Installation and Operating Manual
Natural Gas
FDN-4-ST
FDN-5-ST
FDN-6-ST
FDN-7-ST
Installer: Leave this manual with the appliance.
Consumer: Retain this manual for future reference.
WARNING: If the information in these instructions are not followed exactly, a re or explosion may result
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali ed installer, service agency or the gas supplier.
Heat & Glo, a brand of Hearth & Home Technologies
7571 215th Street West, Lakeville, MN 55044
www.heatnglo.com
Please contact your Heat & Glo dealer with any questions or concerns.
For the location of your nearest Heat & Glo dealer,
This replace complies with ANSI Z21.50-2016·CSA 2.22-2016 “VENTED DECORATIVE GAS APPLIANCES”.
Installation must conform with local building codes or in the absence of local building codes,
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - Current Edition, or the Natural or Propane Installation Code, CSAB149.1
A. SAFETY ICON DESIGNATIONS
Various safety icons appear throughout this installation manual. Please familiarize yourself with the icons making sure you understand the serious
consequences that may occur if ignored or of handling the products inappropriately.
IMPORTANT NOTE
This indicates additional instructions that you should consider
during the installation.
DO NOT
This indicates something that you must never do.
RISK OF FIRE
This designates a danger of risk of re or damage to property.
B. IMPORTANT SAFETY CONSIDERATIONS
• Installation and repair should be done only by a qualied
service person. The appliance should be inspected by a
qualied service person before use. Annual inspection by a
qualied service person is required to maintain warranty. More
frequent cleaning may be required due to excessive lint from
carpeting, bedding materials, etc. It is imperative that control
compartments, burners and circulation air passageways of the
appliance be kept clean.
• Children and adults should be alerted to the hazards of high
surface temperatures and should stay away to avoid burns or
clothing ignition.
• Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children
and others may be susceptible to accidental contact burns. A
physical barrier is recommended if there are at risk individuals
in the house. To restrict access to a replace or stove, install
an adjustable safety gate to keep toddlers, young children and
other at risk individuals out of the room and away from hot
surfaces.
• Clothing or other ammable material should not be placed on
or near the appliance.
• Adequate accessibility clearances for servicing and proper
operation must be maintained.
• This appliance must not share or be connected to a chimney
ue serving any other appliance.
HOT GLASS WARNING
This indicates danger of serious bodily injury or property
damage if glass is handled while still hot.
CAUTION
This indicates danger of serious bodily injury or property
damage.
STOP!
This indicates notes that may include reviewing warnings on
other pages throughout the manual.
• Due to high temperatures the appliance should be located out
of trafc and away from furniture and draperies.
• The glass front or any part removed for servicing the appliance
must be replaced prior to operating the appliance. Work should
be done by a qualied service technician.
• Clean glass only when cool and only with non-abrasive
cleansers.
• Do not operate this appliance with the glass/frame assembly
removed, cracked or broken. Replacement of the glass
assembly must only be performed by a licensed or qualied
service person. DO NOT SUBSTITUTE MATERIALS.
• Do not strike or slam glass assembly.
• Keep burner and control compartment clean.
• Do not use this replace if any part has been under water.
Immediately call a qualied service technician to inspect this
appliance and to replace any part of the control system and any
gas control which has been under water.
• DANGER: Under no circumstances should any solid fuel
(wood, coal, paper or cardboard etc.) be used in this appliance.
• STATE OF CA WARNING: This product and the fuels used
to operate this product (liquid propane or natural gas), and
the combustion of such fuels, can expose you to chemicals
including benzene, which is known to the State of California to
cause cancer and reproductive harm.
For more information go to: www.P65Warnings.ca.gov.
• Keep area around the appliance clear of combustible materials,
gasoline and other ammable vapor and liquids.
• The ow of combustion and ventilation air must not be
obstructed.
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
C. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above nished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the oor
level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas tter shall observe that
a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) in. in size, “GAS
• The referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
This is the allowable nishing width and height required to t the glass panels into the replace.
Finishing materials shall not overlap dimensions.
FLUE
OUTSIDE
AIR INTAKE
DIMENSIONS
Inches
(Millimeters)
A*B*CDEFG
Finishing
Width
50-3/16
[1,275]
62-3/16
[1,580]
74-3/16
[1,884]
86-3/16
[2,189]
Finishing
Height
24
[610]
24
[610]
24
[610]
24
[610]
Height
Firebox
Top
42
[1,067]
42
[1,067]
42
[1,067]
42
[1,067]
Height
Overall
50
[1,270]
50
[1,270]
50
[1,270]
50
[1,270]
Edge to
Center
Flue
26-7/8
[683]
32-7/8
[835]
38-7/8
[987]
44-7/8
[1,140]
Depth
24
[610]
24
[610]
24
[610]
24
[610]
Overall
Width
53-3/4
[1,365]
65-3/4
[1,670]
77-3/4
[1,975]
89-3/4
[2,280]
5
Page 6
2 - FIREPLACE SPECIFICATIONS
MODEL #DESCRIPTIONB-VENTOAREG PVIN-LINEBTU'SNG ORIFICE
FDN-4-ST4X2 SEE THROUGH8”10”PVK-45PVI-4560,000(3X) #43(3X) #55
FDN-5-ST5X2 SEE THROUGH8”10”PVK-45PVI-4580,000(4X) #43(4X) #55
FDN-6-ST6X2 SEE THROUGH10”10”PVK-67PVI-67100,000(5X) #43(5X) #55
FDN-7-ST7X2 SEE THROUGH10”10”PVK-67PVI-67120,000(6X) #43(6X) #55
SPECIFICATIONS TABLE
B. CLEARANCES
WARNING: NON-COMBUSTIBLE ZONE: USE ONLY NON-COMBUSTIBLE MATERIAL IN THIS AREA FOR ENTIRE WIDTH OF
FIREPLACE. DO NOT USE WOOD, SHEETROCK, ETC., IN THIS ZONE. SEE FIGURE 2B.
