING
2 SCREWS
REAR CORNER BRACKET
Specifications are subject to change without notice.
BLOWER BOX
2 SCREWS
2 SCREWS
COIL BOX
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
A. UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4 inch thick (3 to 6 mm thick)
MODEL A
fireproof resilient gasket between duct, unit, and floor. Side return is a field option on slope coil models. Cut opening per dimensions shown in Figure 2. A fieldsupplied bottom closure is required.
B. MODULAR UNITS
FEM4P2400AL 12” (305mm)
ALL 30 FEM4X2400CL REM4X2400BL
FEM4X6000B and REM4X6000B fan coils are two−piece modular units. This allows for modular units to be disassembled and components moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites (Figure 1).
Figure 2 Upflow Installation
POWER ENTRY
OPTIONS
FRONT SERVICE CLEARANCE
18 48 models = 21” (533 mm)
60 model = 24” (610 mm)
ACOIL
UNITS
SLOPE COIL UNITS
18 12” (305mm)
17” (432mm)
36 17” (432mm)
FIELD SUPPLIED SUPPLY DUCT
LOW VOLT ENTRY OPTIONS
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
1½
19” (483mm)
” (64mm)
FIELD MODIFIED SIDE RETURN
A
LOCATION FOR SLOPE COIL UNITS ONLY
FIELD SUPPLIED RETURN PLENUM
496 01 5503 00 3
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
C. DOWNFLOW INSTALLATION
!
CAUTION
PRODUCT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both Acoil and Slopecoil units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, and must be used for downflow. Failure to follow instructions could result in personal injury or product and property damage.
! WARNING
STRUCTURAL DAMAGE
Failure to follow this warning could result in personal injury or death, or property damage.
Combustible floor base is required when installing in a downflow application with electric heat strips.
Structural damage could occur if manufacturer’s downflow base accessory kit is not use when installing in a downflow application.
In this application, field conversion of the evaporator coil is required using accessory Downflow Kit along with an
accessory Base Kit. Set unit on floor over opening and use 1/8 to 1/4 thick fireproof resilient gasket between duct, unit, and floor. Refer to installation instructions packaged with accessory kit. See Product Specification literature for kit part numbers.
During the conversion process, remove the plastic cap covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain low air leak performance of the unit.
NOTE: Gasket kit number (EBAC01GSK) is also required for all downflow applications to maintain low air leak/low sweat performance.
D. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up or down. Access panels must only face to the side.
FEM4X, FEM4P, and REM4X models are factory built for horizontal left installation (refer to Figure 3 and Figure 4). They can be field converted to horizontal right (accessory Gasket Kit required, see Product Specification literature for part number). Refer to Figure 5 and Figure 6.
NOTE: When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps (refer to Figure 3).
NOTE: For optimum condensate drainage performance in horizontal installations, unit should be leveled along its length and width.
Figure 3
LOW VOLT ENTRY OPTIONS
Slope Coil In Horizontal Left Application (FEM4X, FEM4P, REM4X factory configuration)
ACOIL
HORIZONTAL LEFT
FIELD SUPPLIED HANGING STRAPS
SECONDARY DRAIN
SECONDARY DRAIN
FRONT SERVICE CLEARANCE (FULL FACE OF UNIT) 18 48 models = 21” (533mm) 60 model = 24” (610mm)
1¾” (45mm) FILTER ACCESS CLEARANCE
PRIMARY DRAIN
POWER ENTRY OPTIONS
4 496 01 5503 00
PRIMARY DRAIN
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
Figure 4
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
ACoil in Horizontal Left Application (FEM4X, FEM4P, REM4X factory configuration)
A
COIL
BRACKET
COIL
SUPPORT
B C
BRACKET
HORIZONTAL
DRAIN PAN
AIR SEAL ASSEMBLY
REFRIGERANT
CONNECTIONS
HORIZONTAL LEFT
RAIL
DRAIN PAN
SUPPORT BRACKET
COIL
PRIMARY DRAIN
SECONDARY DRAIN
HORIZONTAL LEFT
Horizontal Right Conversion of Units With Slope Coils
1. Remove blower and coil access panel and fitting panel (refer to Figure 5).
2. Remove coil mounting screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
5. Attach coil to casing flange using coil mounting screw previously removed.
6. Align holes with tubing connections and condensate pan connections, and reinstall access panels and fitting panel. After brazing, make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down (refer to
Figure 5).