NOTE: OTHER CLEARANCES APPLY. ALL CLEARANCES MUST BE MAINTAINED.
Refer to Section 5 (Non-Combustible Zone) and Section 10 (Finishing) for more information.
CLEARANCES
From unit left & right sides1"25mm
To ooring under replace00
Unit top to ceiling6"122mm
Unit side to adjacent sidewall1"25mm
From appliance front**See note below
PROPANE
ORIFICE
NO COMBUSTIBLE
MATERIAL WITHIN
1” [25]
OF SIDES OF
FIREPLACE
COMBUSTIBLE
FRAMING AND
FINISHINGMATERIAL
ALLOWED ON THE
FACE OF THE
FIREPLACE BELOW
THE BOTTOM
VIEWING EDGE
ONLY.
NO COMBUSTIBLE
NO COMBUSTIBLE
MATERIAL WITHIN 1”
[25]
OTHER CLEARANCES:
DO NOT PLACE ON CARPET, VINYL OR SOFT SURFACES.
A COMBUSTIBLE MANTEL MAY BE PLACED AT THE TOP OF THE GLASS VIEWING AREA. DO NOT OVERLAP GLASS.
A COMBUSTIBLE HEARTH EXTENSION MAY BE USED AT THE BOTTOM OF GLASS VIEWING. DO NOT OVERLAP GLASS.
* MINIMUM DISTANCE RECOMMENDED FROM VIEWABLE SIDES OF APPLIANCE FOR SERVICE ACCESS = 24 IN. [610 mm].
NOTE: Framing dimensions should allow for wall covering thickness and replace facing materials. When using a hearth,
adjust rough opening size as necessary to maintain at least minimum clearance requirements.
CAUTION: Install replace on metal, concrete or hard wood surface extending the full width and depth of replace.
CAUTION: Vent cap location must be in compliance with guidelines in Section 8 of this manual.
CAUTION: FIREPLACE IS NOT LOAD-BEARING.
If masonry is to be used (optional), prepare the necessary foundation for the masonry load. When masonry construction is being used, a lintel must be
used over top of replace to support the added weight. Build hearth to desired size and height. If a hearth extension is desired, combustible material
may be used.
A. FIREPLACE SHIPPING BRACKETS
Shipping Brackets
Temporary shipping brackets are put in place for shipping
and support during the installation process. The brackets
must stay in place until the replace is fully attached to the
framing. See Figure 4.1. Once the replace is fully attached
to the framing, the shipping brackets can be removed.
FRAMING SHOULD BE BUILT AFTER THE FIREPLACE IS INSTALLED OR EXTRA CLEARANCE MUST
BE PLANNED FOR AT THE INTAKE COLLAR AND FOR THICKNESS OF MATERIALS USED.
23
[584]
23
[584]
23
[584]
23
[584]
FRAMING DIMENSIONS ASSUMING 1/2” [13] DRYWALL AND NON-COMBUSTIBLE BOARD USED.
THESE DIMENSIONS REPRESENT THE FRAMING DIMENSIONS FOR COMBUSTIBLE MATERIAL.
NON-COMBUSTIBLE FRAMING AND FINISHING MATERIALS MAY BE USED WITHIN THESE DIMENSIONS
RIGHT UP TO THE UNIT.
NO COMBUSTIBLE MATERIAL WITHIN 6" [152] OF THE TOP OF THE FIREPLACE.
NO COMBUSTIBLE MATERIAL WITHIN 1" [25] OF THE SIDES OF THE FIREPLACE.
COMBUSTIBLE MATERIAL SHALL NOT BE PLACED DIRECTLY ON THE FACE OF THE FIREPLACE, TOP
AND SIDES.
SEE SECTION 10 (FINISHING) FOR DETAILS REGARDING 1/2 INCH STANDOFFS.
STEEL SURFACE MAY BE COVERED WITH NON-COMBUSTIBLE FINISHING MATERIAL.
1" [25] CLEARANCE TO THE B-VENT MUST BE MAINTAINED.
11
Page 12
5 - MANTEL REQUIREMENTS
A. NON-COMBUSTIBLE ZONE - USING THE PROVIDED 1/2" STANDOFFS
The replace has standoffs installed on the front of the replace standard from the factory. They are located on the
upper left, center and right front of the replace and are to ensure that the 1/2" [12.7mm] required clearance to
combustibles on the surface of the replace is maintained.
If the standoffs are removed, only non-combustible material can be installed against the surface of the replace such as a
non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the 15” [381mm] between the
top of the 3’’ trim to the combustible framing the full width of the replace. The 15” includes a 7” [178mm] minimum above
the top of the replace that is recommended for ease of attachment.
Refer to Figure 5.1 for a standard installation using the provided 1/2"standoffs.
Refer to Figure 5.2 for requirements when not using the provided 1/2" standoffs.
Figure 5.1
WARNING! Risk of Fire! Comply with all
minimum clearances as specifi ed.
COMBUSTIBLE OR NON-COMBUSTIBLE
BACKING MATERIAL (I.E. SHEETROCK)
COMBUSTIBLE FACING
MATERIAL
1/2" [12.7mm] Standoff
COMBUSTIBLE FRAMING
6”
TOP OF FIREPLACE
1/2” [12.7] CLEARANCE TO COMBUSTIBLES ON SURFACE
The fireplace ships with standoffs in place to ensure a 1/2” clearance to
combustibles is maintained on the surface.
TOP OF TRIM
COMBUSTIBLE MANTEL
COMBUSTIBLE HEARTH
COMBUSTIBLE OR
NON-COMBUSTIBLE MATERIAL
3”
GLASS VIEWING AREA
MINIMUM NON-COMBUSTIBLE ZONE
6” [152 mm]
OPEN AIR SPACE
1/2” [12.7 mm]
STANDOFFS
TOP TRIM
BOTTOM 3” TRIM
6”
14”
8”
SINGLE SIDED EXAMPLE: RIGHT SIDE VIEW
APPLIES TO ALL SIDES THAT HAVE A VIEWABLE AREA
NOTE: Refer to Section 10 for more information on nishing the wall.
B. NON-COMBUSTIBLE ZONE - NOT USING THE PROVIDED 1/2" STANDOFFS
The replace has standoffs installed on the front of the replace standard from the factory. They are located on the left,
center and right front hood of the replace and are to ensure that the 1/2" [12.7mm] required clearance to combustibles on
the surface of the replace is maintained.
If the standoffs are removed, only non-combustible material can be installed against the surface of the replace such as a
non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the 15” [381mm] between the
top of the 3’’ trim to the combustible framing the full width of the replace. The 15” includes a 7” [178mm] minimum above
the top of the replace that is recommended for ease of attachment.
Refer to Figure 5.2 for requirements when not using the provided 1/2" standoffs.
Refer to Figure 5.1 for a standard installation using the provided 1/2" standoffs.
Figure 5.2
WARNING! Risk of Fire! Comply with all
minimum clearances as specifi ed.
COMBUSTIBLE FRAMING
COMBUSTIBLE OR NON-COMBUSTIBLE
BACKING MATERIAL (I.E. SHEETROCK)
1/2" [12.7mm] Standoff
COMBUSTIBLE FACING
MATERIAL
7” ABOVE TOP OF FIREPLACE
1/2” [12.7] CLEARANCE TO COMBUSTIBLES ON SURFACE
The fireplace ships with standoffs in place to ensure a 1/2” clearance to
combustibles is maintained on the surface.
If the standoffs are removed, only non-combustible material can be installed
15”
against the surface.
between the top of the 3” trim extending 15” [381mm] high the full width of
the fireplace. The 15” includes a 7” [178mm] minimum above above the
top of the fireplace that is recommended for ease of attachment.
1/2” [12.7mm] minimum thickness must be used
TOP OF TRIM
3”
COMBUSTIBLE MANTEL
GLASS VIEWING AREA
MINIMUM NON-COMBUSTIBLE ZONE
6” [152 mm]
OPEN AIR SPACE
TOP TRIM
BOTTOM 3” TRIM
8”
COMBUSTIBLE HEARTH
COMBUSTIBLE OR
NON-COMBUSTIBLE MATERIAL
NOTE: Refer to Section 10 for more information on nishing the wall.
Refer to Glass Frame Assembly Identication Figures 6A & 6B.1 when installing and removing the glass frame assembly.
B. INSTALL GLASS FRAME ASSEMBLY
U-Shaped
Edge
Protector
Figure 6B.2
Figure 6B.3
Top/Bottom Glass Pane
IMPORTANT: PLASTIC GLASS EDGE PROTECTORS
The replace is shipped with plastic edge protectors on the
outer panes of glass only.
If the edge protectors on the outer panes of glass are not
installed, the glass may rattle during operation. See Figure
6B.2.
Inner Glass
1. Unwrap the panes of glass carefully making sure to
protect the edges.
2. Apply the suction cups to the inner glass assembly,
following instructions included with the suction cups.
3. Lift the glass into place. The top edge slips into the
top groove, lift into the groove until the bottom is clear
of the bottom trim. Slide the glass down into the
inner bottom groove. See Figure 6A.
4. Push inner trim vertical panels into place on each
side. See Figure 6B.3.
5. Place the lower trim panel between the lower glass
clips. Slide back against the vertical trim piece. See
Figure 6B.4.
6. Repeat process for all inner glass panels on
appliance.
Outer Glass
7. Apply the suction cups to the outer unframed glass
(which has the U-shaped edge protector) and lift it
into place in the same manner as the inner glass.
8. Repeat process for installing all outer glass panels on
appliance.
Figure 6B.4
C. REMOVE GLASS FRAME ASSEMBLY
1. Apply the suction cups to the outer glass panel following the instructions included with the suction cups.
2. Gently lift the glass until the bottom edge is clear of the groove it sits in.
3. Bring the bottom edge of the glass towards you while lowering it to disengage it from the top groove.
4. Sit the glass on a padded surface to protect it. IMPORTANT: Protect the glass's edges.
5. Remove the lower trim panel that sits between the layer of glass.
6. Remove the inner trim vertical panels.
7. Using the suction cups, remove the inner panel in the same manner.
WARNING! RISK OF INJURY! DO NOT remove glass until it is cooled to room temperature. Glass breakage could occur.
This replace is manufactured for use with NG (Natural Gas) or P (Propane).
CAUTION: Installation of the gas line must only be done by a qualied person in accordance with local building codes, if any.
If not, follow ANSI Z223.1.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
NOTE: For high altitude installations above 2000 feet, replace does not need to be derated.
A. GAS LINE CONNECTION
GAS LINE CONNECTIONPROPANENG
MINIMUM INLET GAS PRESSURE
MAXIMUM INLET GAS PRESSURE14.0 inches W.C.10.0 inches W.C.
Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI Z223.1. Installation should
be done by a qualied installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts
installation must be performed by a licensed plumber or gas tter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and exible
gas connector are connected to the 1/2 in. (13 mm) control valve inlet.
• If substituting for these components, please consult local codes for compliance.
Each replace will have four points of access for installation and service. There are access panels on the pilot side of the replace front, side and rear
of the replace. Plan in advance of the installation which access location will be used and accommodate for it in the nish work to allow for
easy access to service later. You also have access through the interior of the replace by removing the mesh on the burner pan in the pilot area.
There are gas and electrical gas knock-outs on the bottom if you need to come up from below the replace.
CAUTION: Consult the local and national installation codes to assure adequate combustion and ventilation air is available.
NOTE: Flame height and appearance will vary depending upon venting conguration and type of fuel used. Venting
requirements apply to both Natural and Propane gas.
STOP: MAINTAIN ALL CLEARANCES AS STATED IN THIS INSTALLATION MANUAL.