Figure 5 Conversion for Horizontal Right Applications Slope Coil
COIL SUPPORT RAIL
COIL MOUNTING SCREW
BLOWER ASSEMBLY
SLOPE COIL
DRAINPAN
496 01 5503 00 5
REFRIGERANT CONNECTIONS
Specifications are subject to change without notice.
PRIMARY DRAIN
SECONDARY DRAIN
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
Horizontal Right Conversion of Units With A−Coils
1. Remove blower and coil access panel and fitting panel (refer to Figure 6).
2. Remove coil mounting screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down (refer to Figure 6).
5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit.
6. Convert airseal assembly for horizontal right (refer to Figure 6).
a. Remove air−seal assembly from coil by removing 4
screws.
b. Remove coil drip flanges from A−coil and reinstall
on right side of coil (same side as horizontal drain pan).
c. Remove filler plate (A) and install air splitter (B) in
place of filler plate.
d. Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails.
9. Reinstall 2 snapin clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure horizontal pan.
10. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
11. Remove insulation knockouts on right side of coil access panel.
12. Reinstall access fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan.
13. After brazing, make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
Figure 6 Conversion for Horizontal Right Applications − A−Coil
A
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
REFRIGERANT
CONNECTIONS
AIR SEAL ASSEMBLY
HORIZONTAL RIGHT APPLICATION
B C
6 496 01 5503 00
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
E. MANUFACTURED HOUSING AND MOBILE HOME
APPLICATIONS
1. Fan coil unit must be secured to the structure using fieldsupplied hardware.
2. Allow a minimum of 24 inches (610mm) clearance from access panels.
3. Recommended method of securing for typical applications:
a. If fan coil is away from wall, attach pipe strap to top
of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16” lag screws. Typical both sides of fan coil.
b. If fan coil is against wall, secure fan coil to wall stud
using 1/8” (3mm) wide right−angle brackets. Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16” lag screws (refer to
Figure 7).
Figure 7
Mobile Home or Manufactured
Housing Applications
4” (102mm) MAX
SECURE FAN COIL TO STRUCTURE UNIT AWAY FROM WALL PIPE STRAP
(TYPICAL BOTH SIDES)
OR
UNIT AGAINST WALL
1/8” (3mm) INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
Duct Work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 feet of main duct before first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous duct work may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous duct work shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts.
ELECTRICAL CONNECTIONS
FEM4X, FEM4P, and REM4X Fan Coil models do not have a printed circuit board (PCB), they have a low voltage circuit protective fuse (3 amp) inline on the wire harness. Speed selections are made at the fan motor with the Blue wire. The motor is preprogrammed with the time−delay circuit on some of the speed taps. (See Page 9, Section D)
Before proceeding with electrical connections, make certain that supply voltage, frequency, phase, and circuit ampacity are as specified on the unit rating plate. See unit wiring label for proper field high and low voltage wiring.
!
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, select a location where drill and fasteners will not contact electrical or refrigeration components.
WARNING
DOWN FLOW BASE KIT
SECURE UNIT TO FLOOR ANGLE BRACKET OR PIPE STRAP
4” (102mm) MAX
AIR DUCTS
Connect supplyair duct over the outside of 3/4” flanges provided on supplyair opening. Secure duct to flange using proper fasteners for type of duct used, and seal ducttounit joint.