A. APPROVED VENTING
8 - VENTING
MODEL #DESCRIPTIONB-VENTOUTSIDE AIRPOWER VENT
FDN-4-ST4X2 SEE THROUGH8”10”PVK-45PVI-451204.9.59
FDN-5-ST5X2 SEE THROUGH8”10”PVK-45PVI-451204.9.59
FDN-6-ST6X2 SEE THROUGH10”10”PVK-67PVI-671207.3.88
FDN-7-ST7X2 SEE THROUGH10”10”PVK-67PVI-671207.3.88
*Amperage listed is the maximum required for the appliance with all options.
Refer to the vent systems manufacturer's installation manual for complete installation instructions.
Installation must conform with the venting requirements and restrictions as outlined in this manual.
SEE CHART ABOVE FOR SIZE diameter B-Type Venting that must be used. UL/CSA approved B-Vent only.
DO NOT decrease the vent size.
Vent runs are approved for up to 110 feet with quantity of eleven 90 degree elbows.
Vent runs may also contain a downward component. The downward
component may be a maximum of 6 feet plus the distance to the center line
of the elbow. See Figure 8A.1.
This will be about 87" for 8" diameter pipe and 92" for 10" diameter pipe.
Due to natural buoyancy of ue gas products, venting downward increases
restriction.
Every inch of vertical drop counts as triple inches subtracted off the total
vent run.
Example: a maximum drop of 92" means the total allowed vent run is de-
creased by 276" (23')
IN-LINE
POWER VENT
VACAMP*KW
Once a downward component has been utilized, the vent cannot go
upwards again, Moisture may get trapped in the vent pipe.
Important: Be sure to do your own calculations based on the center
line dimension given from the pipe manufacture you are using for
A power vent (PVK-45 or PVK-67) is approved for use withthis appliance. It is crucial that all B-Vent pipe and elbow joints, and the longitudinal seam
are sealed using a high temperature RTV Silicone and/or foil tape.
NOTE: All pipe and elbow joints must be sealed. This includes the longitudinal seam on the pipe.
High Temp RTV Silicone and/or foil tape MUST be used on each joint/seam.
Failure to do so may cause lack of vacuum and may not trigger the vacuum switch.
MODELPVK-45PVK-67
Fan TypeAxial vaneAxial vane
Motor Type
Totally enclosed,
variable speed,
Class H
Totally enclosed, variable
speed, Class H
Voltage (VAC)1 x 1201 x 120
RPM16001600
CFM9501400
Amperage (Amps)1.21.4
Motor Output HP (kW)1/9 (0.08)1/7 (0.1)
Weight lbs (kg)37 (17) 47 (21)
Dimension A in. (mm)11.5 (292)13.1 (334)
Dimension B x B in.(mm)14.3 (364)16.6 (422)
Dimension C in. (mm)13.5 (344)15.5 (395)
Dimension D in. (mm)3.3 (85)3.9 (100)
Dimension E in. (mm)11.6 (294)13.5 (342)
Temperature Rating-Intermittent575 °F / 300 °C575 °F / 300 °C
Temperature Rating-Continuous482 °F / 250 °C482 °F / 250 °C
Figure 8A.2
Chimney Collar Dimensions
A chimney collar is included for use with the PVK-45 and PVK-67. The chimney collar is used to attach the PVK power vent. Figures 8A.3 and 8A.4
An in-line power vent (PVI-45 or PVI-67) is approved for use withthis appliance. It is crucial that all B-Vent pipe and elbow joints, and the longitudinal
seam are sealed using a high temperature RTV Silicone and/or foil tape.
NOTE: All pipe and elbow joints must be sealed. This includes the longitudinal seam on the pipe.
High Temp RTV Silicone and/or foil tape MUST be used on each joint/seam.
Failure to do so may cause lack of vacuum and may not trigger the vacuum switch.
Perform the following steps when installing the PVI-67 on
six foot and seven foot models.
1. Attach the provided 10 inch B-Vent collar to the intake
side of the powervent. The intake side is located
opposite the fan motor as shown in Figure 8.A6. The
10 inch B-Vent collar is packaged separately from the
powervent. See Figure 8A.7.
2. Note the silhouette circle printed on the intake side of the
powervent. The pre-drilled screw holes within the circle
will be matched with the holes on the intake collar of the
base plate. See Figure 8A.8.
3. Place the intake collar base plate onto the silhouette,
matching up the holes as shown in Figure 8A.9. Fasten
the base plate to the silhouette using ve self-tapping
screws.
4. Add the rope gasket included with the kit to the outlet
side of the inline powervent.
5. An adapter to increase from eight inch pipe to ten inch
pipe is required on the outlet side of the in-line powervent.
The adapter is included in the PVI-67 kit. See Figure
8A.10. Connect the adapter directly to the eight inch
outlet collar of the in-line powervent. Connect the ten
inch exhaust B-Vent to the collar and continue the vent
run.
• The Foundation Series replace must terminate with the approved powervent termination cap.
• NO SUBSTITUTION IS ACCEPTABLE.
• Carefully follow the instructions included with the approved powervent termination cap.
• DO NOT use an additional speed control on this powervent.
• You must use the included Capacitor.
F. HORIZONTAL TERMINATION VENT CAP LOCATION & CLEARANCES
This gas appliance must not be connected to a chimney serving any other appliance.
• DO NOT RECESS TERMINATION KIT INTO OUTSIDE BUILDING MATERIALS - i.e.: brick, stone, siding, etc. If necessary, extend framing so
that termination kit will be exposed once building materials are installed.
• Vent termination must not be located where it will become plugged by snow or other material. The ow of combustion and ventilation air must not
be obstructed.
B. Operable window or door - 12 inches (305 mm).
C. Permanently closed window* - 12 inches (305 mm) (recommended to prevent condensation on window).
D. Ventilated soft* - 24 inches (610 mm).
E. Unventilated soft* - 12 inches (305 mm).
F. Outside corner* - 12 inches (305 mm).
G. Inside corner* to non-combustibles - 12 inches (305 mm). Inside corner* to combustibles - 24 inches (610 mm).
H. Meter / Regulator: Not to be installed above a gas meter/regulator assembly within 3 ft. (914 mm) horizontally from the center-line of the regulator.
I. Gas Service regulator vent outlet - 3 ft. (914 mm).
J. Non-mechanical air supply inlet to building or the combustion air inlet to any other appliance.
US: 9 inches (229 mm) CANADA: 12 inches (305 mm).
K. Mechanical air supply inlet.
US: 3 ft. (914 mm) above if within 10 ft. (3.05 m) horizontal. Massachusetts installations: 10 ft. (3.05 m).
CANADA: 6 ft. (1.83 m).
L. Above paved side-walk or paved driveway located on public property - 7 ft. (2.13 m).
M. Under veranda, porch, deck, or balcony (must be fully opened on a minimum of 2 sides) - Combustible - 24 inches (610 mm),
Non-Combustible - 12 inches (305 mm)
N. Between two horizontal terminations - 12 inches (305 mm) (Not shown in Figure 8F.1).
O. Between two vertical terminations - 12 inches (305 mm). Terminations may be same height (Not shown in Figure 8F.1).
N & O: Minimum of 12 inches (305 mm) required when two exhaust termination caps are placed next to each other. Measurement must be
taken from inside edge of one steel chimney adapter to the inside edge of the other steel chimney adapter. A metal divider plate with same
length and height as termination cap is required to be installed between the caps. Divider plate is not required if caps are at least 24 inches
(610 mm) apart, measured edge to edge.
P. Above furnace exhaust or inlet - 12 inches (305 mm) (Not shown in Figure 8F.1).
*Clearance must be in accordance with local installation codes & the requirements of the gas supplier.
Figure 8F.1
NOTE: A vent cannot be located directly above a side-walk or paved driveway that is located between two single family
dwellings and serves both dwellings.
This replace has the options of air intake connections on the side or the bottom of the replace. This replace is approved
for use with 10 inch rigid metal pipe or UL approved 10 inch Class 0 or Class 1 ex for intake air. Use Table 8J.1 for venting
requirements if using UL approved 10 inch ex for intake air.
Vent runs utilizing 10 inch rigid metal pipe may be 110 feet with 11 elbows. We recommend insulating the intake air duct or
using UL approved Class 1 insulated ex in hot, humid or cold climates.
The intake pipe must maintain 1.5X the square inches of the ue pipe in free area. Intake screen/vent must be sized ap-
propriately. Failure to do so will result in higher operating temperatures.
The replace may also take room air for combustion. Intake screen/vent must be sized appropriately. You must plan for
the replacement air that is consumed from the room by the replace. Do not draw intake air from a crawl space or an attic
(ventilated or not ventilated).
WARNING! Risk of Fire! DO NOT draw intake air from an attic or crawl space. Appliance could overheat.
Use Table 8J.2 for reference on CFM replacement air if drawing intake air from inside the house and open air requirements
for intake screen/vent or consult Hearth & Home Technologies for more information.
Table 8J.1Table 8J.2
UL Approved 10 Inch Class 1 or Class 0 Flex Intake Air Venting Requirements
Number of offsets
0-345678
FDN-4-ST
FDN-5-ST45 ft35 ft25 ft15 ft5 ftN/A
FDN-6-ST70 ft 60 ft50 ft40 ft30 ft20 ft
FDN-7-ST32 ft20 ft15 ft10 ftN/AN/A
Length
of
Run
100 ft90 ft80 ft70 ft60 ft50 ft
Fireplace
Size
FDN-4-ST480 CFM75 Sq. Inches
FDN-5-ST640 CFM75 Sq. Inches
FDN-6-ST800 CFM75 Sq. Inches
FDN-7-ST960 CFM75 Sq. Inches
Required
CFM
Open Air
Requirement
K. CHANGING FROM SIDE INTAKE AIR TO BOTTOM INTAKE AIR
Step 1: Remove 4 screws that hold collar plate in place.
Refer to Figure 8K.1.
REMOVE 4
SCREWS
Figure 8K.1Figure 8K.2
Step 3: Turn plate so collar is facing down, slide plate into slots on each side.
13 CONNECTION FOR EXTERNAL FLUE PRESSURE SWITCH (4 SIDED ONLY)
14 CONNECTION FOR EXTERNAL FLUE PRESSURE SWITCH (4 SIDED ONLY)
14 CONNECTION FOR EXTERNAL FLUE PRESSURE SWITCH (4 SIDED ONLY)
To light the fireplace: Activate the switch.
The fireplace has a pre and post timer, set at the factory for 30 seconds.
The powervent and flame will not turn on for 30-60 seconds after switch is
activated and the powervent will run for 30 seconds after it has been shut off.
BLACK
WHITE
WHITE
NOTES:
120 VOLT LOOP
120 VOLT LOOP
120 VOLT LOOP
120 VOLT LOOP
CONNECT TO CONSTANT POWER SOURCE
CONNECT TO CONSTANT POWER SOURCE
DO NOT SHARE NEUTRAL
FROM SPEED CONTROL
OPTIONAL
OPTIONAL
OPTIONAL. USE PURPLE AND WHITE, NOT RED
OPTIONAL. USE PURPLE AND WHITE, NOT RED
FOUR SIDED ONLY
FOUR SIDED ONLY
A. FINISHING THE WALL - USING THE PROVIDED 1/2" STANDOFFS
NOTE: REFER TO DIMENSIONS SECTION FOR ALLOWABLE FINISHING DIMENSIONS REQUIRED TO FIT THE GLASS
PANELS INTO THE FIREPLACE. FINISHING MATERIALS MUST NOT OVERLAP THE FRAMING DIMENSIONS REFERENCED
IN SECTION 2.A. NEVER COVER THE GLASS WITH FINISHING MATERIALS.