It is a recommendation, but not a requirement, to use flexible connections between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat−resistant material for flexible connector between duct work and unit at discharge connection. Duct work passing through unconditioned space must be insulated and covered with vapor barrier.
Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply. Use copper wire only. The unit must have a separate branch electric circuit with a fieldsupplied disconnect switch located within sight of and readily accessible from the unit.
NOTE: When a pull−out type disconnect is removed from the unit, only the Load side of the circuit is de−energized. The Line side remains live until the main (remote) disconnect is turned off.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn off the main (remote) disconnect device before working on incoming (field) wiring. Incoming (field) wires on the line side of the disconnect found in the fan coil unit remain live, even when the pullout is removed. Service and maintenance to incoming (field) wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off.
496 01 5503 00 7
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
A. LINE VOLTAGE CONNECTIONS
Fan Coils installed without electric heat require the use of a factoryauthorized Power Plug Kit (accessory part number EBAC01PLG). This kit provides the electrical connections necessary to supply the unit with 208/230V power when electric heat is not present. For units without electric heat:
1. Connect 208/230V power leads from field disconnect to yellow and black stripped leads on Power Plug (accessory part number EBAC01PLG).
2. Connect ground wire to unit ground lug.
3. When installing an electric heater, remove and discard power plug (if equipped) from fan coil and connect male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation Instructions.)
B. 24V CONTROL SYSTEM
Connection to Unit
Wire lowvoltage in accordance with wiring label on the blower (also refer to Figure 8 through Figure 13). Use 18 AWG colorcoded, insulated (35 ° C minimum) wire to make the low−voltage connections between the thermostat, the unit, and the outdoor equipment. If the thermostat is located more than 100 feet from the unit (as measured along the low voltage wire), use 16 AWG colorcoded, insulated (35 ° C minimum) wire. All wiring must be NEC Class 1 and must be separated from incoming power leads. Refer to outdoor unit wiring instructions for additional wiring recommendations.
Heater Staging
The controls are factory circuited for singlestage operation (refer to Figure 9). When 2 stages are desired, cut W3 at the W2 wire nut, strip, and reconnect according to the thermostat kit instruction (refer to Figure 11 Outdoor thermostat optional). When 3 stages are desired, cut the W2 wire nut off and discard. Strip W2, W3, and E, and reconnect according to the thermostat kit instructions (refer to
Figure 12 Outdoor thermostats optional).
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If W2, W3, and E on any 3stage heater (18, 20, 24, or 30kW) are individually connected as with outdoor thermostats or any other situation emergency heat relay must be used. If relay is not used, blower may not operate when heaters are energized.
Manufactured Housing
In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor
temperatures above 40_F (4_C), except for a heat pump defrost cycle. Refer to Figure 13 for typical low−voltage wiring with outdoor thermostat.
Figure 8
THERMOSTAT
Figure 9
THERMOSTAT
Wiring Layout Air Conditioning
Unit (Cooling Only)
FAN COIL
(CONTROL)
WHT
RED
GRY
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
AIR COND.
R
G
W
Y
Wiring Layout Air Conditioning
Unit (Cooling and 1Stage Heat)
FAN COIL
(CONTROL)
RED
GRY
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
R
G
W
WHT
Y
C
Y
AIR COND.
C
Y
Wiring Layout Heat Pump Unit
Figure 10
(Cooling and 2Stage Heat with No
Outdoor Thermostat)
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN COIL
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
R
G
C
W
2
W
3
E
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
8 496 01 5503 00
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
Wiring Layout Heat Pump Unit
Figure 11
(Cooling and 2Stage Heat with
One Outdoor Thermostat)
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN COIL
(CONTROL)
RED
GRY
BRN
WHT
VIO
E
BLU
R
G
C
W
2
ODTS
W
3
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
Wiring Layout Heat Pump Unit
Figure 12
(Cooling and 2Stage Heat with
Two Outdoor Thermostats)
THERMOSTAT
R
G
C
W
2
L
E
O
Y
C14 7C96 3
EMERGENCY HEAT RELAY
(CONTROL)
RED
GRY
BRN
WHT
FAN COIL
R
G
C
W
2
BLU
W
3
VIO
E
ODTS1
ODTS2
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
Wiring Layout Heat Pump Unit
Figure 13
(Cooling and 2Stage Heat for
Manufactured Housing)
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN COIL
(CONTROL)
R
G
C
W
2
W
3
E
ODTS
HEAT PUMP (CONTROL)
R
C
W
2
O
Y
Transformer Information
Transformer is factory wired for 230V operation. For 208V applications, disconnect the black wire from the 230V terminal on transformer and connect it to the 208V terminal (refer to
Figure 14).