NOTE: DO NOT PIERCE ANY OF THE BLACK PAINTED SURFACES WITH SCREWS, RIVETS, ETC.
THIS INCLUDES THE 3" BLACK TOP AND BOTTOM GLASS TRIM AND ANY PAINTED SIDES ADJACENT TO THE GLASS.
NOTE: REFER TO MANTEL REQUIREMENTS: NON-COMBUSTIBLE ZONE USING PROVIDED 1/2" STANDOFFS FOR MORE
INFORMATION (SECTION 5A).
Figure 10A.1
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances.
Comply with all minimum clearances to combustibles as specifi ed in this manual.
IMPORTANT: NEVER COVER THE GLASS WITH FINISHING MATERIALS
D - COMBUSTIBLE OR NON-COMBUSTIBLE
BACKER MATERIAL (I.E. SHEETROCK)
SINGLE SIDED FIREPLACE SHOWN:
APPLIES TO BOTH SIDES AND ENDS IF
USING A MULTI-SIDED FIREPLACE
E - COMBUSTIBLE
MANTEL
F - COMBUSTIBLE
HEARTH
G. ACCESS PANEL
B
C - COMBUSTIBLE OR NON-COMBUSTIBLE
FINISHING MATERIAL
COMBUSTIBLE FRAMING
A
3” TOP TRIM
STANDOFF
REFER TO (B)
36
I. COMBUSTIBLE FRAMING
AND FINISHING MATERIAL
A. No combustible materials may be within 6” [152mm] of the top of the fireplace.
B. 1/2” [12.7] CLEARANCE TO COMBUSTIBLES ON SURFACE. The fireplace ships with standoffs in place to ensure a 1/2” clearance to
combustibles is maintained on the surface. See Figure 10A.1. If the standoffs are removed, only non-combustible material can be installed against
the surface of the fireplace such as a non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the 15” [381mm]
between the top of the 3’’ trim to the combustible framing the full width of the fireplace. The 15” includes a 7” [178mm] minimum above above the top of
the fireplace that is recommended for ease of attachment. See Figure 10A.2
C. Combustible material may cover the non-combustible area mentioned in B.
D. Combustible finishing materials allowed.
E. Combustible or Non-Combustible mantel may be placed above the top of the glass viewing area. There are no restrictions on mantel depth.
F. Combustible hearth may be placed below the bottom of the glass viewing area.
G. Flat covers will cover the components access. Gas and electric inlets are located behind this panel. There are four access panel options all
located on the pilot side of the fireplace; front (shown above), side, back and inside behind the glass.
Please take consideration of which option will be used to access the components for service later during planning.
I. Combustible framing and finishing materials allowed.
B FINISHING THE WALL - NOT USING THE PROVIDED 1/2" STANDOFFS
NOTE: REFER TO DIMENSIONS SECTION FOR ALLOWABLE FINISHING DIMENSIONS REQUIRED TO FIT THE GLASS
PANELS INTO THE FIREPLACE. FINISHING MATERIALS MUST NOT OVERLAP THE FRAMING DIMENSIONS REFERENCED
IN SECTION 2.A. NEVER COVER THE GLASS WITH FINISHING MATERIALS.
NOTE: DO NOT PIERCE ANY OF THE BLACK PAINTED SURFACES WITH SCREWS, RIVETS, ETC.
THIS INCLUDES THE 3" BLACK TOP AND BOTTOM GLASS TRIM AND ANY PAINTED SIDES ADJACENT TO THE GLASS.
NOTE: REFER TO MANTEL REQUIREMENTS: NON-COMBUSTIBLE ZONE NOT USING PROVIDED 1/2" STANDOFFS FOR
MORE INFORMATION (SECTION 5B).
Figure 10A.2
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances.
Comply with all minimum clearances to combustibles as specifi ed in this manual.
IMPORTANT: NEVER COVER THE GLASS WITH FINISHING MATERIALS
SINGLE SIDED FIREPLACE SHOWN:
APPLIES TO BOTH SIDES AND
ENDS IF USING A MULTI-SIDED
FIREPLACE
E - COMBUSTIBLE
MANTEL
F - COMBUSTIBLE
HEARTH
G. ACCESS PANEL
D - COMBUSTIBLE OR NON-COMBUSTIBLE
BACKER MATERIAL (I.E. SHEETROCK)
C - COMBUSTIBLE FINISHING MATERIAL
B - NON-COMBUSTIBLE BACKER
CEMENT BOARD
COMBUSTIBLE
FRAMING
A
B
3” TOP TRIM
STANDOFF
REFER TO (B)
I. COMBUSTIBLE
FRAMING AND FINISHING
MATERIAL
A. No combustible materials may be within 6” [152mm] of the top of the fireplace.
B. 1/2” [12.7] CLEARANCE TO COMBUSTIBLES ON SURFACE. The fireplace ships with standoffs in place to ensure a 1/2” clearance to
combustibles is maintained on the surface. See Figure 10A.1. If the standoffs are removed, only non-combustible material can be installed
against the surface of the fireplace such as a non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the
15” [381mm] between the top of the 3’’ trim to the combustible framing the full width of the fireplace. The 15” includes a 7” [178mm] minimum
above above the top of the fireplace that is recommended for ease of attachment. See Figure 10A.2
C. Combustible material may cover the non-combustible area mentioned in B.
D. Combustible finishing materials allowed.
E. Combustible or Non-Combustible mantel may be placed above the top of the glass viewing area. There are no restrictions on mantel depth.
F. Combustible hearth may be placed below the bottom of the glass viewing area.
G. Flat covers will cover the components access. Gas and electric inlets are located behind this panel. There are four access panel options all
located on the pilot side of the fireplace; front (shown above), side, back and inside behind the glass.
Please take consideration of which option will be used to access the components for service later during planning.
I. Combustible framing and finishing materials allowed.
STOP: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
DUE TO HIGH SURFACE TEMPERATURES, KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation
air. It is important to make sure the termination cap remains unobstructed at all times from snow, ice, leaves or other debris.
• This replace is equipped with an ignition device
which automatically lights the pilot and main burner.
The pilot and burner light automatically with the wall
switch. DO NOT try to light the pilot by hand. Before
lighting this replace, follow these instructions exactly.
• BEFORE LIGHTING, smell all around the appliance
for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the oor.
• Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of
the control system which has been under water.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE
NOTE: A PAINT SMELL WILL OCCUR DURING THE FIRST FEW HOURS OF BURNING.
NOTE: THIS FIREPLACE MAY PRODUCE NOISES OF VARYING DEGREE AS IT HEATS AND COOLS DUE TO METAL
EXPANSION AND CONTRACTION. THIS IS NORMAL AND DOES NOT AFFECT THE PERFORMANCE OR LONGEVITY OF THE
FIREPLACE.
WHAT TO DO IF YOU SMELL GAS:
• Do not touch any electrical switches
• Do not try to light any appliance
• Do not use the phone in your building
• Immediately call your gas supplier from a neighbor’s
phone
• Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the re
department
A. LIGHTING THE FIREPLACE
To light the replace:
Activate the wall switch.
The replace has a pre and post timer, set at the factory for 30 seconds. The powervent and ame will not turn on for 30-60 seconds after switch is
activated and the powervent will run for 30 seconds after it has been shut off.
STOP! Read safety information on previous page and front cover of this manual before continuing.
NOTE: This replace is equipped with an ignition device which automatically lights the pilot.
DO NOT try to light the pilot by hand.
B. IF THE FIREPLACE DOES NOT LIGHT
1. Turn off the replace at switch.
2. Turn off all electrical power to replace.
3. Wait ve (5) minutes to allow any gas that may have accumulated
inside rebox to escape. If you then smell gas, STOP! Follow safety
information on front cover and on previous page of the installation
manual. If you don't smell gas, go to next step.
4. Turn ON all electrical power to replace.
5. Turn replace on at switch.
12
OFF
1
OFF
5
ON
Figure 11B
CAUTION: If replace will not operate, follow instructions TO TURN OFF GAS TO APPLIANCE on lighting instructions tag
fastened to the appliance and call your service technician or the gas supplier.
NOTE: When replace is initially lit, condensation will appear on the glass; this is normal in all gas replaces and will
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
INLET PRESSURE TEST
1. The valve has an allen plug on the inlet and outlet.
2. Install a barb tting on the tap you want to measure.
3. Light the replace, check the pressure.
4. Turn off replace; reinstall plug.
5. Check for leaks.
CAUTION: A LOW PRESSURE READING CAN CAUSE DELAYED IGNITION
NOTE: If inlet pressure reading is too high or too low, contact the gas company.
Only a qualied gas service technician should adjust incoming gas pressure.
13 - FINALIZING THE INSTALLATION
A. INSTALLING THE MEDIA
Figure 13A
Place the supplied glass media into the base tray.
Cover the base evenly. Do not use more than the supplied amount.
Do not get any glass media into the pilot area; a hazardous condition
could result!
You should be able to see the burner slightly through the media. If you
can't, push the media back from the burner. Smaller ames will result
from too much media over the burner.
DO NOT COVER THE BURNERS; POOR FLAME APPEARANCE
WILL RESULT.
B. FLAME APPEARANCE
Figure 13A
NOTE: DO NOT SUBSTITUTE THE SUPPLIED MEDIA WITH ANY
OTHER KIND OF MEDIA.
Flame appearance is affected by several factors including altitude, venting conguration and fuel quality. Although the venturi setting has been factory
set, adjustments may be necessary for optimal performance and visual aesthetics.
When replace is rst lit, the ames will be blue. Flames will gradually turn yellowish-orange during rst 15 minutes of operation. If ames remain
blue, or become dark orange with evidence of sooting (black tips), the burner tube venturi may need adjustment.
The appliance is required to be inspected at least once a year by a professional service person. The compartment below rebox (behind
lower access panel) must be cleaned at least once a year, more frequent cleaning may be required due to excessive lint from carpeting,
bedding materials, or other brous materials. It is imperative that the burner be cleaned once a year.
VALVE AND ELECTRICAL ACCESS
There is an access panel in the oor of the rebox should more extensive service be needed. Using the suction cups, remove the inner and
outer glass panels. Remove the glass media or natural stones on the end with the pilot. Remove the screws on the mesh screen and remove
the mesh screen. Remove the Phillips head screws on the LED “U” shaped metal tray and gently fold metal tray over the burners. Remove
the 6 screws on the solid access panel and remove panel.
NOTE: INSTALLATION AND REPAIR SHOULD BE DONE ONLY BY QUALIFIED SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE USE AND ANNUALLY BY A QUALIFIED SERVICE PERSON. MORE FREQUENT CLEANING
MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIALS, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS AND CIRCULATION AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
A. VENT SYSTEM
• Annual examination of venting system by a qualied agency is required.
• IF VENT-AIR INTAKE SYSTEM IS DISASSEMBLED FOR ANY REASON, RE-INSTALL PER INSTRUCTIONS PROVIDED WITH INITIAL
INSTALLATION.
• The ow of combustion air must not be obstructed.
B. GLASS CLEANING & REPLACEMENT
• Clean glass only when cool and only with non-abrasive cleansers.
• Do not operate this replace with glass/frame assembly removed, cracked or broken.
• The glass assembly shall only be replaced as a complete unit, as supplied by Hearth & Home Technologies.
• Replacement of glass & frame assembly, must only be performed by a licensed or qualied service person.
• Do not strike or slam glass assembly.
WARNING! RISK OF INJURY! DO NOT remove glass until it is cooled to room temperature. Glass breakage could occur.
See Section 6 for glass installation and removal instructions.