Figure 14 Transformer Connections
SECONDARY
BROWN
RED
C
208
230
YELLOW
BLACK
PRIMARY
C. GROUND CONNECTIONS
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground in order to minimize potential for personal injury or death if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used.
NOTE: Use UL listed conduit and conduit connectors for connecting supply wire(s) to unit to obtain proper grounding. Grounding may also be accomplished by using grounding lugs provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated.
FEM4X, FEM4P, and REM4X models: fan speed is selected at the motor connector. Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated.
SPEED TAP SELECTION AT MOTOR CONNECTOR
Tap 1 Low 90 sec off delay
Tap 2 Medium 90 sec off delay
Tap 3 High 90 sec off delay
Tap 4 Electric Heat † 0 sec off delay
Tap 5 Max ‡ 0 sec off delay † Electric heat airflow is same CFM as Tap 3, but with 0 sec off delay. ‡ For high static applications, see Airflow Performance
Tables for max airflow.
496 01 5503 00 9
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
To change motor speeds disconnect the BLUE fan lead from motor connector terminal #2 (factory default position) and move to desired speed tap; 1, 2, 3, or 5 (see Figure 15). Speed taps 1, 2, and 3 have a 90 second blower off time delay preprogrammed into the motor. Speed tap 4 is used for electric heat only (with 0 second blower time delay) and the WHITE wire should remain on tap 4. Speed tap 5 is used for high static applications, but has a 0 second blower time delay preprogrammed into the motor (see Airflow Performance Tables for actual CFM for each tap). Also, see
Figure 15 for motor speed selection location. NOTE: In low static applications, lower motor speed tap
should be used to reduce possibility of water being blown off coil.
Figure 15
1 2 3 4 5
Speed Taps may be located on motor, or on plug close to motor.
FEM4X, FEM4P, REM4X
Motor Speed Selection
2. Insert tube into sweat connection on unit until it
bottoms.
3. Braze connection using silver bearing or non−silver
bearing brazing materials. Do not use solder (materials which melt below 800_F / 427_C). Consult local code requirements.
4. Evacuate coil and tubing system to 500 microns using
deep vacuum method.
Size and install refrigerant lines according to information provided with outdoor unit. Route refrigerant lines to the fan coil in a manner that will not obstruct service access to the unit or removal of the filter.
1. Find the liquid tube grommet in the smallparts bag
and slide it onto the liquid refrigerant line (field lineset).
2. Remove the lower door. Remove the tubing plate (with
suction tube grommet) and slide the plate with grommet onto the refrigerant lines (field line−set), away from braze joints.
3. Remove rubber plugs from coil stubs using a pulling
and twisting motion. Hold coil stubs steady to avoid bending or distorting.
4. Wrap TXV and nearby tubing with a heat−sinking
material such as a wet cloth.
5. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
6. Braze using a Sil−Fos or Phos−copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate
back into place and position grommets around suction and liquid tubes to ensure air seal.
1 2 3 4 5
CLGN
REFRIGERANT TUBING
Refrigerant Tubing Connection and Evacuation
Use accessory tubing package or field−supplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flowcontrol device. ALWAYS evacuate the coil and fieldsupplied tubing to 500 microns before opening outdoor unit service valves.