DO NOT SUBSTITUTE MATERIALS.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING. KEEP APPLIANCE AREA
CLEAR OF COMBUSTIBLE MATERIALS, SUCH AS GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Hearth & Home Technologies, on behalf of its hearth brands (“HHT”), extends the following warranty for HHT
gas, wood, pellet, coal and electric hearth appliances that are purchased from an HHT authorized dealer.
WARRANTY COVERAGE:
HHT warrants to the original owner of the HHT appliance at the site of installation, and to any transferee taking ownership
of the appliance at the site of installation within two years following the date of original purchase, that the HHT appliance
will be free from defects in materials and workmanship at the time of manufacture. After installation, if covered components manufactured by HHT are found to be defective in materials or workmanship during the applicable warranty period,
HHT will, at its option, repair or replace the covered components. HHT, at its own discretion, may fully discharge all of its
obligations under such warranties by replacing the product itself or refunding the verified purchase price of the product
itself. The maximum amount recoverable under this warranty is limited to the purchase price of the product. This warranty
is subject to conditions, exclusions and limitations as described below.
WARRANTY PERIOD:
Warranty coverage begins on the date of original purchase. In the case of new home construction, warranty coverage
begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent,
authorized HHT dealer/ distributor, whichever occurs earlier. The warranty shall commence no later than 24 months
following the date of product shipment from HHT, regardless of the installation or occupancy date. The warranty period for
parts and labor for covered components is produced in the following table.
The term “Limited Lifetime” in the table below is defined as: 20 years from the beginning date of warranty coverage for
gas appliances, and 10 years from the beginning date of warranty coverage for wood, pellet, and coal appliances. These
time periods reflect the minimum expected useful lives of the designated components under normal operating conditions.
Warranty PeriodHHT Manufactured Appliances and Venting
PartsLaborGasW oodPellet
1 Year
XXXXXXX
EPA
CoalElectric Venting
XXX
2 years
XMolded refractory panels
X
7 years 3 yearsXXX
10
Limited
1 yearXBurners, logs and refractory
3 yearsXXXXXFirebox and heat exchanger
Components Covered
covered by Conditions,
Exclusions, and Limitations
Ignition Modules
90 Days
4021-645H 10/15 Page 1 of 2
XXXXXXX
See conditions, exclusions, and limitations on next page.
• This warranty only covers HHT appliances that are purchased through an HHT authorized dealer or distributor. A list of
HHT authorized dealers is available on the HHT branded websites.
• This warranty is only valid while the HHT appliance remains at the site of original installation.
• This warranty is only valid in the country in which the HHT authorized dealer or distributor that sold the appliance
resides.
• Contact your installing dealer for warranty service. If the installing dealer is unable to provide necessary parts, contact
the nearest HHT authorized dealer or supplier. Additional service fees may apply if you are seeking warranty service
from a dealer other than the dealer from whom you originally purchased the product.
• Check with your dealer in advance for any costs to you when arranging a warranty call. Travel and shipping charges
for parts are not covered by this warranty.
WARRANTY EXCLUSIONS:
This warranty does not cover the following:
• Changes in surface finishes as a result of normal use. As a heating appliance, some changes in color of interior and
exterior surface finishes may occur. This is not a flaw and is not covered under warranty.
• Damage to printed, plated, or enameled surfaces caused by fingerprints, accidents, misuse, scratches, melted items,
or other external sources and residues left on the plated surfaces from the use of abrasive cleaners or polishes.
• Repair or replacement of parts that are subject to normal wear and tear during the warranty period. These parts
include: paint, wood, pellet and coal gaskets, firebricks, grates, flame guides, batteries and the discoloration of glass.
• Expansion, contraction, or movement of certain parts causing noise. These conditions are normal and complaints
related to this noise are not covered by this warranty.
• Damages resulting from: (1) failure to install, operate, or maintain the appliance in accordance with the installation
instructions, operating instructions, and listing agent identification label furnished with the appliance; (2) failure to
install the appliance in accordance with local building codes; (3) shipping or improper handling; (4) improper operation, abuse, misuse, continued operation with damaged, corroded or failed components, accident, or improperly/
incorrectly performed repairs; (5) environmental conditions, inadequate ventilation, negative pressure, or drafting
caused by tightly sealed constructions, insufficient make-up air supply, or handling devices such as exhaust fans or
forced air furnaces or other such causes; (6) use of fuels other than those specified in the operating instructions; (7)
installation or use of components not supplied with the appliance or any other components not expressly authorized
and approved by HHT; (8) modification of the appliance not expressly authorized and approved by HHT in writing;
and/or (9) interruptions or fluctuations of electrical power supply to the appliance.
• Non-HHT venting components, hearth components or other accessories used in conjunction with the appliance.
• Any part of a pre-existing fireplace system in which an insert or a decorative gas appliance is installed.
• HHT’s obligation under this warranty does not extend to the appliance’s capability to heat the desired space. Informa-
tion is provided to assist the consumer and the dealer in selecting the proper appliance for the application. Consideration must be given to appliance location and configuration, environmental conditions, insulation and air tightness of
the structure.
This warranty is void if:
• The appliance has been over-fired or operated in atmospheres contaminated by chlorine, fluorine, or other damaging
chemicals. Over-firing can be identified by, but not limited to, warped plates or tubes, rust colored cast iron, bubbling,
cracking and discoloration of steel or enamel finishes.
• The appliance is subjected to prolonged periods of dampness or condensation.
• There is any damage to the appliance or other components due to water or weather damage which is the result of, but
not limited to, improper chimney or venting installation.
LIMITATIONS OF LIABILITY:
• The owner’s exclusive remedy and HHT’s sole obligation under this warranty, under any other warranty, express or
implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified above. In no
event will HHT be liable for any incidental or consequential damages caused by defects in the appliance. Some states
do not allow exclusions or limitation of incidental or consequential damages, so these limitations may not apply to you.
This warranty gives you specific rights; you may also have other rights, which vary from state to state. EXCEPT TO
THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY
SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE
EXPRESSED WARRANTY SPECIFIED ABOVE.