Units have sweat suction and liquid tube connections. Make suction tube connection first.
1. Cut tubing to correct length.
10 496 01 5503 00
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to piston assembly or TXV and factorymade joints.
REFRIGERANT FLOW−CONTROL DEVICE
L11S018
Specifications are subject to change without notice.
FEM4P Models:
These units come equipped with a factory installed Piston
metering device with Teflon ring
required, check piston size shown on indoor unit rating plate to see if it matches required outdoor piston size. The outdoor piston size will be found on the outdoor unit rating plate, product data or installation instructions depending on the model shown on outdoor unit rating plate. If the fan coil piston does not match, replace indoor piston with correct outdoor piston. With some outdoor units a piston is shipped with outdoor unit.
When changing piston, use a backup wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ftlbs.
NOTE: The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body,
!
CAUTION
. If a piston replacement REs
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
and must be installed properly to ensure proper seating in the direction for cooling operation.
Always use outdoor units designed to match indoor fan coil applications.
REFRIGERANT METERING DEVICE
FEM4X, REM4X Models:
These Fan Coils have a factory installed hard shutoff TXV designed only for use with R410A refrigerant. Use only with outdoor units designed for R−410A.
TXV is factory set and not field adjustable.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
This Fan Coil has a hard shut−off TXV metering device. A compressor Hard Start Kit is REQUIRED in all applications where the matching outdoor unit has a singlephase reciprocating compressor.
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper prod­uct operation. If using a TXV in conjunction with a singlephase recipro­cating compressor, a compressor start capacitor and relay are required. Consult outdoor unit presale litera­ture for start assist kit part number.
Figure 16 Refrigerant FlowControl Device
BRASS
HEX NUT
CAUTION
CAUTION
TEFLON SEAL
TEFLON RING
PISTON
FLOW IN COOLING
PISTON RETAINER
STRAINER
DISTRIBUTOR
BRASS HEX BODY
CONDENSATE DRAINS
Unit is provided with primary and secondary 3/4” (19mm) NPT drain connections. Refer to Figure 2, Figure 3, Figure 4, Figure 5, and Figure 6 to identify the primary and secondary locations. To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly sized condensate traps (refer to Figure 17). Factory approved condensate traps are available (accessory part number EBAC01CTK).
To connect drainlines, the drain connection knock−outs must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the knock−out. Clean the edge of the opening if necessary. After drain fittings are installed, caulk the seam between the fitting and the cover to retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic condensate pan. Do not overtighten. Fingertighten plus 11/2 turns. Use pipe dope to ensure proper seal.
Install traps in the condensate lines as close to the coil as possible (refer to Figure 19), but avoid blocking filter access panel.
Install drain lines below the bottom of the drain pan and pitch the drain lines down from the coil at least 1/4 inch per foot of run (6mm per 0.3m). Horizontal runs over 15 feet (5m) long must also have an antisiphon air vents (stand pipes), installed ahead of the horizontal runs. Extremely long horizontal runs may require oversized drain lines to eliminate air trapping.
Route primary drain line to the outside or to a floor drain. Check local codes before connecting to a waste (sewer) line.
Route the secondary drain line to a place in compliance with local installation codes where it will be noticed when unit is operational. Condensate flowing from secondary (overflow) drain indicates a plugged primary drain unit requires service or water damage will occur.
Prime all traps, test for leaks, and insulate in areas where sweating of the traps and drain lines could potentially cause water damage. Consult local codes for additional requirements or precautions.
If a gravity drain cannot be used, install a condensate pump. Install the pump as close to the indoor section as possible.
!
PRODUCT or PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Use only full size Ptraps in the condensate line (refer to Figure 17). Shallow, running traps are inadequate and DO NOT allow proper condensate drainage (refer to
Figure 18).
CAUTION
496 01 5503 00 11
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
Figure 17 Recommended Condensate Trap
UNIT
2” MIN (51mm)
2” MIN (51mm)
Figure 18 Insufficient Condensate Trap
ACCESSORIES
A. HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in Figure 20 and Figure 21.
Figure 20
THERMOSTAT
R
G
C
W
2
E
L
O
Y
FAN HUMIDIFIER
Wiring Layout of Humidifier to Heat
Pump
WHT
FAN COIL
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
R
G
C
W W
E
2
3
RELAY
HEAT PUMP
(CONTROL)
R
C
W
2
O
Y
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 19 Condensate Drain
SECONDARY DRAIN WITH APPROPRIATE TRAP REQUIRED (USE FACTORY KIT OR FIELDSUPPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR FIELDSUPPLIED TRAP OF PROPER DEPTH. STANDARD PTRAPS ARE NOT SUFFICIENT. SEE FIGURE OF RECOMMENDED CONDENSATE TRAP)
FILTER ACCESS PANEL
115V M
Figure 21
THERMOSTAT
R
G
W
Y
HUMIDISTAT
Wiring Layout of Humidifier to Fan
Coil with Electric Heat
FAN COIL
(CONTROL)
RED
GRY
WHT
WHT
BLU
VIO
BRN
R
G
W
2
W
3
E
C
HUMIDISTAT
AIR COND.
C
Y
12 496 01 5503 00
115V
Specifications are subject to change without notice.
M
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
SEQUENCE OF OPERATIONS
A. CONTINUOUS FAN
Thermostat closes R to G. G sends signal direct to motor which completes circuit to indoor blower motor. When G is de−energized, there is a 90 second off delay before indoor blower motor stops.
B. COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump only). G sends signal direct to motor, which completes circuit to indoor blower motor. When G is de−energized, there is a 90 second off delay before indoor blower motor stops.
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G sends signal direct to motor, which completes circuit to indoor blower motor. When G is deenergized, there is a 90 second off delay before indoor blower motor stops.
D. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G energizes indoor blower motor. W energizes electric heat relay(s) which completes circuit to heater element(s). When W is deenergized, electric heat relay(s) open, turning off heater elements. When G is de−energized, the indoor blower motor is deenergized and stops.
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat relay(s) which completes circuit to heater element(s). W also energizes the indoor blower motor. When W is deenergized, electric heat relay(s) opens and the indoor blower motor is deenergized and stops.
STARTUP PROCEDURE
Refer to outdoor unit Installation Instructions for system startup instructions and refrigerant charging method details.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified service technician. Consult the servicing dealer for recommended frequency.
Between visits, the only consumer service recommended or required is air filter maintenance and condensate drain operation.
Air Filter
Inspect air filters at least monthly and replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned by soaking in mild detergent and rinsing with cold water. Install filters with the arrows on the side pointing in the direction of air flow.
Condensate Drain
During the cooling season check at least monthly for free flow of drainage and clean if necessary.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit performance and/or product damage.
Never operate unit without a filter. Factory authorized filter kits must be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a fieldsupplied filter must be installed in the return duct system.
CAUTION
496 01 5503 00 13
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
AIRFLOW PERFORMANCE TABLES
Table 1 Airflow Performance (CFM)
MODEL & SIZE BLOWER SPEED
Tap 5 767 739 702 669 620 565 Tap 4 614 569 534 486 436 398
1800
FEM4P2400
FEM4X2400 REM4X2400
3000
3600
4200
4800
6000
- Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factoryapproved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200 through 6000). For FEM4X, FEM4P, and REM4X models, airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal applications of 4200 6000 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 4800 6000 size could result in condensate blowing off coil or splashing out of drain pan.
Tap 3 701 660 616 581 537 499 Tap 2 614 569 534 486 436 398 Tap 1 410 350 304 261 228 203
Tap 5 969 936 892 835 763 676 Tap 4 826 795 766 743 706 660 Tap 3 826 795 766 743 706 660 Tap 2 701 660 616 581 537 499 Tap 1 617 592 552 507 472 420
Tap 5 965 920 870 823 780 740 Tap 4 820 783 740 680 630 575 Tap 3 820 783 740 680 630 575 Tap 2 720 655 610 555 485 450 Tap 1 716 600 540 495 430 328
Tap 5 1108 1090 1065 1034 1009 974 Tap 4 1026 1000 969 938 899 865 Tap 3 1026 1000 969 938 899 865 Tap 2 909 873 842 799 762 724 Tap 1 825 795 757 722 674 634
Tap 5 1301 1276 1245 1218 1176 1121 Tap 4 1227 1191 1169 1143 1105 1074 Tap 3 1227 1191 1169 1143 1105 1074 Tap 2 1087 1062 1030 1001 966 930 Tap 1 1026 1000 969 938 899 865
Tap 5 1560 1544 1507 1464 1424 1358 Tap 4 1419 1397 1358 1320 1279 1239 Tap 3 1419 1397 1358 1320 1279 1239 Tap 2 1249 1220 1184 1142 1093 1052 Tap 1 1242 1205 1158 1110 1069 1026
Tap 5 1743 1712 1679 1642 1610 1574 Tap 4 1669 1634 1599 1564 1531 1499 Tap 3 1669 1634 1599 1564 1531 1499 Tap 2 1452 1413 1377 1339 1308 1271 Tap 1 1300 1256 1221 1182 1142 1101
Tap 5 1897 1867 1836 1808 1774 1736 Tap 4 1817 1785 1757 1724 1693 1655 Tap 3 1817 1785 1757 1724 1693 1655 Tap 2 1657 1621 1589 1557 1518 1474 Tap 1 1443 1412 1377 1332 1286 1243
0.10 0.20 0.30 0.40 0.50 0.60
TOTAL STATIC (inches water column)
14 496 01 5503 00
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
Table 2 Air Delivery Performance Correction Component Pressure Drop (in. wc)
at Indicated Airflow (Dry to Wet Coil)
CFM
UNIT SIZE
18 0.034 0.049 0.063
FEM4P24 0.049 0.063 0.076 0.089
FEM4X24 & REM4X24 0.026 0.038 0.049 0.059
30 0.049 0.059 0.070 0.080
36 0.070 0.080 0.090 0.099
42 0.049 0.056 0.063 0.070
48 0.063 0.070 0.076 0.083 0.090
60 0.049 0.054 0.059 0.065 0.070
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
Table 3 Electric Heater Static Pressure Drop (in. wc)
FEM4X, FEM4P, REM4X
1800 3600
HEATER
ELEMENTS
0 0 +.02 0 0 +.04
1 3, 5 +.01 2 8, 10 +.02
2 8, 10 0 3 9, 15 0
3 9, 15 –.02 4 20 –.02
4 20 –.04 6 18, 24, 30 –.10
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
HEATER
ELEMENTS
FEM4X, FEM4P, REM4X
4200 6000
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
496 01 5503 00 15
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS Fan Coils: FEM4X, FEM4P, REM4X
R410A QUICK REFERENCE GUIDE
R410A refrigerant operates at 50% 70% higher pressures than R22. Be sure that servicing equipment and
replacement components are designed to operate with R410A.
R410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
Manifold sets should be 750 psig highside and 200 psig lowside with 520 psig lowside retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
R410A, as with other HFC refrigerants, is only compatible with POE oils.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Vacuum pumps will not remove moisture from oil.
A liquid line filterdrier is required on every unit.
Do not use liquid line filterdriers with rated working pressures less than 600 psig.
Do not install a suction line filterdrier in liquid line.
Wrap all filterdriers and service valves with wet cloth when brazing.
Do not use capillary tube indoor coils.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace all filterdriers.
Do not vent R410A into the atmosphere.
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
Do NOT use R22 TXV.
Copyright 2017 International Comfort Products
16 496 01 5503 00
Lewisburg, TN 37091 USA
Specifications are subject to change without notice.
Loading...